Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/224122970

On-line condition monitoring system for in-service circuit breaker

Conference Paper · July 2005


DOI: 10.1049/cp:20050962 · Source: IEEE Xplore

CITATIONS READS
7 792

3 authors:

Milthon Serna Silva J.A. Jardini


Federal University of Sergipe, Brazil University of São Paulo
13 PUBLICATIONS   16 CITATIONS    170 PUBLICATIONS   1,528 CITATIONS   

SEE PROFILE SEE PROFILE

Luiz Carlos Magrini


OPERPLAN
51 PUBLICATIONS   189 CITATIONS   

SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Sensor and embedded cameras for transmission lines inspection View project

IoT concepts applied to Dam safety Monitoring System View project

All content following this page was uploaded by Milthon Serna Silva on 15 January 2015.

The user has requested enhancement of the downloaded file.


ON-LINE CONDITION MONITORING SYSTEM FOR IN-SERVICE CIRCUIT BREAKER
Milthon S. Silva, José A. Jardini, Luiz C. Magrini. 1
PEA. Department of Electrical Energy and Automation Engineering, Polytechnic School of the University of Sao Paulo
Brazil

maneuvering and protection of circuits; this is due to its


Summary - This work describes the experience obtained in high isolation interruption capacity of overload currents
the Circuit Breaker System Monitoring project executed for above the nominal value as well as of short circuit currents.
two Brazilian electric utilities, one of transmission and In agreement with previous researches, it can be affirmed
another of distribution. The project had as main that more than 40% of the maintenance cost of the
characteristic the use of market available equipment and substation equipment are spent in Circuit Breakers, and
standardized communication protocols, inside of an open and
60% of that amount is destined for general revision [6] and
flexible architecture, that allows its application to circuit
breakers with different technologies and with different [11]. In this way, the predictive maintenance systems based
operating mechanisms and insulation systems. on the continuous monitoring of Circuit Breaker
parameters can provide significant reductions in those
Keywords: Circuit Breaker System Monitoring, Maintenance costs.
and Diagnostic Equipments. Data acquisition systems.
The challenge of the predictive maintenance systems
I. NOMENCLATURE (monitoring) for Circuit Breakers is the possibility of
working with in-service equipment from different
CB Circuit Breaker.
manufacturers that used different operating mechanism and
CMS Condition Monitoring System.
interruption technologies. In contrast, for example, with
IED Intelligent Electronic Devices.
power transformers, whose operational beginnings and
IHM Interface Human Machine.
monitoring demands are essentially the same,
SCADA Supervisory Control And Date Acquisition.
independently of the manufacturer.

While projecting a Circuit Breaker monitoring system, it


II. INTRODUCTION
should be made acquisition of relative variables data: the

T he circuit breaker maintenance in electric power


substations has been traditionally based in time (fixed
intervals). That criterion, besides having significant costs
internal isolation (for example: pressure of gas SF6); the
operating mechanism (for example: oil pressure in the
hydraulic system); and the command circuits (for example:
for the utilities, usually isn’t the answer to an immediate state of the opening coil contact).
need of maintenance being used since the beginning until
recent times, when the substations possessed permanent An important measurement is the determination of the
maintenance teams. In that way, the equipment could be times involved in the several operative stages of the Circuit
monitored regularly, with the periodic visit of the Breaker (for example: opening command, opening coil
maintenance groups to apply the inspection routines: operation, beginning of arc extinction main contact
making a general revision, executing measurements, opening, end of travel main contact opening and current
recording data and taking samples for analysis. In case a interruption).
bad operation or an imminent fault is determined, an
The variables stored information analysis in the database
extemporaneous maintenance will be, consequently,
makers possible to determine the real condition of the
realized.
Circuit Breaker operation. Nowadays there exist a great
offer of Circuit Breaker monitoring systems, and this
The Circuit Breaker is one of the most important and number is growing quickly, with the emergence of new
complex in all the equipment of the substation. He measurement, supervision and control devices both for
possesses a current interruption system and is used for the hardware and software. On the other hand, that hinders his
1
integration vastly, since very often they are specific for a
M. S. Silva is a researcher in the Generation, Transmission and
determined manufacturer or for a determined Circuit
Distribution Automation Group (GAGTD – EPUSP) at the University of
Sao Paulo, BRAZIL. milthon.silva@poli.usp.br Breaker model. To this reality, it becomes convenient the
J. A. Jardini is Professor in the Department of Electrical Engineering development of a general monitoring standard, based on
(PEA) at the University of Sao Paulo (EPUSP), BRASIL. the use of acquisition devices largely used in the industrial
L. C. Magrini is a consultant and adviser of the Generation, automation.
Transmission and Distribution Automation Group (GAGTD – EPUSP) at
the University of Sao Paulo, BRAZIL.
CIRED2005

Session No 1
The condition information of the Circuit Breaker minimization of the equipment amount of faults and the
collected by the monitoring system can be compared with reduction of the number of programmed maintenances
the data obtained by other equipment already existent in the during the useful life.
substation, in this way making possible a better For the implementation of these monitoring systems
characterization of the real condition of the Circuit Breaker there were chosen: a Circuit Breaker (D1) that maker part
components, as well as of their operational parameters and of a 440 kV transmission substation and other Circuit
so allowing to anticipate and prevent damages or future Breaker (D2) that is installed in a 69 kV distribution
faults whose consequences could cause, aside the substation, whose operating mechanism is detailed:
interruptions and respective penalties, high costs of repair.
That predictive characteristic also allows a best D1) Circuit Breaker 440kV with monopolar operating
programming of the maintenance teams, correct mechanism (independent panel command for each
administration of the stock, aside of better operational phase). Each pole possesses two isolated post mounted
income of the substation and the Circuit Breaker useful life on a common base. The head with double operating and
prolongation. the post is filled out with gas SF6 used as half insulating
and arc extinguisher. The density of the gas is controlled
III. CIRCUIT BREAKER MONITORING through a densimeter, being its pressure shown through a
manometer. The head transforms the vertical movement
Circuit Breakers together with the transformers of the maneuvering rod into a horizontal movement of
constitute the most important equipment in the substation. the movable parts in the interrupting units. The
Considering his maneuvering function it can be said that a maneuvering rod works with an electro hydraulic type
Circuit Breaker is usually in an inactive state, since it mechanism that moves in the vertical direction. The
usually stays open or closed for long periods of time, until energy produced by the nitrogen gas (compressed inside
it occurs an alteration of the normal conditions of system the hydraulic accumulator) activates the circuit Breaker
operation, moment in which it should operate to change of operation mechanism. Tubes leaving this drive the
state. However when a Circuit Breaker has to work, a pressurized oil to the respective operation in each polar
wrong operation or a fault in the interruption can create a post, to the unit of valves and the control cabinet in
severe disturbance in the system, for this reason it should which it is made the supervision and control of the
have a well projected operating mechanism and highly compressor medium (óleo/N2).
safe.
D2) Circuit Breaker 69kV with tripolar operating
The Circuit Breaker monitoring system is a real time mechanism (one panel command for the three phases),
supervision system of the Circuit Breaker main parameters that uses the technique of the arc rotative associate to the
(currents, voltages, pressures, temperatures, contacts, etc.). self-expansion. The current to be interrupted travels a
This supervision is made through digital equipments and concentric coil to the contacts axis. The magnetic field
special sensors that are installed in the Circuit Breaker. The originated induces the arc to make fast rotations on the
data are collected and processed in a data acquisition and surface of the arc contacts, making possible that the
control unit (UAC), to thereafter through a communication heating of the contacts are distributed. The elevation of
network, using desirably a protocol standardized the operation pressure provokes the gas SF6 blow out on
internationally, be sent to a central computer located at the the arc for its extinction. The operating system is
control building of the substation and later to the operation mechanical, composed by a group of levers, with
centers and so allowing a remote supervision. accumulation of energy by springs activated through a
DC current motor.
In the supervision computer it is installed a database
manager program that stores the information history Although those Circuit Breakers work in different
collected during the Circuit Breaker operation. A SCADA voltage levels and possess different principles of operating
program that aside of collecting periodically the mechanisms, some monitoring parameters are similar.
information provided by the UAC, maker possible the IHM Thus, the main characteristics of a Circuit Breaker that can
between the monitoring system and the substation operator. be generally measured and monitored are:
A dedicated program of supervision that allows to
transform the data of the historical database in information, Closing and opening coils currents
continually making calculations and presenting the state of Line phases currents
the Circuit Breaker monitored components, in the form of Motor operating currents
waveforms, graphs or charts, in a way to make possible an Voltages supply (AC and DC)
evaluation and objective analysis of the Circuit Breaker Phases voltages
real condition, which will guide the programming of its Operating mechanism
maintenance. It is the main objective of the system, the Main contacts travel
CIRED2005

Session No 1
Wear of the contacts switch
Insulation medium pressure
Intern temperatures
B. Analogical Inputs
Supervision contacts state

IV. MONITORING SYSTEM PARAMETERS The monitoring of the electric variables comes with two
needs: one with low resolution of time (Low Sampling -
LS), being necessary and enough to collect in minutes
In the acquisition of the variables and states of the intervals, usually used for operation condition variables;
Circuit Breaker it should be considered two basic types of and the other with high resolution (High Sampling - HS)
hardware interface: collected during the Circuit Breaker operation.

A. Digital Inputs Those events are fast so that with a high sampling rate,
it’s possible to make a correct oscillography of the variable
They are signals that are collected continually especially and in that way to observe any type alterations inside of the
in the moment of the Circuit Breaker operation. Depending normal pattern of operation. Table II, shows the different
on the nature of the signal, these can be colleted with fast Circuit Breaker analogical inputs.
resolution (High Sampling - HS) or slow (Low Sampling -
TABLE II
LS). HS is used when we will make the recording events, MONITORED ANALOGICAL INPUTS
for determination of the operation times and for the
comparison with obtained values of other substation The amount of analogical inputs will depend on the type
monitoring equipment. The signals LS are usually used as
alarms, such as information of the state of the pressure CB1 CB2 Signal Sampling
Description
levels and levels of voltages supply DC and AC, and their Yes/Not Tags Rate
resolution is in the order of seconds. In Table I, the Circuit
Breaker digital inputs, are shown. Y Y TA Environment Temperature LS

TABLE I Y Y TI Inside Cabinet Temperature LS


MONITORED DIGITAL INPUTS
CB1 CB2 Signal Sampling Y Y D Gas SF6 density LS
Description
Yes/Not Tags Rate
Breaker normally closed Y N P Oil Pressure LS
Y Y A HS
contact (NC)
Breaker normally open contact Y Y C Close coil current HS
Y Y B HS
(NO)
Y Y T-1 Open coil current (Trip1) HS
Y Y CB Operating locking LS
Low oil pressure, 1st stage Y N T-2 Open coil current (Trip2) HS
Y N Oil-1 LS
(Alarm)
Low oil pressure, 2nd stage Y Y M Motor Current HS
Y N Oil-2 LS
(Trip)
Low SF6 pressure, 1st stage Y Y P Phase Currents HS
Y Y SF6-1 LS
(Alarm)
of the Circuit Breaker (monopolar or tripolar), of the
Low SF6 pressure, 2nd stage comparison need among the values of each phase and of
Y Y SF6-2 LS
(Trip) the operating mechanism type, among others.
N N M-1 Operating motor contact (on) HS
In this monitoring system, the signals of the current and
voltage phases are obtained through the PTs and CTs
Y Y Vol-1 Lack of voltage relay (Vcc) LS command panels of the line, with 5A and 115V outputs
respectively.
Y N Vol-2 Lack of voltage relay (Vca) LS
For the motor and coils (opening / closing) current
Y Y M-2 Spring charging motor (off) HS monitoring, closed loop (compensated) current transducers

CIRED2005
Y N D-P Phases discordance HS

Session
Y NNo 1R Auto-reclosing (on/off) LS
of Hall effect were used, with 100/0.1A relationship of Human Machine function (IHM). The IHM converts the
transformation. data in useful information to the Circuit Breaker real
condition diagnosis and for the communication are used
standard protocols.

V. MONITORING SYSTEM ARCHITECTURE The general architecture of the CB monitoring is show in


the Figure 1.
The monitoring system is composed by a group of
devices (transducers, converters and sensors) that are
linked to an IED that makes the collection, treatment and
subsequent sending of the data to the central computer
that processes, stores and accomplishes the Interface

Figure 1. General architecture of the Circuit Breaker System Monitoring.

A. Acquisition Module B. Digital Transducers

This module is composed by an IED with 240kB of They are transformer units for adaptation of the line
memory configurable, a power supply of 125Vdc with 24 currents and voltages (phases A, B and C), with
Vdc output for feeding possible sensors, data transmission configurable inputs for one or three phase circuits. The
rate from 9600 to 19200 bps, Ethernet communication input for these units are voltage from 0 to 115V and current
card, two EIA RS-232/RS-485 ports. Acquisition Card from 0 to 5 A, being these connected through CTs and PTs
(I/O) of binary inputs with 12/24/125Vdc feeding and of line bay. The transducers are connected to IED
analogical inputs of +/-10Vdc or 0...20mA with 16 bits monitoring through the acquisition card analogical inputs
resolution and accuracy of 0.1%. (0 to 5 Vdc).

The IED is prepared to work in atmospheres with high C. Sensor specifications


noise level originated by the electromagnetic fields and to
support environment temperature appropriate to the Temperature Sensor. - Model Pt-100 class B / RTD,
substation historical temperatures. this sensor is usually fixed in the own CB panel of
command hold a temperature transducer for 4 to 20mA
output, power supply of 10 to 30 Vdc, connection to
two wire, with protection tube in stainless steel,
CIRED2005

Session No 1
measurement of 0°C to +85°C and accuracy of +/- The equipment collecting the data, need to be
0.5%. Another sensor with the same characteristics is synchronized.
used for measurement of the environment temperature
and will be installed close to one of the poles. Manufacturers offer a great variety of data
communication protocols with support to those
Density Sensor. - Model S-10, with pressure functionalities, but many of them are solutions supported
measurement from 0 to 10 bar with temperature just by the market products of the company, which hinders,
compensation, two wires circuit, power supply from or even, prevents its integration with other system
10 to 30 Vdc, output signal from 4 to 20 mA, pressure equipment or even with SCADA.
connection ½" BSP, accurately of +/-0.5% and time
response smaller than 1s. The philosophy of open communication systems values
the adoption of interfaces and standardized protocols, such
Pressure Sensor. - Model S-40, with pressure as IEC 60870-5, DNP 3.0 and more recently, IEC 61850,
measurement from 0 to 400 bar, two wires circuit, which is also known as an extension of UCA 2.0.
power supply from 10 to 30 Vdc, output signal from 4
to 20 mA, pressure connection ½"BSP, accurately of
F. Other Devices
+/-0.5% and time response smaller than 1s.
Current Transducers. - Type close loop (compensated)
of Hall effect, with measurement variation from 0 to Regarding the considerable distances between the field
10 A (DC or AC), three wires circuit with power equipment and the control building, there were used fiber
supply from 20 to 30 Vdc, output signal from 4 to optic cables, with their respective F.O. / RS-232
20mA, connectionless physics used for measurement converters. In case of the Circuit Breaker (D1) because it
of the coil and motor currents, accuracy of +/-0.5% has a monopolar operation it demanded the triple of the
and time response smaller than 1s. amount of sensors and one auxiliary power supply of 125 /

D. Computer Monitoring Server

It consists of a microcomputer, located in the utilities


substation control building, PC of 2 GHz, with 256MB
RAM memory, 40GB HD unit, monitor 17" with card
graphical interface AGP and communication cards with
RS-232 ports. In the computer it was installed the
WINDOWS NT professional operating system, the
SCADA system, a database management program, as well
as a program developed for analysis and data presentation
showing the results in form of graphs, tables, waveforms,
among others.

E. Communication

The needs of data communications of the Circuit


Breaker monitoring system, although they don't involve a
great volume of data, it presents some peculiarities, such
as:
24 Vdc.
Different times of scanning, most of the digital and
Figure 2, shows the prototype that was installed in the
analogical signals are collected every second, while
transmission substation with all the devices before
some others demand a resolution of milliseconds.
mentioned.
The volume of data to be transmitted is usually small,
Figure 2. Prototype installed in the transmission substation.
except when it occurs a maneuver of the circuit
breaker.
VI. OBTAINED DIAGNOSES RESULTS

CIRED2005

Session No 1
Evolution waveforms of the gas density (SF6), oil equipments (transformer, Circuit Breaker, surge
pressure and temperature changing, through data by arrester, among other) inside of a common platform
the sensors installed in the Circuit Breaker. and the appearance of new services such as tools for
Currents and voltages of line oscillographies provided maintenance management.
by the digital transducers, that allowed to make
calculations in an approximate way the main contacts
wear and damage using the relationship I2T. VIII. ACKNOWLEDGE
Evolution of the closing and opening times, through
the measurements of the operation times, as well as by The authors wish to thank Luis Antonio Solis and
the position of the auxiliary contacts. Antonio Corvo of ETEO – Empresa de Transmissão de
Analysis of the Circuit Breaker closing or opening
Energia do Oeste Ltda. and Francisco Eugenio Veiga of
times, through the phase current oscillographies and
COELBA – Companhia de Eletricidade da Bahia, for their
opening / closing coil currents.
Analysis of the main contacts travel. contributions and participation in the project execution.
The analysis of the Circuit Breaker closing and
opening current waveforms will permit to detect
possible faults in the Circuit Breaker operation, IX. REFERENCES
determining his characteristic signature.
Evolution of the Circuit Breaker motor operating [1] A. Poeltl and M. Haines, "Experiences with condition monitoring of
current waveforms. HV Circuit Breaker," in Proc. 2001 Transmission and Distribution
Conf., IEEE/PES, V.2 pp. 1077-1082.
Analysis of the disagreement between main contacts [2] Catalogs Circuit Breaker from Siemens and Schneider.
opening and closing times. [3] CEA Canadian Electricity Association, “On-line Condition
Monitoring of Substation Power Equipment Utility Needs, Dec.
1996.
[4] IEEE “Guide for the selection of monitoring for Circuit Breaker”
IEEE Std. C37.10.1-2000.
VII. CONCLUSIONS [5] J. Corbett and A. Higgins and C. Kelleher, "A procedure for
allocating limited resources to Circuit Breaker planned
maintenance," in Session 2002 CIGRE Conference, V: 13, P: 303.
The Circuit Breaker monitoring in real time is an [6] J. H. Nelson, "Electric utility considerations for Circuit Breaker
emerging technology that it’s growing quickly with the Monitoring," in Proc. 2001 Transmission and Distribution Conf.,
participation of utilities, equipment manufacturers, IEEE/PES, V.2 pp. 1094-1097.
monitoring devices providers and universities research [7] J. P. Dupraz and A. Schiemann, "Design Objectives of new digital
control and monitoring of High Voltage Circuit Breaker," in Proc.
groups. 2001 Transmission and Distribution Conf., IEEE/PES, V.2 pp. 1088-
1093.
The appearance of new acquisition cards with high [8] K. Lehman and L. Zehnder and M. Chapman, "A novel arcing
sampling rate larger to 1ms allows to accomplish monitoring system for SF6 Circuit Breaker," in Session 2002 CIGRE
Conference V: 13, P: 301.
current oscillographies involved during the Circuit [9] M. Landry and G. Diagneault and S. Zelingher, "Benefits of On-line
Breaker operation process, which allows to detect monitoring for High Voltage Circuit Breaker," in Session 2000
probable fault in his operation, besides allowing to CIGRE Conference pp. 358-364.
accomplish much more exhausting analyses through [10] O. S. Lobosco and H. P. Silva, "Monitoring systems for failure
detection and location in Substations Strategic Apparatus," in Proc.
the use of mathematical tools as the Wavelet 2002 Latin America Transmission and Distribution Conf.,
transform. IEEE/PES, V.3, pp. 317-322.
[11] W. J. Bergman, "Selecting Circuit Breaker Monitoring," in Proc.
The selection of data communication protocols is an 2001 Transmission and Distribution Conf., IEEE/PES, V.2, pp.
1071-1076.
important task in order to get an economic solution,
and provide interchangeability avoiding proprietary
systems. X. BIOGRAPHIC

Milthon Serna Silva, born in Cusco, Peru, 30


The standardization of the communication protocols august 1972. Graduated in electrical
for the monitoring systems will allow to reach benefits, engineering at UNSAAC University in 1993.
such as larger integration between equipments, larger He received the MSc and PhD degrees in
reliability in the data management, smaller response 2001 and 2004 at the Polytechnic School of
time before a fault in the system, among others. Sao Paulo University. Worked in construction
of line and substation high voltage systems
projects and Power System Planning. At the
As future tendencies into the electric area monitoring present works at GAGTD (Energy
systems: the compact substations monitoring, the Distribution and Transmission Generation Automation Group) of PEA (the
integration of all monitoring systems of several Department of Energy Engineering and Electric Automation) of EPUSP
CIRED2005

Session No 1
(The Polytechnic School of Sao Paulo University). Member of Brazilian
work group SC13.23 to CIGRE and Member of IEEE.

José Antonio Jardini, born March 27 1941,


graduated at EPUSP- The Polytechnic School
of Sao Paulo University in 1963. MSc in 1970
and PhD in 1973. Associate Professor in 1991
and titular head in 1999, all of them at PEA
(The Department of Energy engineering and
Electric Automation). Worked at Themag
Engineering Ltd in the area of power systems
studies – lines projects and automation. At the moment he is a professor at
the Department of Energy Engineering and Electric automation where he
teaches “Automation of the Generation” and “Transmission and
Distribution of Electric Energy”. Repreesents Brazil at SC38 of CIGRE,
CIGRE member, Fellow Member of IEEE and Distinguished Lecturer of
IAS/IEEE.

Luiz Carlos Magrini, born in São Paulo,


Brazil, on May 3rd, 1954. He graduated from
Polytechnic School of Sao Paulo in 1977
(Electrical Engineering). From the same
institution he received the MSc and PhD degrees
in 1995 and 1999, respectively. For 17 years he
worked for Themag Engenharia Ltda, a leading
consulting company in Brazil. He is currently a researcher at Polytechnic
School of Sao Paulo University - GAGTD group. Member of Brazilian
work group SC13.23 to CIGRE.

CIRED2005

Session No 1

View publication stats

You might also like