Aluminium Conductor Sag Tension Calculator
Aluminium Conductor Sag Tension Calculator
INPUT DATA
No. of Conductor/Span 4
OUTPUT DATA
OBSERVATION
CONDUCTOR TENSION > TERMINAL LOAD OF POINT A, CONDUCTOR TENSION > TERMINAL LOAD OF POINT B,
PLEASE REWORK THE DESIGN PLEASE REWORK THE DESIGN
CONCLUSION
INPUT DATA
No. of Conductor/Span 4
Weight of Conductor/Length, w 4.6 kg/m
Span Length, S 5.5 m
Conductor Sagging at Mid Span, D 0.401 m
Vertical Distance Between Support, h 1.3 m
Terminal Load of Point A (Left Support) 315 kg
Terminal Load of Point B (Right Support) 315 kg
OUTPUT DATA
Dist. - The Left Support Point To The Low Point In The Catenary, XL 4.98 m
Dist. - The Right Support Point To The Low Point In The Catenary, XR 0.52 m
Horizontal Components of Tension, H 173.50 kg
Actual Conductor Length, L 5.73 m
Sag in Right Sub-Span Section, DR 0.01 m
Sag in Left Sub-Span Section, DL 1.31 m
Tension in Right Sub-Span Section, TR 173.77 kg
Tension in Left Sub-Span Section, TL 197.69 kg
OBSERVATION
CONDUCTOR TENSION < TERMINAL LOAD OF POINT A CONDUCTOR TENSION < TERMINAL LOAD OF POINT B
CONCLUSION
DESIGN SUFFICIENT
CONDUCTOR SAGGING AND TENSION CALCULATOR FOR LEVEL SPAN
INPUT DATA
No. of Conductor/Span 4
OUTPUT DATA
OBSERVATION
CONDUCTOR TENSION > TERMINAL LOAD OF POINT A, CONDUCTOR TENSION > TERMINAL LOAD OF POINT B,
PLEASE REWORK THE DESIGN PLEASE REWORK THE DESIGN
CONCLUSION
INPUT DATA
No. of Conductor/Span 2
Weight of Conductor/Length, w 1.145 kg/m
Span Length, S 2.276 m
Horizontal Components of Tension, H 9.89 kg
Vertical Distance Between Support, h 0.473 m
Terminal Load of Point A (Left Support) 12 kg
Terminal Load of Point B (Right Support) 12 kg
OUTPUT DATA
Dist. - The Left Support Point To The Low Point In The Catenary, XL 2.04 m
Dist. - The Right Support Point To The Low Point In The Catenary, XR 0.24 m
Conductor Sagging at Mid Span, D 0.15 m
Actual Conductor Length, L 2.35 m
Sag in Right Sub-Span Section, DR 0.01 m
Sag in Left Sub-Span Section, DL 0.48 m
Tension in Right Sub-Span Section, TR 9.91 kg
Tension in Left Sub-Span Section, TL 10.99 kg
OBSERVATION
CONDUCTOR TENSION < TERMINAL LOAD OF POINT A CONDUCTOR TENSION < TERMINAL LOAD OF POINT B
CONCLUSION
DESIGN SUFFICIENT