Design Calculations for R.C.

C work of STP

Project : STP OF CAPACITY 120 KLD AT ESIC HOSPITAL, IMT MANESAR


Client : EE Manesar Division, CPWD, Manesar
EQUALISATION TANK/ TREATED WATER TANK

Assumptions and Inputs

Unit Wt of Water 10 kN/m3


4
Unit Wt of Submerged Soil 8 kN/m Effective Cover 40 mm
Height of the Wall 4.3 m Concrete Grade M M 30
Depth of the water (h) 4.0 m Steel Grade Fe Fe500
Pressure exerted by of saturated soil P 12.4 kN/m3 DESITY OF SOIL 16 kN/m3
Width of the Long wall (b) 4.3 m ANGLE OF REPOSE 0.5234 RADIAN
HEIGHT OF EARTH 4.0 m
SBC at 1.2 m from NGL 80 kN/m2
Clearly pressure exerted by water is much more than pressure exerted by soil outside,
thus the tank has been designed for completely filled condition.(No presence of UG
water upto 6.5m depth)
Check for pressure exerted by water in tank

Width to Depth Ratio = 1.075


The BM at different points on wall can be obtained from Table 3 IS 3370 - Part 4
Max. coefficient for bending moment at the base = 0.0386
Max B.M in vertical direction at the base of wall M1= .0386x P x h3 = -24.70 kNm
Max B.M in Horizontal direction at the Mid Height of wall M2= .0314x P x h3 = -20.10 kNm

2
Permissible direct tensile stress in concrete for M30 (Tc) = 1.5 N/mm
2
Permissible tensile stress in bending for M30 (Tc1) = 2 N/mm

DESIGN OF VERTICAL WALL

FOR NO CRACKING THICKNESS OF WALL REQUIRED AT BOTTOM(CENTRE) (6 x M1/B/Tc1) ½ = 272 mm

THICKNESS OF WALL PROVIDED = 300 mm

Shear (Table 8 IS 3370 - Part 4)

Max SF at MIDPOINT of bottom edge of wall = 0.252 x P x h2 40.32 KN


Max SF at MIDPOINT of the vertical edge of the wall = 0.267 x P x h2 =44.28 kN

The SF in the wall on the vertical edge will cause tension in the adjacent wall,

Check for criterion for safe design ( MIDDLE OF BOTTOM EDGE)

Direct stress + Bending Stress


<= 1
Per. stress Per. Stress
(40.32/320/1.5) (24.7x6x1000/320^2/2) ~ 1 O.K.
= 0.084 = 0.724
Vertical Reinforcement

At base of wall(inside tank)


Permissible compression stress in concrete(Mpa) = 10 M30
Permissible stress in reinforcement(Mpa) = 130 Fe415
Modular ratio = 9.33
D = 300 mm
d = 280 mm
j = 0.86
2
(24.70x1000x1000/130/0.86/280) Ast = 789 mm /m
2
Ast min = 384 mm /m 0.24%
At Water Face Ast Provided = 807 mm2/m
Provide T12 @ 140 C/C at Water Face.
Provide T12 @ 200 C/C at Outer Face.

Horizontal Reinforcement

Near midpoint of horizontal edge of wall (At base)


(Shear force at corner of bottom edge of the wall is neglected as per D = 300 mm
clause.2.3.3.1 of IS 3370-4 ) d = 260 mm
(20.10x1000x1000/130/320) + (SFx1000/130/2) Ast = 653 mm2/m
2
SF = 44.28 on each face Ast min = 384 mm /m 0.24%

Ast Provided = 654 mm2/m


Provide T10 @ 120 C/C on each face

BASE SLAB DESIGN


The base slab and RCC wall junction has been designed for
the moment and shear that will be transferred to the base slab by wall
Adopt thickness of base slab = 300 mm
Moments tranfered by the wall = -24.70 kNm/m
Shear at the base to the wall = 44.28 kN/m
e = 557.81 mm
D = 320 mm
d = 270 mm
(24.7x1000x1000/130/320) + (40.32x1000/130) Ast = 904 mm2/m
2
Ast min = 384 mm /m 0.24%

Ast Provided = 942 mm2/m


Provide T12 @ 120 C/C in each direction at Top and T12 @ 180 C/C in each Direction at Bottom.