Professional Documents
Culture Documents
Portables, Wheeled Units, and Pre-Engineered Systems: Hydrostatic Test Instructions
Portables, Wheeled Units, and Pre-Engineered Systems: Hydrostatic Test Instructions
Portables, Wheeled Units, and Pre-Engineered Systems: Hydrostatic Test Instructions
TABLE OF CONTENTS
PAgE
general Information 1-6
Introduction 1
Tools and Accessories 1
Hydrotest Recommendations 1
Table 1 – Periodic Hydrostatic Retest Requirements 2-5
Reference Numbers for Code of Federal Regulations 6
Manufacturing Dates 6
Safety Considerations 6
䊱
! DANgER
Indicates a hazardous situation in which a person will
experience serious personal injury or death if the situation is
not avoided.
! WARNINg
Indicates a hazardous situation in which a person could
experience serious personal injury or death if the situation is
not avoided.
! CAUTION
Indicates a hazardous situation in which a person could
experience minor or moderate personal injury if the situation
is not avoided.
CAUTION
NOTICE
Addresses general practices or observations
related to system function that are not related
to personal injury.
Hydrostatic Test Instructions gENERAL INFORMATION
2012-DEC-20 REV. 05 PAGE 1
INTRODUCTION
Tyco Fire Protection Products (TFPP) hand portables, wheeled ! WARNINg
units, and pre-engineered system tanks are designed, produced,
and tested in accordance with standards judged by many to be the If, at any time, a pressure vessel or agent tank shows evidence
most rigid in the fire protection industry. The result is safe, effec- of corrosion or mechanical injury, it shall be subjected to a hydro-
tive, first aid fire extinguishers. static pressure test, or replaced. Important: air or gas should not
be used for pressure testing as failure of a shell could be violent
To assure continued safe, effective operation, the pressure ves- and dangerous. When extinguisher shells, cylinders, cartridges
sels must receive scheduled, periodic maintenance in strict com- or hose fail a hydrostatic pressure test, they shall be destroyed.
pliance with procedures established by the Occupational Safety
and Health Act of 1970. Under the provisions of the Act, the ser-
Table 1 on pages 2-5 is designed to show what TFPP understands
vicing of fire protection equipment must be conducted in accor-
to be the current legal requirements for periodic retest, indicating
dance with the Standards of the National Fire Protection
both test intervals and pressures. These requirements are shown
Association (NFPA) Pamphlets No. 10, 17, 17A, 30, 33, and 96.
for the two principal authorities having jurisdiction over this type of
These standards are available on the NFPA website:
product: the National Fire Protection Association (NFPA), and the
www.nfpa.org.
Code of Federal Regulations (DOT, MSHA, and OSHA). It is
The instructions for testing nitrogen cylinders are not in this man- important to understand the jurisdiction of these two authorities
ual as the test procedures require DOT certification. All ANSUL and how it may affect the product in question. You may wish to
nitrogen and carbon dioxide cartridges should be returned to refer directly to these principal authorities to make your own inter-
TFPP for refilling and hydrostatic testing, unless you are a TFPP pretation of the current legal requirements.
contracted cartridge refiller.
NFPA standards have no force of law in and of themselves unless
adopted by a regulatory entity that is empowered by statute to
TOOLS AND ACCESSORIES
enforce regulations. However, as consensus standards developed
The general use hand tools and accessories listed below are only by teams of recognized experts, they represent sound fire safety
those available from TFPP. For a more comprehensive guide to principles, practices, and procedures, and we recommend that
tools, equipment, parts and lubricants used in hydrostatic testing they be observed in the case of hydrostatic retesting. Moreover,
service operation, refer to the National Association of Fire some states and municipalities have adopted NFPA standards as
Equipment Distributors Incorporated (NAFED) “Service and a part of their fire protection codes, including those parts dealing
Recharge Training Manual.” with the maintenance and hydrostatic retesting of extinguishers.
Part No. Description OSHA has safety jurisdiction over most workplaces in the U.S.,
13133 Cartridge Receiver Wrench and as such its regulations have the force of federal law. OSHA
2609 Handle, Cart. Rec. Wrench has not adopted NFPA standards for hydrotesting per se, but its
10852 Wrench Head, Cart. Rec. requirements follow NFPA standards closely.
6380 Cartridge Strap Wrench DOT’s hydrostatic retest requirements apply only to charged pres-
16511 Spanner Wrench, Fill Cap & Hydro Head sure vessels which are transported in commerce in the U.S. or to
4279 Nitrogen Cylinder Valve Wrench foreign countries. Once the product reaches its original destina-
78689 Pressure Regulator Test Assembly tion, DOT rules apply only when the container is reshipped in a
16246 Recharge Adaptor, SENTRY Dry Chem. charged condition or being re-filled.
79730 Touch-Up Paint, Red, 9 oz. Aerosol Can MSHA has safety jurisdiction over mines and generally references
79731 Touch-Up Paint, “CR” Red, 9 oz. Aerosol Can the appropriate NFPA and DOT regulations for additional guide-
436049 Touch-Up Paint, Red – Post 2008 models, lines on extinguisher hydrostatic testing.
12 – 0.6 oz. Brush-in-cap Bottles
It will be noted that there are some gaps and overlapping in the
59321 Nameplate Adhesive, pint
legal requirements for periodic hydrostatic retesting of some ves-
9030 Grease, Silicone 33, 5.3 oz. sels. However, appropriate retest intervals and test pressures
699 Funnel for 10, 20, 30; 2 1/2 dia. tube have been determined for such vessels through the NFPA
1196 Funnel for Wheeled Equipment (w/screen & legs) Committee process and/or TFPP’s own research and experience.
3923 Cartridge Scale In many cases, compliance to the NFPA standards may put you in
77250 Cartridge Shipping Cap compliance with OSHA. (Refer to the National Consensus
15999 Inspection Seal Standards, Appendix B, Subpart L.) A TFPP recommendation is
11790 Hydrostatic Test Record Label indicated for each of the pressure vessels in Table 1, pages 2-5.
In states where the OSHA regulations differ from local regulations
HYDROTEST RECOMMENDATIONS
or statutes, the Office of the State Fire Marshal is available for
Parts below are taken from NFPA Pamphlet No. 10, 17, 17A, 30, counsel.
33, and 96. They serve as a general guide to the rules and regu-
At intervals not exceeding those specified in Table 1, extinguish-
lations of hydrostatic testing as required by law.
ers shall be hydrostatically tested. For those with a designated test
Extinguishers and agent tanks shall be hydrostatically tested at interval of five years, the first hydrostatic retest may be conducted
regular intervals as required in the NFPA Standards, or more fre- between the fifth and sixth years.
quently when inspection or maintenance indicates a specific need.
Such tests are usually required on extinguisher shells, cylinders,
some cartridges and some hose assemblies.
gENERAL INFORMATION Hydrostatic Test Instructions
PAGE 2 REV. 05 2012-DEC-20
TABLE 1: PERIODIC HYDROSTATIC RETEST REqUIREMENTS FOR PRESSURE VESSELS IN ANSUL
HAND PORTABLES AND WHEELED
ANSUL Stored Pressure Dry Chemical, 10 12 years Factory test pressure (not to exceed 1 12 years
FE-36, and Halon 1211 Extinguishers 3X the normal operating pressure)
(Agent Tanks)
ANSUL Stored Pressure Water and Wet 10 5 years Factory test pressure (not to exceed 1 5 years
Chemical Hand Portable Extinguishers 3X the normal operating pressure)
(Agent Tanks) (See note)
ANSUL CO2 Hand Portable Extinguishers 10 5 years 5/3 service pressure as 1 5 years
(aluminum and steel Agent Tanks) stamped into the cylinder
D.O.T. 3A-1800, 3AA-1800, 3AL-1800
and 3AA-2015
ANSUL Halon 1211 Wheeled 10 Per D.O.T. Factory test pressure (not to exceed 3, 6 7 or 12 years
Extinguishers marking 3X the normal operating pressure) (See Ref. No. 6)
(D.O.T. 4BW-240 Agent Tanks) (See notes)
N2 Cartridges for 20 and 30 10 Per D.O.T. or C.T.C. markings 2, 5 Per stamped markings
Low Temperature Extinguisher Models 5 or 10 years
— As used in this chart, service pressure and operating pressure are the same.
— Dry Powder Extinguishers should be tested at the same intervals and pressures as Dry Chemical Extinguishers.
Hydrostatic Test Instructions gENERAL INFORMATION
2012-DEC-20 REV. 05 PAGE 3
PORTABLES, WHEELED UNITS, AND PRE-ENgINEERED VESSELS
Factory test pressure (not to exceed 12 years Check test pressure • Agent hose assemblies with a shut-off nozzle
3X the service pressure) on nameplate for must be tested @ 300 psi (20.7 bar).
3X normal operating
pressure
Factory test pressure (not to exceed 5 years 200 PSI (13.8 bar) • Exception: Does not apply to ANSUL ENSIGN
2X the service pressure) Model WF-2 1/2 fiberglass extinguishers which
were recalled in 1973. Under no circumstances
are these units to be hydrostatically tested or
recharged.
• Agent hose assemblies must be tested at
same intervals @ 100 psi (6.9 bar) or at ser-
vice pressure, whichever is higher.
5/3 service pressure 5 years 5/3 service pressure • Aluminum tanks suspected of being exposed
to temperatures in excess of 350 °F (177 °C)
shall be removed from service and subjected
to a hydrostatic retest.
• Agent hose assemblies must be tested at
same intervals @ 2,000 psi (137.9 bar) or at
service pressure, whichever is higher.
N/A 12 years 600 PSI (41.4 bar) • Agent hose assemblies must be tested at
same intervals @ 300 PSI (20.7 bar), or at ser-
vice pressure, whichever is higher.
N/A 5 years 600 PSI (41.4 bar) • Agent hose assemblies must be tested at
same intervals @ 300 PSI (20.7 bar), or at ser-
vice pressure, whichever is higher.
2X service pressure 7 or 12 years 480 PSI (33.1 bar) • Agent hose assemblies must be tested at same
intervals @ 300 PSI (20.7 bar).
— Factory test pressures are indicated on the extinguisher nameplates. * See next page for references to Code of Federal Regulations.
— Recording of hydrostatic testing shall be in accordance with NFPA-10 recommendations.
gENERAL INFORMATION Hydrostatic Test Instructions
PAGE 4 REV. 05 2012-DEC-20
TABLE 1: (Continued)
PRE-ENgINEERED SYSTEMS
Industrial Dry Chemical Systems 17 12 years Factory test pressure (not to exceed 1, 3, 6 7 or 12 years
ANSUL Model SPA-50 and IND-X 2X the normal operating pressure)
(D.O.T. 4BW-500 Agent Tanks)
ANSUL R-102 Wet Chemical Agent 17A 12 years Factory test pressure (not to exceed N/A N/A
Tanks (carbon steel and stainless tanks) 3X the normal operating pressure)
PIRANHA
ANSUL Model H-1000 and H-101 12A 12 years Factory test pressure (not to exceed 3, 6 7 or 12 years
(D.O.T. 4BW-500 Agent Tanks) 2X the normal operating pressure)
ANSUL Model H-1000 with 3A or 3AA 12/ 5 years 5/3 service pressure as 1 5 years
D.O.T. Stamp (Agent Tanks) 12A stamped into the cylinder
— As used in this chart, service pressure and operating pressure are the same.
— Dry Powder Extinguishers should be tested at the same intervals and pressures as Dry Chemical Extinguishers.
Hydrostatic Test Instructions gENERAL INFORMATION
2012-DEC-20 REV. 05 PAGE 5
N/A 12 years 600 PSI (41.4 bar) • Agent hose assemblies must be tested at
same intervals @ 300 psi (20.7 bar), or at ser-
vice pressure, whichever is higher.
Factory test pressure (not to exceed 7 or 12 years 1000 PSI (68.9 bar) • At same interval test 1 inch discharge hose
2X the normal operating pressure) and 1/4 inch actuation hose @ 1000 psi
(68.9 bar), or at service pressure, whichever is
higher.
Factory test pressure (not to exceed 7 or 12 years 700 PSI (48.3 bar) • At same interval test 1 inch discharge hose
2X the normal operating pressure) and 1/4 inch actuation hose @ 1000 psi
(68.9 bar), or at service pressure, whichever is
higher.
N/A 12 years 330 PSI (22.8 bar) • At same interval test 1/4 inch gas hose
assembly @ 220 psi (15.2 bar), or at service
pressure, whichever is higher.
Factory test pressure (not to exceed 7 or 12 years 1000 PSI (68.9 bar) • At same interval test 1 inch discharge hose
2X the normal operating pressure) and 1/4 inch actuation hose @ 1000 psi
(68.9 bar), or at service pressure, whichever is
higher.
— Factory test pressures are indicated on the extinguisher nameplates. * See next page for references to Code of Federal Regulations.
— Recording of hydrostatic testing shall be in accordance with NFPA-10 recommendations.
gENERAL INFORMATION Hydrostatic Test Instructions
PAGE 6 REV. 05 2012-DEC-20
HYDROSTATIC TEST FOR PRESSURE VESSELS Note: On the stationary and wheeled units remove fill cap
The following general instructions are used with Table 2, pages assembly and allow water to overflow fill opening. The vent
8-15, which lists the specific adaptors required to test the different valve should not be closed until water flows freely from the
types of extinguishers. valve. Rock tank gently to make certain all air is removed;
return fill cap assembly to the shell and hand tighten.
Always be alert for any indications of damage or inability to oper-
! WARNINg
ate the extinguisher. No manual can anticipate everything that
could happen to an extinguisher. In the event that something not
covered in the manual is found, determine whether any potential
for damage, effect on operation, or safety exists and repair or All air must be removed. Failure to comply may cause the
replace, as necessary. shell to rupture resulting in severe personal injury or death.
1. Carefully release any pressure from the extinguisher and
remove external and internal parts from the shell. Install safe- 8. Turn on hydrostatic pump and apply pressure at a rate-of-
ty shipping cap on gas cylinder or cartridge (if part of assem- pressure rise to reach the designated test pressure within 1
bly) and place all parts in a safe location. (Refer to the minute. (See Table 1, pages 2-5 for test pressure.)
Operation, Recharge, Inspection, and Maintenance Manual 9. Maintain the test pressure for 1 full minute observing shell for
provided with the extinguisher for proper procedures.) any distortion or leakage. If no distortion or leakage is noted
and the test pressure has not dropped, the hydrostatic test is
! CAUTION successful. Stop the hydrostatic pump and open the vent
valve to relieve the pressure in the shell.
Cartridge operated and wheeled unit extinguishers must Note: Any shell that fails this hydrostatic test must be
have gas tube removed prior to hydrostatic test (unless destroyed (see page 6, step 7) to prevent its further use as a
welded to the shell). Failure to remove will result in damage pressure vessel. Shells passing this hydrostatic test must
to the gas tube rubber. have all water and all traces of moisture completely removed
before reassembly of components.
2. Remove agent from shell and place in a labeled container.
(Closed removal system recommended to limit exposure to
personnel.)
! CAUTION
Note: Agent removed from Pre-engineered Systems shall be Relieve pressure through vent valve only. Do not attempt to
replaced. remove adaptors, fittings, fill caps, etc., until pressure is
released.
3. Remove all traces of dry chemical from the shell using dry air
or nitrogen.
10. Disconnect all test fittings and remove water from the shell.
Completely dry the shell (for all non-water type of extinguish-
! CAUTION ers) using a commercial warm air dryer that does not exceed
a temperature of 150 °F (65.5 °C). Do not place dry chemical
Restrain object being cleaned and wear proper protective in shell until the shell and all attachments are completely dry.
clothing and eye protection.
11. Perform hose test (see page 16) on hose assemblies as des-
ignated in Table 1, pages 2-5.
4. Thoroughly examine the entire shell for signs of corrosion or
mechanical damage. Refer to the “Standards for Visual 12. Examine all parts; replace worn or damaged parts with origi-
Inspection of Steel Compressed Gas Cylinders,” Pamphlet nal factory ANSUL components. Reassemble and refill shell
CGA C-6, from the Compressed Gas Association, Inc. according to the Operation, Recharge, Inspection, and
Maintenance Manual provided with the extinguisher.
! CAUTION 13. Record hydrostatic test information (month, year, test pres-
sure, name or initials of person performing the test, and name
of agency performing the test) on the hydrostatic test record
Do not perform hydrostatic test on shell in poor condition. If
label (see Figure 1), Part No. 11790 (or equal) and attach it to
the shell shows evidence of parent metal missing due to
the shell. Update the permanent file on each tested extin-
severe corrosion or mechanical damage, it must be
guisher.
destroyed and replaced. (See page 6, step 7.)
Extinguisher
Identification Part No. Description Directions
RED LINE:
5 26278 Discharge Elbow Plug Select correct plug and wrench tighten into
— 3/8 in. NPT Pipe Plug discharge elbow near base of extinguisher.
(Pre 1968 shells)
27991 Test Head Assembly Insert into shell opening. Wrench tighten, using
spanner wrench (Part No. 16511). Connect
hydrostatic pump hose to inlet elbow.
RED LINE:
10-C, 10-E, 10-G 13133 Cartridge Receiver Wrench Use to remove cartridge receiver.
20-D, 20-E, 20-G
30-D, 30-E, 30-G — 3/4 x 1/4 in. Reducing Bushing Attach to cartridge receiver spud and connect
to hydrostatic pump hose.
Pre-engineered 26288 Test Head Assembly Insert into shell opening and wrench tighten.
Systems:
26278 Elbow Plug Assembly (10) Select appropriate plug and install into
101-10, 101-20, 26280 Elbow Plug Assembly (20) discharge fitting on shell. (Replace burst disk)
101-30 26282 Elbow Plug Assembly (30)
A-101-10, A-101-20, — 3/4 in. NPT Pipe Plug
A-101-30 (Pre-engineered Systems)
K-101-10, K-101-20,
K-101-30
R-101-10, R-101-20,
R-101-30
PS-30, R-100
LVS-5
LT-A-101-50 — 1 in. NPT Pipe Plug Attach to dry chemical outlet. (Replace burst disk)
(LT-A-101-50)
LVS-15, LVS-30 — 3/4 x 1/4 in. Reducing Bushing Attach to wet chemical outlet and Vent Valve.
LT-A-101-125 — 1 1/2 x 1/4 in. Reducing Bushing Attach to dry chemical outlet and Vent Valve.
LT-A-101-250 — 1/4 in. Vent Plug Replace burst disk with pipe plug.
10580 Vent Valve Connect to reducing bushing.
CAUTION: All test fittings are to be high pressure (3000 psi (207 bar)) steel construction.
Hydrostatic Test Instructions HYDROSTATIC TESTINg
2012-DEC-20 REV. 05 PAGE 9
Components
SPANNER WRENCH
PART NO. 16511
TEST HEAD
ASSEMBLY
TEST HEAD ASSEMBLY
PART NO. 26288
ATTACH
HOSE TO
HYDROSTATIC REMOVE BURST
PUMP DISK, ATTACH ATTACH ATTACH
REDUCING HOSE TO REDUCING
BUSHING AND HYDROSTATIC BUSHING
VENT VALVE PUMP AND VENT
VALVE
1 X 1/4 IN.
REDUCING BUSHING
009059 009060
Extinguisher
Identification Part No. Description Directions
Stationary and
Wheeled Units:
150-B, — 3/8 x 1/4 in. Reducing Bushing Select correct bushing and attach to
150-C, — 1/2 x 1/4 in. Reducing Bushing Vent Valve.
150-D
AR-33-D — 1/4 in. Pipe Plug Replace burst disk with pipe plug.
(Model D units)
Halon Wheeled
Units:
H-150-D 76437 Test Head Assembly Attach to shell fill opening, hand tighten.
Connect to hydrostatic pump hose.
CAUTION: All test fittings are to be high pressure (3000 psi (207 bar)) steel construction.
Hydrostatic Test Instructions HYDROSTATIC TESTINg
2012-DEC-20 REV. 05 PAGE 11
Components
VENT VALVE,
PART NO. 10580
GAS INLET
SPUD
DRY CHEMICAL
1/2 X 1/4 IN. OR 3/8 X 1/4 IN.
OUTLET
1 X 1/4 IN. STEEL REDUCING BUSHING
REDUCING BUSHING AND VENT VALVE,
PART NO. 10580
HOSE TO
HYDROSTATIC
PUMP
Extinguisher
Identification Part No. Description Directions
SENTRY:
SY-02, 26292 Test Head Assembly Select appropriate assembly and attach
SY-0515, SY-0516 (Small) to shell fill opening; hand tighten.
SY-0517, SY-0521
SY-0531, SY-0635 Connect hydrostatic hose to assembly.
Pre-engineered
Systems:
CAUTION: All test fittings are to be high pressure (3000 psi (207 bar)) steel construction.
Hydrostatic Test Instructions HYDROSTATIC TESTINg
2012-DEC-20 REV. 05 PAGE 13
Components
TEST HEAD
ASSEMBLY
VENT VALVE, VENT VALVE,
PART NO. PART NO.
10580 10580
HOSE TO
HYDRO-
TEST TEST STATIC
ADAPTOR, ADAPTOR, PUMP
PART NO. VENT VALVE, PART NO. VENT VALVE,
26293 PART NO. 419112 PART NO.
10580 10580
Extinguisher
Identification Part No. Description Directions
SENTRY:
SS-2 1/2, 26285 Test Head Assembly (SS-2 1/2) Select appropriate assembly/adaptor and
attach to shell fill opening; hand tighten.
SS-2 1/2-B (SY-0261), 26283 Test Head Assembly Connect hydrostatic hose to assembly.
SY-0262 (Water),
R-102 (External
threads)
K01, W02 430074 Test Head Assembly Connect hydrostatic hose to assembly
FE13NM
CAUTION: All test fittings are to be high pressure (3000 psi (207 bar)) steel construction.
Hydrostatic Test Instructions HYDROSTATIC TESTINg
2012-DEC-20 REV. 05 PAGE 15
Components
VENT VALVE,
VENT VALVE, PART NO. 10580
PART NO. 10580
TEST
ADAPTOR, TEST
PART NO. ADAPTOR,
26286 PART NO.
26284
GASKET, PART
NO. 26297
GASKET
TEST HEAD ASSEMBLY, PART NO. 26337
PART NO. 26285 SS-2 1/2 TEST HEAD ASSEMBLY, SS-2 1/2B
PART NO. 26283 SY-0261
SY-0262
R-102
HYDROSTATIC TESTINg Hydrostatic Test Instructions
PAGE 16 REV. 05 2012-DEC-20
! CAUTION
FLEXIBLE HOSE
WITH CLAMPS
3. Examine the hose, hose couplings and “O” ring (when includ-
ed). Replace any hose that has cuts, abrasions, cracks, or a
deformed exterior. Replace couplings that appear corroded,
cracked, cross-threaded or worn. Replace “O” ring if neces-
sary.
4. Assemble the appropriate coupling/adaptor (see Table 3, col- HOSE FITTINGS
umn A) to the vent valve and connect the assembly to one
end of the hose. TYPICAL HOSE DRYINg SET-UP
5. On the other hose end attach designated coupling/adaptor FIgURE 3
(see Table 3, column B) and connect to the hydrostatic pump
hose (see Figure 2). 11. Reconnect nozzle to hose and return the complete assembly,
to its original extinguisher shell.
A – COUPLING/ADAPTOR B – COUPLING/ADAPTOR
HOSE TO
VENT VALVE, HYDROSTATIC PUMP
PART NO. 10580
FIgURE 2
6. Place the fitted hose assembly in an appropriate test cage; or
place a substantial shield between the hose and all persons
in the area.
! CAUTION
Position the vent valve slightly higher than the balance of
the assembly to make certain all air is removed before test.
7. Open vent valve and pump water into the hose. When water
starts to flow freely and all entrapped air is bled off, close the
vent valve.
8. Apply pressure at a rate-of-pressure rise to reach the test
pressure listed in Table 1 on pages 2-5 within 1 minute. Then
maintain the test pressure for another full minute, observing
the hose and couplings for any distortion or leakage. If no dis-
tortion or leakage is noted and the test pressure has not
dropped, the hydrostatic test is successful. Stop the hydro-
static pump and open the vent valve to relieve the pressure in
the hose.
Note: Any hose assembly that fails this hydrostatic test must
be destroyed to prevent its further use in connection with a
pressure generating device.
9. Disconnect all test fittings and pour the water from the hose
assembly.
Hydrostatic Test Instructions HYDROSTATIC TESTINg
2012-DEC-20 REV. 05 PAGE 17
5 (Pre-1968 shells) ––– 3/8 x 1/4 in. NPT Reducing Coupling ––– 3/8 x 1/4 in. NPT Reducing Coupling
5 ––– 3/8 x 1/4 in. NPT Reducing Coupling 16178 Hose Adaptor
10-C, 10-E, 10-G ––– 3/8 x 1/4 in. NPT Reducing Coupling 16178 Hose Adaptor
PIRANHA ––– 3/8 x 1/4 in. NPT Reducing Coupling ––– 3/8 x 1/4 in. NPT Reducing Coupling
R-102
PIRANHA Water Hose ––– 1 x 1/4 in. NPT Reducing Coupling ––– 1 x 1/4 in. NPT Reducing Coupling
IND-X, SPA-50 ––– 1 x 1/4 in. Reducing Coupling ––– 1 x 1/4 in. Reducing Coupling
CAUTION: All test fittings are to be high pressure (3000 psi (207 bar)) steel construction.
HYDROSTATIC TESTINg Hydrostatic Test Instructions
PAGE 18 REV. 05 2012-DEC-20
HOSE TO
HYDROSTATIC PUMP
VENT VALVE,
PART NO. 10580
ADAPTOR, ADAPTOR,
PART NO. 10583 PART NO. 10583
VENT VALVE,
PART NO. 10580
HOSE TO HOSE TO
HYDROSTATIC HYDROSTATIC
PUMP PUMP
Form No. F-7602-05 Copyright © 2012 Tyco Fire Products LP. All rights reserved.
715-735-7411
MARINETTE, WI 54143-2542
TYCO FIRE PROTECTION PRODUCTS