Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 12

FM-200 Calculation

Based on NFPA 2001

FM-200 Weight (Lbs) : V/s x C/(100-C)


V = Volume (m³ or ft³)
s = Specific Vol 0.1269 + (0.0005 x t) → Metric
s = Specific Vol 1.885 + (0.0046 x t) → Imperial
t = Temperature (°C or °F)
C = Design Concentration (% v/v)

Note:
- Minimum Design Concentration for Fire Class A 6.7% v/v
- Estimated Air Conditioned Room Temperature Ambient is 10°C (50°F)

PROBLEM 1-1

FM-200 Calculation
- Metric - - Imperial -
Width 1.00 m 3.28 ft
Length 1.00 m 3.28 ft
Height 200.00 m 656.17 ft
Volume (W x L x H) 200.00 m³ 7,062.87 ft³
Temperature ( t ) 10 °C 50 °F
Design Concentration ( C ) 6.7 % v/v 6.7 % v/v
Specific Volume ( s ) 0.1319 m³/kg 2.115 ft³/lb

Weight (V/s){C/(100-C)} 108.89 Kgs 239.81 Lbs


FM-200 Agent Required 109 Kgs 240 Lbs
FM-200 Calculation
Based on NFPA 2001

FM-200 Weight (Lbs) : V/s x C/(100-C)


V = Volume (m³ or ft³)
s = Specific Vol 0.1269 + (0.0005 x t) → Metric
s = Specific Vol 1.885 + (0.0046 x t) → Imperial
t = Temperature (°C or °F)
C = Design Concentration (% v/v)

Note:
- Minimum Design Concentration for Fire Class A 6.7% v/v
- Estimated Air Conditioned Room Temperature Ambient is 20°C (68°F)

PROBLEM 1-2

FM-200 Calculation
- Metric - - Imperial -
Width 1.00 m 3.28 ft
Length 1.00 m 3.28 ft
Height 200.00 m 656.17 ft
Volume (W x L x H) 200.00 m³ 7,062.87 ft³
Temperature ( t ) 20 °C 68 °F
Design Concentration ( C ) 6.7 % v/v 6.7 % v/v
Specific Volume ( s ) 0.1369 m³/kg 2.1978 ft³/lb

Weight (V/s){C/(100-C)} 104.91 Kgs 230.77 Lbs


FM-200 Agent Required 105 Kgs 231 Lbs
FM-200 Weight (Lbs) : V/s x C/(100-C)
V = Volume (m³ or ft³)
s = Specific Vol 0.1269 + (0.0005 x t) → Metric
s = Specific Vol 1.885 + (0.0046 x t) → Imperial
t = Temperature (°C or °F)
C = Design Concentration (% v/v)

Note:
- Minimum Design Concentration for Fire Class A 6.7% v/v
- Estimated Air Conditioned Room Temperature Ambient is 10°C (50°F)

PROBLEM 2-1

FM-200 Calculation
- Metric - - Imperial -
Width 1.00 m 3.28 ft
Length 1.00 m 3.28 ft
Height 200.00 m 656.17 ft
Volume (W x L x H) 200.00 m³ 7,062.87 ft³
Temperature ( t ) 10 °C 50 °F
Design Concentration ( C ) 6.7 % v/v 6.7 % v/v
Specific Volume ( s ) 0.1319 m³/kg 2.115 ft³/lb
Altitude Location 2,700 Mdpl
2,700 Meter
Atmospheric Correction Factor (Al) 0.89

Weight (V/s){C/(100-C)} x Al 96.91 Kgs 213.43 Lbs


NOVEC 1230 Agent Required 97 Kgs 214 Lbs
FM-200 Calculation
Based on NFPA 2001

FM-200 Weight (Lbs) : V/s x C/(100-C)


V = Volume (m³ or ft³)
s = Specific Vol 0.1269 + (0.0005 x t) → Metric
s = Specific Vol 1.885 + (0.0046 x t) → Imperial
t = Temperature (°C or °F)
C = Design Concentration (% v/v)

Note:
- Minimum Design Concentration for Fire Class A 6.7% v/v
- Estimated Air Conditioned Room Temperature Ambient is 20°C (68°F)

PROBLEM 2-2

FM-200 Calculation
- Metric - - Imperial -
Width 1.00 m 3.28 ft
Length 1.00 m 3.28 ft
Height 200.00 m 656.17 ft
Volume (W x L x H) 200.00 m³ 7,062.87 ft³
Temperature ( t ) 20 °C 68 °F
Design Concentration ( C ) 6.7 % v/v 6.7 % v/v
Specific Volume ( s ) 0.1369 m³/kg 2.1978 ft³/lb
Altitude Location 2,700 Mdpl
2,700 Meter
Atmospheric Correction Factor (Al) 0.89

Weight (V/s){C/(100-C)} x Al 93.37 Kgs 205.39 Lbs


NOVEC 1230 Agent Required 94 Kgs 206 Lbs
PROBLEM 3

No Description

1 Room A have agent quantity = 80 kg


2 Room B have agent quantity = 45 kg
Total agent quantity (1+2) = 125 kg

Precentage gas in Room A = 64 %


Precentage gas in Room B = 36 %

Bull Tee we use = 64 % in Room A


= 36 % in Room B
in Room A 70%
in Room B 30%
https://st1.zoom.us/web_client/in43ub/html/externalLinkPage.html?ref=https://sfpe.connectedcommunit