DOCUMENT HISTORY & REVISION

DOCUMENT DESCRIPTION & REFERENCES Supplier Review Stamp

CLIENT NAME: SENSYO PHARMATECH

PROJECT LOCATION : BEN SLIMANE

PROJECT DESCRIPTION : Travaux de VRD et Constructions en TCE du Projet Lion 1

JE PROJECT NUMBER Q5485

PURCHASE ORDER REFERENCE : 3305-22

REQUISITION REFERENCE :

OTHER REFERENCE (tag, unit) :

DISCIPLINE DOCUMENT TITLE

PR Fiche de selection Rooftop

SGTM Document Number


LOGO SGTM
PR-E101-0093

JESA Document Number


SHORE 27, CASABLANCA NEARSHORE PARK, 1100 BD AL QODS, Casablanca 20270.
Tél: +212 (0)5 22 87 70 00 / +212 (0)5 22 87 71 50 Q5485-00-SGTM-3305-PR-E101-0093-00
Fax: +212 (0)5 22 87 72 34

SENSYO Document Number ( if applicable)

HELP JESA DOCUMENT Discipline


Project Num Subproject Sender Code P.O Number Doc Type Sequence JESA Rev
Please Refer to Annex Q, L & DC Procedure NUMBERING SYSTEM Code
. Shall you need help to fill-in this cover page, Example (Trigram is unique to each
please contact JESA Document Controller.
contractor) Q5485 00 SGTM 3305 PR E101 0093 00

17/03/2022 1ère émission 0

Date Description - Revision Subject Prepared by Checked by Approved by Cont Rev JESA Rev
Job Name: Rooftop copy Unit Tag: EIH 085 V1-2
Prepared For: Quantity: 1

Unit Overview
Model IH085
Pre-charged factory refrigerant
Refrigerant
HFC-410A
Unit application Reversible Heat pump
Compressor type Scroll
Auxiliary heat type Electrical heat
Heat recovery type Without
Eurovent EER Energy class B
Eurovent COP Energy class B
Eurovent Seasonal Efficiency
169.80 % Compliant
Class/Cool
Eurovent Seasonal Efficiency
133.00 % Compliant
Class/Heat
Electrical supply 400 Volt 3 Phases 50Hz
Pre-charged factory refrigerant
Refrigerant
HFC-410A

Project Conditions
Cooling Heating
Design supply airflow 19200.00 m3/hr 19200.00 m3/hr
Fresh air 20.00 % /
Available static pressure supply 200.0 Pa / 150.0 Pa
Outdoor air ambient temperature dry bulb 45.0 C 6.0 C
Outdoor air relative humidity 40.83 % 90.00 %
Return air ambient temperature dry bulb 24.0 C 20.0 C
Return air relative humidity 40.00 % 50.00 %

Global Performance data


Cooling Heating
Total Gross capacity 77.47 kW 114.15 kW
Total Net capacity 71.37 kW 120.14 kW
Total Absorbed power 41.26 kW 63.54 kW
Compressor absorbed power 34.89 kW 18.58 kW
Supply fan absorbed power 6.10 kW 6.10 kW
Specific fan power 1.1 W per l/s 1.1 W per l/s
Gross EER / COP 1.878 kW/kW 1.797 kW/kW
Net EER / COP 1.730 kW/kW 1.891 kW/kW
Supply air temperature (dry bulb) 16.0 C 31.0 C

Unit Performance Data


Cooling Heating
Gross cooling capacity 77.47 kW 76.75 kW
Net cooling capacity 71.37 kW 82.75 kW
Net Sensible Heat Ratio 1.00 1.00
Total absorbed power 41.26 kW 26.04 kW
Compressor absorbed power 34.89 kW 18.58 kW
Gross EER / COP 1.878 kW/kW 2.948 kW/kW
Net EER / COP 1.730 kW/kW 3.178 kW/kW
CompEERCOP 2.263 kW/kW 4.217 kW/kW
Mixed air temperature (dry bulb) 28.2 C 17.2 C
Mixed air relative humidity 40.40 % 54.78 %
Supply air temperature (dry bulb) 16.0 C 31.0 C
*according to EN14581:2018

2022/03/07 17:32:21 Trane® Select Assist™ Version: 257 The certified standard performances and the certified software tool version can be verified in http://www.eurovent-certification.com Page 1 of 3
Job Name: Rooftop copy Unit Tag: EIH 085 V1-2
Prepared For: Quantity: 1

Auxiliary Heating - Electric Heat


Aux heat only Total
Net heating capacity 43.49 kW 120.25 kW
Entering air temperature (dry bulb) 17.2 C 31.0 C
Leaving air temperature (dry bulb) 23.5 C 36.4 C

Dehumidification
Post-heating type Electrical heat
Condensate water maximum rate 23.45 kg/hr

Acoustics
Lpa Lwa
Outdoor N/A 85 dBA
Return N/A 84 dBA
Supply N/A 87 dBA
63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
Outdoor 60 dB 70 dB 74 dB 79 dB 82 dB 76 dB 72 dB 63 dB
Return 67 dB 75 dB 74 dB 70 dB 71 dB 78 dB 79 dB 63 dB
Supply 70 dB 78 dB 76 dB 79 dB 77 dB 80 dB 82 dB 65 dB
Lwa: sound power level dB(A)
Lpa: sound pressure level at 10 meters dB(A)
Sound power level measured in accordance with ISO 3744. Sound values according to EN12102.Tolerance of +/- 3 dB(A)

General data
Refrigerant Pre-charged factory refrigerant HFC-410A
Refrigerant GWP 1924
Number of circuit 2
Oil charge per circuit 3.50 L
Compressor quantity 4
Compressor type Scroll
Indoor fan type EC plug fan
Number of indoor fans 2
Filters G4 (isoc.-65%,5cm) + F7 (ePM01-55%,10cm)
Outdoor fan type Axial
Number of outdoor fans 4
Operating map Standard ambient cooling mode (10/46 C)

Electrical data
Electrical supply 400 Volt 3 Phases 50Hz
Maximum running current 127.20 A
Maximum power at maximum current 82.79 kW
Starting current 214.30 A

2022/03/07 17:32:21 Trane® Select Assist™ Version: 257 The certified standard performances and the certified software tool version can be verified in http://www.eurovent-certification.com Page 2 of 3
Job Name: Rooftop copy Unit Tag: EIH 085 V1-2
Prepared For: Quantity: 1

Unit dimensions

Flow configuration (supply / return) Down Flow


Lenght 3890 mm
Width 2250 mm
Height 1585 mm
Operating weight 1320 kg
Note: weight and dimensions values are estimated. Please consult product documentation prior to transportation.

Additional Documentation
https://www.trane.com/commercial/europe/uk/en/products-
Airfinity
systems/equipment/rooftops/airfinity.html
https://www.trane.com/litweb/Litweb.aspx?#/category/bd13efa5-a5bf-4f0a-
afb4-9eab178d9081/range/86b264f9-7f83-4580-955d-
ErP datasheets
b22a10051387/model/0dba5f0e-f8f0-457b-a326-
c80b483eee9c/section/13cdc0e5-73a5-41fe-8025-6deaba71e6ea

Model Number
EIH085S8D**EXD1ABXAE1BBXX1X1XE**XX1XXXXXXXXXA*

2022/03/07 17:32:21 Trane® Select Assist™ Version: 257 The certified standard performances and the certified software tool version can be verified in http://www.eurovent-certification.com Page 3 of 3