Professional Documents
Culture Documents
Clarification No3
Clarification No3
Clarification No3
LOT 2: SUPPLY OF LV and MV UNDERGROUND CABLES (COPPER) and ACCESSORIES. 1. The 15kV
Heat-Shrinkable Termination Kit - The descriptions are 15kV, while in the GTP requirements, the
rated voltages are 24kV. Please indicate which one is correct.
Response: Yes,both are correct. The 15kV is the nominal(normal) operating voltage while 24kV is the
rated voltage; this means that the heat shrinkable termination kit should be designed to withstand
24kV without failure
2. Likewise, the 30kV Heat-Shrinkable Termination Kit – the GTP rated voltages are 36kV. Please
indicate which one is correct.
Response: Yes, both are correct. The 30kV is the nominal(normal) operating voltage while 36Kv is
the rated voltage; this means that the heat shrinkable termination kit should be designed to
withstand 36Kv without failure
LOT 4: SUPPLY OF LV PROTECTION & LV CURRENT TRANSFORMERS. 1. Please indicate what the
yellow highlighted terms mean. See attached highlighted in yellow! LV fuse 63A, T00 LV fuse 100A,T2
Three phases, 3-poles HRC fuse base
2. IEC 60269-4 - We believe that the mentioned standards are for Semiconductor fuses - Please
confirm & state correct standard.
Response: please refer to the following standards: IEC 60269-1 and -2 or equivalent