Easergy P3: Quick Start - IEC
Easergy P3: Quick Start - IEC
P3U_EN_QS_IEC+07
www.schneider-electric.com
Table of Contents Universal Relays P3U10, P3U20 and P3U30
Table of Contents
1 About this manual.......................................................................... 8
3 Operational safety........................................................................ 12
3.1 Electrical safety...............................................................................................12
3.2 Device handling.............................................................................................. 12
3.3 Electrostatic discharge....................................................................................12
4 Wiring........................................................................................... 13
4.1 Installing connections......................................................................................13
4.2 Checking the wiring.........................................................................................13
5 Energizing.................................................................................... 14
6 Front panel................................................................................... 15
6.1 Push-buttons...................................................................................................15
6.2 LED indicators.................................................................................................16
6.3 Controlling the alarm screen........................................................................... 17
6.4 Accessing operating levels............................................................................. 17
6.5 Adjusting the LCD contrast............................................................................. 17
6.6 Testing the LEDs and LCD screen..................................................................17
6.7 Releasing latches............................................................................................18
6.7.1 Releasing latches using Easergy Pro................................................... 18
6.7.2 Releasing latches using buttons and local panel display......................18
6.7.3 Releasing latches using F1 or F2 buttons............................................ 19
6.8 Controlling an object with selective control..................................................... 19
6.9 Controlling an object with direct control.......................................................... 20
6.10 Menus........................................................................................................... 20
6.10.1 Moving in the menus ..........................................................................22
6.10.2 Local panel messages........................................................................ 23
P3U_EN_QS_IEC+07 3
Universal Relays P3U10, P3U20 and P3U30 Table of Contents
9 Local port..................................................................................... 28
10 Block diagrams...........................................................................29
11 Mounting.....................................................................................40
12 Related documents.................................................................... 44
4 P3U_EN_QS_IEC+07
Legal information Universal Relays P3U10, P3U20 and P3U30
Legal information
The Schneider Electric brand and any registered trademarks of Schneider Electric
Industries SAS referred to in this guide are the sole property of Schneider Electric
SA and its subsidiaries. They may not be used for any purpose without the
owner's permission, given in writing. This guide and its content are protected,
within the meaning of the French intellectual property code (Code de la propriété
intellectuelle français, referred to hereafter as "the Code"), under the laws of
copyright covering texts, drawings and models, as well as by trademark law. You
agree not to reproduce, other than for your own personal, noncommercial use as
defined in the Code, all or part of this guide on any medium whatsoever without
Schneider Electric's permission, given in writing. You also agree not to establish
any hypertext links to this guide or its content. Schneider Electric does not grant
any right or license for the personal and noncommercial use of the guide or its
content, except for a non-exclusive license to consult it on an "as is" basis, at your
own risk. All other rights are reserved.
As standards, specifications and designs change from time to time, please ask for
confirmation of the information given in this publication.
P3U_EN_QS_IEC+07 5
Universal Relays P3U10, P3U20 and P3U30 Safety information
Safety information
Important information
Read these instructions carefully and look at the equipment to become familiar
with the device before trying to install, operate, service or maintain it.
The following special messages may appear throughout this publication or on the
equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result
in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could
result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Please note
Protective grounding
The user is responsible for compliance with all the existing international and
national electrical codes concerning protective grounding of any device.
6 P3U_EN_QS_IEC+07
EU directive and UKCA regulations compliance Universal Relays P3U10, P3U20 and P3U30
P3U_EN_QS_IEC+07 7
Universal Relays P3U10, P3U20 and P3U30 1 About this manual
Carefully read through the mounting instruction of this manual before undertaking
any mounting or wiring work.
8 P3U_EN_QS_IEC+07
2 General product information Universal Relays P3U10, P3U20 and P3U30
• Wear your personal protective equipment (PPE) and comply with the safe
electrical work practices. For clothing, see applicable local standards.
• Only qualified personnel should install this equipment. Such work should
be performed only after reading this entire set of instructions and checking
the technical characteristics of the device.
• NEVER work alone.
• Turn off all power supplying this equipment before working on or inside it.
Consider all sources of power, including the possibility of backfeeding.
• Always use a properly rated voltage sensing device to ensure that all
power is off.
• Do not open the secondary circuit of a live current transformer.
• Always connect the polarity of the current transformer (CT) and the voltage
transformer (VT) and their secondary ground wiring according to the
connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
To identify an Easergy P3 protection relay, see the labels on the package and on
the side of the relay.
P3U_EN_QS_IEC+07 9
Universal Relays P3U10, P3U20 and P3U30 2 General product information
Type: P3U30-5AAA1BCAA 7
REL52003 11
S/N: EB173050011 8 VID: P3U30-016985 12
1. Rated voltage Un
2. Rated frequency fn
7. Order code
8. Serial number
9. Manufacturing date
REL52010 A x1
Protection relay
Relais de protection
B Made in Finland
EB172720007
A REL52010
135716
Easergy - P3 C
D P3U30-5AAA2BDA
E
3 606481 3571 68
SCHNEIDER ELECTRIC
CS30323
F-92506 RUEIL MALMAISON CEDEX
2.3 Storage
Store the relay in its original packaging in a closed, sheltered location with the
following ambient conditions:
10 P3U_EN_QS_IEC+07
2 General product information Universal Relays P3U10, P3U20 and P3U30
2.4 Warranty
This product has a standard warranty of 2 years.
Ask your local Schneider Electric representative about our optional 10-year
warranty. Local conditions and availability apply.
2.5 Complaints
Complaints for manufacturing faults are directed in writing to the relay
manufacturer or the authorized dealer from which the product was acquired. Find
more information from our customers care center (www.schneider-electric.com/
ccc).
P3U_EN_QS_IEC+07 11
Universal Relays P3U10, P3U20 and P3U30 3 Operational safety
3 Operational safety
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Wear your personal protective equipment (PPE) and comply with the safe
electrical work practices. For clothing, see applicable local standards.
• Only qualified personnel should install this equipment. Such work should
be performed only after reading this entire set of instructions and checking
the technical characteristics of the device.
• NEVER work alone.
• Turn off all power supplying this equipment before working on or inside it.
Consider all sources of power, including the possibility of backfeeding.
• Always use a properly rated voltage sensing device to ensure that all
power is off.
• Do not open the secondary circuit of a live current transformer.
• Always connect the polarity of the current transformer (CT) and the voltage
transformer (VT) and their secondary ground wiring according to the
connection diagrams presented in this document.
• Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
12 P3U_EN_QS_IEC+07
4 Wiring Universal Relays P3U10, P3U20 and P3U30
4 Wiring
Perform the wiring work according to national standards and possible
requirements from the customer.
1. Check that the rated values of the relay comply with those of the intended
application.
◦ Check that the rated values of the voltage and current transformer
secondaries comply with those of the device. The rated values can be
found on the serial number label.
◦ Check that the load ability of the outputs is adequate.
2. Earth the relay by connecting an earthing wire using a minimum 2.5 mm2
cross-section (AWG 14) to the device's earthing terminal.
3. Wire the relay to the rest of the system according to the wiring diagrams of the
application.
4. Connect the cable shields of shielded signal cables to the device's earthing
terminal.
P3U_EN_QS_IEC+07 13
Universal Relays P3U10, P3U20 and P3U30 5 Energizing
5 Energizing
DANGER
HAZARD OF ELECTRIC SHOCK
Before connecting the devices, disconnect the supply voltage to the unit.
The external auxiliary voltage UAUX 48 (-20%) – 230 (+10%) V ac/dc or optionally
24 (-20% / +50%) V dc or 24-48 (±20%) V dc for the relay is connected to the pins
X2: 3–4.
NOTE: Check the available power supply range from the device's serial
number label.
NOTICE
LOSS OF PROTECTION OR RISK OF NUISANCE TRIPPING
When the device is switched on, it performs the following initialization sequence
that takes approximately 5 seconds:
• Power LED ON, “Starting ..” on the screen.
• Watchdog contact starts.
The first screen displayed at the end of the sequence is the Mimic view screen.
14 P3U_EN_QS_IEC+07
6 Front panel Universal Relays P3U10, P3U20 and P3U30
6 Front panel
Figure 3 - Easergy P3U10, P3U20 and P3U30 front panel
G
B E
6.1 Push-buttons
Symbol Function
P3U_EN_QS_IEC+07 15
Universal Relays P3U10, P3U20 and P3U30 6 Front panel
Symbol Function
1) The default names of the function buttons are Function button 1 and 2. You can change the names
of the buttons in the Control > Names for function buttons setting view.
When the relay is powered, the power LED is green. During normal use, the
service LED is not active, it activates only when an error occurs or the relay is not
operating correctly. Should this happen, contact your local representative for
further guidance. The service LED and watchdog contact are assigned to work
together. Hardwire the status output into the substation's automation system for
alarm purposes.
To customize the LED texts on the front panel for the user-configurable LEDs, the
text may be created using a template and then printed. The printed text may be
placed in the pockets beside the LEDs.
You can also customize the LED texts that are shown on the screen for active
LEDs via Easergy Pro.
16 P3U_EN_QS_IEC+07
6 Front panel Universal Relays P3U10, P3U20 and P3U30
NOTE: By nature, the LCD display changes its contrast depending on the
ambient temperature. The display may become dark or unreadable at low
temperatures. However, this condition does not affect the proper operation of
the protection or other functions.
1. Press .
2. Press .
P3U_EN_QS_IEC+07 17
Universal Relays P3U10, P3U20 and P3U30 6 Front panel
The relay tests the LCD screen and the functionality of all LEDs.
2. From the Easergy Pro toolbar, select Device > Release all latches.
Alternatively, go to Control > Release latches, and click the Release button.
1. Press .
2. Press .
18 P3U_EN_QS_IEC+07
6 Front panel Universal Relays P3U10, P3U20 and P3U30
You can use the function buttons F1 or F2 to release all latches after configuring
this function in Easergy Pro.
After this, pressing the F1 button on the relay’s front panel releases all
latches.
NOTE: The latch release signal can be activated only if the latched
output is active.
P3U_EN_QS_IEC+07 19
Universal Relays P3U10, P3U20 and P3U30 6 Front panel
– Press to cancel.
• Press to open an object.
– Press to cancel.
When direct control is enabled, the control operation is done without confirmation.
• Press to close an object.
• Press to open an object.
6.10 Menus
This section gives an overview of the menus that you can access via the device's
front panel.
Press the right arrow to access more measurements in the main menu.
20 P3U_EN_QS_IEC+07
6 Front panel Universal Relays P3U10, P3U20 and P3U30
P3U_EN_QS_IEC+07 21
Universal Relays P3U10, P3U20 and P3U30 6 Front panel
OK
ISTART setting
OK OK
NOTE: To enter the parameter edit mode, enter the password. When the
value is in edit mode, its background is dark.
22 P3U_EN_QS_IEC+07
6 Front panel Universal Relays P3U10, P3U20 and P3U30
P3U_EN_QS_IEC+07 23
Universal Relays P3U10, P3U20 and P3U30 7 Easergy Pro setting and configuration tool
• General
• Measurements
• Inputs/outputs
• Protection
• Matrix
• Logs
• Communication
The contents of the tabs depend on the relay type and the selected application
mode.
Easergy Pro stores the relay configuration in a setting file. The configuration of
one physical relay is saved in one setting file. The configurations can be printed
out and saved for later use.
NOTICE
HAZARD OF EQUIPMENT DAMAGE
24 P3U_EN_QS_IEC+07
8 Access to device configuration Universal Relays P3U10, P3U20 and P3U30
1. Press and on the front panel. The Enter password view opens.
P3U_EN_QS_IEC+07 25
Universal Relays P3U10, P3U20 and P3U30 8 Access to device configuration
Select a digit value using , and if the password is longer than one digit,
move to the next digit position using .
NOTE: There are 16 digit positions in the Enter password view. Enter the
password starting from the first digit position.
For example, if the password is 2, you can enter 2***, **2*, ***2, or 0002
to log on.
Related topics
8.4 Password management
HTTP conf 2
FTP conf 2
NOTICE
CYBERSECURITY HAZARD
To improve cybersecurity:
• Change all passwords from their default values when taking the protection
device into use.
• Change all passwords regularly.
• Ensure a minimum level of password complexity according to common
password guidelines.
You can change the password for the operator or configurator user accounts in
the General > Device info setting view in Easergy Pro.
The password can contain letters, digits or other characters in the scope of ASCII
0x21~0x7E. However, the new password cannot be any of the default passwords
(digits 0–4 or 9999).
Follow these guidelines to improve the password complexity and thus device
security:
• Use a password of minimum 8 characters.
• Use alphabetic (uppercase and lowercase) and numeric characters in addition
to symbols.
26 P3U_EN_QS_IEC+07
8 Access to device configuration Universal Relays P3U10, P3U20 and P3U30
Also, all users must be aware of the best practices concerning passwords
including:
• not sharing personal passwords
• not displaying passwords during password entry
• not transmitting passwords in email or by other means
• not saving the passwords on PCs or other devices
• no written passwords on any supports
• regularly reminding users about the best practices concerning passwords
Related topics
8.2 Logging on via the front panel
P3U_EN_QS_IEC+07 27
Universal Relays P3U10, P3U20 and P3U30 9 Local port
9 Local port
The relay has a USB port in the front panel.
The front panel USB type B port is always using the command line protocol for
Easergy Pro.
The speed of the interface is defined in the CONF/DEVICE SETUP menu via the
front panel. The default settings for the relay are 38400/8N1.
Connecting a cable between the PC and the relay creates a virtual com-port. The
default settings for the relay are 38400/8N1. The communication parameter
display on the local display shows the active parameter values for the local port.
It is possible to change the front USB port's bit rate. This setting is visible only on
the relay's local display. The bit rate can be set between 1200 and 187500. This
changes the bit rate of the relay, and the Easergy Pro bit rate has to be set
separately. If the bit rate in the setting tool is incorrect, it takes a longer time to
establish the communication.
NOTE: Use the same bit rate in the relay and the Easergy Pro setting tool.
28 P3U_EN_QS_IEC+07
10 Block diagrams Universal Relays P3U10, P3U20 and P3U30
10 Block diagrams
The status of the output contacts is shown when the relay is energized but none
of the protection, controlling or self-supervision elements are activated.
A
X2:1
U4 X2
X2:2
X2:3 ~
P3U10- 5 AA A2 AAA
X2:4 = X3 T1
X3:17
X3:16
X1:1
IL1
X1 T2 X3:15
6
X1:2
X3:14
X1:3
IL2 T3 X3:13
X1:4
X3:12
X1:5
IL3
3 T4 X3:11
1
X1:6
X3:10
X1:7
I0 5A A1 X3:7
X1:8 X3:9
X1:9 X3:8
I0 1A
X1:10 SF X3:20
X3:19
X3:18
X3:3 DI1 DI X3
X3:4 DI1
X3:5 DI2
X3:6 DI2
A. Front
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
P3U_EN_QS_IEC+07 29
Universal Relays P3U10, P3U20 and P3U30 10 Block diagrams
A
X2:1
U4 X2
X2:2 B
P3U20- 5 AA A2 ABAA
X2:3 ~
X2:4 = X4 X4:1 1)
X4:2 RS - 485 GND
X4:3 2)
X1:1
IL1
X1
X4:4 RS - 485 +
6
X1:2
X4:5 RS - 485 -
X1:3 X4:6 3)
IL2
X1:4
X1:5
3
1
IL3
X1:6 X3 T1
X3:17
X1:7
I0 5A X3:16
X1:8 T2 X3:15
X1:9
I0 1A X3:14
T3 X3:13
X1:10
X3:12
T4 X3:11
X3:3 DI1 DI X3
X3:10
X3:4 DI1
A1 X3:7
X3:5 DI2
X3:9
X3:6 DI2 X3:8
SF X3:20
X4:7 DI3 DI X4 X3:19
X4:8 DI3 X3:18
X4:9 DI4
X4:10 DI4
X4:11 DI5
X4:12 DI5
X4:13 DI6
X4:14 DI6
X4:15 COM DI
X4:16 DI7
X4:17 DI8
X4:18 COM DI
X4:19 DI9
X4:20 DI10
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
30 P3U_EN_QS_IEC+07
10 Block diagrams Universal Relays P3U10, P3U20 and P3U30
A
X2:1
U4 X2
X2:2
~
P3U20- 5 AA A2 ACAA
X2:3
X2:4 = X4
Eth1
X1:1
IL1
X1
6
X1:2 Eth2
X1:3
IL2
X1:4
X1:5
3
1
IL3
X1:6 X3 T1
X3:17
X1:7
I0 5A X3:16
X1:8 T2 X3:15
X1:9
I0 1A X3:14
T3 X3:13
X1:10
X3:12
T4 X3:11
X3:3 DI1 DI X3
X3:10
X3:4 DI1
A1 X3:7
X3:5 DI2
X3:9
X3:6 DI2 X3:8
SF X3:20
X4:1 DI3 DI X4 X3:19
X4:2 DI3 X3:18
X4:3 DI4
X4:4 DI4
X4:5 DI5
X4:6 DI5
X4:7 DI6
X4:8 DI6
X4:9 COM DI
X4:10 DI7
X4:11 DI8
X4:12 COM DI
X4:13 DI9
X4:14 DI10
A. Front
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
P3U_EN_QS_IEC+07 31
Universal Relays P3U10, P3U20 and P3U30 10 Block diagrams
A
X2:1
U4 X2
X2:2
~
P3U20- 5 AA A2 AH AA
X2:3
X2:4 = X4
Eth1
X1:1
IL1
X1
6
X1:2 Eth2
X1:3
IL2
X1:4
X1:5
3 I
1
IL3
X1:6 X3 T1
X3:17
X1:7
I0 5A X3:16
X1:8 T2 X3:15
X1:9
I0 1A X3:14
T3 X3:13
X1:10
X3:12
T4 X3:11
X3:3 DI1 DI X3
X3:10
X3:4 DI1
A1 X3:7
X3:5 DI2
X3:9
X3:6 DI2 X3:8
SF X3:20
X4:20 DI8 DI X4 X3:19
X4:19 DI7 X3:18
X4:18 DI6
X4:17 COM
X4 T5 X4:12
X4:16 DI5
X4:15 DI4 X4:11
T6 X4:10
X4:14 DI3
X4:13 COM X4:9
T7 X4:8
X4:7
A. Front
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
32 P3U_EN_QS_IEC+07
10 Block diagrams Universal Relays P3U10, P3U20 and P3U30
A
X2:1
U4 X2
X2:2
~
P3U20- 5 AA A2 AGAA
X2:3
X2:4 = X4
RS-485
X1:1
IL1
X1
6
X1:2
X1:3
IL2
X1:4
X1:5
IL3
3
1
X1:6 X3 T1
X3:17
X1:7
I0 5A X3:16
X1:8 T2 X3:15
X1:9
I0 1A X3:14
T3 X3:13
X1:10
X3:12
T4 X3:11
X3:3 DI1 DI X3
X3:10
X3:4 DI1
A1 X3:7
X3:5 DI2
X3:9
X3:6 DI2 X3:8
SF X3:20
X4:14 DI8 DI X4 X3:19
X4:13 DI7 X3:18
X4:12 DI6
X4:11 COM
X4 T5 X4:6
X4:10 DI5
X4:9 DI4 X4:5
T6 X4:4
X4:8 DI3
X4:7 COM X4:3
T7 X4:2
X4:1
A. Front
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
P3U_EN_QS_IEC+07 33
Universal Relays P3U10, P3U20 and P3U30 10 Block diagrams
A
X2:1
U4 X2
X2:2 B
P3U30- 5 AA A2 BBA
X2:3 ~
X2:4 = X4 X4:1 1)
X4:2 RS-485 GND
X4:3 2)
X1:1 X1
6
IL1 X4:4 RS-485 +
X1:2
X4:5 RS-485 -
X1:3 X4:6 3)
IL2
X1:4
X1:5
3
1
IL3
X1:6 X3 T1 X3:17
X1:7
Io 5A X3:16
X1:8 T2 X3:15
X1:9
Io 1A X3:14
T3 X3:13
X1:10
X3:12
T4 X3:11
X5:20 X5
U1
X5:19 X3:10
A1 X3:7
X5:18
U2 X3:9
X5:17 X3:8
X5:16
U3
X5:15 SF X3:20
X3:19
X3:18
X3:3 DI1 DI X3
X3:4 DI1
X3:5 DI2
X3:6 DI2 X5
T5 X5:14
X5:13
X4:7 DI3 DI X4
X4:8 DI3
T6 X5:12
X4:9 DI4
X5:11
X4:10 DI4
X4:11 DI5 T7 X5:10
X4:12 DI5
X5:9
X4:13 DI6
X4:14 DI6
X4:15 COM DI
X4:16 DI7
X4:17 DI8
X4:18 COM DI
X4:19 DI9
X4:20 DI10
X5:1 COM DI X5
X5:2 DI11
X5:3 DI12
X5:4 DI13
X5:5 COM DI
X5:6 DI14
X5:7 DI15
X5:8 DI16
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
34 P3U_EN_QS_IEC+07
10 Block diagrams Universal Relays P3U10, P3U20 and P3U30
A
X2:1 ~
P3U30-7AA A2 BBA
X2:2 =
X2
B
X4 X4:1 1)
LPCT
IL1 RJ45
X4:2 RS-485 GND
X4:3 2)
IL2 RJ45
X4:4 RS-485 +
IL3 RJ45
X4:5 RS-485 -
LPVT X4:6 3)
3
1
HUB1 U1, U2, U3
HUB2 U4, U5
X3 T1
X3:17
X1:1 X1
Io 5A X3:16
X1:2 T2 X3:15
X1:3
Io 1A X3:14
T3 X3:13
X1:4
X3:12
T4 X3:11
X3:10
A1 X3:7
X3:9
X3:8
SF X3:20
X3:19
X3:18
X3:3 DI1 DI X3
X3:4 DI1
X3:5 DI2
X3:6 DI2 X5
T5 X5:14
X5:13
X4:7 DI3 DI X4
X4:8 DI3
T6 X5:12
X4:9 DI4
X5:11
X4:10 DI4
X4:11 DI5 T7 X5:10
X4:12 DI5
X5:9
X4:13 DI6
X4:14 DI6
X4:15 COM DI
X4:16 DI7
X4:17 DI8
X4:18 COM DI
X4:19 DI9
X4:20 DI10
X5:1 COM DI X5
X5:2 DI11
X5:3 DI12
X5:4 DI13
X5:5 COM DI
X5:6 DI14
X5:7 DI15
X5:8 DI16
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
P3U_EN_QS_IEC+07 35
Universal Relays P3U10, P3U20 and P3U30 10 Block diagrams
A
X2:1
U4 X2
P3U30- 5 AA A2 BCA
X2:2
X2:3 ~
X2:4 = X4
Eth1
6
X1:1
IL1
X1
X1:2 Eth2
X1:3
IL2
X1:4
3
1
X1:5
IL3
X1:6 X3 T1
X3:17
X1:7
I0 5A X3:16
X1:8 T2 X3:15
X1:9
I0 1A X3:14
T3 X3:13
X1:10
X3:12
T4 X3:11
X5:20 X5
U1
X5:19 X3:10
A1 X3:7
X5:18
U2 X3:9
X5:17 X3:8
X5:16
U3
X5:15 SF X3:20
X3:19
X3:18
X3:3 DI1 DI X3
X3:4 DI1
X3:5 DI2
X3:6 DI2 X5
T5 X5:14
X5:13
X4:1 DI3 DI X4
X4:2 DI3
T6 X5:12
X4:3 DI4
X5:11
X4:4 DI4
X4:5 DI5 T7 X5:10
X4:6 DI5 X5:9
X4:7 DI6
X4:8 DI6
X4:9 COM DI
X4:10 DI7
X4:11 DI8
X4:12 COM DI
X4:13 DI9
X4:14 DI10
X5:1 COM DI X5
X5:2 DI11
X5:3 DI12
X5:4 DI13
X5:5 COM DI
X5:6 DI14
X5:7 DI15
X5:8 DI16
A. Front
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
36 P3U_EN_QS_IEC+07
10 Block diagrams Universal Relays P3U10, P3U20 and P3U30
A
X2:1
U4 X2
X2:2
P3U30-5 AA A2 BHA
X2:3 ~
X2:4 = X4
Eth1
X1:1 X1
6
IL1
X1:2 Eth2
X1:3
IL2
X1:4
X1:5
IL3
X3
3
1
X1:6 T1 X3:17
X1:7
Io 5A X3:16
X1:8 T2 X3:15
X1:9
Io 1A X3:14
T3 X3:13
X1:10
X3:12
T4 X3:11
X5:20 X5
U1 X3:10
X5:19
A1 X3:7
X5:18
U2 X3:9
X5:17 X3:8
X5:16
U3
X5:15 SF X3:20
X3:19
X3:18
X3:3 DI1 DI X3
X3:4 DI1
X3:5 DI2
X3:6 DI2 X4
T5 X4:6
X4:5
A. Front
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
Failure to follow this instruction will result in death or serious injury.
P3U_EN_QS_IEC+07 37
Universal Relays P3U10, P3U20 and P3U30 10 Block diagrams
Terminal X1 X2 X3 X4 X5
characteris
tics
Maximum 2.5
wire cross
(14)
section if
directly
mounted
under screw,
mm2 (AWG)
Maximum 1.5 Nm
wiring screw
(13)
tightening
torgue Nm
(Ib-in)
38 P3U_EN_QS_IEC+07
10 Block diagrams Universal Relays P3U10, P3U20 and P3U30
Terminal X1 X2 X3 X4 X5
characteris
tics
Maximum 1.4
connector
(12)
retention
screw
tightening
torque Nm
(Ib-in)
P3U_EN_QS_IEC+07 39
Universal Relays P3U10, P3U20 and P3U30 11 Mounting
11 Mounting
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Wear your personal protective equipment (PPE) and comply with the safe
electrical work practices. For clothing refer applicable local standards.
• Only qualified personnel should install this equipment. Such work should
be performed only after reading this entire set of instructions and checking
the technical characteristics of the device.
• NEVER work alone.
• Turn off all power supplying this equipment before working on or inside it.
Consider all sources of power, including the possibility of backfeeding.
• Always use a properly rated voltage sensing relay to ensure that all power
is off.
• Do not open the secondary circuit of a live current transformer.
• Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
40 P3U_EN_QS_IEC+07
11 Mounting Universal Relays P3U10, P3U20 and P3U30
A B
P3Uxx-5 214mm / 8.4″ 192mm / 7.6″
P3Uxx-6 226mm / 8.9″ 204mm / 8.0″
mm
128
171
in 5.04 A 2.5 124.5
6.72
155 0.1 4.90
Easergy 6.10
OK
176 137 B
F1 F2 6.94 5.39
O
I
13.25
0.52 144.5 6
5.69 12 6
A B 4.9
9.25 5.0 mm
0.36 0.2 in
28.5
1.12
Ea se rg
y 2 Ea se rg
y
9.5
0.37
120
139 4.72
OK
5.47
OK
F2
F2
F1
9.5 F1
O 0.37 O
I
1. I
0.040-10
- 0.3
9
X1 (P3Uxx-6) X1 (P3Uxx-5) X2, X3, X4, X5
T max. 1.40Nm T max. 1.40Nm T max. 0.6Nm
12lb.in 12lb.in 5.3lb.in
0.8 x 4.0
5/32in x 0.03in
T max. 0.80Nm
7lb.in
> 20
min. 2.5mm2
C 0.79
Ø 4-6mm
y
Ea se rg
y
Ea se rg
Nut M4
7mm 1.5Nm OK
OK
9/32in 13.3Ib in F2
F2
F1
F1
OK
OK
F2
F2 O
O
F1
F1
I
I
OO
II
P3U_EN_QS_IEC+07 41
Universal Relays P3U10, P3U20 and P3U30 11 Mounting
2.5
0.1
A B C
y
Ea se rg Ea se rg
y
rgyy
serg
Ease
Ea
OK
OK
F2
F2
F1 OK
OK
F1
F2
F2
F1
F1
O
O
I
I
OO
II
X1 (P3Uxx-6) 13.25
0.52
T max. 1.40Nm
D 144.5 6
12lb.in 5.69 12 6
4.9 mm
9.25 5.0 in
0.8 x 4.0 0.36 0.2
5/32in x 0.03in
28.5
1.12
X1 (P3Uxx-5) 2 Ea se rg y y
Ea se rg
T max. 1.40Nm 9.5
12lb.in 0.37
0.8 x 4.0 120
5/32in x 0.03in 139 4.72
T max. 0.80Nm
5.47
OK
7lb.in OK
F2
0.4 x 2.5 F2
0.37 O
X2, X3, X4, X5 O
1. I
0.040-12
T max. 0.6Nm I
5.3lb.in - 0.4
7
0.4 x 2.5
> 20
3/32in x 0.015in E 0.79
min. 2.5mm2
y
Ø 4-6mm Ea se rg
y
Ea se rg
OK
OK
Nut M4 F2
F2
7mm 1.5Nm F1
F1
9/32in 13.3Ib in OK
F2
O
O
F1
I
I
CAUTION
HAZARD OF CUTS
Trim the edges of the cut-out plates to remove any jagged edges.
42 P3U_EN_QS_IEC+07
11 Mounting Universal Relays P3U10, P3U20 and P3U30
See "P3 Standard Series facial label instruction" document for more information.
Protective film
NOTICE
RISK OF DESTRUCTION OF THE RELAY
The protective film on the relay's display is plastic and can melt if exposed to
high temperatures intensive sunlight. Remove the protective film after mounting
the relay.
Failure to follow these instructions can result in equipment damage.
P3U_EN_QS_IEC+07 43
Universal Relays P3U10, P3U20 and P3U30 12 Related documents
12 Related documents
Table 7 - Related documents
Document Identification2)
44 P3U_EN_QS_IEC+07
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison - France
Phone: +33 (0) 1 41 29 70 00
www.schneider-electric.com
P3U_EN_QS_IEC+07 — 02/2022