ATN 905&910C&950B&950C&980B Series

Multi-Service Access Equipment


Quick Installation Guide
(IMB Network Cabinet)

Issue: 06
Date: 2019-10-30

HUAWEI TECHNOLOGIES CO., LTD.


Copyright © Huawei Technologies Co., Ltd. 2019. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means
without prior written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions


and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their
respective holders.

Notice
The purchased products, services and features are stipulated by the contract made
between Huawei and the customer. All or part of the products, services and features
described in this document may not be within the purchase scope or the usage scope.
Unless otherwise specified in the contract, all statements, information, and
recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been
made in the preparation of this document to ensure accuracy of the contents, but all
statements, information, and recommendations in this document do not constitute a
warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China
Website: https://www.huawei.com
Email: support@huawei.com
Installation Requirements
Category Example Environment Solutio Reference
n
Class A •Standard central 1.An enclosed space is Normal ATN Series
(Favorable equipment room used. procedure: Quick
environment: An •Residential simple 2.Air conditioners are 1.Install ATN Installation
indoor equipment room provided to adjust the in cabinet. Guide
installation •Outdoor and temperature and humidity. 2.Install ATN (19inch&21inch
environment properly enclosed, 3.The environment is in rack. Cabinet)
with both the a small room or clean with little dust.
temperature and compartment with 4.Outdoor independent
humidity strictly air conditioners space meets the
controlled) preceding conditions.

Class B •Corridor of a 1.An unsealed space is Use an IMB ATN Series


(Common residential building well-ventilated, but not network Quick
environment: An •Top-floor elevator air-conditioned. cabinet to Installation
environment •Open office area 2.There is a litter dusty. improve Guide (IMB
with •Utility room 3.The space is protected security. Network
temperature and from rain and pollution Cabinet)
humidity not sources.
under control,
while away from
oceans and
pollution
sources)

Class C •On the outdoor 1.Installed outdoor, on Use an ATN R01S100


(Poor floor, far away from rooftop, ground floor, or outdoor Cabinet Quick
environment: pollution sources rack over the ground. cabinet to Installation
Close to oceans and oceans 2.The space is dusty and improve Guide
or pollution •Roof areas, far not rain-proof. security.(Cab ATN R01S200
sources, with the away from 3.The space is away from inets with Cabinet Quick
temperature and pollution sources pollution sources. heat Installation
humidity not and oceans exchangers Guide
under control) are
recommende
d.)
•Outdoor areas, Non-class A areas, such as Use an ATN Series
close to pollution close to pollution sources, outdoor Quick
sources and oceans coastal land, and islands. cabinet with Installation
•Indoor areas, close an air Guide (APM30H)
to pollution sources conditioner
(automobile or heat
exhaust) exchanger.

NOTE
1.Class C environment (poor): In the environment close to pollution sources and oceans, outdoor cabinets
with heat exchangers or air conditioners must be used to effectively isolate the device environment from the
atmosphere environment close to oceans or pollution sources. In the outdoor environment far away from
pollution sources and oceans, outdoor cabinets, especially those with heat exchangers or air
conditioners, must be used to improve security. Direct-ventilation cabinets can be used in this environment,
with ATN devices being installed far away from the air intake vents of the cabinets.)
2.Class B environment (common): In an indoor environment, network cabinets can be used to minimize
humidity risks. The measures applicable to a Class C environment can be used for a Class B
environment, but the measures applicable to a Class B environment cannot be used for a Class C
environment.
Installation Flow

Start

Page 1 Precautions
Preparation
for
installation
Page 2 Tools for Installation

Pages Introduction to the Page 8 Overview of IMB


3-7 Chassis

Pages Introduction to IMB Pages Installation Clearance


8-9 (Indoor Mini Box) 8-9 Requirements

Pages Introduction to AC/DC


10-11 power system

Pages Installing the IMB on the


12-13 Wall

Installing Devices in the


Page 14
IMB

Pages Connecting and Routing


15-17 Cables

Page 18 Installation Checklist

Powering On the
Page 19
Equipment

Installing the Cover Plate


Page 20
for the IMB

Page 21 Appendixes

End
Precautions

NOTE
This document provides simple and distinctive guidelines for quick hardware installation of the ATN
905&910C&950B&950C&980B.
Based on the height of a device, the ATN 910C-A&910C-B&910C-D&910C-F&910C-G are
considered 1 U devices, and the ATN 950B&950C are considered 2 U devices, and the ATN 980B is
considered 3.5 U device. 1 U = 44.45 mm (1.75 in.)
As the installation methods are similar, the fixed ATN910C-A is used as an example for the 1 U
device, the board-inserted ATN 950B is used as an example for the 2 U device, and the board-
inserted ATN 980C is used as an example for the 3.5 U device. The installation differences are
specially described in this document.
This document does not describe pre-delivery assembly. This document only describes procedures
for onsite installation.

CAUTION

Electrostatic Discharge
Wear ESD gloves or Antistatic Wrist Strap prior to contact
with the equipment or before handling the plug-boards,
boards, and IC chips to prevent damage to sensitive
components caused by electrostatic discharge from the
human body.

CAUTION

Bundling cables

Binding intervals between cable ties or optical fiber binding straps inside the cabinet cannot exceed
250 mm.

CAUTION

Pre-Installation Check

Verify that the equipment room, power supply, ground cables and optical cables are ready for installation.
Start the installation according to the engineering design documents after confirming that conditions are
met. Refer to the Installation Guide for information about specific operational requirements and technical
specifications.

1
Tools for Installation

Tape Measure Level Philips Screwdriver Flathead Screwdriver Rubber hammer


(M2-M6) (M2-M6)

Percussion Drill Torque Wrench Ratchet Crimp Tool Cable Cutter Wire Stripper

Network Cable Diagonal Pliers ESD Gloves Antistatic Wrist Strap Coax Stripper
Crimping Pliers

Heat Gun Marker Pen Paper Knife Multimeter Cable Tester

Binding Strap Insulation Tape Cleaner

2
Introduction to the 1U Height Chassis

ATN 905-F

Power supply USB NM interface NM interface


interface (Console interface)
FE/GE electrical FE/GE optical/electrical FE/GE optical interface
interface interface

ATN 910C-A

10

DC Power supply Protective 10GE optical FE/GE/10GE optical


interface grounding point interface interface
FE/GE optical NM interface Clock input/output Alarm input/output
interface (Console interface) interface interface
Time input/output 10 USB debugging
interface interface

3
ATN 910C-B

11

10

DC Power supply Protective 10GE optical FE/GE/10GE optical


interface grounding point interface interface
FE/GE optical NM interface Clock input/output Alarm input/output
interface (Console interface interface interface
Time input/output 10 USB debugging 11 FE/GE electrical
interface interface interface

ATN 910C-D

11

10

DC Power supply PGND point 10GE optical FE/GE/10GE optical


interface interface interface
FE/GE electrical NM interface Clock input/output Alarm input/output
interface (Console interface) interface interface
Time input/output 10 USB NM interface 11 E1 service signal
interface input/output interface

4
ATN 910C-F

10
DC Power supply PGND point FE/GE/10GE optical FE/GE optical interface
interface interface
FE/GE electrical NM interface Clock input/output Alarm input/output
interface (Console interface) interface interface
Time input/output
interface
10 USB NM interface

ATN 910C-G

10

DC Power supply PGND point FE/GE/10GE optical FE/GE/10GE optical


interface interface interface (Long-distance
optical modules are not
FE/GE optical NM interface Clock input/output supported.)
interface (Console interface) interface

Alarm input/output Time input/output FE/GE electrical


interface interface 10 interface

10

AC Power supply PGND point FE/GE/10GE optical FE/GE/10GE optical


interface interface interface (Long-distance
NM interface optical modules are not
FE/GE optical Clock input/output supported.)
interface (Console interface) interface
Alarm input/output Time input/output FE/GE electrical
interface interface 10 interface

5
Introduction to the 2U Height Chassis
ATN 950B

10

Power supply Anti-static wrist NM interface External clock interface


interface interface

Time interface 10GE optical Switch interface Protective


interface grounding point

Ethernet Service 10 FE/GE optical


Interface interface

ATN 950C

10

Power supply Anti-static wrist NM interface External clock interface


interface interface

Time interface 10GE optical Switch interface Protective


interface grounding point

Ethernet Service 10 10GE optical


Interface interface

6
ATN 980B

10

11 12 13

Protective FE/GE electrical interface 1GE optical 10GE optical


grounding point interface interface
Clock test interface Console interface Management network External clock interface
port
External time interface 10 Alarm input/output ESD wrist strap 12 Power supply interface
interface
11
interface
13 E1 interface

7
Introduction to IMB (Indoor Mini Box)

Overview of IMB

1. NO STEPPING sign 2. Protection plate

3. Slot assignment label 4. Cover plate

Installation Clearance Requirements

1.Installation clearance requirements for the IMB right-side-mounted on the wall

Recommended installation clearance Minimum installation clearance

8
Installation Clearance Requirements for the IMB

2.Installation clearance requirements for the IMB left-side-mounted on the wall

Recommended installation clearance Minimum installation clearance

3.Installation clearance requirements for the IMB back-mounted on the wall

Recommended installation clearance Minimum installation clearance

9
Introduction to AC/DC power system

AC/DC power system (ETP4830-4815AF power system)

When an ATN device requires DC power but only the AC power module is available, use the ETP4830-
4815AF to convert the AC power to DC power.

Fuse of battery

Output terminals of
load 1
Output terminals of
load 2
Output terminals of
Monitoring module Rectifier module battery

Fuse of load 1
Fuse of load 2

Mapping between the fuses of the output tributaries and the load tributaries

Fuse for the Output Tributary Load Tributary


FU-1 (20A) Load1 (20A)
FU-2 (20A) Load2 (20A)
FU-BT (20A) Battery (20A)

Pin assignment of a monitoring cable


•Connect the device to the ETP4830-4815AF power system with a monitoring cable, which is a standard non-shielded
network cable, so that the NMS can detect the working status of the power system.

•Connect one end of a monitoring cable to the TOD port or the CLK0/TOD0 port on the device and the other end to an
RJ45 port on the monitoring module of the ETP4830-4815AF power system.

10
AC/DC power system (ETP4830-4815AF power system)

•To ensure that the power supply of the equipment is not interrupted, you can also connect the device to batteries. Then, if
the mains supply is interrupted, the device can be powered by batteries.

•A storage battery array consists of four 12 V -40 Ah storage batteries. The dimensions of each storage battery are 197
mm (W) x 165 mm (D) x 170 mm (H).

•The positive and negative of the ATN are connected to the negative and positive of the ETP4830-4815AF respectively,
and the positive and negative of the storage battery are connected to the positive and negative of the ETP4830-4815AF
respectively.

•The BOM number of the power cable for the ETP4830-4815AF is 04042957. Use the power cable (BOM number:
04042957) to connect the ATN 950B and ETP4830-4815AF for example.
(1) One end of the power cable (BOM number 04042957) has 4 pins. Connect this end to the output interface of load on
the right of the ETP4830-4815AF.
(2) Remove the red-and-black power terminal (BOM number 14180253) of the ATN 950B power cable.
(3) Insert the other end of the power cable (BOM number 04042957) into the red-and-black power terminal (BOM number
14180253) and connect this terminal to the power interface of the ATN 950B.

Connecting the ATN to the ETP4830-4815AF and storage battery.

ATN 950B

ATN 910I

11
Installing the IMB on the Wall

Installing the IMB on the Wall (Side-Mounted)

NOTE
The IMB can be installed with the right side or left side mounting on the wall. The installation methods are
the same. Mounting the right side of the IMB on a wall is used as an example.
Removing the protection plate Installing mounting ears
(1) Insulation washer

(2) Installation positions


for bolts

(1) Protection plate

Marking anchor points Drill holes at the anchor points, and


install expansion bolt assemblies
•Use a level to check that the two anchor holes on the marking
template are on a horizontal plane, place the marking template Before mounting the IMB on a wall, ensure that the wall can
against the wall, and then use a marker to mark anchor points. stand the 1.25kN pull force.
•Holes marked A are used as anchor points. The distance
between the marking plate and the ground is 1000-1200 mm.

Level

Anchor holes

(1) M10x60 bolt (2) Spring washer (3) Flat washer

(4) Expansion tube (5) Insulation washer

Fix the IMB


(1)Insulation washer
(2)Mounting ears

(1) Spring washer


(2) Flat washer
(3) Insulation washer

Place the IMB onto the two bolts at the upper anchor points,
Align the mounting ears at the lower part of the IMB with
and then use a torque wrench to pre-tighten the two bolts
the anchor holes, and then use a torque wrench to tighten the bolts.
until a 20-30 mm length of each bolt is reserved out of the
wall.

12
Installing the IMB on the Wall (Back-Mounted)

Removing the protection plate Installing mounting ears


(1) Insulation washer

(2) Installation positions


for bolts

(1) Protection plate

Marking anchor points Drill holes at the anchor points, and


install expansion bolt assemblies
•Use a level to check that the two anchor holes on the marking
template are on a horizontal plane, place the marking template
Before mounting the IMB on a wall, ensure that the wall can
against the wall, and then use a marker to mark anchor points.
•Holes marked B are used as anchor points. The distance stand the 1.25kN pull force.
between the marking plate and the ground is 1000-1200 mm.

Level

Anchor holes

(1) M10x60 bolt (2) Spring washer (3) Flat washer

(4) Expansion tube (5) Insulation washer

Fix the IMB


(1)Insulation washer
(2)Mounting ears

(1) Spring washer


(2) Flat washer
(3) Insulation washer

Place the IMB onto the two bolts at the upper anchor Align the mounting ears at the lower part of the IMB with the
points, and then use a torque wrench to pre-tighten anchor holes, and then use a torque wrench to tighten the bolts.
the two bolts until a 20-30 mm length of each bolt is
reserved out of the wall.

13
Installing Devices in the IMB

Installing the ATN Chassis

NOTE
•Make sure that the fan unit of the ATN equipment is on the top of the ATN equipment.
•Install the device of the 2 U height on the right of the network cabinet and the device of the 1 U height on
the right or in the middle of the network cabinet.
Slide the chassis along the guide rails into the corresponding slot until it is fully engaged, and then tighten the four
M6x12 bolts on the panel.

(1) Fan Unit

(2) ATN Device

Installing the ETP4830-4815AF Power Device

NOTE
•When an ATN device requires DC power but only the AC power module is available, use the ETP4830-
4815AF to convert the AC power to DC power.
•When installing the ETP4830-4815AF, align the external input power interface on the bottom.

Slide the AC/DC power device along the guide rails into the corresponding slot until it is fully engaged, and then
tighten the four M6 x 12 bolts on the panel.

(1) External Input Power Interface

(2) ETP4830-4815AF power


device

14
Connecting and Routing Cables

1 Common Cables for the Chassis

PGND cable AC power cable DC power cable Fiber

Shielded network cable E1 cable (120-ohm ) E1 cable (75-ohm)

2 Insert power cables into the DC connector

1U-height DC chassis
1U-height chassis (ATN 910C) 2U-height chassis
use a screw to fix the OT
BGND power cable
terminal of the DC power cable Positive pole: +
BGND power cable at the DC power interface -48V power cable
Positive pole: + Negative pole: -

-48V power cable


Negative pole: -
1U DC connector 2U DC connector

- + M2.5
M2

0.4-0.5 N·M
0.22±0.03 N·M

WARNING
The conductor body of the power cable should be completely inserted into the DC connector to
avoid electric shock to the operator.
3 Cable connections in the external AC/DC power supply scenario
NOTE
•Before installing cables, use a marker to mark the two ends so that the two ends of one cable can easily
match each other.
•You must prepare cables according to actual cable routes during the installation.
•A connector has been made at one end for a 10 m long ground cable before shipment. On site, tailor the
cable and make an M6 connector at the other end, as required.
•Attach engineering labels to both ends of each cable after the cable is installed.
•During equipment installation, bundle power cables if they are too long.
Cable Installation Process
1. Install ground cable for the IMB network cabinet. Then install ground cable for the
ETP4830-4815AF power device and ATN equipment.
2. Install external power cables for the ETP4830-4815AF power device.
3. Install power cables between the ETP4830-4815AF power device and ATN
equipment.
4. Install E1 cables.
5. Install Shielded network cables.
6. Install fibers.

2U-height chassis: 1U-height chassis:

Ground cable for the External power cables Ground cable for the
IMB network cabinet ATN equipment
Power cables for the E1 cables Shielded network
ATN equipment cables
Fibers
4 Cable connections in the embedded AC/DC power supply scenario
NOTE
A 2 U device (ATN 950B) is capable of housing an AC/DC power module.

Cable Installation Process


1. Install ground cable for the IMB network cabinet. Then install ground cable for the ATN equipment.
2. Install power cables for ATN equipment.
3. Install E1 cables.
4. Install Shielded network cables.
5. Install fibers.

2U-height chassis:

Ground cable for the IMB External power cables Ground cable for the
network cabinet ATN equipment
E1 cables Shielded network cables Fibers

15
Installation Checklist

No. Item

1 The position for each piece of equipment conforms to the engineering design and meets the space
requirement. Sufficient space is reserved for equipment maintenance.

2 The holes for the frame are in proper contact with the holes for the expansion bolt, and the frame and the
wall surface are in proper horizontal contact.

3 When the IMB network cabinet is installed on the wall, for a single-mode G.657A2 optical fiber, the
bending radius is greater than or equal to 10 mm. The bending radius of a multi-mode A1b optical fiber is
greater than or equal to 30 mm.
4 During equipment installation, all signal cables need to be routed in underfloor mode and then be led out
of the chassis. If the cables are routed in overhead mode, water vapor is condensed to water, which flows
to the cabinet along the cables and then corrodes the boards. As a result, the boards are short-circuited.
5 When routing the power and PGND cables on the bottom of the IMB network cabinet, ensure that the
holes for heat dissipation are not covered.

6 After routing the cables for the equipment, bundle all the cables at the outlet of the cabinet, avoiding stress
generated on the internal cable connectors when the external cables are pulled.

7 Lead fibers out of the cabinet outlet using winding pipes and bundle the winding pipes instead of the fibers
using cable ties.

8 The distance between the bundled fiber and the ATN panel is between 40 mm and 70 mm.

9 There are no connectors or joints on the power cable or PGND cable.。

10 All the power cables and PGND cables are not short-circuited or reversely connected. In addition, no
damaged or broken parts exist.

11 The working grounding and protection grounding of the base station and the surge protection grounding of
the building share one group of grounding conductors.

12 The connector of the signal cable is intact, and no damaged or broken parts exist on the cable.

13 The lugs at both ends of the power cable or the PGND cable are securely soldered or crimped.

14 The bare wire and OT terminal at the wiring terminal are tightly wrapped with the insulation tape or heat
shrink tubing.

15 After all cables are routed, cut parts of the protection plate to seal cable holes if there is spare space in the
cable holes.

16 The surface of the overall equipment is clean and tidy. The exterior paint is intact.

17 The door and lock of the cabinet are proper.

18 All labels, tags, and nameplates are correct, legible, and complete.

16
Powering On the Equipment

1 Powering On the Equipment


CAUTION
Before the equipment is powered on, you must use the multimeter to test whether a short-circuit occurs between
the positive and negative terminals of the PDU.
For a running ATN 910C, you must turn on the switches of both AC power modules operating in 1+1 backup mode.
The board hardware
Use the ATN 905-F as an example for an AC device: is faulty

Indicator State Description

Indicator State Description

PWR On and green The power supply is normal.

Off The power supply fails.

STAT On and green The board is working normally.

On and red The board hardware is faulty.

Off The board is not powered on or created.

Use the ATN 950B as an example for a DC device:

The fan is faulty.


Contact the
engineering
supervisor or
software
engineer.

The power
supply fails.

Mapping relation between indicators and their status

Indicator Indicator Status Status Description

PWR On (green) The power supply is normal.

Off The power supply fails.

FAN On (green) The fan is running normally.

On (red) The fan fails.

Off The fan is not powered on.

17
Installing the Cover Plate for the IMB

Installing the Cover Plate

Fit the tabs on the cover plate into the slots in Tighten the M3×8 bolt on the bottom of the
the IMB cover plate for the IMB

18
Appendixes
1 HW-100-48AC14D-1 Power System

The HW-100-48AC14D-1 power system supports AC power ranging from 90 V to 264 V, and outputs -48 V DC
power for ATN 910I and ATN 910B in natural heat dissipation mode.

Pole Colour of cables


+ Black

- Bule

Single channel of -48 V input power

Two channels of -48 V input power

To provide two channels of -48 V input power, remove the terminal of one channel and
connect the channel to the available binding post in the terminal of the other channel.

CAUTION

Ensure that the positive and negative charges are correctly connected.

19
Huawei Technologies Co., Ltd.
Huawei Industrial Base Bantian Longgang
Shenzhen 518129
People's Republic of China
www.huawei.com