Power Load Calculation Revision-R00: November 2021
Power Load Calculation Revision-R00: November 2021
CALCULATION
REVISION-R00
NOVEMBER 2021
EE-2
1 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR ECEC DATE 25-Nov-2021
PANELBOARD NAME: USS-1 @ 1500 KVA SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 2649.98 Amps.
Main CB Size : ICB = IL x 1.25.0= 2252.48 Amps. ( As per 2017 NFPA 70 @ Table 450.3(A))
EE-3
2 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR ECEC DATE 25-Nov-2021
PANELBOARD NAME: MPG1-B1 @ USS-1 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 400.01 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-4
3 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPG2-B2 @ USS-1 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 422.40 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-5
4 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR ECEC DATE 25-Nov-2021
PANELBOARD NAME: MPF1-B1 @ USS-1 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 386.54 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-6
5 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR ECEC DATE 25-Nov-2021
PANELBOARD NAME: MPF2-B1 @ USS-1 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 425.80 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-7
6 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPS1-B1 @ USS-1 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 387.41 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-8
7 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPS2-B3 @ USS-1 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 426.95 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-9
8 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR ECEC DATE 25-Nov-2021
PANELBOARD NAME: MPA4 @ USS-1 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 316.77 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-10
1 of 9
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR ECEC DATE 25-Nov-2021
PANELBOARD NAME: USS-2 @ 1500 KVA SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 2572.96 Amps.
Main CB Size : ICB = IL x 1.25.0= 2187.02 Amps. ( As per 2017 NFPA 70 @ Table 450.3(A))
EE-11
2 of 9
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPG3-B1/B8 @ USS-2 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 405.17 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-12
3 of 9
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR ECEC DATE 25-Nov-2021
PANELBOARD NAME: MPG4-B1/B8 @ USS-2 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 395.19 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-13
4 of 9
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPF3-B4 @ USS-2 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 432.72 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-14
5 of 9
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR ECEC DATE 25-Nov-2021
PANELBOARD NAME: MPF4-B4 @ USS-2 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 397.22 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-15
6 of 9
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPS3-B4 @ USS-2 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 432.26 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-16
7 of 9
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPS4-B4 @ USS-2 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 397.22 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-17
8 of 9
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPA2-B4 @ USS-2 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 338.50 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-18
9 of 9
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: SDP-1@ USS-2 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 89.15 Amps.
EE-19
1 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: USS-3 @ 1500 KVA SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 1985.26 Amps.
Main CB Size : ICB = IL x 1.25.0= 1687.47 Amps. ( As per 2017 NFPA 70 @ Table 450.3(A))
EE-20
2 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPG5-B5 @ USS-3 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 372.52 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-21
3 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPG6-B5 @ USS-3 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 372.58 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-22
4 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPF5-B5 @ USS-3 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 375.86 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-23
5 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPF6-B5 @ USS-3 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 375.86 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-24
6 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPS5-B5 @ USS-3 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 376.75 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-25
7 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPS6-B5/B6 @ USS-3 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 376.76 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-26
8 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPA3-B5 @ USS-3 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 319.98 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-27
1 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR ECEC DATE 25-Nov-2021
PANELBOARD NAME: USS-4 @ 1500 KVA SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 1984.60 Amps.
Main CB Size : ICB = IL x 1.25.0= 1686.91 Amps. ( As per 2017 NFPA 70 @ Table 450.3(A))
EE-28
2 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPG7-B7 @ USS-4 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 323.05 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-29
3 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPG8-B7 @ USS-4 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 316.68 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-30
4 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPF7-B6 & B7 @ USS-4 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 325.90 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-31
5 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPF8-B7 @ USS-4 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 319.44 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-32
6 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPS7-B6 & B7 @ USS-4 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 326.50 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-33
7 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPS8-B7 @ USS-4 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 320.23 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-34
8 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPA4-B6 & B7 @ USS-4 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 400.52 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-35
1 of 9
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: USS-5 @ 1500 KVA SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 2420.07 Amps.
Main CB Size : ICB = IL x 1.25.0= 2057.06 Amps. ( As per 2017 NFPA 70 @ Table 450.3(A))
EE-36
2 of 9
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPG9-B1/B8 @ USS-5 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 299.73 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-37
3 of 9
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPG10-B8 @ USS-5 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 316.74 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-38
4 of 9
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPF9-B1/B8 @ USS-5 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 311.07 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-39
5 of 9
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPF10-B8 @ USS-5 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 319.35 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-40
6 of 9
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPS9-B1/B8 @ USS-5 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 316.69 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-41
7 of 9
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPS10-B8 @ USS-5 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 320.21 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-42
8 of 9
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPA5-B1/B8 @ USS-5 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 432.15 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-43
9 of 9
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: SDP-2 @ USS-2 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 427.34 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-44
1 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR ECEC DATE 25-Nov-2021
PANELBOARD NAME: USS-6 @ 1500 KVA SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 2154.64 Amps.
Main CB Size : ICB = IL x 1.25.0= 1831.44 Amps. ( As per 2017 NFPA 70 @ Table 450.3(A))
EE-45
2 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPG11-B1 @ USS-6 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 410.98 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-46
3 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: MPG12-B1 @ USS-6 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 318.40 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-47
4 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: SDP-3 @ USS-6 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 392.79 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-48
5 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: EDP-B8 @ USS-6 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 751.71 Amps.
Use : 2 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRAY)
EE-49
6 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: ESDP-1 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 286.79 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)
EE-50
7 of 8
JOB NO. J21-005 DEPARTMENT ELECTRICAL AUTHOR DATE 25-Nov-2021
PANELBOARD NAME: ESDP-2 SERVICE VOLTAGE: 400 Y/230V, 3PH, 4W, 60Hz
Feeder : IF = IL x 1.25 / 0.85 (Derating Factor for XLPE/PVC 90oC Rated Cable @ 50oC Ambient Temp.)
= 233.96 Amps.
Use : 1 Set- 4C x 300 + 120 E XLPE / PVC COPPER CABLE (CABLE TRENCH)