Professional Documents
Culture Documents
OneAsia Digital Infra BKK 20220620 V3
OneAsia Digital Infra BKK 20220620 V3
OneAsia Digital Infra BKK 20220620 V3
1
• Offers end-to-end cloud computing, data center and
connectivity solution to facilitate business digitalization.
North Bangkok
• GFA: 20,000 sqm Shanghai
• Capacity: 20MW • GFA: 26,000 sqm
• Ready-for-Service: Q1 2023 • Capacity: 20MW
• Commenced operation in 2017
• Nantong
• GFA: 130,800 sqm Hong Kong
• Capacity: 80MW • GFA: 16,500 sqm
• Phase I commenced operation in 2021 • Capacity: 20MW
• Ready for Phase II expansion • Commenced operation in 2018
3
North Bangkok
Nava Nakorn Pathumthani Industrial Zone
4
Travelling Distance – OneAsia Data centre to/from Airport and Bangkok
Nava Nakorn to Suvarnabhumi International Airport – Nava Nakorn to Bangkok – 1 hr 7 min.
1hr 12 min.
Site Plan
Nava Nakorn Pathumthani Industrial Zone
Electricity Supply
▪ 4 power substations, distributing 515 MW from Provincial Electricity Authority (PEA)
▪ 185MW Co-Generation Power Station operated by Nava Nakorn Electricity
Generating Company Limited (NNEG)
Telecommunication Services
▪ Underground fiber optic network throughout the industrial zone in addition to all
major mobile providers are available
Security System
▪ Monitoring by CCTVs and security personnel assist by a local police station and a
fire station
Permanent Flood Protection
▪ Permanent Flood Protection System consisted of 5.5 meters corrugated concrete
sheet piles protecting the zone, closed and opened V-Ditch system and 4 pump
stations.
North Bangkok
Nava Nakorn Pathumthani Industrial Zone
Concept Design
7
Data Center Specifications OneAsia Data Center
Electrical
Total Power Available to Site: 2 x 20MVA
No. of Feeds Available to Site: 2 Feeds
City Power Capacity: 20 MVA
Generators (For IT & MVAC load): 12 x 2.5MVA (N+1)
UPS (For IT & Critical Building load): 14 MVA (2N)
Colocation Infrastructure
Rack Height: 47U
Number of Racks: ~2,300 racks
IT load per Rack: 6kW in average
Total IT load: 13,800kW
PUE: 1.45
Security
Surveillance Monitoring: CCTV
Building Security: Infra-red + HV Fence
Access Control: REID + Biometric
Others
Diesel Storage Tanks Capacity: 24 hours
Thermal Buffer Water Storage: 15 mins
Make-up Water Storage: 12 hours
Floor Load: 16kPA Nava Nakorn Pathumthani Industrial Zone
North Bangkok
Nava Nakorn Pathumthani Industrial Zone
Site Plan
▪ 2 x 4 Story Buildings
▪ Collocation Space at 1st Floor – 3rd Floor
9
Multiple Fiber Point of Entry (POE)
POE 1
POE 3
Site Plan
POE 2
General Floor Plan of Collocation Floor
Site Plan
General Floor Plan of Data Hall
Site Plan
Thank You
www.oneas1a.com