King Abdul-Aziz International Airport The Sub Contractor The Construction Manager: The Contractor

Development Project (Phase I) Jeddah,


KSA
Sheet Package Building: Generator
System: 13.8 kV System Ref. no. Building -2
Plant Ref. Rev
Title: Generator Control Panel - 13

TESTING OF POWER FACTOR METER:

1. Energy Meter General Data

Function POWER FACTOR Range. -0.5 to 0.5

Make DEIF Tag No. P407

Diagram no. 12003123 Model No. -

2. Visual Inspection

Sr. No. Description Checks

1 Inspect for physical damage/ defects OK

2 Checking of wires for any damage and that they are connected properly OK

3 Inspect for physical connection as per approved drawing OK

4 Inspect isolating terminals and earthing connections OK

5 Inspect for correct tightness of the connection OK

6 Checking ferrules as per drawing OK

7 Check test switch/plug for correct function OK

Reviewed By Reviewed By Reviewed By Approved By


Test information
ZAHID TRACTOR INMA SBG (CM)
     
Readings by:TAMILSELVAN(BSC)
     
     
Dates:
     
     
Instruments used: Freja300
     
KAIA-INMA-005 GCP Page 1 of 2
King Abdul-Aziz International Airport The Sub Contractor The Construction Manager: The Contractor
Development Project (Phase I) Jeddah,
KSA
Sheet Package Building: Generator
System: 13.8 kV System Ref. no. Building -2
Plant Ref. Rev
Title: Generator Control Panel - 13

3. Electrical Test

3.1 Meter Accuracy Test

Applied Voltage Applied Expected Measured % Error = (b−a)


(V Current Power Factor power factor a
(I) X100 Result
(a) (b)
VR=66.39∟0°, IR=5∟0°,
VY=66.39∟240°, IY=5∟240°,
1 1 0 OK
VB=66.39∟120° IB=5∟120°

VR=66.39∟36.5°, IR=5∟0°,
VY=66.39∟276.5°, IY=5∟240°,
0.8 0.8 0 OK
VB=66.39∟156.5° IB=5∟120°

VR=66.39∟216.5° IR=5∟0°,
, VY=66.39∟96.5°, IY=5∟240°,
-0.8 -0.8 0 OK
VB=66.39∟336.5° IB=5∟120°

Comments:

Reviewed By Reviewed By Reviewed By Approved By


Test information
ZAHID TRACTOR INMA SBG (CM)
     
Readings by:TAMILSELVAN(BSC)
     
     
Dates:
     
     
Instruments used: Freja300
     
KAIA-INMA-005 GCP Page 2 of 2