000-GD-C-002 R.2 Civil & Structural Design
000-GD-C-002 R.2 Civil & Structural Design
C-560
TOROMOCHO PROJECT
DISTRIBUTION A B C 0 1 2 3 4 5 6 7 8 9 10
Client 5-6 6-6 7-28 9-11
Procurement
Field
Internal 4-22 5-1 9-9 6-6 7-28
INDEX
PAGE
1 SCOPE ...............................................................................................................................3
4 ORE SPECIFICATIONS.....................................................................................................6
5 CIVIL WORKS....................................................................................................................7
7 DEFLECTIONS ................................................................................................................10
8 GEOTECHNICAL INFORMATION...................................................................................11
9 MATERIALS.....................................................................................................................11
10 DESIGN DETAILS............................................................................................................13
Q:\Doc_Control\R0534200\01_Eng_Doc\02_Str\01_Design_Criteria\560-000-GD-C-002_2.doc
2 of 16
Project No. C560
General Specification No. 000-GD-C-002
Civil and Structural Design Criteria
Rev. 2
1 SCOPE
This specification establishes criteria for the design of all civil and structural work for the
Toromocho Project owned by Minera Chinalco Perú S.A., located 140 km northeast of
Lima, in Morococha, Department of Junin, Peru, and is located at an altitude of between
4,500 and 5,000 m above sea level.
The design life for the structures shall be 32 years unless noted otherwise.
2.1 ABREVIATIONS
Q:\Doc_Control\R0534200\01_Eng_Doc\02_Str\01_Design_Criteria\560-000-GD-C-002_2.doc
3 of 16
Project No. C560
General Specification No. 000-GD-C-002
Civil and Structural Design Criteria
Rev. 2
2.2 CODES
Peruvian Codes:
E.020 Cargas
E.070 Albañilería
International Codes:
IBC International Building Code 2006
ASCE Minimum Design Loads for Building and Others Structures, SEI 7-05
AISE TR-13, Guide for the Design and Construction of Mill Buildings
Q:\Doc_Control\R0534200\01_Eng_Doc\02_Str\01_Design_Criteria\560-000-GD-C-002_2.doc
4 of 16
Project No. C560
General Specification No. 000-GD-C-002
Civil and Structural Design Criteria
Rev. 2
AWWA M11, Steel Water Pipe: A Guide for Design and Installation
NFPA Technical Standards to reduce the burden of fire and other hazards
Others:
AS Appendix A, Standard Technical and Site Data
Golder Doc-206, Long Period Transition Period for Toromocho Project Site
2.3 UNITS
The dimensions on the structural steel and concrete drawings must be in millimeters.
Does not require the abbreviation "mm"
Q:\Doc_Control\R0534200\01_Eng_Doc\02_Str\01_Design_Criteria\560-000-GD-C-002_2.doc
5 of 16
Project No. C560
General Specification No. 000-GD-C-002
Civil and Structural Design Criteria
Rev. 2
3.1 TEMPERATURE
Design high temperature: 20 °C (68 °F)
Design low temperature: -4 °C (25 °F)
Relative humidity: 68.5 %
Net annual evaporation: N/A
3.2 RAINFALL
Rainfall annual average: 629 mm (24.8”)
3.3 SNOWFALL
Snowfall: 50 mm accumulation (2”)
3.4 FROST
Frost depth: 0 mm, According Appendix A
3.5 STORM
24 hr - 100 year storm: 76.4 mm
Frequency of electrical storms: High
3.6 WIND
Maximum speed: 30 km/hr (recorded)
Design velocity 135 km/hr
Prevailing direction: NE
4 ORE SPECIFICATIONS
Angle of repose 38° (degrees)
Drawdown angle 40° (degrees)
Q:\Doc_Control\R0534200\01_Eng_Doc\02_Str\01_Design_Criteria\560-000-GD-C-002_2.doc
6 of 16
Project No. C560
General Specification No. 000-GD-C-002
Civil and Structural Design Criteria
Rev. 2
5 CIVIL WORKS
All the civil works: earth movement, site preparation, unsupported and supported slopes,
methods of excavation, foundation design criteria, slopes and radius for roads, etc., must
be in according with Overall Mine Site Geotechnical Design Recommendations by Golder.
6 DESIGN LOADS
Q:\Doc_Control\R0534200\01_Eng_Doc\02_Str\01_Design_Criteria\560-000-GD-C-002_2.doc
7 of 16
Project No. C560
General Specification No. 000-GD-C-002
Civil and Structural Design Criteria
Rev. 2
Occupancy Load
Roof 100 kg/m2
2
Offices 250 kg/m
2
Laboratories 500 kg/m
2
Dining 500 kg/m
2
Bathrooms 250 kg/m
2 where only pedestrian
Maintenance access walkways 250 kg/m traffic is probable
2
Stairs and ramps 500 kg/m
2
Control rooms 1250 kg/m
2
Warehouse (light load) 600 kg/m
2
Warehouse (heavy load) 1200 kg/m
2
Conveyor walkways 150 kg/m for truss design
2
Conveyor walkways 250 kg/m for walkways design
2
Others floors, as required for occupancy 500 kg/m minimum
additional to all other
Concentrated load on any panel 1000 kg loads
considered with dead
Concentrated load on elevated slabs 1000 kg load only
additional to all other
Concentrated load on floor 1000 kg loads
2
Operating platform 500 kg/m unless otherwise noted
2
Platform around mills 1250 kg/m
2
Liner platform 2000 kg/m
Reclaim Tunnel Platform 800 Kg/m²
2
Slab on grade around mills 3200 kg/m
Bridge AASHTO HS20-44
Non process building: will be in accordance with Peruvian code with a minimum basic
wind speed not less than 75 km/hr.
Q:\Doc_Control\R0534200\01_Eng_Doc\02_Str\01_Design_Criteria\560-000-GD-C-002_2.doc
8 of 16
Project No. C560
General Specification No. 000-GD-C-002
Civil and Structural Design Criteria
Rev. 2
Non process building: will be in accordance with Peruvian code with a minimum basic
snow load not less than 40 kg/m2.
For process building, the seismic coefficient resulting from IBC shall not be less than
the seismic coefficient resulting from Peruvian code E.030.
The factor for vibrating loads shall be the same for the live loads in combinations.
Foundations for vibrating equipment will be designed to reduce vibration to levels that are
acceptable for operation of equipment and for peoples, according to Richart and Whitman.
The ratio between frequency of the equipment operation and the frequency of vibration
equipment foundation should be outside the following range: 0.7 - 1.4.
Surface Coefficient
Steel - Steel 0.30
Seel - Concrete 0.50
Q:\Doc_Control\R0534200\01_Eng_Doc\02_Str\01_Design_Criteria\560-000-GD-C-002_2.doc
9 of 16
Project No. C560
General Specification No. 000-GD-C-002
Civil and Structural Design Criteria
Rev. 2
7 DEFLECTIONS
Roofing and Siding:
Roofing and Siding plates L / 200
Girt & Purling L / 200
Beams L / 300
Trusses L / 700
Q:\Doc_Control\R0534200\01_Eng_Doc\02_Str\01_Design_Criteria\560-000-GD-C-002_2.doc
10 of 16
Project No. C560
General Specification No. 000-GD-C-002
Civil and Structural Design Criteria
Rev. 2
8 GEOTECHNICAL INFORMATION
Unless otherwise noted, bottom of all footings and mat foundations shall be a minimum of
600mm (24”) below finish grade.
8.3 FRICTION
According Golder Associates – Geotechnical Report 089-4151026\18000 – Latest version
9 MATERIALS
Specific makes and catalog numbers of the various items of materials and equipment
included in this specification are to establish a minimum acceptable quality of the items.
Items of equal quality by other manufacturers may be used.
All material shall be new and shall conform to the following requirements unless noted
otherwise on the drawings:
9.1 CONCRETE
All structural concrete and concrete for floor slabs, walkways and ramps shall develop a
minimum compressive strength of f’c = 30 MPa at 28 days.
Sag Mill & Ball Mill Piers shall have a minimum of f’c = 45 MPa
For light modular buildings foundation (Construction camp, offices), concrete shall develop
a minimum compressive strength of f’c = 21 MPa at 28 days.
Q:\Doc_Control\R0534200\01_Eng_Doc\02_Str\01_Design_Criteria\560-000-GD-C-002_2.doc
11 of 16
Project No. C560
General Specification No. 000-GD-C-002
Civil and Structural Design Criteria
Rev. 2
Reinforcing steel shall be deformed bars, limited to diameter: #3 to #11, except for #9 and
#10, and shall conform to ASTM A615M, Grade 420, Fy=420 MPa or Peruvian quality
ARN 420, according ITINTEC 341.031 (Fy=420 MPa).
Also is acceptable Chinese quality HRB500E (Fy=500 MPa), but for design purposes use
Fy=420 MPa. For Chinese steel bars, diameters will be considered in mm.
2
Welded wire fabric shall be an electrically welded approved brand, 152 x 152-MW18.7 x
MW18.7 conforming to ASTM A 185.
Metal deck under elevated slabs shall be at less 0.8 mm Type B Formlock galvanized
panels or equivalent.
Anchor bolts shall conform to ASTM A307, except all nuts shall be American Standard
Hexagon Heavy Series conforming to ASTM A 563.
9.3 STEEL
Structural steel for main structures, including steel plate, shall be according to Chinese
Standard GB/T1591-1994, Q345 (B or C Quality). Main structures are defined in spec
number 000-GC-S-004 Miscellaneous and Structural Steel.
Structural steel for secondary structures, including plate, shall be according to ASTM A36
Secondary Structures are defined in the Spec 000-GC-S-004
Yield Point = 251 MPa
Also Structures designed with ASTM A36 properties, may be replaced by Chinese quality
Q345.
Shielded metal arc welding electrodes shall conform to E70XX series of AWS A5.1.
Q:\Doc_Control\R0534200\01_Eng_Doc\02_Str\01_Design_Criteria\560-000-GD-C-002_2.doc
12 of 16
Project No. C560
General Specification No. 000-GD-C-002
Civil and Structural Design Criteria
Rev. 2
Open web steel joists shall be K-Series with 207 MPa allowable stress.
Floor plate shall be 6 mm thick skid resistant, raised medium pattern, steel plate. Steel
Quality Shall be ASTM A36 or Chinese quality Q235.
Purling and Girt, Steel Quality Shall be ASTM A36 or Chinese quality Q235
Stair treads shall be welded bar grating with checkered plate nosing. Stair treads shall
have 32 mm x 5 mm steel bearing bars with cross bars at 100 mm on centers. Treads
shall be as manufactured by IKG Industries.
Handrail shall be fabricated from 32 mm nominal diameter standard weight steel pipe
conforming to ASTM A53M, Grade B with 125 mm by 6 mm kick plate.
Trench frames and covers shall be heavy duty, 50 mm thick, gray iron, catalog no. R-
4990, type A, as manufactured by Neenah Foundry Company.
Adhesive anchoring shall be Hilti HIT HY 150 anchoring system, with Hilti HIT or HAS
threaded anchor rod meeting the requirements of ASTM A36M.
10 DESIGN DETAILS
10.1 CIVIL
Side slopes of cuts and fills shall be in accordance with Doc 305 by Golder.
2
Minimum cover for culverts shall be 400 mm.
Q:\Doc_Control\R0534200\01_Eng_Doc\02_Str\01_Design_Criteria\560-000-GD-C-002_2.doc
13 of 16
Project No. C560
General Specification No. 000-GD-C-002
Civil and Structural Design Criteria
Rev. 2
Main plant access roads shall be designed for HS20-44 (AASHTO) loading, a maximum
speed of 50 km/hr, a maximum grade of 10 percent (8% recommended) and a minimum
horizontal curve radius of 35 meters. Minimum length of vertical curve 61 meters.
Road width for two lane traffic shall not be less than 7000 mm plus shoulder width of 1000
mm each side.
Internal plant site roads shall be designed for a maximum travel speed of 30 km/hr, a
maximum grade of 10 percent (8 recommended) and a minimum horizontal curve radius
of 10 meters. Minimum length of vertical curve 15 meters.
Road width for two lane traffic shall not be less than 6000 mm plus shoulder width of 500
mm each side. Special road wide requirement could be necessary for erection &
maintenance purposes.
For one way, road minimum wide must be 5000 mm, and 500 mm shoulders to each side.
10.2 CONCRETE
Either the strength design or working stress design method may be used for structural
concrete.
Splicing of reinforcing bars shall be in accordance with section 12 ACI 318. All splices
shall be Class B unless specified otherwise.
Q:\Doc_Control\R0534200\01_Eng_Doc\02_Str\01_Design_Criteria\560-000-GD-C-002_2.doc
14 of 16
Project No. C560
General Specification No. 000-GD-C-002
Civil and Structural Design Criteria
Rev. 2
10.4 STEEL
In general, ASD (Allowable Stress Design) or LRFD (Load Reduction Factor Design) could
be used for all structural steel design, according Steel Construction Manual AISC
Thirteenth edition.
Where possible all shop connections shall be welded and all field connections shall be
bolted.
All bolted beam connections shall conform to the AISC Manual of Steel Construction,
Thirteenth edition, Part 7, Tables 7-1 at 7-6, using the minimum row of bolts listed below,
unless otherwise indicated on the drawings or in this specification.
Single-plate shear connections, conforming to Table X-A, may be used for 200 mm and
250 mm beams in platform framing.
All welded beam connections shall conform to the AISC Manual of Steel Construction,
Thirteenth edition, Part 8, Table 8-1 at 8-11, unless otherwise indicated on the drawings.
Unless detailed on the drawings, end connections for truss members, bracing members
and axially loaded struts shall be apportioned to develop the forces shown on the
drawings, but not less than 6.5 tons for single angles and not less than 13 tons for double
angles and structural tees. End connections for wide flange shape bracing members shall
be claw angle type per AISC Vol. II, Connections.
20 mm minimum diameter high-strength bolts shall be used for connections of all main
structural members and all platforms, unless otherwise indicated on the drawings.
In general, high strength bolted connections shall be slip critical type. For connections,
which are not subjected to vibration or stress reversal or where slippage can be allowed,
bearing type connections may be used if so indicated on the drawings. For such bearing
type connections, threads shall be excluded from the shear plane.
Q:\Doc_Control\R0534200\01_Eng_Doc\02_Str\01_Design_Criteria\560-000-GD-C-002_2.doc
15 of 16
Project No. C560
General Specification No. 000-GD-C-002
Civil and Structural Design Criteria
Rev. 2
16 mm diameter machine bolts may be used for connecting purlins, girts, handrail and
miscellaneous steel.
10 mm diameter machine bolts shall be used for connecting all stair treads unless
otherwise noted on the drawings.
Safety cage shall be provided for ladder rise of 6 meters or more and also for ladder rise
of 3.6 meters or more, where the front landing radius is less than 2.5 meters.
Q:\Doc_Control\R0534200\01_Eng_Doc\02_Str\01_Design_Criteria\560-000-GD-C-002_2.doc
16 of 16