Pvt Sugar Plant

Electric load data enquiry


Mill section 1
SR Main Incomer items Breaker No’s Feeder No’s of Total load Starter
No. As per Motor (HP)
load
andyour
SLD
1 Weight bridge You 1 2Hp only 5amp DOL
defined incoming to
office.
2 Fiberize control Panel You 1 500HP/1nos 1000A ASR and
defined only LRRS
3 Feeding Table You 2 2/Each5HP 15 A DOL
defined
4 Cane Unloader You 2 2/cross travel 80 A DOL
defined Each 5HP
2/long travel
Each 5HP
2/20HP
Eachunloadin
g.
2/20HP Each
loading.
5 Cane Carrier Motor You 1 20 HP 33A VFD
(inter lock system) defined
6 Rack elevator (inter lock You 1 10HP 20A VFD
system) defined
7 Cane kicker You 1 5 HP 7.5A DOL
defined
8 Cane leveller You 1 150HP 200A DOL
defined
9 Work shop You 1 15HP 30A DOL
defined
10 Spare You 1 25HP 50A DOL
defined
11 Mill no.:-1,2,3,4 You 4 4/Each 75HP 400A VFD
defined
12 Mill No.:-5 You 1 150 HP 193A VFD
defined
13 Inter rack carrier(inter You 1 4/Each 5HP 40A DOL
lock system) defined
14 Mill House crane You 1 2/Each 4HP 12A DOL
defined for cross and
long travel.
15 Mill bearing oil pump You 1 2/Each 3 HP 10amp DOL
defined
Millsection 2

SR Main incomer items Breakerstobe No’s No’s of Total Starter


NO design and Feeder Motor load
SLD prepare (HP)
1 Raw juice pump ( 1 stand by) You defined 2 2/20HPEach 30A DOL
2 Strained juice pump (1stand by) You defined 2 2/10HPEach 18 A DOL
3 Mill hot water pump (1stand by) You defined 2 2/3HPEach 6A DOL
4 Unstrained juice pump ( 4 stand by) You defined 8 8/3HPEach 25A DOL
5 Clear juice pump (1stand by) You defined 2 2/10HP Each 16A DOL
6 Rotary screen and hot water pump. You defined 1 1for rotary 20A DOL
screen/10HP
and
1 for spray
hot water
pump/3HP

BoilerSection
Only power house feeder (PCC) and ACB tube install.and after finalising the next enquiry
ofcabel laying and Connection to allpanels.because boiler.DM plant.and RBC manufacturer will
be given allMCC all panels.

Breaker No’s of
loadto Motor
SR No’s Total
Main Incomer – 1000AMP be (HP) Starter
No. Feeder load
degine
and SLD
Return bagasse carrier(on-door You
1 1 25 37A S/D
Interlock/bypass switch) defined
2 Bagasse blower You 1 10 13A DOL
defined
Changes over switch feed pump to DG set You
3 2 2 250A S/D
/ M.S.E.B / T.G defined
4 D.M Plant Main Switch You 1 6 25A DOL
defined
5 ID.FD.SA.Scrubber.bagasse feeder.feed You Design 7 1000A As boiler
pump.transeper pump. defined purchase
scope

PowerHouseTurbine:-
Turbine and generator set (1.5 MW)are purchasednewly.OnlyPCC and breakerfeeder to be
provided at power house and remaining cabel laying andconnection to TG set MCC panels
enquiry will besubmitting after finalize the enquiry of remaining work.
SR.
Title Load
No.
1 Power House Turbine 35 A
BoilingHousesection

SR Main Incomer items Breaker No’s of Total load Starter


No. to be Motor (HP)
design
with
SLD
1 Evaporation condensed pumps ----- 12/Each pump 30A DOL
(6 pump stand by) 3Hp
2 Pan section condensed pumps ------ 12/Each pump 30A DOL
(6 pump stand by) 3HP
3 Rab constraints condensed ------ 8/Each pump 20A DOL
pumps (4pump stand by) 3HP
4 Service water pump (1stand by) ------ 2/Each pump 30A S/D
20HP
5 Lime pumps(1stand by) ----- 2/Each pump 4.5 A DOL
3HP
6 Lime stirrer ------ 3 HP /only 4.5 A DOL
1motor
7 Sugar Melter mixer ------- 5 HP/Each 5 45 A DOL
motor
8 Pug mill mixer ------- 5HP/Each 45 A DOL
5motor
9 Air compressor ------- 10 HP /only 1 20 A S/D / DOL
motor
10 Molasses tank pump ------ 5HP/Each 20 A DOL
2motor
11 Mud mixer ------- 3 HP /only 1 4.5 A DOL
motor
12 Agitator ------ 2HP /only 1 3.5 A DOL
motor
13 Door (clarifier) center tube. ------- 5HP/only 1 7.5 A DOL
motor
14 Vacuum pump ------- 3 HP /only 1 4.5 A S/D
motor
15 Injection pump ------- 20 HP/Each 65 A S/D
2motor
16 Service water pump ------ 10,HP/Each 2 15 A DOL
motor
17 Jack well pump ------ 25 HP/Each 35A S/D
2motor

Crystallizers
Crystallizers

SR Main Incomer Items Breaker No’s of Total load Starter


No. to Motor (HP)
bedesign
1 Crystallizer ---- 3 HP /110Each 459 A DOL
motor

Centrifugal section

Factory will be purchased 1 continued machine and 1batch type machine hence we need only
at power house station breaker and PCC panels. after finalising next enquiry of cabel laying and
connection at both the motors.

SR Main Incomer items Breaker No’s of Motor Total load Starter


No. (HP)
1 Centrifugal Machine continues 125 A 75 HP/2 180 A S/D
motors only
2 Batch type machine 250 A 110 HP DC 200 A DC drive
motor/1motor
only

Sugar house
ETP will be purchased Clint Only you are do power house breaker and PCC
panels.after finalize enquiry of cabel laying and conntivity of all motor of
ETP.

SR Main Incomer items Breaker No’s of Motor Total load Starter


No. to be (HP)
design
1 Sugar Elevator ---- 5 HP/Each 2 12A DOL
motor
2 Sugar grader ----- 15 HP /Each 1 20A DOL
motor
3 Sugar hopper ----- 20 HP/only 1 28 A
motor
3 Hot Blower for hopper ----- 5 HP/Each 7.5A DOL
1motor
4 Sugar Melter ------ 5 HP /Each 1 7.5A DOL
motor
5 ETP ------ Clint scope 200A DOL

Spray pand (cooling tower)


SR Main Incomer items Breaker No’s of Motor Total load Starter
No. to be (HP)
design
1 Cooling fan ----- 30HP/Each 2 90 A S/D
motor
2 Cooling pump ----- 50 HP/Each 2 150 A S/D
motor
3 Transfer pump ---- 30 HP 90 A S/D

Factory Lighting

SR.
No. Title Load Breaker

Factory Lighting
60 A 90 A

1 a)Only factory Light. 25 A


b)Only Street Light. 32A
c)General Office, Guest House, Colony. 25 A
Note: - Per M.C.C Panel 25 KVAR Capacitor attachment is required