New project
Any Company
Project number: ---
Any Street 21
Location: Iraq / Van
54321 Any Town
Date: 1/26/2023
Tel.: +49 123 456-0
Internet: www.any-company.de
Any Company
Any Street 21
E-Mail: info@any-company.de
System overview
SMA Fuel Save Controller - contact SMA for further details: FuelSaveSolution@SMA.de
PV design data
Total number of PV modules: 8 Energy usability factor: 100 %
Peak power: 5.28 kWp Spec. energy yield*: 1658 kWh/kWp
Number of PV inverters: 1 Line losses (in % of PV energy): ---
Nominal AC power of the PV inverters: 12.00 kW Used PV energy: 0.00 kWh
AC active power: 12.00 kW Used PV share: 0%
Active power ratio: 227.3 % PV share of the energy supply (total): 0%
Max. available PV energy*: 8,753 kWh PV share of the energy supply (during the 0%
day):
*Important: The yield values displayed are estimates. They are determined mathematically. SMA Solar Technology AG accepts no responsibility for the real
yield value which can deviate from the yield values displayed here. Reasons for deviations are various external conditions, such as soiling of the PV modules
or fluctuations in the efficiency of the PV modules.
Subproject Subproject 1
1 x SMA STP 12-50 (PV system section 1)
Peak power: 5.28 kWp
Total number of PV modules: 8
Number of PV inverters: 1
Max. DC power (cos φ = 1): 12.25 kW
Max. AC active power (cos φ = 1): 12.00 kW
Grid voltage: 380V (220V / 380V)
Nominal power ratio: 232 %
Dimensioning factor: 44 %
Displacement power factor cos φ: 1
Full load hours: 729.4 h
PV design data
Input A: PV array 1
8 x Seraphim Solar System Co.Ltd. SRP-660-BMC-HV (07/2022), Azimuth angle: 36 °, Tilt angle: 32 °, Mounting type: Ground
mount
You get this inverter including SMA ShadeFix. SMA ShadeFix is a patented inverter software that automatically optimizes the
yield of PV systems in any situation. Even under shading conditions.
Overview
DC
LV
Total
Power loss at nominal operation 48.46 W 7.92 W 56.38 W
Rel. power loss at rated nominal operation 0.75 % 0.13 % 0.87 %
Total cable length 20.00 m 10.00 m 30.00 m
Cable cross-sections 3,5 mm² 6 mm² 3,5 mm²
6 mm²
Graphic
DC cables
Cable material Single length Cross section Voltage drop Rel. power loss
Subproject 1
A Copper 10.00 m 3,5 mm² 2.2 V 0.75 %
1 x SMA STP 12-50
B Copper 10.00 m 2,5 mm² --- ---
PV system section 1
C Copper 10.00 m 2,5 mm² --- ---
Cables LV1
Cable material Single length Cross section Cable resistance Rel. power loss
Subproject 1
1 x SMA STP 12-50 Copper 10.00 m 6 mm² R: 9.556 mΩ
0.13 %
PV system section 1 XL: 0.750 mΩ
New project
The same load profile is used for all seasons. There is no distinction by season.
Subproject 1
1 x SMA STP 12-50 (PV system section 1)
PV array and inverter type are only conditionally compatible, since the inverter is oversized in this combination (> 135 %).
You get this inverter including SMA ShadeFix. SMA ShadeFix is a patented inverter software that automatically optimizes the
yield of PV systems in any situation. Even under shading conditions.
Overview
Year Summer Spring/fall Winter
Minimum power requirement 912 W 912 W 912 W 1,092 W
Maximum power requirement 6,105 W 5,285 W 6,105 W 6,105 W
Average daily energy requirement 55 kWh 50 kWh 55 kWh 60 kWh
Energy requirement 20,000 kWh 4,587 kWh 9,891 kWh 5,521 kWh
The displayed results are approximate values to give a general indication to users of possible operating results. The results are determined mathematically
based on standardized assumptions. The actual operating results will be dictated significantly by the actual irradiation conditions, the actual efficiency, the
genset operating conditions and the individual consumption behavior and can deviate from the calculated results. SMA SOLAR TECHNOLOGY AG
THEREFORE ASSUMES NO LIABILITY FOR YIELD SHORTFALLS IN THE EVENT OF DEVIATIONS BETWEEN THE CALCULATED- AND ACTUAL OPERATING
RESULTS.
Overall view
Gensets Load profile
Max apparent power 26250 VA
6267 VA
Design conditions
The minimum power of the gensets, adjusted for the load, takes into account an additional power reserve that can be provided
by the gensets. A load-related minimum power of 110% means a power reserve of 10%. The minimum PV power to be expected
shows what portion of the original PV power can be expected if clouds suddenly appear.
Minimum genset load 30 %
Load-related minimum power 110 % (of the maximum power requirement)
Minimum PV power to be expected 20 % (of the possible PV power with no clouds)
The displayed results are approximate values to give a general indication to users of possible operating results. The results are determined mathematically
based on standardized assumptions. The actual operating results will be dictated significantly by the actual irradiation conditions, the actual efficiency, the
genset operating conditions and the individual consumption behavior and can deviate from the calculated results. SMA SOLAR TECHNOLOGY AG
THEREFORE ASSUMES NO LIABILITY FOR YIELD SHORTFALLS IN THE EVENT OF DEVIATIONS BETWEEN THE CALCULATED- AND ACTUAL OPERATING
RESULTS.
Details
The displayed results are approximate values to give a general indication to users of possible operating results. The results are determined mathematically
based on standardized assumptions. The actual operating results will be dictated significantly by the actual irradiation conditions, the actual efficiency, the
genset operating conditions and the individual consumption behavior and can deviate from the calculated results. SMA SOLAR TECHNOLOGY AG
THEREFORE ASSUMES NO LIABILITY FOR YIELD SHORTFALLS IN THE EVENT OF DEVIATIONS BETWEEN THE CALCULATED- AND ACTUAL OPERATING
RESULTS.