Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Code:

SDS-E-43

Shop drawing submittal

Project title: NZAKOU


Contractor Employer Consultant Client Rep. (where applicable)

B-ENGINEERING SCI SALIGNY TECHNO GROUP


Shop Drawing Type

Mechanical Electrical Other:_______

Consultant Decision*
Drawing # Rev. Description Consultant Comments
A AAN R&R NA
E-SD-FA-RI00 00 FIRE ALARM RISER x Addressable Fire alarm loops
DIAGRAM can take up to 100 devices.
Please reduce number of loops
to reduce cost.

Filled by / Date Ghady Ziade / 13-02-2023

Consultant Signature / Date 20-3-23

Client representative Signature / Date (where


applicable):

*A: Approved, AAN: Approved as noted, R&R: revise and resubmit, NA: not approved