Facility Qualification in Pharmaceuticals

Civil Construction:

Check the room number allotted as per the drawing and design.

Check number of doors and type of the door .

Check whether the floor as per the design specification. Whether it is Trimix or Epoxy.

Check the vision panel. Whether it is double glazed or single glazed.

Check the false ceiling and its material of construction.

Check the wall finish and type of the paint used.

Check coving, material of construction of coving and location i.e. between floor and wall and between
ceiling and the wall. Check for the skirting on the wall.

Check whether there is any hatch provided. Describe its location.

Check the dimension of the room. Whether it is flame proof or non flame proof. Also check the size of
the room and whether it  is as per the design specification.

Utility:

Power:  Check location of the connections and its voltage and phase with design specification.

Water:  Check supply of potable, domestic hot  and purified water supply and number of points.

Steam:  Check availability of low-pressure steam and number of points.

Gas/compressed air: check compressed air connection and number of points.

Drains:  check number of drain points and type of drain trap.

HVAC supply &return diffusers: Check for number of supply and return air diffusers. Also record the
temperature and humidity. Compare with that of design specification.

Lighting: Check the type of light fixture. Whether it is flame proof or non flame proof. Also check and
record the intensity of light.

Dust extractor system: Check the number of the dust extractor points.

Equipments: record all the equipments that are installed in the area.

Check all the safety systems such as alarm push button, location of closest fire extinguisher, fire
detection system, eyewash station, intercom/ telephone and its location.

Attach all related drawings of the area and their availability with revision status..

Prepare summary report of qualification and shall be reviewed . Variance has to be recorded.

The final report of the qualification shall be reviewed and  conclusion should be drawn by head of
production and head of quality control and quality assurance.