3
ADJACENT TENANT
RTU
10"x12"
PROGRAMMABLE THERMOSTAT. CONTRACTOR SHALL FURNISH AND INSTALL A ZONE DAMPER
TG-2 7 · THE SYSTEM SHALL AUTOMATICALLY INDEX EQUIPMENT TO WITH CONTROLS EQUAL TO YOUNG REGULATOR #2000.
4 2 FURNISH #2075 ROUND DAMPER OR #2085 RECTANGULAR
(TYP.) ADJACENT TENANT THE HEATING, COOLING, AND OCCUPIED AND UNOCCUPIED ARCHITECT OF RECORD
M611 M611 DAMPER, SIZED FOR DUCT INDICATED ON THE PLAN, WITH
RTU MODES OF OPERATION.
· CONTINUOUS SUPPLY FAN OPERATION MUST BE MAINTAINED MODEL #T-312-CE ZONE THERMOSTAT MOUNTED AT 48" A.F.F.
4.7 FITROOMS 5 5.6 6 DURING OCCUPIED HOURS. WHERE INDICATED ON THE PLAN. THE DAMPER AND SUSANNA CHAN, AIA, NCARB
ZD ZD-1 • •• • • • THERMOSTAT SHALL BE MODULATING TYPE AND CAPABLE OF
· OUTSIDE AIR SYSTEMS SHALL INCLUDE A MOTORIZED
HEIGHT 9'-6" DAMPER INTERLOCKED TO CLOSE WHEN THE UNIT SUPPLY AUTO-CHANGEOVER. MOUNT CHANGE-OVER SENSOR IN THE OR LICENSE NO: ARI-13711
CEILING GWB FAN IS DE-ENERGIZED. DUCT PER MANUFACTURER'S PRINTED INSTRUCTIONS, SET
OFFICE SD-1 SG-2 FOR MIN. OPENING TO BE 30%. 120V. CONNECTION BY THE 9425 SHORE ROAD, 3D
200 9 225
2. RTU-1&2 - NEW ROOFTOP UNITS ELECTRICAL CONTRACTOR. ALL LOW VOLTAGE SYSTEMS BY BROOKLYN, NY 11209
HEIGHT 8'-0" THIS CONTRACTOR.
T
T-STAT CONTRACTOR SHALL FURNISH AND INSTALL A ROOF MOUNTED 327-994-9411
CEILING GWB T
T
RTU-1&2 SG-2
AIR TO AIR HVAC UNIT AT EXISTING LOCATION. SEE ROOF TOP SUSANNA.T.CHAN@GMAIL.COM
3 UNIT SCHEDULE FOR FURTHER INFORMATION. CONTRACTOR 10. MOUNT CO2 SENSOR BETWEEN 48" AND 60" AFF FOR DEMAND
1 225
M611 MUST VERIFY MODEL NUMBERS AND ELECTRICAL CONTROL VENTILATION. THE MINIMUM CODE REQUIRED ARCHITECT
(TYP.) 7 TG-3 14 14 14 REQUIREMENTS PRIOR TO INSTALLATION. SUPPLY AND OUTDOOR AIR CFM WILL BE MAINTAINED WHENEVER THE
14 14
RETURN AIR DUCT CONNECTIONS TO RTU SHALL BE MADE SPACE IS OCCUPIED REGARDLESS OF C02 SENSOR CONTROL.
RG-1 3 SENSOR FULL SIZE OF EQUIPMENT OPENING WITH FLEXIBLE DUCT
SG-2 1 10
CO2 RTU-1 CONNECTIONS AT UNIT. INCLUDE A COMPLETE ECONOMIZER 11. BOTTOM OF DUCTWORK HEIGHT TO BE COORDINATED WITH
225 SD
PACKAGE WITH ALL CONTROLS AND WIRING FACTORY
20"x12"
S
ARCHITECTURAL ELEMENTS. DUCTWORK TO BE MOUNTED NOT
(E) CEILING @ BACK DOOR MOUNTED. UNIT SHALL BE FURNISHED WITH TWO SETS OF HIGHER THAN 14'-0" AFF. FIELD VERIFY PRIOR TO BID THE 14'-0"
8 MERV 8 FILTERS. CONTRACTOR TO REPLACE FILTERS PRIOR CAN BE ACHIEVED.
• •• • • • • •• • • •
HEIGHT 9'-0" (TYP.)
11 10 TO TURNING STORE OVER TO TENANT. PROVIDE UNIT WITH
SD-1 SD-1 M611 M611 MANUFACTURERS OPTIONAL POWER EXHAUST IF AVAILABLE.
CEILING (E) GWB 175 175 ALL ROOF WORK INVOLVED WITH SETTING OF THE ROOF 12. PROVIDE DOOR WITH 18"X18" DOOR GRILLE. TITUS MODEL
MEP ENGINEER
SD-4 SD-4 SD-4 SD-4 CT-700 OR EQUAL.
RG-3 CURB ADAPTOR AND UNIT SHALL BE DONE BY THE
HALLWAY 20"x14" 20"x18" 20"x14"
200 RG-3 200 200 RG-3 200
LANDLORD'S ROOFING CONTRACTOR AT THE GENERAL
CONTRACTOR'S EXPENSE UNLESS NOTED OTHERWISE. 13. TF-1
HEIGHT 9'-2" • •• • • • • •• • • • GENERAL CONTRACTOR SHALL PROVIDE ANY ADDITIONAL FANTECH CENTRIFICAL INLINE TRANSFER FAN MODEL FG 4XL
M-Engineering
CEILING GWB 5 • •• • • • • •• • • • STRUCTURAL STEEL REQUIRED TO SUPPORT RTU, PER SHALL BE FURNISHED AND INSTALLED BY MECHANICAL
(TYP.) LANDLORD'S REQUIREMENTS. CONTRACTOR. EXHAUST CAPACITY SHALL BE 100 CFM UP TO
RTU-1 M611 • •• • • • 20"x14"
RESTROOM • •• • • • • •• • • • 4000 4 2 12"x14" 0.75" S.P. REFER TO PLANS FOR FURTHER INFORMATION.
(BY 3. SMOKE DETECTOR FURNISHED AND INSTALLED BY CONTRACTOR TO FURNISH AND INSTALL EXHAUST DUCT AND
• •• • • •
HEIGHT 8'-0" LLL) 1
MECHANICAL CONTRACTOR. SMOKE DETECTOR TO BE ACCESSORIES AS REQUIRED. REFER TO PLANS FOR LOCATION.
14 (TYP.) INSTALLED IN THE RETURN AIR DUCT OF THE ROOF TOP UNIT. PROVIDE THERMOSTAT FOR CONTROL. SET THERMOSTAT TO
CEILING GWB SD-1 STRUCTURAL ENGINEER
14 SD-1 • •• • • • • •• • • • M611 • •• • • • THE SMOKE DETECTOR SHALL SHUT DOWN THE HVAC UNIT • • ••• •••••••
SD-1 175 • •• • • •
SD-1 175 RG-3 UPON SENSING SMOKE.
5 EF-1 200 7 TG-3
50 80 14. 1" SLOT FOR RETURN AIR PATH. REFER TO ARCHITECTURAL
• •• • • • 4. CONTRACTOR SHALL FURNISH AND INSTALL CONDENSATE PLANS FOR DETAILS. TM
E.9 8
DRAINS FROM ALL UNITS. MINIMUM DRAIN SIZE TO BE 1" OR AS OSBORN
9 SPECIFIED ON PLANS. CONDENSATE DRAIN TO BE TRAPPED ENGINEERING
(TYP.) 990 West Third Avenue - Suite 200 | Columbus, OH 43212
M611 WITH A MINIMUM 5" TRAP DEPTH. DRAINS SHALL BE EXTENDED 15. AIR CURTAIN-1 1100 Superior Avenue - Suite 300 | Cleveland, OH 44114
AT A SLOPE OF 1" PER 40'. ROUTE DRAINS TO SPLASH BLOCK CONTRACTOR TO PROVIDE A BERNER AIR CURTAIN MODEL
F ON ROOF. ROOFTOP/EXTERIOR PIPING TO SPLASH BLOCK,
(614) 556-4272 www.osborn-eng.com
SD-4 SD-4 SD-4 SD-4 SD-4 SD-4 SD-4 SD-4 SD-4 SD-4
14
200 200 200 200 200 200 200 200 200 200
RG-3(TYP) RG-3(TYP) RG-3(TYP) M611
SENSOR
1 10
CO2 RTU-2
S