Automatic Fire Extinguisher Systems

Telephone 01473-744090. Fax 01473-744901. Email- info@firetrace.co.uk


Firetrace Ltd. - Unit 22 Knightsdale Road - Ipswich IP1 4JJ

027 - Summary of Basic


Design Specifications

Type of Firetrace Minimum amount


Maximum length Maximum length
system and of extinguishant
of Trace detection of 8mm diffuser
extinguishant per unit volume or
tube – to burst tubing -
contents type area
Powder
Direct Low Pressure 1kg per cubic metre 5 metres N/A
Firetrace system
Powder
Indirect Low Pressure 1kg per cubic metre 25 metres 6 metres
Firetrace system
FE-36
Direct Low Pressure 1kg per cubic metre 20 metres N/A
Firetrace system
FE-36
Indirect Low Pressure 1kg per cubic metre 25 metres 12 metres
Firetrace system
AFFF Foam 3 litres per square
Indirect Low Pressure metre of floor area 25 metres 6 metres
Firetrace system to be protected
CO²
2.5 kg per cubic
Direct High Pressure 25 metres N/A
metre
Firetrace system
CO²
1.5kg per cubic
Indirect High Pressure 25 metres 12 metres
metre
Firetrace system
CO²
Direct/Indirect High 1.5kg per cubic
25 metres N/A
Pressure Firetrace metre
system

027 Revised June 2007