Professional Documents
Culture Documents
Electrical Installation of Buildings: EBCS-10
Electrical Installation of Buildings: EBCS-10
ELECTRICAL INSTALLATION
OF BUILDINGS
FOREWORD
The Proclamation to define the powers and duties of the Central and Regional Executive
Organs of the Transitional Government of Ethiopia No. 41/1993 empowers the Ministry of Works
and Urban Development to prepare the Country's Building Code, issue Standards for design and
construction works, and follow up and supervise the implementation of same.
In exercise of these powers and in discharge of its responsibility, the Ministry is issuing a
series of Building Code Standards of general application.
The major benefits to be gained in applying these standards are the harmonization of
professional practice and the ensuring of appropriate levels of safety, health and economy with due
consideration of the objective conditions and needs of the country.
As these standards are technical docum~nts which, by their very nature, require periodic
updating, revised editions will be issued by the Ministry from time to time as.appropriate.
The Ministry welcomes comments and suggestions on all aspect of the Ethiopian Building
Code Standards. All feedback received will be carefully reviewed by professional experts in the
field of building construction with a view to possible incorporation of amendments in future
editions.
Haile Assegidie
Minister
Ministry of Works and
Urban Development
1995
INTRODUCTION
This Code Standard for the Electrical Installation of Buildings is part of the Building Code
of Ethiopia:
This Code Standard for the Electrical Instaijation of Buildings is mairily adopted from
lEE Regulations for Electrical Installations and Canadian Electrical Code, Part 1, to suit
the Ethiopian conditions. Other publications quoted are shown in the respective sections
of the Code and the Ethiopian Authority for Standardization maintains registers of a
number of foreign national and international standards.
The Code embr~ces several aspects of electrical installation work and sets standards and
provisions for safe utilization of electricity.
The Technical Committee for Code Standards for the Electrical Installation of Buildings
comprises of the following Institutions representing balanced interest of all segments of the
public concerned with the subject matter:
TABLE OF CONTENTS
1.1 Scope 1
1.2 Nonnative references 1
1J Defmitions 2
2.1 Administrative 20
2.1.1 Authority for rules i ••••••••••••••.•••••••••• i ••• 20
2.1.2 Pennit 20
2.1.3 Application for inspection 20
2.1.4 Posting of penn it ', , 20
2.1.5 Notification re-inspection 20
2.1.6 Plans and specifications 21
2.1.7 Connection authorization 21
2.1.8 Re-inspection 21
2.1.9 Renovation of existing installation 21
2.1.10 Use of approved equipment 22
2.1.11 Deviation or postponement 22
2.1.12 Powers of rejection 22
2.1.13 Installation of electrical equipment 22
2.1.14 Damage and interfer•••.• ~e 22
2.2 Technical 23
2.2.1 Conventional symbols '.' 23
2.2.2 Co-ordination 23
2.2.3 Location and requirement of substation 23
2.2.4 Rooms (spaces) required 23
2.2.5 Location and requirements of distribution boards 24
2.2.6 Location and requirements of PBX/PABX rooms 24
2.3 Planning and designing 25
2.3:1 General 25
2.3.2 Layout and installation drawing 25
2.3.3 Design 25
Section 3 Illumination
3.1 Scope 29
3.2 Normative references 29
3.3 Definitions , 30
3.4 Lighting requirements 35
3.4.1 IllumiQance " 35
3.4.2 Luminance '.. " 35
3.4.3 Glare' ' 36
3.4.4 Light direction and modelling 36
3.4.5 Colour rendering , .. , 36
II
Se~tion 4 Conductors
Annex (preface) 74
Annex A (Normative) - Correction factors 85
Annex B (Normative) - Type of cable and ampacity 90
III
5.6 Wiring methods 148
5.6.1 Underground consumer's service conductors 148
5.6.2 Overhead consumer's service conductors 148
IV
7.4 Location of system earthing connections 159
7.4.1 D.C. systems 159
7.4.2 A.C. systems 159
7.4.3 Isolated systems , , , '.' 1·59
7.4.4 Single service supply to two or more buildings or structures ., 160
7.4,5 Conductors to be earthed , , 160
7.4.6 Current over earthing conductor ,, , , .. 160
Bonding 161
7.5.1 Non-current carrying metal parts , , , 161
1.5.2 Exposed non-current-carrying metal parts of equipment •....... 161
7.5.3 Non-metallic wiring systems 161
7.5.4 Non-electrical services 161
7.5.5 Extraneous fixed metalwork 164
v
7.9 Earthing and bonding conduc;tors 171
VI
!
7.17 Down conductor , , 186
7,17.1 General " , ' 186
7.17.2 Routing , 187
7,17.3 Recommended number ,., 187
7.17.4 Mechanical protection 187
7.17.5 Corrosive soil .....•............................... 187
7.17.6 External routes not available , , .. , " 187
7.17 .7 Lift shafts , ,,. , 188
7.17.8 Re-entrant loops . , '.' 188
7.17,9 Sharp bends , 188
7.17.10 Bonding to prevent side flashing 188
7.1 7.11 Bonds ' 188
7.17.12 Testpoints , : 189
Annex (Informative)
Annex A - System design 219
Annex B - Consultation , .. , 220
VII
Section 8 Wiring Methods
8.6 Exposed wiring on exterior of buildings and between Buildings on the same premises 229
8.6.1 Location of conductors 229
8.6.2 Clearance of conductors 229
8.6.3 Power supply conductors 229
VIII
Section ® Protection and Control
IX
10.5 Class 2 circuits , 249
10.5.1 Limitations of Class 2 circuits 249
10.5.2 Methods of installation on supply side of overcurrent protection or
Transformers or other devices for Class 2 circuits 250
10.5.3 Marking 250
10.5.4 Overcurrent protection for Class 2 circuits 250
10.5.5 Location of over current devices '" 251
10.5.6 Conductors for Class 2 circuit wiring 251
10.5.7 Separation of Class 2 circuit conductors from other circuits 251
10.5.8 Conductors of different Class 2 circuits in the same cable, enclosure, or
raceway 252
10.5.9 Penetration ofa fire separation 252
10.5.10 Conductors in vertical shafts and hoistways ; . 252
10.5.11 Class 2 conductors and equipment in ducts and plenum chambers .. 252
10.5.12 Equipment located on the load side of overcurrent protection, transformers, or
current-limiting devices for Class 2 circuits , , , 252
10.5.13 Class 2 circuits extending beyond a building 253
10.5.14 Underground installations , , 253
x
11.8 Air conditioning and refrigerating equipment '.' 268
11.8.1 General 268
11.82 Branch circuit 268
11.8.3 Disconnecting means 269
11.8.4 Supply cords , 269
XI
Section 13 Fhimmable Liquid Dispensing and Service Stations, Garages, Bulk Storage
Plants, Finishing Processes and Aircraft Hangars
13.8 Aircraft; hangars .:. 0 •••• 0 •••••••••• o' 0 ••• 0 ••••••••••••••••• 305
13.8.1 Hazardous . areas.. .. ... 0 .' .' ••••• 0 ••••• '. 0 •• \ • , ' ••••••••••••• 305
13.8.2 Wiring .and equipment in ,hazardous 'areas ... '0' o. : 0 •••••••••• 306
13.8.3 Wiring not within' hazardous area. " '.' 0.' •••• 0 ••••••••••••• 306
13.8.4 Equipment-not within hazardous' areas 0 ••••••••••••••••••• 307
XII
14.3 Definitions 308'
14.4 Circuits in basic care areas 31 i
14.4.1 Branch circuits '...•.. 311
14.4.2 Bonding to earth in basic-care areas ,311
14.4.3 Socket outlets in basic-care areas ' '.' .: ' 312
15.1 Scope : 3 18
15.2 Normative references " , . :.' .. '.' . " 318
15.3 Interior lighting :quipment : '.' , . '.. ~.~.. , 318
15.3.1 General ' ' 318
15.3.2 Location of lighting equipment· ..........•.............. 320
15.3.3 Installation. of ligpting equipment ' 323
15.3.4 Wirin~ of lighting. equipment .' ~ 323
15.3.5 Earthing of-lighting equipment :." 326
15.3.6 Electric-discharge lighting systems operating at 1000V or less 326
XIII
Section 16 Fire Alarm System and Fire. Pumps
XIV
, '
17.4 High-voltage luminous discharge tube signs and outline Lighting ' 373
17.4.1 Enclosure .' ~ . '.. : .. '.: .. , ; .. 373
17.4.2 Protection of uninsulat.edpart : , 374
17.4.3 Transformers : ' : .. 374
17.4.4 High-voltage wiring methods '.< 375
xv
18.6 Installation of conductors ' 380
18.6.1 Number of conductors in raceway ~ 380
18.6.2 Supports 380
18.6.3 Different systems in one raceway or travelling cable , 380
18.6.4 Wiring in hoistway 381
18.6.5 Electric equipment in garages and similar occupancies 381
18.6.6 Sidewalk lifts 381
XVI
18.14 Machine rooms and hoistway pits lighting and Auxiliary 386
18.14.1 Machine room 386
llU4.2 Hoist pits 387
Section 19 Theatrelnstallation
XVII
Section 20 Emergency Systems, Unit Equipment, and Exit Signs
Section 21 Motion Picture Studios, Projection Rooms, Film Exchanges and Factory
XVIII
~_. ------ ~I
21.6 Motion picture projection rooms .. i ••••••••••••••••••••••••••• 404
21.6.1 Lamps in projection rooms 404
21.6.2 Arc lamp current supply 404
21.6.3 Ventilation 404
XIX
23.5 Equipment 414
23.5.1 Communication equipment in bathrooms 414
23.5.2 Equipment in air ducts, plenums, or suspended ceilings 414
23.5.3 Exposed equipment and terminations : 415
23.5.4 Earth circuits 415
23.5.5 Communication systems in hospitals 415
Section 24.. Community Antenna Installation For Radio And television Reception
xx
\
24.5.4 Supports 423
24.5.5 Earthing of outer conductive shield'of a coaxial cable 423
24.5.6 Earthing conductor 423
24.5.7 Earthing electrode 424
24.5.8 Earthing electrode connection 424
XXI
25.4.4 Bonding to earth 449
25.4.5 Junction and deck boxes 450
25.4.6 Transformers and transformer enclosure 451
25.4.7 Socket outlets 452
25.4.8 Luminaries and lighting equipment 452
25.4.9 Earth-fault circuit breakers 454
XXII
26.4 Symbols 463
Annex A - (Infonnative) 470
Annex B - (Infonnative) 471
Appendices
XXIII
ECTION 1
SCOPE AND DEFINITIONS
1.1 SCOPE
(1) This Code applies to the design, selection, erection, ~nspection and testing of electrical
installations for residential, commercial, public and industrial premises including prefabricated
buildings, construction sites, exhibitions, fairs and other temporary installations up to and
including lOOO.OY a.c. or I500.0Y d.c.
(I) The following references contain provisions which, through reference in this text, constitute
provisions of the Ethiopian Building Code Standards on Electrical Installation of Buildings.
(2) At the time of publication of this Building Code Standard, the editions indicated were valid.
All references are subject to revisions, and parties to agreement and based on this Ethiopian
Building Code Standard are encouraged to investigate the possibility of applying the most recent
editions of the references indicated below. The Ethiopian Authority for Standardization
maintains registers of a number of foreign national and international standards.
1.3 DEFINITIONS
(1) For the purpose of this Code, the following definitions shall apply.
accessible (as applied to wiring methods) not permanently closed in by the structure or
finish of the building and capable of being
removed without disturbing the building
structure or finish.
branch circuit that portion of the wiring installation between the final
overcurrent device protecting the circuit and the outlet(s).
building void, accessible a space within the structure or the components of a building
accessible only at certain points.
bunched cables cables are said to be bunched when two or more are contained
within a single conduit, duct, ducting, or trunking or, if not
enclosed, are not separated from each other by a specified
distance.
cable tray a cable support consisting of a continuous base with raised edges
and no covering. A cable tray is considered to be non-perforated,
where less than 30% of the material is removed from the base.
a) fire, electric shock, and bums arising from the use of electrical
energy;
b) mechanical movement of electric~lly controlled equipment, in
so far as such danger is intended to be prevented by electrical
emergency switching or by ~lectrical ~witching for mechanical
maintenance of nop-electrical parts of such equipment.
design c14rrent (of a circuit) the magnitude of the current (r.m.s. valll,e for a.c.) to be carried by
the circuit in normal service.
direct contact contact of perSOnSor livestock with live parts which may result in
electric shock.
a) an item of switchgear,
b) an item of controlgear, or
c) a distribution board
earth the conductive mass of the Earth, whose electric potential at any
point is conventionally taken as zero.
earth-fault loop impedance the impedance of the earth-fault current loop starting and ending at
the point of earth fault. The earth fault loop comprises the
followiBg, starting at the point of fault:
(a) the circuit protective conductor;
(b) the consumer's earthing terminal and earthing conductor;
(c) the earth return path;
(d) the path through the earthen neutral point of the transformer
and the transformer winding; and the phase conduCtor from the
transformer to the point of fault.
-- -- --------~---------------------'---
SECTION 1: SCOPE AND DEFINITIONS
electrically independent earth electrodes earth electrodes located at such a distance from one another
that the maximum current likely to flow through one of them
does not significantly affect the potential of the other(s).
)
electrode boUer, electrode water heater equipment for the electrical heating of water or electrolyte by
the passage of an electric current between electrodes immersed
in the water or electrolyte.
emergency switching rapid cutting off of electrical energy to remove any unexpected
hazard to persons, livestock, or property.
external influence any influence external to an electrical installation which affects the
design and safe operation of that installation.
flexible wiring system a wiring system designed to provide mechanical flexibility in use
without degradation of the electrical components.
funcJionaJ earthing .
connection to earth necessary for proper functioning of electrical
equipment.
functional extra-Iow volt4ge any extra-low voltage system in which not all of the protective
measures required for SELV have been applied.
fuse a device that by the fusing of one or more of its specially designed
and proportioned components, opens the circuit in which it is
inserted by breaking ther current when this exceeds a give~ value
for a sufficient time. The fuse comprises all the parts that form the
complete device.
fuse element a part of a fuse designed to melt when the fuse operates.
fuse lin~ a part of a fuse, including the fuse element(s), which requires
replacement by a new or renewable fuse link after the fuse has
operated and before the fuse is put back into service.
hot air sauna a room or location in which air is heated to a high temperature and
in which the rekrtive humidity is normally low, rising for short
periods of time only when water is poured over the heater.
isolation a function intended to cut off for reasons of safety the supply from
all, or a discrete section, of the installation by separating the
installation or section from ~very source of electrical energy.
luminaire supporting coupler (LSC) a means, comprising an LSC outlet and an LSC plug,
providing mecl1a.n-malsupport for a lu.minaire and the
electrical connection to and disconnection from a fixed
wiring installation.
main earthing terminal the tenninal or bar provided for the CC/lili".:tlOnof
}lrotective conductors, including equipotential bonding
conductors, and conductors for functional earthing if
any, to the means of earthing.
obstacle a part preventing unintentional contact with live parts but not
preventing deliberate contact.
overcurrent a current exceeding the rated value. For conductors the rated value
is the current-carrying- capacity. \
prospective fault current the value of overcurrent at a given point in a circuit resulting from
a fault of negligible impedance between live conductors having a
difference of potential under normal operating conditions, or
between a live' conductor and an exposed-conductive-part.
protective conductor a conductor used for some measures of protection against electric
shock and intended for connecting together any of the following
parts (refer to Figure 1.1):
reduced low voltage sysiem a system in which the nominal phase to phase voltage does not
exceed 110.0V ahd the nominal phase to earth 'voltage does not
exceed 63.5V.
reinforced insulation single insulation applied to live parts, which proyides a degree of
protection against electric shock equivalent to double insulation
standard .
4
c
z p
B
residual current the vector sum of the instantaneous values of current flowing
through all live conductors of a circuit at a point in the electrical
installation.
residual upet'atlng current residual current which causes the residual current device to operate
under specified conditions.
resistance area (for an earth electrode only) the surface area of ground (around an earth electrode)
on which a significant voltage gradient may exist.
ring final circuit a final circuit arranged in the form of a ring and
connected to a single point of supply.
switch, linked a switch the contacts of which are so arranged as to make or break
all poles simultaneously or in a definite sequence.
temporary supply unit an enclosure containing" equipment for the purpose of taking a
temporary electrical supply safely from an item of street furniture.
The actual voltage of the installation may differ from the nominal
value by a quantity within normal tolerance.
SOURCE OF ENERJi
1I
L2
L3
~
CONSUMERS
SOURCE EARlH r-
I
I
J'~'~\.-------,
I
I
,
I
I
•I
,I
I I , I
, I ,
I I EQUf'tolENl IN
I
I INStALLAllON - I.
,
,
L _ EXPOSED
CONDUCTJV
1
.J
INSlALLAlI~ PARlS
fAR1H __ INSlAUAllOi
ELE:ClROOE fARlH ELCCTROfl:
wiring system. an assembly made up of cable or busbars and parts which secure
and, if necessary, enclose the cable or busbars.
9ENERAL REQUIREMENTS
2.1 ADMINISTRATIVE
(1) By virtue of the authority vested in the Authority having jurisdiction, this Code has been
adopted and hereby orders and directs its ·observance.
2.1.2 Permit
(1) Electric~l contractors or others responsible for the carrying out of the work shall obtain a
permit from the Authority having jurisdiction before commencing work with respect to
installation, alteration, repair, or extension of any electrical equipment.
(1) An application for inspection shall be fixed with the Authority having jurisdiction on a form
provided by the latter at the time the permit is obtained;
(1) A copy of the permit shall be posted in a conspicuous place on the site of the work and shall
not be removed until the inspection is completed.
(1) The Authority having jurisdiction shall be notified in writing by the electrical contractor ~at
work is ready for inspection at such time or times as will permit inspection being made before
any work or portion thereof is commenced.
(1) Plans and specifications in duplicate or in greater number if required by the Authority having
jurisdiction one copy to be retained by the Authority, shall be submitted by the owner or his
agent to, and acceptance obtained from, the Authority before work is commenced on:
(I) Where any electrical installation or part thereof to which electrical power or energy has not
previously been supplied is made in or upon any land building or premises, where any electrical
installation or part thereof has been disconnected or cut off from any service or other source of
supply under this Code, no supply authority, contractor or other person shall connect or re-
connect the installation or part thereof to any service or other source of supply unless:
a) the installation and all work in respect thereof have been inspected by an inspector; and
b) a connection authorizatioft has been issued by the Authority having jurisdiction in respect
of the installation.
2.1.8 Re-inspection
(1) The Authority having jurisdiction reserves the right to re-inspect at any time electrical
installation notwithstanding any previous inspection and acceptance, if and when it considers
suc~ action to be necessary.
(1) The Authority having jurisdiction may require such changes as may be necessary to be made
to existing installations where, through hard usage, wear and tear, or as a result of alteration or
extensions, dangerous conditions have developed.
(1) No one shall use any electrical equipment other than approved electrical equipment of a kind
or type and rating approved for the specific purpose for which it is to b e employed.
(1) 10 any case where deviation or postponement of this Code may be necessary, special
permission shall be obtained befo~ proceeding with the work, but this special permission shall
apply only to the particular installation for which it is given.
(1) Even though approval has previously been granted, the Authority having jurisdiction may
reject, at any time, any electrical equipment under any of the following conditions:
a) If the equipment is substandard with respect to the sample' on which approval was
granted.
b) If the conditions of use indicate that the equipment is not suitable.
c) If the terms of the approval agreement are not being carried out.
(1) Electrical equipment shall be installed as to ensure that, after installation, ,there is ready
access to nameplates and access to parts requiring maintenance.
(1) No person shall interfere with any electrical installation or component thereof except when,
in the course of alterations or repairs to non-electrical equipment or structures, it may be
necessary to disconnect or move components of an electrical installations.
(2) It shall be the responsibility of the persGiDiCarryingout thelalterations or repairs to ensure that
the electrical installation is restored to a safe operating condition as soon as the progress of the
alterations or repair will permit.
1.1 TECHNICAL
(1) Graphical symbols that are to be used in all drawings, wiring plans, etc for electrical
installations of buildings shall be as indicated in Section 26 of this Code.
1.1.1 Coordination
(1) Proper coordination and collaboration between the architect, building engineer and the
electrical engineer shall be effected from the planning stage of the installation.
(2) The provisions that will be needed for tile accommodation of substation, transformer, switch
room, lift wells and other appurtenant rooms, service cable ducts, rising mains and distribution
cables,sub-distribution boards, openings and chases in floor and walls for all required electrical
installation, etc, shall be specified in advance.
(1) The ideal location of an electrical subsbttion for a group of buildings would be at the load
centre and shall be located on the ground floor.
(2) In multi-storeyed buildings, the substation shall preferably be installed on the lowest floor
level, but direct access from the street for installation or removal of the equipment shall be
provided. The floor level of the substation or switch room shall !>eabove the highest flood level
ofthe locality. 'In this case, the load centre would be somewhere between the geometrical centre
andthe air-conditioning plant room.
(3) The availability of power lines nearby may also be kept in view while deciding the location
of the substation.
(I) In allocating area of a substation, it shall be noted that the flow of electric power is from
su~ly company's room to high tension room, then to transformer and finally to the low voltage
switchgear room. The layout of rooms shall be in accordance with this flow.
a) Switchgear Room - Supply 60mpany's switchgear room and/or space for meters.
b) Transformer Rooms - The number and size of transformer rooms shall be ascertained
from the total power requirement of the consumer.
c) Low-Voltage Switch RoomS - The floor area requirement in respect of low voltage
switchgear room shall be ascertained from the number of feeders.
d) Stand-by Generators. A room space not less than 6.0m x 9.0m may be provided for
housing a stand-by generator.
(1) The electrical control gear distribution boards and other apparatus, which are required on
each floor may conveniently be mouuted adjacent to the rising mains, and adequate space should
be provided at each floor for this purpose.
(1) Information regarding provjsion for and location ofPBXlPABX shall be obtained from the
relevant authority and adequate space should be provided for installation of t!te boards.
2.3.1 General
(1) The design and planning of an electrical installation shall take into account all the prevailing
conditionswhich may include some .or all of the following:
a) Type of supply.
b) Envisaged load having regard to the requirements of the owner or occupant.
c) The probable modifications and future extensions.
d) The degree of electrical and mechanical protection necessary.
e) The probable operation and maintenance cost taking into account the electricity supply
tariffs available.
£) The relative cost of various alternative methods.
g) The need for radio and telecommunication interference abatement.
(1) The electrical layout should be considered after proper locations of all outlets for lamps,
fans,appliances - both fixed and transportable, motors, etc, have been selected and best methods
of wiring determined.
(2) All runs of wiring and exact positions of all points of switch-boxes and other outlets shall
be first marked on the plans of the building and approved by the engineer in charge or the owner
before the actual commencement of the work.
2.3.3 Design
(3) The design shall comply with the requirements of this Code.
2.4.1 General
(1) Each piece of electrical equipment shall bear such of the following markings as may be
necessary to identify the equipment and ensure that it is suitable for the particular installation:
(2) Each service box, at the time of installation, shall be marked in a conspicuous, legible, and
pennanent manner to indicate clearly the maximum rating of the overcurrent device which may
be used for this installation.
(3) At each distribution point, circuit breakers, fuses, and switches shall be marked, adjacent
thereto, in a conspicuous and legible manner to indicate clearly:
(1) Careful attention shall be paid to the m~chanical execution of the work in connection with
any electrical installation.
(2) Any insta1!ation that has been badly arranged or poorly executed, either generally or in any
particular way, will not be accepted by the Authority having jurisdjction.
(1) Wood or other similar materials shall not be used as an anchor into masonry or concrete for
the support of any electrical equipment.
(1) Electrical equipment shall be installed and guarded so that adequate provision is made for
the safety of persons and property and for the protection of the electrical equipment from
mechanicalor other injury to which it is liable to be exposed.
2.4.5 Maintainability
(1)An assessment shall be made of the frequency and quality of maintenance the installation
canreasonably be expected to receive during its intended life.
(2)Where an authority is to be responsible for the operation of the installation, that authority
shallbe consulted.
(3) The following characteristics are to be taken into account in applying the requirements of
this Code, having regard to the frequency and quality of maintenance expected:
a) Any periodic inspection and testing and maintenance and repairs likely to be necessary
during the intended .life can be readily and safely carried out.
b) The effectiveness of the protective measures for safety during the intended life IS
ensured.
2.4.6 Enclosures
(1) Degree of protection provided by enclosures for ~lectrical equipment shall be in accordance
with mc 529.
3.1 SCOPE
(I) This Section of the Code gives guidance on design and installation of artificial lighting
systemsin interio.rs; it also applies to artificial lighting of outdoor areas.
(l) The following references contain provisions which, through reference in this text, constitute
provisionsof the Ethiopian Building Code Standards on Electrical Installation of Buildings.
(b) DIN 5035:1990 Part 1 - Artificial Lighting, Terminology and General Requirements.
(c) DIN 5035:1990 Part 2 - Artificial Lighting, Recommended Values for Lighting
Parameters for Indoor and Outdoor Workplaces.
(e) DIN 5035: 1983 Part 4- Artificial Lighting of Interiors, Special Recommendations for
Lighting Educational establishments
(g) DIN 5035: 1988 Part 7 - Artificial Lighting ofInteriors, Lighting of Rooms with VDU
Workstation or VDU Assisted Workplaces.
ETHIOPIAN
BUILDING CODE STANDARD EBCS-10 1995 29
ELECTRICAL INSTALLATION OF BUILDINGS
3.3 DEFINITIONS
.
(1) For the purpose of this Section of the Code, the following definitions shall apply in addition
to the terms defined in Section 1.
mean illuminance (E) the arithmetical mean of the illuminance in a room or in a room
zone being defined as that area of a room in which the same type
of activity is performed at a number of work-places or which is
used for similar purposes.
rated illuminance (E,) the nominal value of the mean illuminance that the lighting
installation is {fesigned to illuminate.
light loss factor (V) the ratio of the rated illuminance, En' to the design value of the
mean illuminance of a lighting system.
reflectance (Pc) the ratio of the luminous flux reflected from a surface to the
luminous flux incident on it.
localized lighting a non-uniform illuminance over the whole work area (see
Figure 3.2).
local lighting lighting for individual workplace in addition to the general lighting
produced by placing luminaries close to the visual task and
supplemented by a general lighting (see Figure 3.1).
/\
-
1\
- .
---.----.- ----.-.- - --------~~-._
1\
- :-;-.-.
/\
.._---_
1\
..---.-
1\/ \/ \/ \/ \
" I \ I I
I \ I \ I \ I \
;. a) grouped
b)awitched
/\ 1\ 1\ 1\
/ V \ / V \
I/\ \ /\
/ \ B
reflected glare glare and contrast reduction caused by reflection of high luminance
from glossy surfaces.
Note: The main disturbances caused by such reflection are contrast reduction, and impaired accommodation
and fusion.
Note: The colour of the light emitted by a near-white sources can be indicated by its correlated colour
temperature (CCT). Each lamp type has a specific CCT; but for practical use, they have been grouped
into three classes (see Table 3.1).
.
-
Correlated colour temperature
Intermediate
Warm (white)
Cool WW (white)
•(daylight whlte)-• NW
TW
CCT CI18S H
5300
3300 < CCT < 5300
c%ur rendering the relationship between the original colour of an object and the
colour in which it is rendered by artificial lighting.
Note: The ability of light source to render colours of s~ace accurately can be conveniently quantified by'
the CIE general colour rendering index. This index is based on the accuracy with which a set of test
colour'are reproduced by the lampt of interest relative to how they are reproduced by an appropriate
standard light source, identical agreement being given a value of tOO.Ou. Each lamp type has a
specific CIE general colour rendering index; but for practical use they can be divided into a number
of groups (see Table 3.2)
Colour
CIE general colour
rendering Typical application
rendering Index (AJ
groups
1A R.>90 Wherever accurate colour matching is required;
e.g. colour printing inspection.
emergency lighting lighting designed to become operative promptly if the power supply
to normal artificial lighting fails.
safety lighting an emergency lighting required for reasons of safety (general safety,
prevention of accidents).
t For tabular florescent lamps apparent colour and colour rendering characteristics, refer to Table 3.4.
sll/ety /igllting lor partial/Ju hazardous WOI'kplacu safety lighting designed to ensure that the work
performed at such workplaces can be safely
terminated in the manner required and the
workplaces themselves evacuated' without
danger.
Note: Particular hazardous workplaces are those which represent an immediate risk of accident or a potential
source of danger to third parties if the supply to the 'lighting should fail, raised platfonns, theatre
stages, race-courses and arenas counting as particularly hazardous workplaces.
response time the interval between a failure in the power supply to, the
normal artificial lighting and the provision of the required
illuminance by the emergency lighting.
.rated duration 01 operation the period of time for which an emergency lighting system is
designed to operate.
Umit duration 01 operatiOn the minimum period of time during which an emergency
lighting system shall still be capable of achieving the minimum
illuminance specified for the given application.
safety luminaries a luminary which mayor may not be provided witll its own
power supply and which is used for safety lighting.
standby lighting luminaries a luminary which mayor may not be provided with its own
power supply and which is used for standby lighting.
3.4.1 D1umin~nce
(1) Recommended illuminance for different types of interiors, tasks and workspaces given in
Table 3.5 and Table 3.6 shall be taken as the recommended minimum values on which the
design and assessment of lighting install~ions are to be based.
(2) For indoor workplaces that are manned full-time, a minimu~ rated illuminance of 200.01x
shall be provided unless other factors (such as nature of operation, physiological reasons) require v
different values.
(3) (it) In interiors designed for permanent human occupation, a minimum rated illuminance of
100.01x is required.
(b) If tasks are performed at fixed-location workplaces outdoors that correspond to tasks
performed indoors (e.g. operation of wood-work machines), then a rated illuminance
specified for such tasks in Table 3.5 for indoor workplaces shall be provided.
/ (4) At no stages in the useful life of the lighting installation shall the mean illuminance, E,
obtained at the workplaces be less than 0.8 times the value ofthe rated illuminance; at no single
workplace shall illuminance ever fall to less than 0.6 times the rated illuminance.
3.4.2 Luminance
(1) Reflectance in the working zone shall be planned so that the ratio between task luminance
(inner field) and that of the surrounding of the task are no greater than approximately 3: 1.
3.4.3 Glare
(1) Glare shall not be caused by lamps 0/ luminaries (direct glare) nor by reflection of high
luminance from glossy surface (reflected glare).
(2) Lamps with a high luminance (e.g. filament lamps and high discharge lamps) shall always
be shielded. \I
(3) In case of luminaries for local workplaces lighting, a direct view of the lamps shall be
precluded by shielding or by arranging them in a suitable position.
(1) Lighting shall be directed to produce an adequate degree of modelling shadow to enable
objects and surface texture to be easily recognized.
(2) Unduly hard shadows shall be,avoide,d. If the ratio Ez (cylindrical):En (horizontal) at a hight
of I.20m above floor is not smaller than 0.3, unduly hard shadows can be avoid~d.
(1) For inspection and comparison of colours, the CIE general colour rendering index ~ shall
not exceed 90 and the rated illuminance shall be IOOO.O/x.
(2) Only lamps meeting the requirements of Colour Rendering Group 3 (or higher) shall be used
for lighting interiors.
3.5.1.1 Illuminance
(1) The minimum illuminance of the safety lighting for escape routes shall be 1.0/x. This
requirement applies to the centre line of an escape route along a horizontal plane O.2m above
floor level.
(3) The rated duration of operation shall at least equal to the time that will be specified by safetY
law to be enacted by the concerned government body.
(4) The limit duration of operation shall be % (for l.Ohr) or % (for 3.0hr) of the rated duration.
(5) Safety luminaries for escape routes shall be sited according to their luminance distribution
so as to meet the requirements specified for safety lighting and in such a way that they cannot
easily be rendered ineffective. (Principal locations for the sitting of safety luminaries are, thus,
near the exits of escape routes and at poil}ts where it is necessary to emphasize the positions of
potential hazards.)
3.5.2.1 I/Iuminance
(I) The minimum illuminance for such workplaces shall be O.1En (rated illuminance specified
for the task and room of such workplaces in Table 3.5) but not less than IS.O/x.
(2) The minimum illuminance for platform and theatre stages shall be 3.0/x, and I5.0/x for
arenas and race-courses.
(1) The colour rendering shall at least be equivalent to Group 3 so as to ensure that safety
colours remain recognizable as such.
(1) The response time of safety lighting shall not exceed a maximum of 6.5s.
(2) In case of raised platform, theatre stages, arenas and race-courses, the maximum response
time shall be 1.0s.
(1) For workplaces, the lighting shall be effective for as long as the hazard subsists, with a
minimum duration of 1.0min.
(2) For raised platform, theatre stages, race-courses and arenas, the rated duration of operation
shall at least be equal to the duration required by law.
(1) Safety luminaries shall be sited so as to ensure that the required illuminance is provided over
the entire area in which hazardous tasks are carried out.
(1) The requirements to be met by standby lighting are analogous to those applying for normal
artificial lighting. To enable normal activities to continue, a minimum illuminance of 10% of
the rated illuminance value is generally required.
3.6.1 General
(1) The design objectives for lighting shall be to provide both good task visibility and a
satisfactory visual environment.
(2) (a) The lighting of workspaces shall ensure good visibility of the visual objects.
(b) The lighting of workplaces shall also be conducive to concentration and performance
attitudes, counteract premature fatigue and permit any potential hazards to be clearly
recognized.
(I) In addition to the lighting required for specific tasks, a general illumination shall be provided
to allow safe movement through the building at all material times.
(2) Where critical colour matching is to be done for a long period, a minimum illuminance of
IOOO.Olx shall be provided.
3.6.3 Offices
(I) As indicated on rated illuminance tables, for general offices illuminance of 500.01x and for
drawing offices illuminance of 750.01x shall be provided.
(2) Where VDU (Visual Display Units) are used, the illuminance shall be restricted to 500.01x
or less to minimize the high brightness reflection from the screen and large luminance
differences between screen, any source documents and the backgrounds against which these
items are seen.
(3) Where localized lighting is used, the ratio of illuminance between adjacent areas shall not
be more than 3: 1 with a minimum illuminance for lUtycontinuously occupied area of 200.0/x.
(4) Where locallightingjs used, the ratio of illuminance between task area and the surrounding
area shall not exceed 3: 1.
(5) A glare limiting index of 19 is appropriate for general office rooms and an index of 16 is
desirable for drawing offices because of the more demanding nature of work.
(6) Where daylight makes a substantial contribution, lamps with a CCT of 4000.0k or above
should be used.
(1) In dinning rooms and restaurants an illuminance of 100.0lx is recommended on a dinning table.
(3) In kitchens.and other service areas, a general illuminance of 300.0/x is recommended and
working areas should have an illuminance of 500.01x.
(4) Escape lighting shall be provided for public rooms, staircases and corridors and provisions
shall be made for emergency lighting and exit signs.
(1) The wide range of activities carried out in teaching and 'the variety of working media used
create constant changes in visual tasks; due to this, special requirements, over and above those
given in Clause 3.4.1, shall apply to the quality of the lighting in teaching rooms. This
requirements are given in the following Clauses.
(2) The guideline values for illuminance, colour appearance, colour rendering group and quality
of class of direct glare restriction given in Table 3.7 shall be applied in teaching spaces.
(3) Should the relevant type of room or activity not be listed in Table 3.7, the values given for
a similar, comparable room or activity shall be used mutatis mutandis.
(4) The guideline values given in Tables 3.5 and 3.6 for workspaces shall appJy to rooms which
have the same visual requirements as comparable workplaces, as well as to general purpose and
office-type rooms.
(5) The main chalkboard in teaching rooms and demonstration desks in teaching rooms for
special subjects shall be equipped with a supplementary lighting system to increase the vertical
illuminance.
3.6.6 Hospitals
(1) The guideline values for hospital lighting set in Table 3.8 shall apply to all rooms and zones
of a hospital.
(2) The lighting of bedded areas shall be conducive to the well-being of the patient, while also
~nabling examination or treatment to be carried out. To achieve these goals:
a) (i) the general lighting illuminance shall be IOO.Olx and shall not dazzle the patients or
nursing staff.
(ii) the mean luminance as perceived by the recumbent patients shall be limited to
IOOO.Ocdlm2while the luminance of the ceiling shall nowhere exceed 500.0cdlm2•
b) (i) Each bed shall be equipped with a rigidly mounted, adjustable luminaire. A rated
illuminance of 300.0lx shall be achieved on the reading plane (see Figure 3.4).
(ii) To avoid glare in multi-bed wards, the luminance of reading luminaries in the field
of vision of other patients shall not exceed IOOO.Ocd/m2•
c) (i) For the examination and treatmen~ of patients at.the bedside, a rated horizontal
illuminance of 300.Olx, inclusive of the general lighting, shall be provided O.ISm
above the longitudinal axis of the plane of the bed surface.
(ii) At no point along the axis in (i) above shall the illuminance be less than ISO.Olx.
(iii) The uniformity ratio of illuminance Emin:Eishall here not be less than 1:2.
d) (i) Night watch lighting with illuminance of approximately S.Olx shall be provided for
keeping patients under observation during the night. .
(3) (a) General lighting with a rated illuminance of 500.0lx and Group I colour rendering
properties shall be provided for examination and treatment.
(b) In addition to the general lighting an illuminance of at least IOOO.Olx is generally "
required at the site of examination.
(4) (a) The lighting in operating theatre shall always be designed in conjunction with the
lighting of the operating theatre field.
(b) In view of the illuminances of 20,OOOlx to IOO,OOO.Olx required in the operating field,
the surrounding lighting shall be designed to reduce the adaptation problems which
would be caused by extreme difference in the luminance between operating field and the
surrounding area.
(c) The illuminance of the surrounding light shall not be less than IOOO.Olx at a height of
I.Om above floor level.
(5) (a) Standby lighting system shall be provided for the operating theatres, anaesthetic rooms,
sterilizing sinks and recovery rooms.
(b) The standby lighting of the -operating table should be equal in all respects to the normal
lighting of this area, and should be of the maintained type to ensure continuous
illumination.
800
900
Reading plane
Examination
plane
Plane'a;-'
be~ lurf.lce °l
C>
C>
0' ::
gl
•....
lG
3.7.1 Illuminance
(1) For outdoor workspaces, circulation areas/zones and work roads, the recommended rated
illuminances in Table 3.6 shall be provided and they are to be taken as the recommended
minimum values.
(2) If the type of application of interest to the user is not listed, the recommended values
specified for a similar space shall be applied analogously.
(1) At fixed location workspaces, the colour rendering capability shall at . least meet the
requirements of Group 3t; safety colours and colours used for classification purposes shall be
recognizable as such.
t
Data on the group to which lamps belong with respect to their colour rendering capability are given in
product lists of manufacturers.
(1) Limitation of direct glare shall be based on Clause 3.4.3 of this Section.
(2) If the outdoor workplace is floodlight, the luminaries used shall be so located and arranged
that hazards due to direct glare are precluded.
(I) If-tasks are performed at fixed location work spaces outdoors that correspond to tasks
performed indoor, then, local workplace lightings shall be provided with rated illuminance
equivalent to the values specified for such tasks in Table 3.5.
Table 3.3 Typical characteristics of lighting sources used for general lighting
Hot cathode Cold cathode High-pressure
Tungsten Tungsten Low-pressure High-pressure
Characteristics tul;lular tubular mercury Mercury halide
Filament halogen sodium sodium
fluorescent fluorescent fluorescent
Range of luminous
efficacy (1.0 Irn/W) 8 to 18 18 to 24 100 to 175 65 to 120 35 to 90 40 to 60 35 to 55 65 to 85
Need for control gear No No Yes Yes Yes Yes Yes Yes
Operating position Any Horizontal Horizontal Any Any . Any Any Some restrictien
CCT(K) 25000 to 3000 28ooot03100 Not applicable 2200 2700 to 6500 2700 to 6500 4000 3600 to 4400
Note: Detailed information about any specific lamp type should be obtained from the manufacturer.
Table 3.4 Tubular fluorescent lamps apparent colour and colour rendering characteristics of lamps in general use
Lamp name 18 Apparent
23given
18 colour Typical application
Warm Equal
similar
Similar emphasis
Emphasizes
Emphasizes
to 1A
to IInorth
Colour 1A
subdues
group
yellows
northsky Intermediate
3oranges,·
oranges, Cool
Warm
Cool
yellows
and,
greens
light/colour
yellows, light;
and to and
to emphasizes
rendering less deep
allmatching
colours
blues
andextent. reds
reds
I[but
extent, is
blue-violets,
and towards
blues
BS
subdues
slightly
needed
green
violets;
emits
and,
greens;
95:Part
Factories,
significant
Factories,
Hotels,
Social
colour
Used
but some
where
areas,
subdued,
Ishops,
violet
Commercial/public 1fine
offices
rendering
critical,is
offices
blues
required
and
yellows
proportion
homes;
criticaland
restaurants,
colour
or to
shops
f'nd
of
colour
subdued
less
buildings
shops,
as
matching
shops adeep
rendering extent,
daylight
hotelsis reds
matching
where
and
greens
is admitted
replacement
particularly
required
and
or
shifted
where
for
matching
good, buttungsten
complying
homestogether
wherea daylight
isnot
with
required
critical,
with
good
s,
al which
sky light Colour rendering characteristics Used where
fl<Jt colour colour judgements
rendering similar are
to required,
north sky e.g.
filament lamps
orange
ower compact shift towards
hospitals, violet
art galleries and museums
high luminous efficacy
"
~
VI
"
•••
0\
L
I
Supplementary
atmosphere.
lighting
to
optional
be create
used
Incandescent
direct
I1.2.3 Control
Warehouses mirror
specific
lighting
lampswithmayis
reading tasks
ww,nw 1.3.2
100 group platform En. in Ix
, retrieval 1.2.1
tasksWarehouses for goods of one kind or of large unit size I
"
•••
~
00
2 3 4 I 5 I 6
Class limitation
glare of direct I
Remark
1_
. 'I
-- in~
I
group_ I __ I
3 Offices and similar rooms I I
I I
I I
3.1 Offices with daylight-oriented workplaces,
all in immediate vicinity of windows 300 ww,nw 2 I 1 I Workplace-oriented general lighting;
minimum of 0.8 En at workplace
~
\0
ov. Table 3.5 Indoor workspaces recommended illuminance (conte'd)
appearance 1
3group ~ may be lessRemark
than 3oo.0~
g, 345
glare
wvr,nw
ww,nw
Colour
may
Where 32112A
ww,nw,tw
ww,nw 2A
Cliiss
exceed 6 2
of direct
limitation
rendering
required 5oo.01x
for operational reasons, 100
50 500
200
300
500
750 200
300
200
illuminance, En'
Vfoundrl&!
mills,deviations
rolled less
stations
intervention
machining
plants
permissible
cold plant
Colour
than 0.1
deviations
sectional mm
greater
strip than 0.1 mm ~
6.1
7.1 Production plants ofnotsmall
Hammer-forging requiring
parts manual
Table 3.5 Indoor works paces recommended illuminance (conte'd)
appearance 1 Remark
Underfloor
Class
Tool, Local 45
ww,nw
ww,nw
ww,nw
ww,nw,tw1132manufacture;
3Colour
3
2
men-sized
ww,nw,tw
gauge of
2- 3Alimitation
direct
workplace
jig 6
trenches,
glare
lighting 2precision
belt
recommended 50 1000 lIIumlnance,E.,
100 300
200
300
500
750 200
Colour rendering group
7.14.1
7.16.1
7.12.1
mechanics; Electroplating
Low precision
highprecision
conveyor roads, cellars, etc. assembly
7.12 Assembly
Vl
N
Table 3.5 Indoor workspaces recommended illuminance (conte'd)
Colour
Cable
Loading
Electrical assembly
Where
require.
manufacture; 21-212A
3
ifww,nw
ww,nw
ww,nw
ww,nw,tw
ww,nw,tw
By providing
plant
with the
Shielding
fluorescent
engineering 2Blines
varnishing
against with
3operational
3required
45 13lighting 6local
fordirect workplace
2glare
operational
and
supplementary
Industrymay limitation
impregnation
conditions
be lighting
at
dispensed
rendering
groupso 500
1000
750
300
Remark 50
300
50 .500
200
100
illuminance,
Class Colour
of direct glare
while
stations
rooms
and
of work
7.18.1
coils;
reasons, is
Shell
armatures carried
~ maywith
simple out.
manufacture
be heavy-gauge
assembly
less than wire
tasks;300.0~.
winding of coils
9.1 8.1
7.18 Motor vehicle manufacture
521121A
43
3 12A
1A
3
limitation13 Industry
2A
1B group
2 making 500 1500
1000
500 500
100 Remark
200
1500
300
750
1000
Work recommended
Jewellery
Electrical
Woodworking Local nw,tw
ww,nw,tw
ww,nw
ww,nw
ww,nw,tw
engineering
Industry,
at woodworking
workplace
Colour
Class watch and6 clock
lighting
appearance
of direct (conte'd)
machines;
glare turning, illuminance, ,ac:l;';'::.~3nded
Local workplace lighting (
Colour rendering
11.6
calibration
chamfering,
marquetry
Industry
gaugecomponents
winding
cutting, wire ofdressing,
work coils andrebating,
sawing,sinking armaturesslotting,
with medium-
11.1 10.1
Steam Manufacture
pits of jewellery
Table 3.5 Indoor workspa~es recommended illuminance (conte'd)
--- ww,nw
1------------ for -- --
-- --Remark
shoe
mills
cardboard
to
avoided
500
Leather
vertical
hand
sorting;
composing; by
Cia
incidence.
I Industry
lighting,
composing,means
pressing;
1
Colour
appearance
--recommended.
...............
___
45
ww,nw,tw
ww,nw
ww,nw,tw",
For tubs,
selection
Saddlery work;
Colour
3glare
2A
••321of-
limitation
of
due1A
2A dlutet
•• OOO+OI}o(.
WW.OW
quilting;
group
reflections
suitable
obliquely
AV6idance
cutting
make-ready
6sewing
edtention
correct
being
to from
of
lightmust
3 For dark materials, increase to
manufacture
fabricedion
Local ofworkplace lighting
light
size the
reflected
be render!ng
glare by
punching;
given
incidence;
polishing;
1-
lC)CaJ _ClIrk,?,I~~
- ,lighting
500
2000
1000
750
300
200
300
1500
illuminance,
2
side.
~I-
13.1 12.1
WorkWork
ed vl'.ds; tubs, pits
ed Hollanders, edge runners, grinding
Table 3.5 Indoor workspaces recommended illuminance (conte'd)
rated illuminance,
InJ!
-t--~-Colour
Colour
4
.rendering
5
Class of direct
glare
6
Remark
Em appearance
group limitation
13 Leather Industry (conte'd)
I nw,tw 1
VI
VI
Table 3.5 Indoor works paces recommended iIIuminance(conte'd)
Colour
1glass rendering' Rated illuminance,
500
Cutting
Workplaces
Making
For
Colour colour
Depending
Workplace
Inspection
Sorting of 2A
45
Class11
2
32A
limitation
ww,nw
nw
ww,nw
ww,nw,tw
matching;
and 1A
sorting
delicatessen
matching,
and
on
and
ofwashing work
the
ofwork 6
directofoffruit 2in
andand
zones
shield
products;
laboratories
layout
zones
jars glareofin
produce;from
theabattoirs,
breweries
product 300
200
500
group 1000 300 illuminance.
Colour appearance Remark
recommended.
beds
cellar
sorting
kitchens;
light sources
control;
and
barrels,
fermenting
grinding,
i1luminant.
vegetables
workplace,
cooking
work cigar
malthouses;
zones
chocolate and Local and
with
garnishing,
cleaning,
mixing.
ensurE! a
leaf cigarette
different
decorating,
sieving,
tobacco;
packaging
workplace
inboiling
sugar
factories; adequate
washing,
in
refineries.
canning
workplaces manufacture
peeling,
fermenting
lightingand
vertical
tiling for
and
in
anddrying
15.1
16.1 Sales areas
Table 3.5 Indoor works paces recommended illuminance (conte'd)
I group Colour
1 rendering II Rated
Wharfs
Docks
Repair
Quayage I 4
20
0.2
Workspaces for mixed
passenger
facilities in 30.2
0.5
,I 0.2
0.2
0.2, 44
trafficII3shipping
harbour
inilluminance,
Idepot
Uniformity
iI Supplementary
Dazzling traffic
areas
ofIE. oflocal5to 2 I•••
workplace I lighting
be avoided. I 3035 30
100
20.
20
50
10 required in containers.
30 34!I
10 i I
!I
I I
9! =E~ Remarks g." in Ix
ance, 3.3.1 Unit loads I IiI
I I
3.1.2 Loading and unloading I containers
0\
o
Colour
appearance
Community stacks
If ww,nw
wW,nw
ww,nw
Room for objects 51-23aids
43direct
cabinets
ww:nw
Remarks
ww,nw
teaching
necessary,
rooms
Quality
1 supplementary
23exhibited,
restriction
and of
glare 6 2 and
collections
platforms lighting
lighting )
shelves.
for
for 200
10<:\
50
200 300
100
20
200
300
500
Colourclass
property group rendering illuminance, ~
3.6 above
3.1 1.1
Corridors
2.1 Roofed recreation area
Table 3.7 Guideline values for educational establishment lighting (conte'd)
illuminance, En 2 4 in Rated
Ix 3property
5
I Remarks
rendering 6
restriction
Colour
Quality class
direct glareof
appearance group
Colour
J.----.--+-----
5.7 Technical drawing' ww,nw
~._~ 1 : ---
7at a height of 1.2m
6 Lecture theatres
- --1-- 700---l- I
I
I I
t The values of the luminance restriction curve belonging to the next highest nominal illuminance shall be observed
Table 3. 8 Guidance value for hospital lighting
-i--~- t
Room type i I I I I
='
L
"IYIpelof alct vlty type I illuminance,
n~ 'I 91t ng renderinggro
up i
i
restriction
9 areof direct I Remarks
Infants ward
Night watch lighting
Examination lighting
Night lighting
General lighting
Night-watch lighting
L
I
'II
300
200
I
:
I
I
ww
ww
ww
ww
:
I
I'
1
1
1
1
r---
'I
II
1
1
1
I
I
I
Approximately 5.0~
I~
I
I >1000 ww,nw, 1 I
--+ ----~
Special examination
treatment rooms
and
Preparation ww,nw
ww,nw
ww,nw
WW,nw
I
I
20
500
55
50
I
Ii I---~---I
I
I
1
I
I
I
,
I
i
I
If required, switchable or
yonitor
ry
metry
ycopy For endoscope examination , 1 I
• I controllable to give lower
1 ! illuminance values
hting
1 I
colour
nw colour Rated
- lighting
1ww
1WW
nw
ww,nw
Workplace
Reduced
required.
Quality11 Remarks
Illuminance:
tw
100000.0Ix,
ww,nw
restriction
minimum; from
1ooo.01x
glare of for
desired 20000
direct
lighting,
class for 500
to1000
300
100
General
rendering
patients
if General lightinglighting
room for changing Illuminance, illuminance: 2OOO.01x
glare
Wash rooms
treatment
rooms
areas
Medicinal rooms
preparation
treatment
Ughting
group1)
baths (conte,d)
s.. !!
Type ofin activity / Type of
Intensive
Operating
Dialysis care areas
for
for dentalrooms
theatre
dermatological suites
examinationsexaminations
Table 3. 8 Guidance value for hospital lighting (conte'd)
Colour
colour-1 Remarks Rated
1
22
1nw
ww
ww
nw2-1
nw
nw Bedded areas
I If restriction
ww,nw
required,
Quality
lighting forclassof direct
workplace
filling
glare
~~--
group'
for 200
50
300
100500
1000
300
hypodermic200
100 for
>5000
Lighting
General
Sanitary
rendering
Type difficult
lighting
blocks
--- of activity
in...!!
visualof tasks
connecting
/ Type to illuminance s.. -
etc. Lighting
- day-time
syringes, sorting medicines
ELECTICAL INSTALLATION OF BUILDINGS
SECTION 4
CONDUCTORS
4.1 SCOPE
1) This Section of the Code specifies the nom inal cross-sectional areas of conductors in electric
cables and cords used for lighting, appliance and power supply circuits for a nominal voltage
not exceeding 1.0kV.
2) The conductors include solid and stranded copper and aluminium conductors in cables for
fixed installation and flexible copper conductors.
3) The provisions of this Section do not apply to conductors for telecommunication purposes.
(1) The following references contain provisions which, through reference in this text, constitute
provisions of the Ethiopian Building Code Standards on Electrical Installation of Buildings.
(1) C22.1: 1990 Canadian Electrical Code, Part I, Safety Standard for Electrical
Installations, Sixteenth Edition.
4.3 DEFINITIONS
\
j
(1) For the purpose of this Section of the Code, the following definitions shall apply in addition
to those terms defined in Section 1.
conductor (of a cable) a part of a cable which has the specific function of carrying current.
plain conductor a metal conductor in which the wire or wires are not coated with
an additional metal.
metal coated conductor a conductor in which eacn individual wire is covered with a thin
layer of a different metal or metal alloy.
flexible conductor a stranded conductor having wires of diameters small enough and
so assembled that the conductor is suitable for use in a flexible
cable.
insulation (of a cable) insulating materials incorporated in a cable with the specific
function of withstanding voltage.
insulating screen; core screen an electrical screen of non-metallic material covering the insulation.
shield (of a cable) a surrounding earthed metallic layer to confine the electric field
within the cable and/or to protect the cable from external electrical
influence. (Metallic sheaths, armours and earthed concentric
conductors may also serve as shields).
core (insulated conductor) an assembly comprising a conductor with its own insulation (and
screen if any).
flat (multicore) cable a multicore cable having cores or groups of cores arranged in
parallel flat formation.
aerial (insulated) cable an insulated cable designed to be suspended overhead and outdoors.
a) .1.0mm2 for cables and insulated copper conductors for power and lighting circuits;
b) 10.0mm2 for bare copper conductors for power circuits;
c) 16.0mm2 fo~ bare aluminium conductors for power circuits; .•.
d) O.5mm2 for flexible cables of copper conductors for extra low voltage.
(1) For a polyphase circuits in which imbalance may occur in normal service, the neutral
conductor shall have a cross-sectional area adequate to carry the maximum connected load
between the neutral and anyone ungrounded conductor.
(2) For a polyphase circuit in which serious imbalance is unlikely to occur in normal service,
other than a discharge lighting circuit, multicore cables incorporating a reduced neutral conductor
may be used. When single-core cables are used in such circuits, the neutral conductor shall have
a cross-sectional area appropriate to the expected value of the neutral current.
(3) In a discharge lighting circuit, the neutral conductors shall have a cross-sectional area not
.less than that of the· phase conductor(s).
(1) The current to be carried by any conductor for sustained periods during normal operation
shall be such that conductor operating temperature given in the appropriate table of current-
carrying capacity in Annex B of this Section is not exceeded.
(1) Except for a ring final circuit, cables connected in parallel shall be of the same construction,
of cross-sectional area, length and disposition, without branch circuits and arranged so as to
carry substantially equal current.
(1) Where a cable is to be connected to a bare conductor busbar, its type of insulation and/or
sheath shall be suitable for the maximum operating temperature of the bare conductor or busbar.
(1) The size of conductors shall be, such that the voltage drop between the supply terminal and.
fixed current-using equipment shall not exceed 4% of the nominal voltage of the supply line,
when the conductors are carrying the full, load current.
a) as a substitute for the fixed wiring of structures and shall not be:
c) for the suspension of any device weighing more than 2.3kg unless the cord and device
assembly are marked as capable of supporting a weight upto 11.Okg.
(3) Flexible cord shall be protected by insulating bushing or in some other acceptable manner
where it enters or passes through the enclosure wall or the partitioning of a device or enters a
lampholder.
(4) Where a flexible cord is used as an extension cord or to plug into an appliance or other
device, no live parts shall be exposed when one end is connected to a source of supply and the
other end is free.
(1) Colour identification of conductors shall be as specified in Tables 4.1 anr 4.2 V'
(1) Any cable must be capable of withstanding the maximum expected short-circuit current in
its circuit for the maximum expected disconnection time of its protective device without
exceeding the maximum pennissible temperature given in Table 4.3 ,,/
Conduct Insulation
60°C
70°C rubber
220
200
250 material
160(general
85°C 160/140t
Mineral160/140t 250°C
160
temperature
Umltlng
p.v.c
p.v.c final
purpose) 105 80
70
60
90
70 (sheath) Conductor
(sheath)
85
operating temperature °C
combustible
- Plasticinmaterials
touchnor contact with
covered or exposed to
t above 300.6m2
The current-carrying capacity set out in Annex B takes account of IEC Publica~ion 364-5-523(1983),
so far as the later is applicable.
For types of cable not treated in the IEC publication (e.g. annoured cables), the current-carrying
capacity of Annex B is based on data provided by ERA Technology Ltd.ttt, and the British
Cable Makers' Confederation (see also ERA Report 69-30 'current Rating Standards for
Distribution Cables"),
The tabulated current-carrying' capacity relates to continuous service and is also known as the
full thermal current rating' of the cable, corresponding to the conductor operating temperature
indicated in the headings to the tables concerned.
It is intended to provide for a satisfactory life of conductor and insulation subject to the thermal
effects of carrying current for sustained periods in normal service. A cable may be seriously
damaged, leading to early failure, or its service life may be significantly reduced, if it is operated
for any prolonged period at a temperature higher than the indicated value.
In addition, there are other considerations affecting the choice of the cross-sectional area of a
conductor, such as the requirements for protection against electric shock, protection against
thermal effects, overcurrent protection (see A.5 below), voltage drop (see A.7 below) and the
limiting temperatures for terminals of equipment to which the conductors are connected.
The tabulated current-carrying capacity relates to a single circuit in the instanation methods
shown in Annex A of Section 8, in an ambient air temperature of 30°C. The curr<?nt-carrying
capacity given in the tables for a.c. operation apply only to frequencies in the range 49.0 to
61.0Hz. For other conditions, appropriate correction factors are to be applied as described below.
The current ratings given for, single-core armoured cable are for the condition of armour bonded
at 'both ends and to earth.
Tables A.I, A.2 and A.3 give the correction factors to be applied to tPe tabulated current-
carrying capacity where cables or <rcuits are grouped.
In practice, the ambient air temperatures may be detennined by thennometers placed in free air
as close as practicable to the position at which the cables are installed or are to be installed,
subject to the provision that the measurements are not to be influenced by the heat arising from
the cables; thus, if the measurements are made while the cables are loaded, the thennometers
should be placed about 0.5m or ten times the overall diameter of the cable, which ever is the
lesser, from the cables, in the horizontal phme, or 150.0mm below the lowest of the cables.
Tables AA and A.5 do not take account of temperature increase, if any, due to solar or other
infra-red radiations; where cables are subject to such radiation, the current-carrying, capacity may
need to be specially calculated.
In extreme cases, notably for large multicore cables, the reduction in current-carrying capacity
of cables carrying, for example, balanced 400.0Hz a.c. compared with the current-carrying
capacity at 50.0Hz, may be as much as 50%. For small cables and flexible cords, such as may
be used to supply individual tools, the difference in the 50.0Hz and the 400.0Hz current-carrying
capacities may be negligible.
The current-carrying capacity of a cable corresponds to the maximum current that can be carried
in specified conditions without the conductors exceediQg the permissible limit of steady state
temperature for the type of insulation concerned.
The values of tabulated current represent the effective current carrying capacity only where no
correction factor is applicable; otherwise, the current-carrying capacity corresponds to the
tabulated value multiplied by the appropriate factor or factors for ambient temperature, grouping
and thermal insulation, l!S applicable.
Irrespective of the type of overcurrent protective device associated with the conductors
concerned, the ambient temperature correction factors to be used when calculating current-
carrying capacity (as opposed to those used when selecting cable sizes) are those given in
Table A.4.
v the current-carrying capacity of a cable for continuous service, under the particular
installation conditIons concerned.
It the value of current tabulated in Annex B for the type of cable and installation
method concerned, for a single circuit in an ambient temperature of 30°C. ,
~ Ib the design current of the circuit, i.e. the current intended to be carried by the circuit
in normal service.
In the nominal current or current setting of the device. protecting the circuit against /"
overcurrent.
12 the operating current (Le. the fusing current or tripping current for the conventional
operating time) of the device protecting the circuit against overload.
G - A correction factor to be applied where the installation conditions differ from those for
which values of current carrying capacity are tabulated in Annex B. The various
correction factors are identified as follows:
In all circumstances, Iz must be not less than Ib, and In also must be not less than lb.
Where the overcurrent device is intended to afford protection against overload, 12 must not
exceed 1.451. and In must not exceed Iz (see A.5 below).
Where the overcurrent device is intended to afford short circuit protection only, In can be
greater than Iz and 12 can be greater than 1.451z.
Where overload protection is required, the type of protection provided does n9t affect the
current-carrying capacity of a cable for continuous service (lz), but it may affect the choice of
conductor size. The operating conditiQns of a cable are influenced not only by the limiting
conductor temperature for continuous service, but also by the conductor temperature which might
be attained during the conventional operating time of the overload protection device, in the event
of an overload.
This means that the operating current of the protective device must not exceed 1.45Iz. Where the
protective device is a fuse or a miniature circuit-breaker, this requirement is satisfied by selecting
a value of Iz not less than In
In practice, because of the standard steps in nominal rating of fuses and circuit-breakers, it is
often necessary to select a value of In exceeding lb' In that case, because it is also necessary for
Iz in turn to be not less than the selected value of Iu, the choice of conductor cross-sectional area
may be dictated by the overload conditions and the current-carrying capacity (IJ of the
conductors will not always be fully used.
The size needed for a conductor protected against overload by a semi-enclosed fuse can be
obtained by the use of a correction factor, 1.45/2=0.725, which results in the same degree of
protection as that afforded by other overload protective devices. This factor is to be applied to
the nominal rating of the fuse as a divisor, thus indicating the minimum value of -4 required of
the conductor to be protected. In this case also, the choice of conductor size is dictated by the
overload conditions and the current-carrying capacity (IJ of the conductors cannot be fully used.
Having established the design current (Ib) of the circuit under consideration, the appropriate
procedure described in A-6.1 to A-6.4 below will enable the designer to determine the size of
the cable that will be necessary to use.
As a preliminary step, it is useful to identify the length of the cable run and the permissible
voltage drop for the equipment being supplied, as this may be an over-riding consideration (see
A.7 below). The permissible voltage drop in mV, divided by Ib and by the length of run, will
give the value of voltage drop in mv/Alm which can be tolerated. A voltage drop not exceeding
that value is identified in the appropriate table and the corresponding cross-sectional area of
conductor needed on this account can be read-off directly before any other calculations are made.
The conductor size necessary from consideration of the conditions of normal load and overload
is then detennined. All correction factors affecting Iz (that is, the factors for ambient
temperature, grouping and thermal insulation) can, if desired, be applied to the values of -4 as
multipliers. This involves a process of trial and error until a cross-sectional area is reached
which ensures that Iz is not less than Ib and not less than Iu of any protective device that is
intended to select. In any event, if a correction factot for protection by a semi-enclosed fuse is
necessary, this has to be applied to Iu as a divisor. It is, therefore, more convenient to apply all
the correction factors to In as divisors.
This methojl is u"sed in A.6.1 through A.6.3 and produces a value of current and that value (or
the next larger value) can readily be located in the appropriate table of current-carrying capacity
and the corresponding cross-sectional area of conductor can be identified directly. It should be
noted that the value of -4 appearing against the chosen cross-sectional area is not Iz. It is not
necessary to know Iz where the size of conductor is chosen by this method; but if it is desired
to identify Iz the value is determined by the method indicated in A.3 above.
However, this method cannot be used. for cables installed in enclosed trenches (Installation
Methods 18, 19 and 20 of Annex A, Section 8) because the correction factors given in Table A3
are related to conductor cross-sectional areas. For such cables, it is, therefore, necessary to use
the process of trial and error described above, selecting on a trial basis a particular size of cable
from, for instance, voltage drop considerations.
- divide nominal current of the protective device (In) by any applicable correction factor
for ambient temperature (CJ given in Table AA.
(2) The size of cable to be used shall be such that its tabulated current-carrying capacity (~)
give in Equation (AI) below is not less than the value of nominal current of the protective
device adjusted as above:
~ (AI)
~J! -I) (Ampere)
Ca~:
- divide the nominal current of the protective device (In) by the correction factor for
grouping (Cg) given in Table::. A.l, A.2" or A.3:
(A2)
Alternatively, it may be selected in accordance with the following formulae, provided that the
circuits of the group are not liable to simultaneous overload:
------~--~----~---~--~~---~--~---~----~--~---~
ELECTRICAL INSTALLATION OF BUILDINGS
(A.3)
and
(AA)
(Ampere ).
I: +0.48/; [1~/e2l
t'c;; Ct."
The size of cable to be used shall be such that its tabulated single-circuit current-ca.rrYing
capacity (It) is not less than the value of It calculated in accordance with Equation (A.2) ab~ve
or, where Equations.(A.3) and (A.4) are used, not less than the larger of the resulting two values
of~.
Where correction factors C. and/or Cj are applicable, they are to be applied as divisors to the
value of It determined by the above formulae.
- divided the nominal current of the fuse (In) by any applicable correction .factor for
ambient temperature (CJ given in Table A.Sj
- then further divide by any applicable correction factor for thermal insulation, (Cj);
J ~ then further divide by 0.725.
The size of cable to be used shall be such that its tabulated current-carrying capacity (~) is not
less than the value of nominal current of the fuse adjusted as above:
(A. 5)
- divided the nominal current of the fuse In by 0.725 and by the applicaole correction
factor for grouping (Cg) given in Tables AI, A2 ,or AJ
(A6)
Alternatively, it may be selected by the following formulae, provided that the circuits of the
group are not liable to simultaneous overload.
(A7)
and
(AS)
(Ampere)
The size of cable to be used shall be such that its tabulated single-circuit current-carrying
capacity (It) is not less than the value of It calculated in accordanc€; with Equation (A6) above
or, where Equation (A7) and (AS) are used, not less than the larger of the resulting two values
of It.
(J) Where correction factors C. and/or Cj are applicable, they are to be applied as divisors to -the
value of It determined by the above Equation.
Where the cable under consideration is not required to be protected against overload, the design
current of the circuit (Ib) is to be divided by any applicable correction factors, and the size of
the cable to be used shall be such that its tabulated current-carrying capacity (It)given by
Equation (A.9) below for the installation method concerned is not less than the value of Ib
adjusted as above:
(A.9)
(Ainpere)
The procedures in A.6.1 through A.6.3 above are based on the assumption that all the conditions
necessitating the use of correction factors apply ,to the same part of the route of the conductors
of the circuit. Where various factors apply to different parts of the route, each part may be
treated separately or, alternatively, only the factor or combination of factors appropriate to the
roost onerous conditions encountered along the route may be applied to the whole of the route.
It is permissible to obtain more precise factors by calculation of the various conductor
temperature rises that will occur along such a route, provided that the appropriate limiting
temperature of the conductor is nowhere exceeded.
In the tables, values of voltage drop are given for a current of one ampere for a metre run, i.e,
for a distance of 1.Om along the route taken by the cables, and represent the result of the voltage
drops in all the circuit conductors. The values of voltage drop assume that the conductors are
at their maximum permitted nolffial operating temperatures.
The values in the tables, for a.c. operation, apply only to frequencies in the range 49.0Hz to
61.0Hz; and for single-core armoured cables, the tabulated values apply where the armour is
bonded to earth at both ends. - The values of voltage drop for cables operating at higher
frequencies may be substantially gre&ter.
For a given run, to calculate the voltage drop (in mY) the tabulated value for the cable
concerned has to be multiplied by the length of the run in metres and by the current the cable
is intended to carry; namely, the design current of the circuit (Ib) in amperes. For three-phase
circuits, the tabulated mV/AIm values relate to the line voltage and balanced conditions have
been assumed.
For cables having conductors of 16.0mm2 or less cross-sectional area, their inductances can be
ignored and (mV/Alm)r values only are tabulated. For cables having conductors greater than
16.0mm2 cross-sectional area, the impedance values are given as (mV/Alm)z, together with the
resistive component (mV/Alm)r and the reactive component (mV/Alm)x
The direct use of the tabulated (mV/Alm)r or (mV/Alm)z values, as appropriate, may lead to
pessimistically high calculated values of voltage drop or, in other words, to unnecessarily low
values of permitted circuit lengths. For example, where the design current of a circuit is
significantly less than the effective current-carrying capacity of the cable chosen, the actual
voltage drop would be less than the calculated value because the conductor temperature (and,
hence, its resistance) will be less than that on which the tabulated mV/Aim had been based.
As regards power factor in a.c. circuits, the use of the tabulated mV/Aim values, (for the larger
cable sizes, the tabulated (mV/Alm)z values) to calculate the voltage drop is strictly correct only
when the phase angle of the cable equals that of the load. When the phase angle of the cable
does not equal that of the load, the direct use of the tabulated mV/Aim or (mV/Alm)z values
leads to a calculated value of voltage drop higher than the actual yalue. In some cases, it may
be advantageous to take account of the load power factor wher calculating voltage drop.
Where a more accurate assessment of voltage drop is desirable the following methods may be
used.
For cables having conductors of cross-sectional area 16.0mm2 or less, the design value of
mV/Aim is obtained by multiplying the tabulated value by a factor Ct, given by
12
c=
t
230 + t -
p
(CC - ~)(t
a g i t p
- 30) (A. 10)
230 + tp
Equation (A. 10) applies only where the overcurrent protective device is other than a fuse and
where the actual ambient temperature is equal to or greater than 30°C.
Note: For convenience, the above fonnula is based on the resistance-temperature coefficient of 0.004 per °C at 20
°C for both copper and aluminium conductors.
For cables having conductors of cross-sectional area greater than 16.0mm2, only the resistive
component of the voltage drop is affected by the temperature and the factor Ct, is therefore
applied only to the tabulated value of (mV/Alm), and the design value of (mV/Alm)z is given
by the vector sum of Ct (mV/Alm), and (mV/Alm)x'
For very large conductor sIzes where the resistive component of voltage drop is much less than
the corresponding reactive part (i.e when x/r~3) this correction factor need not be considered.
For cables having conductors of cross-sectional area of 16.0mm2 or less, the design value of
mV/Aim is obtained approximately by multiplying the tabulated value by the power factor of
the load, CDS ~.
For cables having conductors of cross-sectional area greater than 16.0mm2 the design value of
mV/Aim is given approximately by: CDS ~ [tabulated (mV/Aim),] + sin ~ [(tabulated (mV/Alm)xl
For single-core cables in flat formation, the tabulated values apply to outer cables and may
underestimate for the voltage drop between an outer cable and the centre cable for cross-
sectional areas above 240.0mm2 and power factors greater than 0.8.
(c) Combined correction for both operating temperature and load power factor
From (a) and (b) above, where it is considered appropriate to correct the tabulated mV/Aim
values for both operating temperature and load power factor, the design values of mV/Aim are
given as follows:
CORRECTION FACTORS
Table A.I: Correction factors for groups of more than one circuit of single-core cables, or more than one multi~ore cable ;/.1
([0 be applied to the corresponding current-carrying capacity for a single circuit in Tables B.I through B.8, B.9 through B.16, B.l7 throughB.l9, B.20, B.2?, B.28, B.31 through B.38, B.39 through B.46t) Il.-
,
-- -,-,--
320
-,, -, ,--
0.81
60.67
0.69
0.70
0.71
0.73
7100.39
90.38
14
0.72
0,74
0.70
0.66
0.77
0.76
0.62
0.90
0.50
0.52
0.54
0.57
0.60
0.65
0.43
0.72
0.75
0.79
5
4 0.90
12
0.730.41-
0.45
0.460.77
0.90
0.90
16 0.65
0.71 I0.91
0.6 0.66
0.7
0.94
7~.
-
Vertical
Spacedtt#
0.60
0.66
Correction factor (C~
l;",
J.-'t
Number touching
of circuits (Method
horizontal (method 11)
11) cables
or multicore ../' Spacedtt J.:r
J,b
'c9-<f
3cs
t When cables having differing conductor operating temperatures are grouped together, the current rating shall be based upon the lowest operating temperature of any cable "
in the group.
tt Spaced by a clearance between adjacent surfaces of at least one cable diameter (D.) where the horizontal clearances between adjacent cable exceeds 2D., no correction factor need be applied.
# Not applicable to mineral insulated cables, see Table A.2.
00
V\
/
ELECTRICAL INSTALLATION OF BUILDINGS
U'f~(~~!St
Table A.2 Correction factors for mineral insulated cables installed on
perforated tray
(To be Applied to the Corresponding Current-Carrying Capacity for Single Circuits for Reference Method 11 ~
Table B.27)
l
Tray 93.
.0.95
4
0.90
21;0
0.75
0.80
0.70
0.75
1.0
1.0
0.85
1.0 1
-6Number of multicore
Multiconductor
Arrangement
Single cables
of cables
conductor or1
cablestouching
cables
cables er of
circuits
touching
spacedt
1trefoil
spaced t Numb
••
I c
Vertical Trays ~I
"C
(
,
c
C
I
c
.!
"C
~
C
~I
.!
l
~
t l
Spaced by a clearance by between adjacent surfaces of at least one cable diameter (Dc) I
tt Spaced by a clearance between adjacent surfaces of at least one cable diameter ( 2De). ~
I
c
1
~
Notes to Tables A.I and A.2
Ic
(i) The factors in the Tables are applicable to groups of cables all of one size. The value of current derived from 1
application of the appropriate factors is the maximum current to be carried by any {)f the cables in the group. I
(
I;,
(ii) If, due to known operating conditions, a cable is expected to carry not more than 30% of its grouped rating, it
may be ignored for the purpose of obtaining the rating factor of its grouped rating, it may be ignored for the
purpose of obtaining the rating factor for the rest of the group. For example, a group ofN loaded cables would
normally require a group reduction factor of Cgapplied to the tabulated~. H,owever,if M cables in the group
carry loads which are not greater than O.3CgLtamperes the other cables can be sized by using the group rating
factor corresponding to (N-M) cables.
(iii) When cables having differing conductor operatihrgtemperatures are grouped together, the current rating shall be
based on the lowest operating temperature of any cable in the group.
(iv) Where the horizontal clearances between adjacent cables exceeds 2Dc, no correction factor need be applied.
~taIlation Methods 18, 19 and 20 of Annex A, Section 8yt j' l' e-vCf ~[qq7 .
The correction factms tabu1atedbelow relate to the di'l""ition of cable illustrated m lrem No. 18 to lrem No. 20 of Annex A, Soroon 8, and are "1'Plicable to the curren~~.
capacities for Reference Methods 12 or 13 of Annex A, Section 8, as given in the relevant tables of this Annex.
1 0.93
0.92
0.88
core0.90
0.89
0.87
1610
0.81
2
0.76
0.87
0.71
0.82
0.75
0.85
0.84
0.79
3
8
0.67
0.73
0.81
0.66
0.72
0.63
11
0.90
0.61
0.56
0.88
0.83
0.64
0.89
7
0.57
0.52
0.60
0.68
0.51
0.69
0.74
0.63
0.48
0.53
0.67
0.80
0.66
0.72
0.78
0.59
0.82
0.73
5
0.50
0.41
0.43
80.81
0.83
0.85
0.59
0.74
0.80
0.65
0.49
0.55
~0.65
0.91
0.86
0.82
0.80
0.78
0.77
0.69
0.78
0.49
three-0.86
0.54
0.62
4
6
0.46
0.76
9
0.44
0.47
four-
or
0.84
three-
core
core two-core
two-core
0.77
0.70
0.58
\9.86
cables,
42 8 cables
three-
cables
core
or3
three-
cables,
core 63or
cables,
cables,
3 cables,
24
12 core
four-corefour-
two-core
cables
cables
or
cables
three-
three-
cables
or
or
four-
two-core
single-core
0.56
cables,
cables,
core or 41
cables,
cables, four-
cables,
8or
cables, four-
or
4or
single-
single-core 12 9or
6or
212
4
two-
two- cables Installation Installatior:l
Method Installation
18Method
6 single-Method
20core 19
18 6 single-core
single- core' 12 single-core
cross-
{
0)
~
~
'0
o
~J
t when cables having different conductor operating temperatures are grouped together, the current rating shall be based on the lowest operating temperature of any cable in the group.
(Y:)
-J
00
00
Table A.4 Correction factors for ambient temperature where protection is against short-circuit
. Note This table applies where the associated overcurrent protective device is intended to provide short-circuit protection only. Except where the device is a semi-enclosed fuse, the table also applies where the
device is intended to provide overload protection.
---
------- -
0.41
0.29
0.96
0.50
0.54
0.3
0.47
Type90 0.76
0.65
0.40
0.60
0.30
80
95
85 0.75
0.80
0.92
0.43
0.74
0.60
0.58
0.90
0.52
35
60
55
0.95
0.94
0.32
0.93
0.79
0.87
0.35
0.55
0.77
0.67
'0.50
0.35
0.97
0.91
0.94
0.71
0.70
0.88
0.91
7540
65
50
701.0insulation
0.89
0.85
0.41
0.82
4530
0.61
0.63
0.31
0.45
0.57
0.50
0.84
of 1.02
1.02
1.04
1.03 "8Soe
gOOesheath
sooe
800e
700e
700e
Operating Ambient temperature °c
1.03
25
NOTE: (i) Correction factors for flexible cords and for 85°C or 150°C rubber insulated flexible cables are give in the relevant table of current-carrying capacity.
(ii) This table also applies whep determining the current-carrying capacity of a cable.
(t) These factors are applicable ~~ly to rating in Columns 2 through 5 of Tables B.l and B.2.
Table A.5 Correction factors for ambient temperature where the overload protective device is a semi-enclosed fuse
- - -- 1.03
0.86
0.83
0.97
0.84
0.49
0.39
0.48
0.68
0.89
0.42
0.86
0.96
0.88
0.41
0.58
0.71
30
60
55
45
40
80
75
90
35
65
85
95
0.98
0.72
0.62
0.91
0.93
0.95
0.87
0.56
0.69
0.79
0.94
0.80
0.90
0.92
0.89
0.85
0.76
0.96
0.77
0.82
0.55
0.64
0.43
70
50
1.02
-1.021.03
1.01.04 25
1.02
.
85 85
0.90
80
70
60 - -
Ambient temperature FC]
70, sheath
105, sheath
temperature
./
• These factors are applicable only to ratings in columns 2 to 5 of Tables B.I ~d B.2.
Note: Correction factors for flexible cords and for 85°C or 150°Crubber-insulated flexible cables are given in the relevant table of current-carrying capacity.
ANNEX B (NORMATIVE)
TYPE OF CABLE AND AMP ACITY
Table B.1 Single-core P.V.C. insulated cables, non-armoured, with or without sheath
(copper conductor)
'l',V
-{
I,
p.•..O<,>.eoc•.••••• by - ooen"Ii-enclo~ E'•.•se. see A.6.2 o£ the preCace 'to this Ar1nex.
Table B.2 Voltage drop (per ampere per meter)
Conductor operating temperature : 70°C
10xz0.20
z)(z rr44
x1.75
0.29
0.195
0.28
0.190
0.180
0.27
0.185
0.28
0.175
0.26 r0.29
29
180.068
20.39
1.80
1.30
0.54
0.69
0.970.059
0.060
Reference
and
r1.30
7.3
11
4.4r1.75
0.63
1.75
1.25
0.46
0.93
1.50
0.49
0.95
0.65
1.80
0.41
1.10
0.55
0.80
0.50
1.50
1.25
0.43
0.57
0.95
0.66
1.10
0.053
0.068
0.180
0.086
0.105
0.145
0.23
0.36
0.45
0.35
0.31
0.39
0.25
0.32
0.11040.33
11
2.8
2.8
29
44
18
7.3
4.4
0.28
0.30
0.29
0.24
1.25
0.81
0.56
0.93
0.47
0.63
0.1300.26
0.160
0.21
0.1950.26
0.086
0.094
0.105
0.130
0.072
0.34
0.30
0.36
0.26
0.160
0.175
0.190
0.150
0.042
0.060
0.052
0.145
0.1400.25
0.31
0.27
0.23
0.220.150
0.0520.130
0.130
0.26
0.25
0.27
0.33
0.22
0.29
0.37
0.21
0.20 -Methods
(Enclosed
59mV
9.5
1.30
0.56
0.72
1.80
1.55
1.002.8
29
18
4.4
1.10
0.93
0.47
0.80
0.84
0.63
1.75
0.41
0.60
1.25
1.50
0.26
0.086
0.081
0.105 0.160
0.165
and
0.1300.140
0.0720.135
0.41
0.47
0.37
0.120
0.150
0.185
0.160
0.40
0.30
0.37
0.24
0.31
0.32
0.21 44
11
9.5
0.55
0.061
0.050
0.::!8
0.27
0.29
0.31
0.33
0.23
0.24
0.25
0.22
0.212.8-
2.4
7.3
25
3.8
0.066
0.26
0.115
0.150
0.185
0.08
0.053 in
84Reference 3etc.
11
0.170
0.165
0.155
0.175
0.85
0.61
0.100.22
0.12
0.14
0.076
0.093
0.140
0.135
0.145
0.155
0.36
0.41
0.32 (Flat
r0.25-in andon 1 touching) Reference Methods 1
0.170
2mV ~conduit
0.82
0.160
0.26
0.29
0.22 1.50
0.42
1.10
0.24
mV 0.55
0.29
0.34
0.27
0.26
0.160
0.098 7
38
15
6.4
1.10
0.80
1.50
0.081
0.32
0.100
mV
conduit
0.40
11
touching)
and
Reference
and 40.31
0.160
1.55
1.10
0.48
0.1300.29
0.21
0.17
0.044 110.160
0.165
0.22
0.23
0.28
0.32
0.32
0.150
0.20
0.30
0.29 0.24
in (Encl~
direct
(spacedt)
and 0.63
0.40
1.15
0.86
1.55
0.34
0.44
0.36
0.30
0.31
0.320.25
0.24
0.24
0.25
0.175
0.27
0.20
0.22
0.25
0.27
0.29
0.31
0.290.26
0.29
0.28
0.185
0.51
Method
12
(clipped
Methods
on or
Methods
trays,
(in or121,a
in 2Reference
cables Method 12 3 ac.
wall ')- single-phase
Reference Methods 3 4 cables
or cross- cables etc.
(flat or
spaced ont)atrefoiQ or - thr~phase ac.
~ t •
~ Spacing larger than those specified in Method 12 (see Annex A, section 8) will result in larger voltage drop.
Table B.3 Multicore P.V.C. insulated cables, non-armoured
(copper conductors)
32
25
11 470
11099
139
167
16.5
43
219
246
57
9263
7566
192
291
21413
334 3634
8A
-19.5
95
4150
16.5
14.5
16.5
133
111
136
112
119
213
201
256
232
125
39
69
90
1
30
29
223
2
13
10
166
46
60
70
52
62
94
144
23
36
34
20
25
43
344
294
461
297
430
464
497
236
262
57
76
101
206
276
326
259
116
153
160
40
24
51
196
225
319
379
255
364
434
341
403
7
11.5
13.5
63
65
or
-cablet
cablet
cable
or
597
715
557
164
179
514
593
99
23
299
27
392
339
39415
22
196
17
72
61
96
7.5
149
223
146
119
32
41
17.5
cablet
A 402
96
530
t or
d.c.
d.c.
11a.c.
three
or or
1I four-
three-core
three-core
1three-
four-
or Icore
d.c.conduit
four- Reference
on
1core acable,
three-core Method
ceiling,3or(enclosed
wall orthree- in in
A
core
1Reference
two-core
single-phase 12.6
G cable,
cable
Method
a.c. t core cable,
cable
phase
Reference
4t.t (enclosed three-
intray),
a.c. or Reference
anMethod 1 (clippedMethod
direct)13 Reference
trunking) (free air)Method 11 (on a perforated
11phase
phase single-phase
two-core
two-core a.c..
a.c. cable
cable 1 two-core cable t,
single-phase
single-phase a.c. a.c.
SECTION 4: CONDUCTORS
Conductor
0.135
0.100
0.185
0.21
0.185
.J...0.21
0.165
0.55
0.26
0.33
1.50
0.80
1.10
0.41 z.135
x0.34
0.145
0.160
0.24
0.29
0.150
0.130
0.25
0.41
0.65
0.94
1.75
1.25
0.50
0.125
0.145
0.150
0.170
0.140
Q0.21
0.29
1.500.155
0.115
0.130
0.25
00.165
0.155
0.35
0.81
1.10
.1450.190
.130
.135
.140
0.63
1.75
0.93
0.43
0.30
1.25
0.47
0.57
-~ 0.38 '0.105
0.145
0.180
0.23
7.3
11
2.8
4.4
29
18
0.63
1.75
44
0.29
0.46
1.25
0.36
0.93,
mV
Two-core11
7.3
18
4.4three-phase
44
29
2.8
mV
phase 9.5
2.4
3.8
6.4
25
15
38
Three-or
mV
cable four-core
a.c. single-a.c. cable
Two-core
cable d.c.
mm2
flat
a.c. 3
105678
21685
4349
9332
11
12
Vertical
a.c.a.c. or spaced
d.c.
cables
trefoil
flat
or
or
and44flat
and Reference Method 12 (free air)
2 296
7720
1041
1441
447
1008
1218
919
843
763
687
525
594
624
976
710
943
891
669
893
805
622
245
193313
269
723
575
469
399
490
465
492
648
1627
816
975
777
1390
728
1174
809
676
721
673
205
179
259
225
342
1035
737
8fO
360
309
401
668
567
501
945
856
731
229
A
,263 285
338
340
357
327
385
396
415
383
578
616
719
748
640
618
632
674
851
885
525
548
422
456
515
550
593
528
566
547
808
967
872
771
997
212
230
216
217
286
279
294
287
238
2Horizontal
Horizontal
cables,
280
324
657
707
489
511
425
568
905
824
231
886
229
272
189
181
33
Vertical cables
cables,
cables,
Vertical,
three~phase
three-phase
flatshingle-
phase
spaced
touching
touching
spaced
A Reference flat Reference
a.c. 2Method
cables
or 4 cables,
perforated cable 11 on a
d.c.
three-phase
tray a.c.
single-phase
Horizontal 2Method
3cables 1single-phase a.c.
cross-
Note: Where the conductor is to be protected by a semi-enclosed fuse, see A.6.2 of the Preface to this Annex.
Table B.6 Voltage drop (per ampere per metre)
Conductor operating temperature: 70°C
z0.95
zrx
x0.24
0.86
0.97
0.190
0.26
0.72
0.25
0.68
0.32
0.58
0.175
0..28
0.170
0.24
0.50
0.27
0.45
0.30
0.23
0.160
0.41
0.29
0.34
0.68
0.30
0.29
0.52
0.28
0.180
0.57
0.165
0.37
0.28
0.31 x0.92
x0.190
0.43
0.190
0.38
0.30
0.180r0.079
0.500.33
0.35
0.43
0.37
0.27
0.21
0.84
0.22
0.21
0.20
0.195
0.440.27
0.390.22
0.32
0.22
0.62
0.50
0.34
0.180
0.165 r0.20
0.450.44
0.180
0.320.30
0.270.25
0.170
0.580.57
0.42
0.34
0.23
0.66
0.51
0.370.36
0.175
0.165
0.160
0.155
0.820.79
0.29 r0.135
0.120
0.091
0.175
0.80
0.42
0.165
0.105
0.082
0.140
0.560.125
0.145
0.175
0.30
0.47
0.24
0.29
0.39
0.31
0.095
0.93
0.64
0.48
0.160
0.32
0.140
0.30
0.120
0.27
0.20
0.21
0.1600.21
0.195
0.170
0.24
0.155
0.28
0.26
0.23
0.170
0.165
0.20
0.280.140
0.190
0.79
0.59
0.40
0.34
0.260.135
0.130
0.105
0.091
0.026
0.25
0.29
0.23
0.220.160
0.180
0.160
0.23
0.240.22
0.195
0.185
0.180
0.21
0.150
0.145 3mV
20.22
0.63
0.46
0.086
0.068
0.053
0.145
0.180
0.105
0.36
0.29
0.23
0.20
0.042
0.145
0.140
0.155
0.21
0.93
0.195
0.165 4mV
0.190
0.195
0.170
0.24
11
mV mV
0.22
0.21etouching)
512
andm7V
mV
0.26
0.24
and12 (in
Reference
Reference
(spacedt)
and 11 Reference
trefoil
Methods
Method
11 (Touching)
(Flat and 12 Methods 1 Reference
cables - single-phase
3 or a.c. Methods
4 cables 1, Method
- Reference
three-phac;e a.c. 12
2 cables d.c.
(Flat spacedt)
t, Spacings larger than those specified in Method 12 (see Annex A. Section 8) will result in larger voltage drop.
\0
VI
ELECTRICAL INSTALLATION OF BUILDINGS
Note:
Where the conductor is to be protected by a semi-enclosed fuse, see A. 6.2 of the Preface to this
Annex.
Conductor
r 0.34
0.41
1.75
1.25
0.145
0.140
0.135
0.94
0.50
0.65
0.29
0.24
0.21
0.130
0.41
0.21z0.185
x0.26
Q.1300.29
0.80
1.50
1.10
0.125
0.33
0.165
0.130
0.55 x.21
0.160
00.155
0.150
0.35z1.75
0.170
0.165
0.81
1.10
0.155
0.155
0.57
0.25
1.50
0.160
0.1501.25
0.38
0.100
0.30
0.145
0.43 7.3
0.63
0.145
1.75
11
4.4
0.36
0.63
0.93
0.47
0.25229
0.155
0.11518
0.190
0.93
0.46
0.105
0.180
1.25
2.8
0.29
0.23
phase mV a.c. 2.8
0.185 4.4
7.3
29
18
11
3 9.5
mV
Two-core 2.4
3.8
6.4
25
4 threethree-phase
15
mV
cable or four-corea.c.
single- cable,
d.c.
Two-core cable
1
.--10
1288
1443
900
683
783 -phase
--andTrefoil
cables
-ac. flat
three-
and
2459
a.c.
149
189
10091
228
124
341
263
300
400
14
33
32423
1817
58
76
43 or
or1n5
3439
859
1130
1065
1044
1228
17.5 95
12
11
1358
1581
1214
1520
126
228
240
290
336
13
22
109
53
95 990
820-trunking
or
61671
ac.
1191
1423
1069
1485
1323
30
111
375
445
426
189
135
209
170
293
308
351
270
205
355
330
235
143
183
138
156
176
195
436
17
19
25
40
71
81
70
1349
51
3
phase 584
666
904
1150
764
1033
1338
1179
1275
1436
1115
849
936
994
495
385
34
306
573
410
701
606
500
358
511
168
246
274
214
318
259
389
15
46
63
74
7
45793
868
111
163
171
203
299
379
453
26
31
476
328
824
886
794
681
743
493
711
769
630
590
524
570
370
600
651
530
579
279
341
130
140
398
644
461
23
19
85
35
54
915
973
158
226
413
505
545
215
268
730
686
326
161
41
99
3three-phase
cables, touching
three-phase
342d.c.
4cables
trefoil cables
ac.
ac.
Verticalor ac.
three-
cables
cables,
three-phase
three-
three-
single3 cables,
single
spaced ac.d.c. orflat
phase
phase
phase ..or Reference
Horizontal
cables
cables flat orflat
in direct)
3 orReference
trefoil
cables
2conduit 4 a wall1 Method
Method
onMethod or in . 12 (fee air)Reference Method 11 (on a
(clipped
orReference
trunking etc.) (enclosed
and 2ac.
Reference 2
single-phase
.rt33
Insulating
touching
ac. orMethod
or wall
d.c.
d.c. flat
flatetc.)
4 (enclosed 3 3 or 4 cables spaced,
in
and conduit
single-phase
single-phase touching in thermally vertical
perforated cable tray horizontal
I area
Note: Where the conductor is to 'be protected by a semi-enclosed fuse, see A.6.2 of the Preface to this Annex.
The current-carrying capacity in Columm 2 to 5 are also applicable to flexible cables where the cables are used in fixed installations. For cable in rigid p.v.c. conduit, the values stated
~~>~':..~e.::...~}
..~?.?_~!_~~:.~~~~::,~:';.:.~~~re a conductor operates at a temperature exceeding 7cPC. it shall be ascertained that the equipment connected to the conductor is suitable
Table B.10 Voltage drop (per ampere per meter)
Conductor operating temperature: 90°C
z0.062
0.9550.072 0.150
0.1300.145
0.0630.150
0.1300.140 Reference
Methods
touching)
direct 0.170
0.165
or 3 and
on trays, Reference
4single-phase
r rrxr0.31
rMethods
z0.28
z1.15
0.29
0.180
0.25
0.155
0.26
0.75
0.28
0.58
0.27
0.24
0.150
0.48
0.43
0.23
0.140
0.37
0.33
1.05
1.35
0.180
0.175
0.170
0.165
0.145z0.22
0.37
x1.65
x0.34
0.165
0.190
0.27
0.26
0.27·
0.73
0.56·
0.41
0.33
0.36
0.99
0.89
0.65
0.25
0.49
0.42
0.24
1.20
1.35
0.68
0.26
0.39
0.49
0.195
0.25
0.0860.155
0.1050.155
0.10
0.155
1.60
0.87
0.61
0.37
0.45
0.25
0.26
0.24
0.1300.155
0.20
0.59
0.43
0.28
0.24
0.240.045
1.90
1.85
0.23
0.47
1.00
0/2.7 231
0.87
0.125
0.088
0.60
0.35
0.44
0.29
0.185
1.35
0.70
0.51
0.41
0.33
0.27
0.175
0.140
0.100
0.120
1.00
0.99
0.68
0.49
0.056
0.072
0.093
0
0.21
0.155
0.120
112
1.85
0.23
7.9
460.39
0.32
0.25
.190
.35
0.90
0.65
0.42
0.32
1.15
1.85
4.7
2.9
19 37.9
0.180
0.175
0.170
0.165
0.31
0.29
0.28
0.160
0.27
1.60
1.15
0.87
0.62
0.46
0.28
0.38
0.32
0.43
0.28
0.20
1.35
0.71
0.43
0.52
0.25
0.36
0.30
0.22
1.00
0.34
0.28
0.22
0.43
1.60
1.15
0.190
x4(Enclosed
0.32
0.31
0.1~5
1.15
0.86
1.850.150
0.100
1.15
0.23
1.60 0.50
0.37
conduit
mV 0.86
0.59
1.15
0.86
0.59
0.34
0.22
1.65 -and
0.21
1.85
0.24
19
31
12
46
3
mV0.22
0.25
4.7
2.9
etc.-0.140
89610
512
446
0.090
0.175
0.185
0.170
0.135
0.110
0.085
31
7.9
4.7
2.9
19
31
0.110
0.074
0.170
inmV7
4.0
16
40
27 0.170
0.078
0.23
0.29
0.25
0.071
0.068
0.110
0.064
0.055
0.059
0.054
0.047
0.050
4.0
0.098
0.088
0.27
0.24
0.135
6.8
4.7
2.5
Reference 0.1400.195
Methods0.135
20.1600.195
0.165
0.155 t0.160
0.1350.175
0.1350.150
0.140
Reference0.160
0.160
or(Spacedcables,
1
12 )0.170
0.24
0.165
0.22
0.180
Method
and 0.21
11
(Flat a.c.
0.24 Cabled.c. oninconduit
s 1.60 and
12
spacedt)
(Flat
1aand 12
wall)
Reference 1,
(In
touching)
11etc.
11,
trefoil)
Method
(Clipped
in or on a wall)
3 or(Enclosed
4 cables- in
three-phase .a.c.
\0
\0 t Spacing larger than those specified in Method 12 (see Annex A, Section B) will result in larger voltage drop'
-oo
Table B.11 . Multicore, non-armouroo cable having thermosetting insulation
(copper conductors)
~ 11456 -three-or
three-phase
1076251phase
phase three-
-33 orfour-
a.c.
a.c. four-
or conduitor onReference
acable Method
wallthree-
or ceiling 3
, or(enclosed
in three-in
d.c.
4146
119
1265
221
1759A
9180
384
459
305
334
532
A
phase 8276·
246
298
158
127
100
346
399
538
621
192
220
.253
115
183
145
121
225
290
741
289
352
185
149
741A
A563803
410
473
329
542
641
99
386
442
269
209
171
138
295
164
2
130
109
89
68
865 two-core
7
382
268
259
424
506
346
599
396
455
229
197
278
147
119
322
371
500
576
179
667
536
two-core
328
441
1
1281
A
cable227
96
340
693
A00
54
05
98
94 a.c. orcable
single- 1d.c.
core
1 two-core
d.c.
core cable
two-core
perforated
Reference three-
cable
an tray)
or inMethod core orcable trunking)
Reference
1 (clipped Method Reference
direct) 13 (free air)Method 11 (on a
Reference
phase four-core
phase
cablea.c.
cable a.c.cable 4 1(enclosed
Method
single-
single- three-
Note: (i) Where the conductor is to be protected by a semi-enclosed fuse, see A.6.2 of the Preface to the Annex.
(ii) Where a conductor operates at a temperature exceeding 70°C, it shall be ascertained that the equipment connected to the conductor is suitable for the conductor
operating temperature.
SECTION 4: CONDUCTORS
r0.150
Conductor
0.145
0.145
0.140
0.175
0.130
0.125
0.86
0.43
0.59
0.115
0.34
0.28
0.22
0.195
0.125
0.155
0.160 z1.90
x0.52
z0.21
0.24
0.42
0.120
0.35
0.29
0.69
1.00
0.135
0:140
1.15
1.600.170
0.185
0.21
0.45
0.37
0.30
0.60
0.87
1.350.50
0.67
0.99
0.40
0.32
0.26
0.26
1.650.130
0.160
0.2000.98
1.85
1.35
1.15 3 2.5
0.120
0.155
0.49
0.67
0.195
0.39
0.31
0.25
1.35
1.85
2.9
2mVmV
phase 4mV
2.9
Three-or
three-phase
Two-corea.c. four-core
a.c.
cable single- cable
Two-core cable
d.c.
1
tv
Table B.13 Single-core cables having thermosetting insulation, non-magnetic armour
(copper conductors)
Current-carrying .capacity (Amperes): Ambient temperature: 30"c
Conductor operating temperature: 90"C
or&3single- d.c.
cablesflata.c.
trefoil
2
10
303
2374phase
3A220
Horizontal
Vertical
277
1082
1170
21139
1137
1016
1032
1314
1146
1246
1204
557
1345
488
425
962
496
791
717
853
662
755
579357
293
322
358
1261
437
383
333
899
792
1055
2100
477
889
929
352
389
425
Horizontal
656
,367
phase
flat
flat
or
phase A
284
266
282
232
253
288
349
331
1266
1474
1528
1092
943
805
842
1744
1809
1155
815
714
749
612
689
587
688
614
643
1238
2026
462
516
600
539
449
497
446
412
436 touching
567spaced
11
93270
A
1094
797
871
940
767
904
700
755
810
906
1042
666
715
782
1041
524
574
618
660
1289
566
510
549
575
504
405
519
485
426
393
3:J7
356 861
961
1110
989
935
851
987
848
923
992
978
and 112
Reference
Horizontal
flat
three-
A
285
222
1214
815
918
720
625
529
463
402
346
027
Vertical
cables,
1119
cables
or 4&&
a.c.
spaced
spaced
d.c.a.c. flat
flata.c. Methodor or
3cables
single-phase
a perforated
Reference
3 414 cable
Method
cables,tray)
three-phase
11(on a.c. 2 cables d.c.
onductor single-
phase flat
three-
touching a.c. Reference Method 12 (free air)
Note: (i) Where the conductor is to be protected by a seini-enclosed fuse, see A.6.2 of the Preface to this Annex.
(ii) Where a conductor operates at a temperature exceeding 7Cf'C, it shall be ascertained tbat the equipment connected to the conductor is suitable for the conductor operating
t.empera'turc.
Table B.14 Voltage drop (per ampere per metre)
t Spacings larger than those specified in Method 12 (see Annex A, Section 8) will result in larger voltage drop.
ELECTRICAL INSTALLATION OF BUILDINGS
1 .5
520
, 11 three-or
23
three-or
phase
34289
31
66544
732
599
636
546
39
52
78
472
463
628
673
847
728
115
90
A 29
73
42
53
25
228
124
154
238
335
386
441
A3323456727
5685
304
251
338
406
49
62
152
188
354
291
410
131
162
99
94110
187
353
197
219
279
146
180
539
three-phase
cable,
87
92
607
51
15
98
36
four-
fouror
a.c.
A1 two-core
a.c.
single-
a.c.
perforated horizontal or vertical
d.c.
1 two-core
core cable, Reference (free air) 11 (on
Method
single-
cable, cable tray} or Reference Method 13
Method 1 (clipped direct)
Note: (i) Where the conductor is to be protected by a semi-enclosed fuse, see A.6.2 of the Preface to this
Annex.
(ii) Where a conductor operates at a temperature exceeding 7fJ'C, it shall be ascertained that the
equipment connected to the conductor is suitable for the conductor operating temperature.
, 1.60
Conductor 0.120
0.1250.115
z0.185
x0.140 01z1.65
x 0.160
0.59
0.28
0.140
0.175
r0.86
0.43
1.15
0.22
0.34
0.170
0.145
0.21
0.24
0.140
1.135
0.155
1.35
0.135
0.130
0.125
0.69
0.52
0.150
0.29
0.42
1.00
0.195
1.351.90
0.35 0.16'
1.85
0.99
Two-core
0.13
0.20
.21
.15
.262.9
1.35
0.67
0.50
0.32
0.26
0.40
0.195
1.85
7.9
12
4.7
231
19
.300.25
.370.31
.87
.600.120
0.155
.450.39
0.67
0.49
0.98
mV 331
d.c.Cable
2.9
12
7.9
4.7 4three-phase
19 a.c.
mV
phase
Two-core 10
27
16
2.5
6.8
4.0
mVThree-or four-core
a.c.
cable single- cable
cross-
1
Note:(i) Where the conduc~or is to be protected by a semi-enclosed fuse, see A.6.2 oft the Preface to Annex ..
(ii) Where a conductor operates at a temperature exceeding 70"C ,it shall be ascertained that the equipment cottnected to the conductor is suitable for the conductor operating temperature.
Table B.18 Voltage drop (per ampere per metre)
Conductor operating temperature: 85°C
zxz
xz0.24
xz x1.200.95
z0.27
x0.25
0.24
0.22
0.29
0.26
0.25
0.23
0.28
0.29
0.31
0.26
0.48
0.91
1.20r0.87
z0.37
0.280.24
0.25
0.175
0.170
0.155
0.24
0.51
0.37
0.43
0.33 r1.30
r0.58
r0.100
0.073
0.085
0.067
0.073
0.300.072
0.110
0.105
0.29
0.32
0.65
0.27
0.41
0.30
0.88
0.23
0.28
1.15
1.650.135
0.150
0.170
0.135
0.650.48
0.72
0.56
0.40
0.47
0.45
0.52
0.900.65
0.36
0.370.190
1.35
1.00
1.85
1.651.30
0.60
0.44
0.29
0.35
0.23
0.089
0.105
0.130
0.320.085cables
0.22
0.155
0.091
1.15
1.600.140
0.24
0.150
46
0.115
0.180
0.66 0.26
0.170
0.21
0.57
0.84
0.22
1.15
1.60
0.27
1.85
0.57
0.43
1.15
0.84
1.60
0.22
1.60
0.68
0.40
1.35
0.51
0.27
1.80
0.30
0.38
0.25
7.7
4.6
120.35
1.85
1.60
0.62
231
18
2.9
0.115
0.33
0.34
0.42
0.34
1.15
1.85
1.00
mV 0.29
0.23
0.26
0.28
0.29
Reference
3(Enclosed
.
20.28
0.310.21
0.140
0.28
0.26
0.270.29
0.34
0.32
0.31
0.690.23
0.30
46
0.360.31
0.430.39
0.300.25
1.35
1.15
1.600.170
0.175
0.155
0.150
0.165
0.160
0.49
0.25
0.31
0.29
31
3
18
12
4.6
7.7
2.9
.0.25
0.135
0.22
mV0.26
0.145
0.195
d.c.0.32
0.27
0.30
Reference
director
26
16
4.0
2.5
(Flat
40
6.7
10
0.077
0.125
0.175
0.120
0.30 and
spaced
--trefoil
-0.089
0.110
. Reference
0.155
0.195
0.155
0.195
0.31
46
0.25
0.970.135
0.180
0.74
0.39
0.49
1.30
1.40
1.85
0.38
0.49
0.97
0.45
0.86
0.26
0.60
0.27
0.22
0.57
0.84
40
31
7
5
4
18
26
12
4.6
7.7
10
6.7
2.9
0.082
0.27
0.100
0.165
0.28
0.097
0.22
0.170
0.66
0.31
0.42
1.90
1.05
0.43
40
Reference
9
6
8
26
16
4.0
2.5
mV
Reference
mV
Method
inReference
etc. conduit
in
11
0.160
Methods
On
0.25
0.165
0.22
0.190
0.195
0.20
0.52
0.23
0.22
0.24
0.155
1,11,
and 0.21
0.24
0.26
0.22
0.185
Spaced
Meth~
touching)
11
)trays,
(clipped
and 0.20
0.23
1
12 1 2 cables
0.99
)0.175
(Flat
or on aM~hod
3(Enclosed wall)
0.185
Methods
Methods
12(in
touching)
12
in conduit
- single-phase ac.
Reference Method 3 or 4 cables - three-phase ac.
s·
t
Spacings larger than those specified in Method 12 (see Annex A of Section 8) will result in larger voltage drop.
o00
•....
Table B.19 Multicore, sheathed and non-armoured cables having 85°C rubber insulation
(copper conductors)
470499
553
359
636
1
2439
211185
254222
292
509
167147
114100
139122
6.5
48
38 103
1 n
In
34482
5A213
109
19.5
J II 333 1 two-core
phase
cable.
1 6A
256
555
2118.5
2925
1AA
320
368
66
87 329
269
310
272
675
587
436
201
409
381
312
14.5
32
16
58 174
136
144
168
88
20
34
23
413
287
438
326
37
43
33
55
81
76
59
222
117
4825
28
46
6618 7
287
237
593
515
437
151
17.5
three-
cable.
;359
two-core
two-core Reference
123
94
383
40
52
71
186
A
22
30
11phase
three-
three-
ac. or
phaseor Method
or four-core
orcable.
ac.
three-phase
cablephase
cable four-core
four-core
d.c.
ac.
or
single-ac. 3 Reference
ac. cable.
d.c.
single- (enclosed)
three..
ReferenceMethod
Method111 (on
(clipped direct) cable tray). or
a perforated Refrence Metthod 13 (free air)
II
Note: (i) Where the conductor is to be protected by a semi-enclosed fuse. se{,A.6.2 of the Preface to this Annex.
(ii) Where a conductor operates at a temperature exceeding 70DC, it shall be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature.
SECTION 4: CONDUCTORS
,
Conductor 0.25
0.99
0.68
1.35
19
r0.155
z0.170
z0
x0.26
0.165
0.150
1.15
0.84
0.86
0.59
1.85
0.175
0.22
0.42
0.52
0.160
0.35 .58
1.60
0.185
0.45
.34
.43
0.135
.27
0.145
0.140
0.150
0.160
0.130
0.30 Two-core
x 0.66
0.97
0.130
0.22
0.36
.170
0.130
0.30
.22 0.65
0.95
46
0.49
1.30
1.850.38
0.31
0.25231
12
0.30
7.7
2.9
4.6
1.30
1.80
0.195
0.155
0.39
0.190
0.150
0.48
0.25
mV cable
2.9 single-phase
3mV
19
12
7.7
46
31
4.6
cable d.c.
Two-core
16
2.5
4
40
26
10
6.7
4.0
mV a.c.
Three- or four-core,
phase a.c.
cable three-
..
ELECTRICAL INSTALLATION OF BUILDINGS
Table B.2l 60°C rubber-insulated flexible cables, other than flexible cords
Notes: (i) The tabulated current ratings are for cables in free air, but may also be used for cables resting on a surface.
If the cable is to wound on a drum on load, the ratings should be reduced in accordance with (iii) below and,
for cables which may be covered, (iv) below.
(ii) Where the conductor is to be protected by a semi-enclosed fuse, see A.6.2 of the preface to this Annex.
(iii) The current ratings of cables used on reeling drums are to be reduced by the following factors:
A ventilated cylindrical cable drum is one where layers of cable are accommodated between widely spaced flanges
and the drum and end flanges have suitable ventilating apertures.
(iv) Where cable may be covered over or coiled up whilst on load, or the air movement over the cable restricted,
the current rating should be reduced.
It is not possible to specify the amount of reduction; but the table of rating factors for reeling drums can be used
as a guide.
Conductor
-zzxTwo-core
r zx-1.80 - 0.068
0.090
0.115
-0.49
x0.130 - --
0.170
-- 0.135
0.83
0.57
0.42
1.10
0.33
0.27
0.22
-0.079 - -- d.c.
1.55 1.85
0.175
0.1801.80
4.6
2.9
0.93
1.32
0.36
0.30
0.200.27
0.19512
0.67
0.53
7.80.91
0.140
0.64
0.150
0.1851.55'
0.21
0.130
0.170
0.21 0.190
0.185
0.1900.135
0.145
0.125
0.24
0.43
0.36
0.84
1.15
0.26
0.32
0.20
0.175 0.38
0.150
0.49
0.58
0.44
0.21
mV0.195
1.31
0.31
0.38
0.31
1.31
0.91
0.155
0.25
0.099
0.64
0.120
cable
0.25
Two-core 4.6
2.9
12
7.8
mV
d.c. a.c.mV
cable
cable mV 10r
4.0
2.5
mV
6.7
three-phase
1 three-core,
single-phase a.~
four-core or five-core
Single-phase a.c. t 2 single-core cables touching
t
Larger voltage drop will result if the cables are spaced.
ELECTRICAL INSTALLATION OF BUILDINGS
. (1 53
or 41 cors,
cors
47
two-cors
99
73 64
86
36
without 192
414
645
297
354
Singlecable}
four-cors
cable,
touching
sing/I-cors
protlctivs
phasla.c.or(1five-
with
a.c.
cables
or dc. 216
thrsl- 262
397
348
467
537 885
0.105
0.130
0.084 - 0.190 - z0.185
z x-zx-0.180 -
0.29
0.61
0.145
0.46
0.36
0.24
1.20
0.90
Conductor
r 0.21
r0.27
0.33
0.70
0.99
0.41
0.53
1.42 x0.20
0.130
0.140
0.170
0.135
0.175
0.150
0.38
0.130
0.28
0.72
0.125
0.25
0.46
0.33
0.56
0.145
1.01
1.700.150
1.43
0.22 0.190
0.195
2.00
0.185
0.20
0.21 2.00
0.175
0.32
0.22
0.63
00.170
.195
0.48
0.39
0.27
0.91
1.70
1.20 0.165
0.53
0.27
0.073
core 3 --three-phase
2mV cable
8.4
0.125
13
0.33
0.41
0.21
0.70
0.99
0.098
1.42
2.0
5.0
3.1 13
5.0
3.1
8.4
mV 52-three-core,
4mV
7.3
4.3
2.7
Two-core - single-core
a.c.
11
1mV cable a.c.cables touching
single-phase
four-core
1 two-corecables d.c.
or single-core Single-phase a.c.tor flve-
1
Note:(i) The voltage drop figures given above are based on a conductor operating temperature of 85°C and are, therefore, not accurate when the operating temperature is
in excess of 85°C. In the case of the 15<J'C cables with a conductor temperature of 15<J'C, the above resistive values should be increased by a factor of 1.2 (This factor is only
applicable to the range of 1500C rubber-insulated cables up to 16mm2 nominal cross-sectional area).
t (ii) Larger voltage drop will result if the cables are spaced .•
ELECTRICAL INSTALLATION OF BUILDINGS
5342520
twin -225
3A6Three-phase
25
16
10 32
10 16
313 Current-carrying
6flexible cord Maximum capacity
mass
Conductor cross- kg A a.c.
Single-phase a.c.
supportable by
85°C rubber cords having a h.oJ.r. sheath or a heat-resisting p.Y.c. sheath and for 85°C heat-resisting p.Y.c.
cords:
Ambient Temperature (0C): 35 to 50 55 60 65 70
Correction factor: 1.00 0.96 0.83 0.67 0.47
130
145
140
135
0.40
0.57
0.71
0.82
0.92
ISOOC 160
175
170
165
0.42
0.60
0.74
0.85
0.96
rubber cords: 1.00 155
125
Ambient Temperature (°C):35 to 120
150
Conductor cross- - .
d.c.2318
2:7
10
32
12
19
54
40
80
46
37
93
62'
mV
m Three-phase a.c.
orV single-phase
1
The tabulated yalues are for 60"C rubber-insulated and p.y.c.-insulated flexible cords. For other types of ..
flexible cords, they are to be multiplied by the following factors:
Note: i) For single-core cables, the sheaths of the circuit are assumed to be connected together at both ends.
ii) For bare cable exposed to touch, the tabulated values should be multiplied by 0.9.
..•
..• Table Dol7 Mineral insulated cables bare and exposed to touch (see note 2) or having overall covering of P.V.C•
10
(copper conductors and sheath) (conte'd)
I
.•
- Horizont
A20
213
259
353
309
400
446
497
110
142
173
26
34
45
37
49
62
84
40 496
30
32
5622
1
377
241
132
26
25
41
34
45
426
331
31
242
23
29
39
51
43
57
71
77
95
289
351
507
565
102
125
161
197
402
198
18
294
162A
29
32
45,4-
20
A A
- -cables
all-9---cores
loaded
1all
loaded
core
19
A
11
28
27
28
26
15.5
10
11
17
21
12
1416
59
44
101
core18
14
24
35
25
20
27
78
13
Vertical
Touchin
phase
loaded
cable
-- 1or
1 cores
seven-
load
1 loaded
16
89
28
24
30
23
21
25
33
19.5
44
21
174
264
47
60
3
cores
twelve-
four-core
cable
cable
cable
16.5
37
22
30
223
466
40
92
9nineteen-
A A A
A399
18
68
51
116
472
26
36
317
215
109
82
416
552
142 308
2
23
17.5
21
147
267
69
352
51
182
120
a.c.
cables
three-
cores
four-core
1 two-
al
8 all
phase
1cable,
three
orind.c. a.c.or
core
trefoil phasea.c.
3 phase a.c.
single-core
3 single-core cables three-
spaced
.
1.0
1 spaced three-
I
Note_" ~~ble~~~"",s?..=:,-~s
i) For ~in_gle-c?~e_ .~"O~ ~ •• ~~~"'~~~~~dt~~..-..a~::~:::~~~~g~t:Per
~_~~c::';~~ at both ends.
SECTION 4: CONDUCTORS
TableB.28 Mineral insulated cables bare and exposed to touch or having an overall covering
of p.v.c
(copper conductors and sheath)
Voltagedrop (per ampere per meter) for single-phase operation sheath operating temperature: 70°C
-z--x-z
r 0.200
x0.145
0.160
0.25
0.185
0.165
0.175
0.49
0.91
0.29
0.180
0.64
0.170
0.41
0.34
0.195
1.65
1.65
1.20
1.65 0.62
0.37
1.20
0.190
0.89
0.46
0.25
0.30
1.65 2.6
102.6
4.2
2728
42
1"1
317
.
42 Multicore
4.2
10
mV
Touching
mV
Two cables
single-core cables,
--
Table B.28 Mineral insulated cables bare and exposed to touch or having an overall covering
of p.v.c
(copper conductors and sheath) (conte'd)
Voltage drop (per ampere per meter) for single-phase operation sheath operating temperature: 70°C
--- r r r
x x-z0.21 10.31 Three single-core cables cables
0.200.29 0.28Spaced
0.21
0.54
0.32
0.78
0.40
0.26
1.05
1.45 0.140
0.26
0.155
0.58
22441.600.1251.60
0.150 3m0.41
50.44
0.36
0.1650.1400.22
0.36
0.26
0.320.160
0.150
0.145
0.25
0.27
6.06.0
9.19.1
2.3
3.6
3636
14
0.165
0.1702.3
3.6
6.0
9.1
14
24
36
1.45
1.05
0.82
mVmV240.21
0.79
2.3
3.6
141.05
1.45
0.29
0.25
0.55 cable
-V-0.56
0.26
0.330.39
0.30
0.36
0.28
0.80
0.43
0.30
0.36
0.42
0.22
1.05
1.45
0.32
0.25
0.29
0.23 0.60Touching.Flat formation
0.65
0.220.46
0.24 0.47
0.83
1.10
1.50
1.10
1.45
0.87
0.53
0.40
Multicore
Conductor Trefoil, touching
diameter apart
-
Table B.30 Mineral insulated cables, bare and neither exposed to touch nor in contact with
combustible materials
(copper conductors and sheath)
Voltage drop (per ampere per metre) for single-phase operation Sheath Operating Temperature:
105°C
, --
x-z-1.85
x0.145 - 0.51
r 0.26
z1.00 Touching
6 Conductor
0.155
1.850.180
0.150
0.160
0.165
0.175
0.170 0.36
0.44
0.31
1.85
0.71
0.540.33
1.85
0.41
0.27
1.350.21
1.35
0.69
1.00 3.0
4.7
231
7.8
1247
19 331
47
12
4.7
7.8
19
~ i.
3.0 A A Multicore cables
l Two single-core cables
Table B.30 Mineral insulated cables, bare and neither exposed to touch nor in contact with
combustible materials (conte' d)
(copper conductors and sheath)
Voltage drop (per ampere per metre) for single-phase operation: Sheath operating temperature: 105°C
- zr-x -76Trefoil
xz r
xrx 0.60
0.36
0.29
0.87
1.15
1.60
0.45
0.23 0.145
0.135
0.26
0.63
0.39
0.34
0.150
0.90
0.155
0.160
1.60
0.140
0.48
0.130
0.29
5
43
mV0.61
0.31
0.22
0.37
0.88
1.15
1.60
0.46
0.26
'4.1
27
16
4.1
40
10
2.6
6.8
10
16
40
27
6.8
2
40
1
mV
10
2.6
Spaced4.1
1.20
mV
2.6 touching
0.1800.1300.22
6.8
2.6
2 0.62
0.25
0.290.70
0.38
0.27
0.195
0.32
0.21
0.20
0.88
0.29
0.22
1.20
0.125
1.65
0.31
0.23
0.47
0.28
0.21
0.26
0.27
Flat
10.30 0.36
0.43
0.48
0.29
0.65
0.37
0.42
0.95
0.91
1.65
1.60
1.20
1.65
0.56
0.50
0.39
0.33
formation
cable1.25 Touching
Three single-core cables cables
Multicore
diameter apart
Nnte: Where the conductor is to be protected by a semi-enclosedfuse, see A.6.2 of the Preface to this Annex.
~
~
Table B.32 Voltage drop (per ampere per meter)
,
"C
,,,.Zx
z0.91
A
0.25
D.26
0.77
0.39
0.22
D.22z1.35
x0.21
D.24
1.40
0.26
0.70
0.770.24
0.155
0.34
0,48
0.31
0.26
D.29
0.37
0.79
0.52
0.145
0.30
0.35
0.67
0.170
0.59
0.61
1.550.45
D.25
0.92
1.40
1.55
1.35
1.55
1.35
0.071
0.155
0.230.24
0.089
0.135
D.28
0.42
0.21
0.67
0.53
0.26
0.34
0.24
0.91
0.61
0.49
1.05
0.170
0.195
0.23
0.55
0.45
0.36
0.125
0.190
0.135
030
0.110
0.140
0.24
0.21
0.61
0.53
0.49
0.30
0.28
0.26
0.40
0.165
1.05
0.91
0.42
0.67
0.130
0.32
0.29
0.30
D.27
0.71
0.58
0.51
0.145
0.74
0.160
0.61
0.27
0.40
0.35
0.44
0.1511
0.28
D.28
0.41
0.97
0.94
0.64
-'.,0
0.26
D.23
0.140
0.35
0.27
0.43
0.21
0.185
0.190
0.28
0.32
1.05
0.30
0.23
0.82
0.25
0.31
0.55
0.37
0.86
0.185
0.70
0.1811
0.175
0.42
D.24
D.26
0.511
0.52
0.36
0.27
0.74
0.26
0.40
0,47
0.46
0.96
0.22
0.165
0.29
0.23
0.69
0.55
0.160
0.30
1.60
0.25
0.37
0.23
0.22
D.23
0.0590.22
..1.55
1.35
0.94 1 J I5
zZXxx 0.26
1.15
1.35
0.155 0.64
0.81
0.51
0.32
1.60
0.42
1.10
D.220.110
0.18110.24
1.55
2mV
"0.1811
0.155
0.170
0.082
0.077
0.068
0.075
D.29
0.060
0.165
0.094
0.1511
•0.195
0.190
0.1811
0.140
0.23
0.1511
0.120
0.77
0.099
0.190
1.05
0.61
0.49
0.39
0.30
0.28
0.27
0.100 mV
0.094
Reference
Reference
fin tray$,
,nd
4mV
C8bJesd~.
Cflnduit
,nd 4,nd
11
7etc.
ow
mV
0.066
11
tflUching}
tflUChing}
Referenc,
andIFIIt
(fndostJd
Reference
Reference in
Methods
12 {Indirect
Mllthods
,nd{cippetl
0.077
M,thod
4ctmduit
0.066
{enclosed
sp,c.!}
II'
in
0.074
fiR ,0.105
"1 fI'
treflJi
0.086
Reference
MiJtlllJds
MethlJd
{sp,c.!}
11 {Flat
12
.0.135
in
etc.
tflUchingJ
If fin0.1511
inMethods
121
, 3
wall
Reference
2 c,bIes . singfe-p/llse a.c. Methods 3
3 " 4 c,bIes· tJuee.(Jhasea.e.
t Spacings larger than those specified in Method 12 (see Annex Annex A of Section 8) will result in larger voltage drop.
Table B.33 Multicore P.V.C,-insulated cables, non-armoured
(aluminium conductors)
4 cable,
·1 207
237
135
155
176
11381
245
210
280
330
285
212
227
259
248
305
351
160
197
184
cable,
phase
phase n
6110
278
or
104
86150
140
58
three-
.130
108
131
118
210
116
139
44173
157
170
195
54
41
73
71
53
65
3
A66
48
61
89
83
62
125
111
117
135
103 -single-
-A
89559
160
183
98
A
92
96
90 d.c.
a.c.
three- a.c.
d.c.
three-phase
phase
cable,
cable, three-
core
1
phase
core or
core
1a.c. or7four-
cable
two-core
cable,three- four-
two-core,
three-phase
a.c.
a.c.
or
a.c.
single-
cable,
single-
single-
1
Reference two-core or
Reference
direct)
Reference
MethodMethod
Reference 4 Reference
(enclosed
Method 3 11
Method (on a
(enclosed
in air) 1 (clipped
trunking)
13 Method
(free
in
perforated cable tray), or
cross- sectional
Note: Where the conductor is to be protected by a semi-enclosed fuse, see A.6.2 of the Preface to this Annex.
Table B.32 Voltage drop (per ampere per meter)
,
"C
.
II II 0.53
0.26
0.77
1.05
0.36
0.77
0.40
D.28
0.26
0.42
0.49
0.67
0.34
0.91
0.53
0.61
0.39
0.55
0.70
z1.05
r0.28
030
0.155x0.37
IZ0.135
0.53
0.61Z
1.35
A
X
0.165
1.05
0.30
0.91
0.67
0.34
0.58
0.61
D.29
0.71
0.42
0.23
0.22
0.45 X
0.35
0.74
0.43
1.40
D.35zZD.21
1.15
0.15/1
0.40
0.79
0.31
D.24
0.86
0.185
0.61
0.5/1
0.37
0.51
D.29
0.190
1.550.27
0.26
1.55
1.55
0.160
0.44
0.97
0.37
0.41
0.94
"1.10
0.64
0.185
0.190
D.28
0.32
0.67
0.27
0.70
0.180
0.82
0.25
0.74
D.26
0.46
0.47
0.40
0.42
0.96
0.55
1.60
1.40
0.30
0.92
0.089
0.071
0.059
0.49
0.42
0.48
0.21
0.24
D.28
D.26 D.23
0.24
0.25
0.52
0.135
0.155
0.170
0.195
0.125
0.23 0.55
0.26
0.30
0.59
0.175
0.52
0.45
D.24
0.24
0.110
0.140
0.130
0.24
0.155
0.21
0.32
0.29
0.30
D.27
0.31
D.26
D.280.23
0.145
1.350.23
0.145
0.140
0.27
0.21
0.30
0.35
0.170
0.36
0.23
1.35
1.35
0.69
.;1.55
0.94
X
1.35
0.21
0.165
0.22
0.29
0.25
0.160
D.25
0.26
0.22
0.22
D.22 1 J I5
XX 0.64
1.10
0.51
0.26
0.180
1.60
0.42
0.81
0.32 1.55
0.61
0.49
0.24
0.099
0.180
'0.28
0.21
0.15/1
/0.23 mV
0.094
Reference
In tny£.
touching)
2mVubles
0.77
0.39
1.05
0.30
0.170
0.165
0.082
0.155
0.068
0.094
0.077
0.075
0.29
0.060
0.195
0.180
0.140
0.110
0.15/1
0.120
0.190
0.190
D.27
0.100 7
4mV
mV
mr
mVd.c.
0.066
Reference
andIFIIIt
1Int14 Reference
conduit etcy in
(EndtJSIJd
Reference
IInd
MethlJds
tlUelling)
Reference
1111nt1
1Int1 12 {TntrefrJi
MethtJds
11 {tipped
4ClJndtit
0.077
0.066
bl
11 (Flatin
0.074
MethtJd
"1 01
direct
0.086
In II0.105
{endtJstJdin
SPIIC.!)
Reference
MethIJd
.0.135
etcy 12
tluclling)121
Methods
(spac.!)
0.15/1
inMethtJds
IJf on II 3 2 cilbies . single-p/lIISBII.C.
WIIIJ
Reference MethtJds 3
3 II 4 cilbies . t!IrrJe.pMSBII.t.
t Spacings larger than those specified in Method 12 (see Annex Annex A of Section 8) will result in larger voltage drop.
Table B.33 Multicore P.V.C,-insulated cables, non-armoured
(aluminium conductors)
11207
210
248
330
237
285
381
135
155
176
259
305
351
184
212
245
280
227
160
197
4 cable,
cable,
phase
phase n
83110
2118
or
58
78
150
three-
44
54
41
71
53
65
.130
108
131
104
12566
48
61
139
157
116
86
three-
73
89
210
111
1A 83
6259-core
56140
195
183
160
98
92
90
96
173
A03-single-
9a.c.
170
117
135 d.c.
a.c.
A d.c.
cable,
core
three-phase
phase
cable,
cable, phase
Reference
or
core7a.c.
three-
1a.c. orfour-
two-core
or
cablefour-
two-core,
three-
cable,
three-phase
a.c.
a.c.
single-
single-
single-
1 two-core or
Method
Reference Method
Reference
direct)
Reference Method 3 11
Method
4 {enclosed in
trunking)
Reference
13 (free
Method
air) 1 {clipped
(on a
{enclosed in
perforated cable tray), or
cross- sectional
Note: Where the conductor is to be protected by a semi-enclosed fuse, see A.6.2 of the Preface to this Annex .
•
r
I
Table B.35 Single-core armoured P.V.C.-Insulated cable, Non-magnetic armour.
(aluminum conductors)
~
IV
\0 Note: Where the conductor is to be protected by a semi-enclosedfuse, see A.6.2 of the Preface to this Annex.
Table B.36 Voltage drop (per ampere per metre)
z0.23
0.21z0.22
rrrr 0.190
x0.23
0.170
0.155
0.30
0.38
0.320.21
0.22
0.26
0.28
0.35
0.40
0.29
0.38
0.44
0.26
0.51
0.30
0.58
0.170
0.28
0.39
0.160
0.165
0.28
0.39
0.47
0.24
0.54
0.81
0.68
0.70
1.35
0.93
0.92
1.35
0.31
0.195
0.33
1.35
1.10
0.190
0.93
1.35
0.22
0.26
0.185
0.26
0.27
0.094
0.180
0.115
0.100
0.195
0.185
0.145
0.175
0.140
0.165
0.32
0.24
0.200
0.175
0.31
0.22
0.150
0.23
0.145
0.20
0.170
0.160
0.21
0.24
0.180
0.185
0.25
0.32
0.29
0.54
0.28
0.33
0.42
0.50
0.460.160
0.195
0.24
0.155
0.37
0.45
0.53
0.24
0.34
0.27
0.44
0.34
0.185
0.22
0.45
0.27
0.52
0.25
0.35
0.36
0.27
0.32
0.18
0.190
0.195
0.66
0.60
0.57
0.65
0.62
0.68
0.71
0.180
0.57
0.25
0.73
0.70
0.81
0.75
0.80
0.86
0.21
0.95
1.30
1.55
1.05
0.96
1.55
1.00
0.1300.20
0.21 2 cables
xzz 3 0.160
x0.60 0.26
0.190
0.170
0.15
0.50
0.41
0.62
0.78
1.55
1.05
0.200
0.1650.120
0.135
0.115
0.110
0.180
0.22
Reference
0.060
0.39
0.49
0.30
0.61
0.77 56Reference
1,11
0.097
0.075
0.190
0.150
0.24
1.55 7mV
2mVrY)V
1.05 mV d.c.and 12
Reference 4Methods
(In
Method
Methods
:
0.3~ 1 and
Referencetouching)
11 (Flat
12 (Spacedt)
Methods 2 cables, 3 single-phase
or 4 cables, a.c.
three-phase a.c.
12Reference Method1 and 11 (Touching)
(Flat spacedt)
t Spacings larger than those specified in Method 12 (see Annex A, Section 8 ) will result in. a larger voltage drop.
SECTION 4: CONDUCTORS
Note: Where the conductor is to be protected by a semi-enclosed fuse. see A.6.2 of the Preface to this
Annex.
Note: 1. Where the conductor is to be protected by a semi-enclosed fuse, see A.6.2 of the Preface to this Annex.
ii .Where a conductor operates at a temperature exceeding 7fJ'C, it shall be ascertained that the equipment connected to the conductor is suittable for the
conductor operating temperature
Table 8.40 Voltage drop (per ampere per meter)
t Spacings larger than those specified in Method 12 (see Annex A of Section 8) will result in a larger voltage drop.
Tabl •••B~ ftIlI••• tI_·~8 1•••••••• • non-•••••••
ou..-
(aluminium conductors)
Note: i) Where the conductor is to be protected by a semi-enclosed fuse, see A.62 of th" Preface to this Annex ..
ii) Where a conductor operates at·a temperature exceeding 7ffc, it shall be ascertained that the equipment connected to the conductor is suitable for the conductor operating
temperature.
ELECIAICAlINSTALLATION OF BUILDINGS
Note: i) Where the conductor is to be protected by a semi-enclosed fuse, see A.6.2 of the Preface to this Annex.
ii) Where a conductor operates at a temperature exceeding 7rflC, it shall be ascertained that the equipment connected to the conductor is suitable for the
conductor operating temperature.
-
l.H
00
Table B.44 Voltage drop (per ampere per meter)
rr r 0.29
0.27
0.165
0.160
0.22
0.175
0.140
0.24
0.105
0.21
0.150
0.210.160
0.175
0.135
0.175
0.31
0.24
0.20
0.29
0.29
0.32
0.26
0.1600.22
0.46
0.40
0.41
0.32
0.35
0.175
0.23
0.160
0.39
0.165
0.40
1.40
0.71
0.760.29
0.30
0.165
0.90
0.175
0.76
0.490.26
0.190
0.24
0.20
0.47
0.60
0.46
0.99z0.34
0.97
0.60
1.05z1.10
x0.25
0.160
0.26
0.170
0.21
0.54
0.64x.31
0.96
0.49Reference
0.140
0.34
0.41
0.74
1.40.29
0.23
1.60
0.43
0.60
0.33
0.66
0.53 0.160
0.32
0.26
0.21
1.60
1.10
0.52
0.66 Reference
- Methods
mV mV
,11 and 1(Flat Methods 1,
oss-
0.20
0.190
0.25
0.170
0.195
0.135
0.093
0.140
0.24
0.22
0.190
0.120
0.26
0.39
0.35
0.33
0.25
0.24
0.37
0.30
0.195
0.23
.0.160
0.25
0.36
0.45
0.47
0.44
1.60
0.65
1.35
0.46
0.74
0.54
0.27
1.60
1.40
0.63
0.15
0.96
0.69
0.57
1.10
0.52
0.56
0.69
0.29
0.70
0.74
1.15
0.62
1.00
0.220.26
0.145
0.33
0.20
0.165
0.36
0.53
0.57
0.195
0,20 0.120
0.170
0.195
0.21
0.34
0.25
0.22
0.155
0.34
0.27
0.26
0.63
0.22
0.25 0.105
0.080
0.064
0.160
0.34
0.27
0.32
0.63
.30
0.30
0 0.105
0.130
0.185
0.62
0.42
mV
2d.c.
cables and12
mV
mV (In(Flat
Reference
Reference
Reference
11 trefoil
(Spaced1) Method
Method 2 Cables
Methods
andspacedt)
1 - single-phase
1212
11touching)
(Touching)
a.c.
3 or 4 cables - three-phase a.c.
t Spacings larger than tho~ specified in Method 12 (see Annex A. Section 8) will result larger voltage drop.
SECTION 4: CONDUCTORS
Note: i) Where the conductor is to be protected by a semi-enclosed fuse, see A.6.2 of the Preface to this
Annex.
ii) Where a 'conductor operates at a temperature exceeding 7fYC, it shall be ascertained that the
equipment connected to the conductor is suitable for the conductor operating temperature.
5.1 SCOPE
(1) This. Section covers services, service equjpment, and metering equipment and their
installation requirements for systems operating at 1000. OV or less.
(1) The following references contain provisions which, through reference in this text, constitute
provisions of the Ethiopian Building Code Standard on Electrical Installation of Buildings.
(a) C22.1:1992 Canadian Electrical Code Part 1, Safety Standard for Electrical
Installations, Sixteenth Edition
(b) NFP A 70/NEC: 1986 National Fire Protection Association/ AmericanNational Electrical
~ Code, 1987 Edition
5.3 DEFINITIONS
(1) For the purpose of this Section, in addition to the terms defined in Section 1, the following
defmitions shall apply.
service conductors / cable the supply conductors/cable that extend from the street main or
from transformers to the service equipment of the consumer's
installation.
service drop the overhead service conductors from the last pole or other aerial
support to and including the splice, if any, connecting to the
service-entrance conductors at the building or other structure.
Note: Where service equipment is located outside the building walls, there may be no service-entrance conductors,
or they may be entirely outside the building.
consumer's in$tallations wiring and apparatus situated upon the consumer's premises installed
and controlled by him, excluding any switchgear of the Supply Authority·which the consumer
may be permitted to use.
5.4 GENERALREQUIREMENTS
(1) Except as provided in 5.4.1.2" each consumer's installation shall be supplied with a single
service.
(b) Due to capacity requirements, two or more services shall be permitted where:
(e) For different characteristics, such as for different voltage, frequencies or phase, or for
different uses, such as different rate schedules.
(
5.4.1.3 Marking
(I) Where more than one service is permitted or provided, a pennanent plaque or directory shall
be installed adjacent each service equipment location denoting all other services on or in the
consumers' installation and the area served by each.
5.4.1.4 Grouping
(1) When two or more supply services are installed to a building, all service boxes associated
with the various consumer's services shall be grouped, where practicable.
(1) Service conductors supplying a consumer's installation shall not pass through the interior of
another building or other structure.
(1) Conductors shall be considered outside of building or other structure under any of the
following conditions:
(a) Where installed under not less than 50.0mm of concrete beneath a building or other
structure; and
(b) Where installed within a building or other structure in a raceway that is enclosed by
concrete or brick not less than 50.0mm thick.
(1) Conductors other than service conductors shall not be installed in the same service' way or
service~entrance cable.
Exemption: Earthing conductors and load management control conductor having overcurrent protection.
(1) Service conductors installed as open conductors or multi conductor cable without an overall
outer jacket shall have a clearance of not less than 925.0mm from windows, doors, porches, fire
escape, or similar locations.
(2) Service conductors shall not be installed beneath openings through which materials may be
moved, such as openings in farm and commercial buildings.
(3) Overhead wire shall not be run such that they obstruct entrance to these building openings.
Exemption: Conductors running above the top level of a window shall be permitted for a clearance of requirements
of less than 925.0mm as in (1) above.
5.5.1 General
(1) Service equipment's live parts shall be enclosed or guarded as specified below:
(a) They shall be enclosed so that they will not be exposed to accidental contact; or
(b) If not enclosed they shall be installed on a switch board, panel board, or control board
and guarded by providing a means for locking or sealing doors giving access to them.
(1) Service equipment, raceway, cable armour, cable sheaths, panel boards, etc and any service
conductors that are to be earthed shall be done in accordance with the relevant Parts of
Section 7.
(1) Service equipment shall be suitable for the short-circuit current available at its supply
tenninal.
(1) Sufficient working space shall be provided to the vicinity of the service equipment to permit
safe operation, inspection, and repairs.
5.5.1.5 Location
(1) Service boxes or other consumer's serVice equipment shall be installed in an acceptable
location and in compliance with applicable Codes or Standards or by-laws of the Supply
Authority concerning the location of service boxes or other equipment and shall be:
5.5.2 Control
5.5.2.1 General
(1) Every consumer's installation shall be adequately controlled by switchgear readily accessible
to the consumer and which shall incorporate:
Note: Where the Supply Authority provides switchgear and pennits part of it to be used by the consumer, the
consumer need not then duplicate that part.
(1) The means of disconnect required by 5.5.2.1 shall comprise a linked switch suitable for
operation on load or a linked circuit breaker, arranged to disconnect all circuit.
(2) Alternatively, for systems where one conductor is connected with earth, the linked switch
or circuit-breaker may be arranged to disconnect the live conductors only and an isolating link
may be inserted in the earthed conductor; such an isolating link shall be so arranged that it is
in contact before the linked switch can be closed, or shall be securely fixed. by bolts or screws.
Overcurrent protection
/ 5.5.2.3
/
(1) The means of overcurrent protection referred to in 5.5.2.1 shall comprise either a fuse
inserted in each live conductor of the supply or a circuit-breaker having an overcurrent release
fitted in each live conductor of the supply.
i) the rating of all cables connected between the Supply Authority's fuse or circuit-breaker and the consumer's
sub-circuit fuse or circuit breakers is not less than the rating of the Supply Authority's fuse or circuit-
breaker; and
ii) the overcurrent device protecting all circuits controlled by the switchgear are located within the same
enclosure as the switchgear or, alternatively, are fixed immediately adjacent to it.
(1) Means for earth-leakage protection shall be provid~d for service equipment in accordance
with Clause 9.4.2, Section 9.
Note: When an installation is being planned, it is desirable to consult the Supply Authority, or a competent person
having knowledge of local conditions, to ascertain whether satisfactory protection against earth leakage will be
obtained by the use of the fuses or circuit breakers provided for overcurrent protection or by the use of earth-leakage
circuit breaker.
(1) The sequence of the equipment forming the switchgear required by 5.5.2.1 shall be such that
the means of disconnect follows the consumer's terminal without the intervention of any other
apparatus (see Figure 5.1).
~ f~ lObi
IIII
~:~:~~n~lu~in.~p~ue.::e~t'l~~!:"~I=
owltchaut ••.• Included.) ::d t~c.ica~~-::~
Note: The consumer:s linked switch and the consumer's main fuse may be combined in a switch and fuse unit
(1) Every means of overcurrent protection shall be suitable for the maximum short-circuit current
attainable or available. V
5.5.2.8 Discrimination
(1) The characteristics and settings of overcurrent protective gear, including fuses, and the
arrangement of the installajion shall be such that discrimination in the operation of the
overcurrent protective gear is ensured.
(a) installed in rigid conduit and be of a type suitable for use in wet locations;
(b) a single or multiple conductor cable for service entrance use below ground provided that:
(1) Consumer's service conduit entering a building underground shall be suitably drained.
5.6.1.3 Conduitseal
.(1) ·Consumer's service conduit connected to an underground system shall be sealed with a
suitable compound to prevent the entrance of moisture or gases.
(1) Conductors of a consumer's service which is connected to an overhead supply service at any
point above ground on a building or other structure shall be installed in a rigid metal conduit
or in one of the following ways, if acceptable:
(2)Bare overhead supply conductors running on the outside walls of a building may be run as
exposed wiring using types of conductor suitable fdr exposure to the weather .
.(3) The length of consumer's service conductors beyond the service head shall ~e adequate. to
enableconnection to tHe supply service conductors or to the conductors referred to in·5.6.2. with
a minimum length of 750.0mm.
(5) Consumer's service conductors shall be suitable for the temperature which can be
experienced in the particular locality.
5.7.1 Connection
(1) Metering equipment shall be connected on the load side of the service box except that it may
be connected on the supply where:
Note:- Transfonnerrated meter mounting device means a meter mounting device with current transfonners and with
or without test sw.itches mounted in the same enclosure~
6.1 SCOPE
(1) This section covers conductor ampacities and equipment ratings required for consumer's
services, feeders and branch circuits.
6.2 NORMATIVEREFERENCES
(1) The following references contain provisions which, through reference in this text, constitute
provisions of the Ethiopian Building Code Standard on Electrical Installation of Buildings.
(a) C22.1: 1990 Canadian Electrical Code, Safety Standard for Electrical Installations
Sixteenth Edition.
(b) NEC Hand book 1981 National Electrical Code Handbook Based on the 1981
(NEC), Seventeenth Edition.
6.3 DEFINITIONS
(1) For the purpose of this Section, the followingdefinitions shall apply in addition to the terms
defined in Section 1.
demand factor it is the ratio of the maximum demand of a system or part ora
system, to the total connected load on the system, to the maximum
demand of the whole system,or part of a system, under
consideration.
diversity factor the ratio of the sum of the individual maximum demands of the
various subdivisions of a system, or part of a system, to t~e
maximum demand of the whole system, or part of a system, under
consideration.
continuous load any condition in which the maximum load current in a circuit flows
without interruption for a period of not less than 3.0hrs.
6.4 GENERAL
(1) When calculating the currents from loads expressed in watts or volt-amperes, to be supplied
by a low voltage a.c. system, the voltage divisor to be used shall be 230.0Y or 380.0Y as
applicable.
(1) Voltage drop in an installation shall be based upon the calculated demand load of the branch
circuits and shall satisfy the requirements of Clause 4.5.4.
For loads other than motors, the total load on consumer's service, feeder or a branch circuit shall v
be 80% .of the circuit rating when the load is a continuous one ..
(1) Where two or more loads are so installed that only one can be used at anyone time, the one
providing the greatest demand shall be used in determining the calculated demand.
(2) Where a feeder supplies loads of a cyclic or similar nature such that the maximum connected
load will not be supplied at the same time, the ampacity of the feeder conductors shall be based
on the maximum load that may be connected at anyone time .•.....
(3) The ampacity of conductors of a feeder or branch circuit shall not exceed the ampacity of
the conductors of 'the service or of the feeder from which they are supplied.
(1) The minimum ampacity of service or feeder conductors supplying a single-family dwelling
shall be based on the following:
(a) a basic load of 2500.0W for the first 70.0m2 of living area; plus
(b) an additional 1000.OW for each 70.0m2 or portion thereof in excess of 70.0m2; plus
(c) 3500.0W for any electric "Injera Mitad"; plus
(d) 6000.0W for a single cooking stove having a rating of 12.0kW or less, plus 40% of the
amount by which the rating of the cooking stove exceeds 12.0kW; plus
(e) any electric water heater with a demand factor of 100%.
(1) The minimum ampacity of service or feed,er conductors from a main service supplying loads
in dwelling units shall be based on the following:
(a) a basic load of 2500.0W for the first 45.0m2 of living area; plus
(b) an additional 1500.0W for the second 45.0m2 or portion thereof; plus
(c) an additional 1000.0W for each 'additional 90.0m2 or portion thereof in excess of the
initial 90.0m2; plus
(d) 3500.0W for any electric "Injera Mitad"; plus
(e) 6000.0W for a single cooking stove having a rating of 12.0kW or less, plus 40% of the
amount by which the rating of the cooking store exceeds 12.0kW; plus
(t) any electric water heaters with a demand of 100%
(2) The minimum ampacity of service or feeder cond~tors from a main service supplying two
or more dwelling units shall be based on the calculated load obtained from Clause 6.5.2(1) and
the following:
(a) Exciuding any air-conditioning loads, the load shall be considered to l;?e:
i) 100% of the calculated load in the unit having the heaviest load; plus
ii) 65% of the sum of the calculated loads in the next 2 units having the same or next
smaller load to those specified in (i) above; plus
iii) 40% of the sum of the calculated loads in the next 2 units having the same or next
smaller loads to those specified in (i) above; plus
iv) 25% of the sum of the calculated loads in the next 15 units having the same or next
smaller loads to those specified in (i) above; plus
v) 10% of the sum of the calculated loads in the remaining units;
(b) If air-conditioning is used, the amount by which the sum of all the air-conditioning loads
exceeds 1500.0V A shall be added, with a demand factor of 100%, to the load determined
in accordance with (a) above.
(c) In addition, any lighting, heating, and power loads not located in dwelling units shall be
added with a demand factor of 75%.
Note: The living area designated in Clause 6.5.1 and 6.5.2 shall be determined from the outside dimensions of the
group floor of the dwelling plus 75% of the basement area based on the inside dimensions, plus any area
which might normally be used for living purposes on the upper floors.
6.5.3 Schools
(l) The minimum ampacity of service or feeder conductors shall be based on the following:
(a) 75% for a building with an area upto and including 900.0m2 based on the outside
dimensions.
(b) For a building with an area exceeding 900.0m2 based on the outside dimensions, the load
may, be divided by the number of square meters to obtain a load-pre-square-meter rating
and the demand load may be considered to be the sum of: V
i) 75% of the load per square meter multiplied by 900; and
ii) 50% of the load per square meter multiplied by the area of the building in excess of
900.0m2•
6.5.4 Hospitals
(1) The minimum ampacity of service or feeder conductors shall be based on the following:
(a) a basic load of 20.0W/m2 of the area of the',building based on the outside dimensions;
plus
(b) 100.0W/m2 for high intensity area such as operating rooms; plus
(c) air conditioning, and power loads based on the rating of the installed equipment
••
ELECTRICAL INSTALLATION OF BUILDINGS
(a) 80% for a building with an area upto and including 900.0m2 based on the outside
dimensions;
(b) For a building with an area exceeding 900.0m based on the outside dimensions, the
balance of the load may be divided by the number of square meters to obtain a load-per-
square-meter rating aDd the demand load may be considered to be the sum of:
(1) The minimum ampacity of service or feeder conductors shall be based on the following:
(a) a basic load of 20.0W/m2 of the area of the building based on the outside dimensions;
plus
(b) lighting loads for special areas such as ballrooms; based on the rating of the equipment
installed; plus
(c) air conditioning and power loads based on the rating of the equipment installed.
a) 80% for a building with an area upto and including 900.0m2 based on the outside
dimensions;
b) For a building with an area exceeding 900.0m2 based on the outside dimensions, the
balance of the load may be divided by the number of square meters to obtain a load-per-
square meter rating and the demand load may be considered to be the sum of:
(1) The minimum ampacity of service of feeder conductors for the types of occupancies
specified in Table 6.1 shall be based on the following:
(a) a basic load to be calculated on the basis of watts per square meter required by Table
6.1 for the area served based on the outside dimensions, with application of demand
factors as indicated therein; plus
(b) special loads such as air conditioning, power loads, show window lighting, stage lighting,
etc, based on the rating of the equipment installed with such demand factors as are
permitted by this Code.
(1) Conductors of a branch circuit supplying "Injera Mitad" and/or cooking stove in a dwelling
unit shall be considered as having a demand of
Note: For the purpose of Clause 6.5.7(1), two or more separate built-in cooking units may be considered as one
cooking
(2) For "Injera Mitadn and or a cooking stove installed in commercial, industrial, and
institutional establishments, the demand shall be considered as not being less than the rating.
(3) The demand loads given in (1) above shall not apply to cord-connected hotplates or other
appliances.
(1) Feeder demand factors for lifts shall be as shown in Table 6.2.
Table 6.1 Demand factor for service and feeders and watts per square meter for
various types of occupancy
Feeders
100
90
100
80
70
80
100
70-90
70
75
95qO Watts30
50
15
10
20
5per m2
25
1Q Demand factor [%] -.
Service
conductor
Note: Demand factors (DF) are based on 50% duty (i.e, half-time load, half-time no load).
7.1 SCOPE
(1) Part I of this Section covers the prote;:ctionof electrical installation by earthing and bonding.
(2) This part also covers provisions for insulating and guarding as suitable alternatives to
earthing where permi~d by this Code.
(1) The following references contain provisions which, through reference in this text, constitute
provisions of the Ethiopian Building Code Standard on Electrical Installation of Buildings.
(a) C22.1: 1992 Canadian Electrical Code, Part 1, Safety Standard for
Electrical Installations, Sixteenth Edition.
(1) A two~wire direct-current system suppiying interior wiring and operating at not more than
300.0V or not less than 50.0V between conductors shall be earthed, unless such system is used.
for supplying industrial equipment in limited areas and the circuit is equipped with an earth
detector.
(2) The neutral conductor of all3-wire direct-current systems supplying interior wiring shall be
earthed.·
(1) Except as otherwise provided for in this Code, alternating-current systems shall be earthed
if:
(2) Wiring ,.. systems supplied by an unearthed supply shall be equipped with a suitable earth
(
Idetection device to indicate the presence of an earth fault.
(3) Circuits of less than 50.0V shall be earthed under any of the following conditions:
(4) Where primary windings of current and voltage instrument transformers are connected to
circuits of 230.0V-or-more-to-earth, the secondary circuits of the transformer shall be earthed.
(5) Where the transformers are on switchboards, the secondary circuits shall be earthed
irrespective of the voltage of the circuits.
(1) D.C. systems to be e~hed shall have the earthing connection made at one or more supply
stations; but not at individual services nor elsewhere on interior wiring.
(1) An internal wiring system that is supplied by an a.c. service and which is to be earthed shall
have at each service, an earthing conductor connected to an earth electrode which complies with
Clause 7.8 below.
(2) The earthing conductor shall be connected to the earthed service conductor at any accessible
point from the load end of service drop or service lateral.
(3) Where the transformer supplying the services is located outside the building, at least one
additional earthing connection shall be made from the earthed service conductor to an .earth
electrode, either at the transformer or elsewhere outside the building.
(4) An earthing connection shall not be made'toany earthed circuit conductor on the load side
of the service disconnecting
\
means.
\
(5) For circuits that are supplied from two sources in a common enclosure or grouped together
in separate enclosure and employing a tie, a single earthing electrode connection to the tie point
of the earthed circuit conductors from each power-supply source shall be permitted.
(6) Where the system is earthed at any point, the earthed conductor shall be run to each
individual service and not be smaller than the required earthing conductor specified in Table 7.1,
and where the earthed circuit conductor also serves as the neutral, the requirements of the
relevant Clauses of Section 4 shall be met.
(1) For a wiring system or circuit which is required to be earthed, and which is not conductively
connected to a distribution system, the earthing connection shall be made at the transformer, or
other source of supply, or on the supply side of the first switch controlling the system, and
satisfying both the following conditions:
a) The earthing conductor shall not be smaller than that specified in Table 7.1.
b) If two or more systems are employed, a common system earthing conductor shall be
installed unless separate earthing is supplied for each such system, in which case the
earthing for the individual systems shall be interconnected.
(1) Where to or more buildings or structures are supplied from a single service:
a) the earthed circuit conductor at each of the buildings or structures shall be connected to
an earthing electrode and bonded to the non-current-carrying metal parts of the electrical
equipment; or
b) except for buildings housing livestock, the non-current-carrying metal parts of the
~lectrical equipment in or on the building or structure shall be pennitted to be bonded
to earth by a bonding conductor run with the feeder or branch circuit conductors.
(1) For a.c. wiring systems, the conductors to be earthed shall be as follows:
(1) Where wiring systems, circuits, electrical equipment, cable annour, conduit and other metal
./ . raceways are earthed as a protective measure, the earthing shall be arranged so that there is no
objectionable passage of current over the earthing conductor or earthing path.
(2) If the use of multiple earthing connecti9ns results in an objectionable flow of current, one
or more of the following alterations shall be made:
c)· Interrupt the continuity of the conductors between the earthing connections.
d) Take other suitable remedial 'action to limit the current.
Note; The temporary currents which are set up under accidental conditions while the earth conductors are
performing their intended protective functions are not considered objectionable.
7.5 BONDING
(1) Atl non-current-carrying metal work of wiring systems including cable sheaths and armour,
conduit, ducts, trucking boxes, and catenary wires, shall be bonded to earth.
(2) Where isolation of metal is adopted as a protective measure (prevention of dangerous earth-
leakage current), it shall be confined to the following items: .
a) Short isolated lengths of metal used 'for the mechanical protection of cables having a
non-metallic sheath.
b) Metal clips used for fixing cables.
c) Small metal parts such as screws, '''r name-plates isolated by isolating material.
(1) Exposed non-current-carrying metal parts of equipment shall be bonded to earth; however
this does not apply to double-insulated equipment or isolated metal parts referred to in Clause
7.5.1(2).
(1) Metal parts of water supply services and gas services which may become energized shall be
bonded to earth.
(2) The bonding conductor shall be attached to the water supply service or gas service:
(3) The water supply service or the gas service shall be bonded by means of a copper bonding
conductor riot less than the appropriate value shown in Table 7.1 subject to a minimum size of
2.5mm2•
Note:- i) For the purpose of Clause 7.,5 the associated circuit conductor is the largest conductor connected into
the input side of the consumer's switchgear.'
ii) Conductor of material other than copper shall have a resistance not exceeding that of the prescribed
copper conductor. _
Hi) Connection to the pipes of the services shall be made by means of a clamp.
-Nominal cross-sectional 16
50
506670 of bonding
1.0t
Nominal
50'
70
2.5
1
6
6
2.5t
1.0t
mm2
area
mm2 cross-sectional
coductor
~ are.
Nominal
of earthing
cross-sectional
conductor
mm2
t 2.Smm2 for bonding metal work of other services at points of entry to premises.
(1) The exposed metal parts of all equipment which is required by this part of the Code to be
earthed, which might otherwise come into fortuitous contact with extraneous fixed metalwork,
shall be either effectively segregated therefrom, or effectually bonded thereto, so as to prevent
appreciable voltage differences at such possible points of contact.
(1) The path to earth from circuits, equipment, or conductor enclosures shall be permanent and
continuous and shall have:
/ a) sufficient ampacity to conduct safely any current liable to be imposed on it; and
b) impedance sufficiently low to limit the voltage above earth, and to facilitate the operation
of overcurrent devices in the circuit.
(1) The earthing conductor for circuits shall be permitted to be used as a bonding conductor for
equipment, conduit, and other metal raceways, or enclosure for conductors, including service
conduit or cable sheath and service equipment.
t _
SECTION 7: EARTHING, BONDING AND LIGHTENING PR01ECTION
(I) Where an underground service cable is served from a continuous underground metal sheathed
cablesystem and the sheath or armour of the service cable is connected to the underground
system,the sheath or armour of the service cable shall not be required to be bonded to earth at
thebuilding if it is insulated from the interior conduit or piping.
(2) Where a metal-sheathed service cable served from a continuous underground metal sheathed
cablesystem is bonded to the underground system and is contained in an underground service
conduit,the conduit shall not be required to be bonded to earth at the building if it is insulated
fromthe interior conduit or piping.
(1) Isolated section of metal raceway or cable armour, if required to be bonded to earth, shall
preferably be bonded so by connecting to other earthed raceway or armour.
(I) Fixed equipment shall be bonded to earth in one of the following ways:
b) A bon,ding conductor which is run with circuit conductors as a part of a cable assembly
and which may be uninsulated; but, if provided with an individual covering, the covering
shall be finished to show a green colour or a green/yellow combination.
c) A separate bonding conductor installed the same as a bonding conductor for conduit and
the like.
(2) The armour of armoured cables incorporating a bonding conductor shali not be considered
as fulfilling the requirements of a bonding conductor for the purpose of this ~lause, and the
bonding conductor provided in these cables shall comply with (1b) above.
(3) The armour of flexible metal conduit and liquid-tight flexible metal conduit shall not be
considered as fulfilling the requirements of bonding conductor for the purposes of this Clause,
and a separate bonding conductor shall be run within the conduit.
7.7.
(4) The sheath of mineral-insulated cable having a stainless steel shall not be considered as
(1)
fulfilling the requirements of a bonding conductor for the purposes of this Clause and bonding
con
shall be by one of the methods specified in (1b) or (1d) above.
ear
(1) The electrical continuity of the earthing circuit at the service equipment shall be assured by
one of-the means given in Clause 7.7.3 for the following equipment and enclosures if of metal:
7.
b) the use of threadless couplings made up tight where electrical metallic tubing is used;
or
c) the use of bonding jumpers meeting the requirements of Clauses 7.7.7 and 7.9, or
d) other devices (not standard locknuts and bushings) such as earthing bushings equipped
with bonding jumpers meeting the requirements of Clause 7.7.7 below.
(1) Where service cable has an un insulated earthed service conductor in continuous electrical
contactwith its metal armour or tape, the metal covering shall be c,?nsidered to be adequately
earthed.
(1) The electrical continuity of metal raceway, metal sheathed, or armoured cable shall be
assuredby one of the methods specified in Clauses 7.7.3 or by the use of:
(1) Expansion joints and telescoping sections of raceways shall be made electrically continuous
by bonding jumpers or other acceptable means.
(2) Metal through raceways used in connection with sound recording and reproducting equipment
madeup in sections shall contain an earthing conductor to which each section shall be bonded.
A bonding jumper is a reliable conductor to assure the required electrical conductivity between metal
parts required to be electrically connected.
7.8.1 General
(1) The type and embedded depth of an earth electrode shall be such that the drying and
freezing of soil will not increase its resistance above the required value.
(2) The design used in and the construction of an earth electrode shall be such as to withstand
damage and to take account of possible increase in resistance due to corrosion.
(1) Where a service water pipe from a public water main to a building is used as earthing
electrode, it shall be:
a) continuously conductive;
b) located or placed underground not less than 2S0.0mm below the normal permanent
moisture level; and
c) the underground portion extends not less than 3.0m beyond the extremities of the
building served.
(1) Where a conductive independent metal water piping system is used as earthing electrode, it
shall be placed underground not less than 2S0.0mm below the normal permanent moisture level
and the underground portion extend not less 3.0m beyond extremities of the building served.
(1) Where a metal casing of a pump system is used as earthing electrode, it shall not be less than
75.0mm in diameter and shall extend at least 15.0m below the well-head.
7.8.2.4 Bonding
(1) Where more than one of the earthing means listed under Clause 7.8.2 exist at a building,
they shall be bonded together with a conductor complying with Clause 7.5.4(3).
(1) A concrete-encased electrode shall be encased within the bottom 50.0mm of a concrete
foundation footing that is in direct contact with the ground and shall be:
a) a bare copper conductor not less than 6.0m in length and of size specified in Table 7.2,
or
b) a plate electrode that shall:
i) present not less 0.4m2 of surface to the concrete encasing the plate;
i
ii). be not less than 6.0mm in thickness if of iron or steel; or .5mm in thickness if
non-ferrous metal; and
iii) have a means of attachment for' the system earthing conductor that shall be
accessible after the concrete is poured.
a) be not less than 16.0mm in diameter if of iron or steel, or 12.7mm if non-ferrous metal
or ferrous metal clad with a non-ferrous metal;
b) be not less than 3.0m in length;
c) have a clean metal surface which is not covered with paint, enamel, or other poor
conducting material; and
d) be spaced not less than 3.0m apart (if more than two rods are required).
(1) Plate electrode shall present not, less than O.2m2 of surface to exterior soil and be not less
than 6.35mm in thickness if of iron or steel, or 1.5mm if of ferrous metal.
7.8.3.4 Laying
(1) A rod electrode shall be driven to a depth of no less than 3.0m regardless of the size or
number used, except that:
'.
J.
a) where rock bottom is encountered at a depth of 1.2m or more, it shall be driven to rock
bottom; or
b) where rock bottom is encountered at a depth of less than 1.2m, it shall be buried in a
horizontal trench and be not less 3.0m long.
7.8.3.6 ~l'acing
(1) Each electrode shall be separated at least 2.0m from any other electrode including an
electrode used for signal circuits, radio, lightning, or any other purpose.
(1) Where separation of the different system electrodes is not possible, the electrodes shall be
connectedtogether, at or below ground level, with a copper conductor of a size not less than that
of the earthing conductor for the electrical system and in no case shall the conductor be smaller
than l6.0mm2 copper.
7.8.3.8 Bonding
(1) Where any or all of the separate earthing electrodes are bonded together the bonding ,
conductor shall be:
7.9.1 General
(1) No automatic cutout or switch shall be placed in the earthing or bonding conductor of a
wiring system unless the opening of the cutout or switch disconnects all sources of energy.
(I) The earthing conductor of a wiring system, whether also used for earthing electrical
equipment or not, may be insulated or bare, an~ shall be of copper.
(1) The earthing conductor of a wiring system, whether also used for earthing electrical
equipment or not, may be insulated or bare, and shall be:
c) rigid metal canduit, except where used undergraund ar in any lacatian where material
.
having a deteriarating effect may came into. cantact with the metal, ar in any expased
raceway installed autdaars where it may be subject to. mechanical damage fram vehicular
traffic, in which case a separate canductar as required in (a) abave shall be installed
within the canduit;
d) electrical metallic tUbing, except where used in cancrete ar masanry slabs in cantact with
the graund ar in any lacatian where material having a deteriarating effect may came into.
cantact with the metal, ar in any expased raceway installed autdaars where it may be
subject to. mechanical damage fram vehicular tra~c, in which case, separate canductar
as required in (a) abave shall be installed within"the tubing;
e) the sheath af mineral-insulated cable, except when it is stainless steel, ar any canductar
af a mineral-insulated cable if it is permanently marked at the time af installatian so. that
it can be readily distinguished fram canductars that are nat used as banding canductars,
except that if the sheath is af aluminium in an undergraund run ar in a lacatian where
materials having a deteriarating effect may came in cantact with the metal, carrosion
resistant protection suitable for the carrasive condition encauntered shall be provided;
f) the sheath af aluminium-sheathed cable, but if used far underground runs or in lac~atians
where materials having a deteriorating effect may came in contact with the metal,
c~)ITasian-resistant pratectian suitable far the corrasive canditions encauntered shall be
pravided; ar
(1) The earthing canductar far a system shall be withaut jaint ar splice throughaut its length,
except in the case af bus bars, thermit welded jaints, campressian connectars applied with a
campressian taal compatible with the particular cannectar, ar devices acceptable far connection
in series with the earthing canductor.
(2) 16.0mm2 ar larger capper earthing canductar which is free from expasure to. mechanical
injury may be run alang the surface af the building constructian withaut metal cavering or
protectian, if it is rigidly stapled to. the canstructian; o.therwise, it shall be in conduit, electrical
metallic tubing or cable armour.
(3) A copper earthing conductor of IO.Omm2 shall be in conduit, electrical metallic tubing or
cable annour.
(4) Metal enclosures for earthing conductors shall be continuous from the point of attachmen~
to cabinets or equipment to the earthing electrode and shall be securely fastened to the earthing
clamp or fitting.
(S) Where an earthing conductor is run in the same raceway with other conductors of the system
to which it is connected, it shall be insulated, except that where the length of the raceway does
not exceed IS.Om between pull points and does not contain more than the equival~ll_tof two
quarter bends between pull points, an uninsulated earthing conductor may be used.
(6) Notwithstanding the requirements of (2) above, earthing conductor of I6.0mm2 or larger may
be embedded in concrete provided that the points of emergency are so located or guarded as not
to constitute exposure to mechanical injury.
(1) The bonding conductor for equipment shall be pennitted to be spliced or tapped; but such
splices or taps shall be }.nadeonly within boxes except that, in the case of open wiring, they shall
be pennitted to be -made externally from boxes and shall be covered with insulation.
(2) Where more than one bonding conductor enters a box, all such conductors shall be in good
. electrical contact with each other by securing all bonding conductors under bonding screws, or
by connecting them together with an acceptable solderless connector and connecting one
conductor only to the box by a bonding screw or a bonding device, and the arrangement shall
be such that the disconnection or removal of a receptacle, fixture, or other device fed from the
box, will not interfere with or interrupt the bonding continuity.
(3) Where a bonding conductor is run in the same raceway with other conductors of the system
to which it is connected, it shall be insulated, except that where the length of the raceway does
not exceed I5.0m and does not contain more than the equivalent of two quarter bends, an
uninsulated bonding conductor shall be pennitted to be used.
(4) Where a t;igid metal conduit or steel pipe is used as a bonding conductor, the installation
.shall comply with Section 8 of this Code.
(7) Where a separate bonding conductor supplements the bonding afforded by a ferrous metal
raceway, it shall be installed in the same raceway as the circuit conductor.
(1) The ampacity of the earthing conductor for a direct-current supply system or generator shall
be not le~s than that of the largest conductor supplied by the system, except where the earthing
circuit conductor is a neutral derived from a balancer winding or a balancer set, the size or the
earthing conductor shall be not less than that of the neutral conductor.
(2) The system earthing conductor shall be copper and in no case smaller than IO.OmrW.
(I ) The size of the earthing conductor shall not be less than those given in Table 7.1
(1) The size of a bonding conductor shall be not less that.l that given in Table 7.1; but in no case
does it need to be larger than the largest unearthed conductor in the circuit.-,
(1) The point of connection of the bonding conductor to interior metal raceways, cable armour
and the like shall be as near as practicable to the source of supply and shall be chosen so that
no raceway or cable armour is bonded through a run of smaller size that is called for in
Clause 7.9.6.
(1) Where the earth electrode is a metal water-piping system to which a common earthing
conductor or the earthing conductor of a system is attached, the point of attachment shall be
(3) The metal cold water system shall be made electrically continuous from the point of
attachment of the earthing conductor to the water service entrance by bonding together all parts
thereof if these parts contain insulating section or may become disconnected at meters, valves
and unions.
(4) Equipment may be earthed to a cold-water pipe which is near the equipment.
(1) Where aI metal water-piping system is not available, the earthing conductor shall be attached
to other electrodes at a point which will assure a permanent earth.
(2) Where practicable, the point of attachment in (1) above shall be accessible.
(1) The bonding conductor or bonding jumper shall be attached to circuits, conduits cabinets
equipment and the like, which are to be bonded, by means of lugs, pressure wire connector
clamps, or. other acceptable means.
(3) The bonding conductor shall be secured to every metal box by means of a bonding screw
which shall be used for no other purpose.
(4) The bonding conductor shall be brought into every nonmetallic outlet box in such a manner
than it can be connected to any fitting or device which may require bonding to earth.
(5) Equipment shall be so installed that, if the connections between the branch circuit and the
. internal conductors pass through an access c'over, the bonding connection shall remain
continuous when the cover is removed.
(6) A bonding jumper shall be installed to connect the bonding conductor to the earthing
terminal of a socket outlet and in such a manner that disconnection or removal of the socket
outlet will not interfere with or interrupt earthing continuity.
(7) In the case of metal-enclosed systems where the earthing path is provided by the metal
enclosure, a bonding jumper shall be installed to bond the earthing terminal of the socket outlet
to the enclosure.
(8) Notwithstanding the Provisions of (6) and (7) above, the bonding jumper, in the case of
socket outlets having earthing terminals isolated from the mounting strap required for special
equipment, may be extended directly back to the distribution panel.
(1) The earthing conductor shall be attached to the earthing electrode by means of:
a) a bolted clamp,
b) a pipe fitting plug or other device screwed into the pipe or into the fitting,
c) copper welding by the thermit process brazing or silver solder, or
d) other equally substantial means.
(2) Where a bolted clamp is used for a wet location or for direct earth burial, the clamp shall
be of copper, bronze or brass, and the bolts shall be of a similar material or of stainless steel.
(3) The earthing conductor shall be attached to the earthing fitting as required by
Clause 7.10.4(1).
(4) Connections which depend on solder shall not be used except for connections utilizing silver
solder.
(5) Not more than one conductor shall be connected to the earthing electrode by a:single clamp
or fitting unless the clamp or fitting is specifically designed for multiple conductor connection.
7.11 SCOPE
(1) This Part of the Code covers the installation of lightning protection requirements for all types
of structures with the exception of those structures used for manufacturing explosives.
(2) Electric generation, transmission and distribution systems, overhead telephone lines, and ,
radar stations are not covered by this Code.
(1) The following references contain provisions which, through reference in this text, constitute
provisions of the Ethiopian Building Code Standard on Electrical Installation of Buildings.
(a) BS 6651: 1986 British Standard Code of Practice for Protection of Structures against
Lightning, 1990
(c) UL 96A: 1983 Under writers Laboratories Standard for Installation Requirements for
Lighting Protection systems, Ninth Edition.
7.13 DEFINITIONS
(1) For the purpose Qfthis Section, In addition to the terms defmed in Section I, the following
definitions shaliapply:
lightning protection system a 'complete system of air termination, conductors, earth termination;
interconnection conductors, and other connectors and fittings
required to protect a 'structure from the effect of. lightning.
test joint a joint designed and situated so ·as to enable .resistance 'or 'Continuity
measurement to be made.
ring (loop) earth electrode an earth electrode fonning a closed loop round the structure below
or on the surface of the earth, or within or under the foundations.
It may be ~sed for interconnecting other earth electrodes.
7.14 MATERIALS
7.14.1 General
(1) A lightning protection systemt shall be made of materials that are resistant to corrosion or
shall be acceptably protected against corrosion.
(2) No combination of materials that forms an electrolytic-couple of such nature that, in the
presence of moisture, corrosion is accelerated shall be used.
i) Copper of the grade ordinarily required for commercial electrical work, generally designated as being of
98% conductivity when annealed.
ii) A copper alloy as resistant to corrosion as copper under similar condition.
iii) Aluminium conductors of electrical grade aluminium.
iv) Galvanized steel with cross~sectionalarea equivalent to that of copper.
t The principal parts of a lightning protection system are air termination, down conductors, joints and bonds, test
joints, earth termination, and earth electrode.
(1) Components shall be protected against corrosion; any part of a copper system that is
exposed to direct action or chimney gases or other similar cOlTosive gases shall be protected by
a co,ntinuous hot-dipped coating of lead.
(2) All components located within 610.0rnm of the chimney top shall be so protected.
(1) Any part of a lightning protection system that is subject to mechanical damage or
displacement shall be protected with a protective moulding or tubing.
(2) Metal pipe or tubing shall be bonded to the conduit at both ends of the tubing.
(3) Conductors shall be securely attached to objects upon which they are placed (see Figure 7.1
and Table 7.5).
(1) Aluminium systems shall be installed in accordance with other applicable clauses and subject
to the following conditions:
b) (i) Aluminium components shall not be used where they come into direct contract with
earth.
(ii) Fittings used for the connection of aluminium earthing equipment shall be of the
bimetallic type; such bimetallic connectors shall be installed not less than 460.0mm
above ground level.
Note:' Co'pper lightning-protection components shaH not lie insfalled directly on alumihium routing, siding or other
aiuminium surfaces,
P!m~"e!(l Area
CO!l'lPpnent.
fie
.d Compgnent
mm mm~
Airtermination!!; Fixe~ co""~iQl'\!l (Qond!l) In
~urpir\ium, c;opper 20 lC2.5 50·9 llI.umini\J!'fl, alurnlni\lm alloy, P\lpl?llr
1I11c1.
gl!lvan~{l~ ~1l81 AAd \IalV¥l~!ld st,~I;
!!trip. {lxterpaj ~~p ?Q x g,? 5().Q
exterl'\al rodll ll·Odi~ 5()·()
alu!TI!ni\lm, al\lmini\lm 8.0 dia. ~O.O Intllmal !l'\rip 2,0 ~ 1.? 3().()
alloy, copper, interp.l!l rods e.? dis, ~~.O
I1ho~phor, b.rc:mze~d
galvanized steel rods
P9Wl1C;qnd4ctOI"1l:
~\!mil1hJm, popper 50.()
!!'ld Qalvanized
steel strip
~Y!'fliF1i\lm,~l,Iminium
~19Y,pOPPllr I¥1d
Table 7.4 Minimum thicknesses of sheet metal used for roofing and forming Part of the
air termination net work
Material Aluminium
Zinc
LeadMinimum
nd0.7
2.0
Material
Minimum
thickness
0.4 thickness[mm]
0.5
0.3
Note: The figures in this table are based on contemporary building practice and will be satisfactory where the
roofs form part of the lightning protection system. However, damage by way of puncturing may occur with a direct
arc-connected strike.
Arrangement 750
500
1000
500
1000
Fixing centres [mm]
s ~
Note: This table does not apply to built-in type fixings which may require special consideration.
(2) Horizontal air terminations shall be made of solid conductor, strips or cables.
7.15.2 Conductors
(1) Conductors shall be in the form of multiple strand cables, single wires, rods, or flat strips.
(1) The component part of lightning protection system shall have dimensions not less than those
given in Tables 7.3 and 7.4.
7.16.1 General
(1) Ajr termination networks shall be provided for all parts of a structure that are likely to be
damaged by direct lightning Flashes.
Note: Air networks may consist of vertical or horizontal conductors or combination or both. Various forms of air
terminations are shown in Figures 7.7 through 7.15.
7.16.2 Support
-
(1) Vertical air terminals shall be secured against overturning either by attachment to the object
to be protected or by means of braces which shall be permanently and rigidly attached to the
building.
(1) All metallic projections on or above the main surface of the roof which are connected,
intentionally or fortuitously, to the general mass of the earth shall be bonded to and form part
of the air termination network (see Figures 7.4 and 7.5).
(1) Metallic coping, roof coverings, hand rails, window washing equipment and metallic screens
around play areas shall be considered for inclusion as part of the air termination network (see
Figures 7.4, 7.5 and 7.6).
(1) Air termination shall not be required for those parts of a structure located within a zone of
protection.
(2) If portions of a structure vary considerably in height, any necessary air termination or air
termination network for the lower portions shall be joineQ to the down conductors of the taller
portions in addition tJt> being joined to their own down conductor.
(1) One roof air termination 'shall be placed or. ridges of a roof and around the perimeter of the
roof.
(1) If the reinforcing bars are used as down conductors, the air termination shall be connected
to the reinforced bars in the number of positions required for down conductors.
7.17 DOWNCONDUCTOR
7.17.1 General
(1) A down conductor shall provide a low impedance path from air termination to earth
termination so that the lightning current can be safely conducted to earth.
Note: In addition to the various types of down conductors; i.e., strips, rods, reinforcing bars and structural steel
stanchions, etc any good conductor which may form part of the building structure can be included provided
that it is appropriately jointed to the air and earth terminations.
--- ----------
SECTION'?': EARTHING, BONDING AND liGHTENING PROTECTION
7.17.2 Routing
Down conductors shall follow the most direct path possible between air and earth termination
networks. The conductors shall be arranged as evenly as practicable around the outside walls
of .the structure (see Figure 7.1 7).
(I) At least two down conductors shall be provided on any kind of structure.
(1) Each down conductor located in a runway, school play ground, or other similar·location shall·
be guarded against mechanical damage or displacement.
(2) The down conductor shall be protected for a minimum distance of 1.8m above grade level.
(1) A down conductor entering cOITosive soil shall be protected against cOITosion for not less
. than 91S.0mm above grade level and for entire length below grade level.
(I) When the provision of suitable routes for down conductors is impossible, ego buildings of
cantilever construction from first floor upwards (see Figure 7.18), down conductors shall not
follow the outside contours of the buildings.
(2) In cases such as (1) above, down conductors may be housed in an air space provided by
non-metallic, non-combustible internal duct and taken straight down to ground.
Note: Any suitable covered recess not smaller than 76.0mm x 13.0mm or any suitable service duct running the full
height of the building may be used for this purpose provided it does not contain an unarmored or non-metal.
sheathed service cable.
(3) In case where an unrestricted duct is used, seals at each floor level may be required for fire
protection.
(4) Where p()ssible, access to the interior of the duct shall be available.
(1) Lift shafts shall not be used for fixing down conductor.
(1) When a large re-entrant loops [s~e Figure 7.18 (b)] cannot be avoided, the conductor shall
pass through holes as shown in Figure 7.18 (c).
(1) No bend of a conductor shall fonn an included angle of less than 90° or have a radius of
bend less than 203.0mm (see Figure 7.16).
(1) Any metal in or fonning part of the structure or any building services having metallic parts
by design or fortuitously and in contact with general mass of the earth shall be either isolated
from or bonded to the down conductor.
Note: Unless extra bonding is required, items already in metallic contact with the lightning protection system,
directly or indirectly, through permanent and reliable metal-to-metal joints do not require additional bonding
conductors.
7.17.11 Bonds
7.17.11.1 General
(1) Since bonds have to join a variety of metallic parts of different shapes and composition,
careful attention shall be given to .the metals involved; i.e, that of the bond and of the items
being bonded.
(1) A bond shall be mechanically and electrically effective and protected from corrosion and
erosion by the operating environment.
(1) External metal on or forming part of a structure shall be bonded to the lightning protection
system with a main-sized conductor.
(1) Internal metal bonds may be reduced in size; but shall not be smaller than 35.0mm2 copper
or its equivalent.
(1) In all buildings, at each fldor level, provision shall be mad~ for bonding futijre machinery
or equipment to the lightning protection system; i.e, by connection to metallic gas, water,
drainage or similar services.
7.17.11.6 Joints
a) be as few as possible;
b) be mechanically and electrically effective; .
c) be protected against corrosion or erosion from the elements of the environment; and
d) present an adequate contact area.
Note: Contact surface shall fIrst be cleaned and then inhibited from oxidation with a suitable non-corrosive
compound.
(2) With overlap joints, the o,rerlap shall not be less than 20.0mm for all types of conductors.
(1) Earth down conductor shall be provided with a test joint in such a position that, whilst not
inviting unauthorized interference, it is convenient for test (see Figure 7.25 for typical test
joints),
Note: Plates indicating the position, number and type of earth electrodes should be fItted above each test point.
1.18 EARmTERMlNATION
1.18.1 Termination
(l) Each earth electrode shall have a resistance (in ohm) not. exc~ding the product given by 10
times ti.N number
. Qf earth eleotrodes to be provided
. .
(2) The whole of the earth termination network shall have a combined resistance to earthn<;>t
exceeding 1Q ohm without taking account of any bonding to other services.
7.18.3.1 General
(l)Earth eleotrodes shall oonsist of metal rods~ tubes Of strips or a combinatiol.l of these Or
natural earths such as piles and foundatiol.ls (see Figure 7.20).
(2) Clamps shall be secured with at least two bolts or screw caps and shall make Contact with
the earth rod for at least 380.0mm.
(1) The point of connectiol.l of the earth termination network shall be removable and easily
accessible fr"Om above~earth to facilitate inspectiol.l, testing and maintenance of the Ughtnil.lg
protection system.
(1) 'Earthing rod ,shall extend vertically not less than 3J)m into theeatth.
(2) The ground shall be compacted and m:ade tight against the full leltgth of thecond:uctrrr or
earth rod (see Figure 7.19).
to In sand or gravel, two or more 'earth rods at not less than 3.0m :spacings 'shall be driven
vertically to a minimum depth of 3.0m below grade (see Figure 7.21).
(1) if bedrock is neat the surface, the conductor shan be laid in trenclres extending away from
the building at each down conductor.
(3) If these methods should prove impracticablej the lightning ptoteetloncahlemay be :laid
directly on the bedrock with a m1nimumdistance of 610J)mm from the fomid-ation 'C)r'exterior
footing and termin'iltehy a:ttachrn:ent to a buried copper earth platea't ltlast O.:8mmthic'kand
having amlnimufil surface area of 'O.18m2 •
(I) If soil is less than O.3m in depth, down conductors shall beconhected to a 1000p conductot
installed in a trench or in rock :ctevlces around thestrucmre.
(2) '(1) The 100p conductor shall not be less than the equivalent of :amainsize lightning
conductor.
{ii) Optional earth plates may be attached to the loop conductor to enhance its earth
contact, where the measured earthing resistance is found to be high to provide
effective earthing (see Figure 7.22).
(1) When earth terminations in built-up areas pass through a tanked structure, a seal similar to
that shown in Figure 7.23 shall be used.
7.18.4.6 Corrosion
(1) Because of the harmful corrosion which is likely to result, coke breeze shall not be allowed
to be in contact with copper electrodes and salting of the ground in the vicinity of any earth
electrode is not recommended.
(1) All earthing mediums in or on a structure shall be interconnected to provide a common earth
potential.
(2) The Provision in (1) above shall include lightning protection, electric service, telephone and
antenna system earths as well as underground metallic piping systems; main size lightning
conductors shall be used for interconnecting these earthing systems to the lightning protection
system.
(1) If electric, teiephone, or other systems are earthed to a common earthing terminal (see
Figure 7.24), one connection from the lightning protection system to the terminal is required.
(2) If the service systems are earthed to a metallic WlJ,terpipe; only one connection to the
lightning system is required provided that the water pipe is electrically continuous qetween all
systems.
(3) If the water pipe in (2) above is not continuous, the non-conductive sections shall be bridged
withmain size conductors, or the connection shall be made at a point where electrical continuity
is assured.
7.20.1 General
(1) Detail on how to use concrete reinforcing bars shall be worked out at the design stage before
building construction begins (see Clause B.6, Annex B).
a) Good contact between reinforcing bars should be ensured; i.e, by fixing bars with tying
WIres.
b) Ties shall be provided for both vertical to vertical and horizontal to vertical bars.
(1) Lightning protection conductors shall not be connected to prestressed concrete columns,
beams or braces where the wires or strands are_ not linked and, therefore, not electrically
continuous.
(1) In the case of precast reinforced concrete columns, beams or braces, the reinforcement may
be used as a conductor if the individual elements of reinforcement are bonded together and
electrical continuity is ensured.
7~21.1 Gene..,.1
(I) Air termination shall be bonded directly lothe steel framework or by conductors leading
through the ridges, roof, or coping walls, or connected together with a conductor on the exterior
of the building that is bonded to the steel framework.
(2) If <such a conductor in (1) above is employed, it shall be bonded to the framework ~t
intervals not more than 3.0m.
7.21.3 Connection
{l) COMe-ctio-n shall be made on cleaned areas ofthe steel work by use of bonding plates with
pressure 'cable connectors ,lravingasurface 'contact ;areaof not le-ssthan 5200J~mm~; ~ol.ted,
welded, or brazed securely to the steel S0as to maintainelectricalcontinulty.
7·.21.4 Earth'ing
(1) £afthing connections :shall be made ,at approximately 'every other 'sreel column around the
:perimeter and shaU not average more than n.Oma;part.
(2) The earthing conductor shall be connected to steel columns using bonding plates (s'ee 7 :21.3).
(3) The bonding plate shan be bolted or welded securely to a cleaned 'area of the column .at the
lowest 'available point (see Figure 7.26).
7.21.5 Interconnection
'-....
(l) Metal bodies that are required to be bonded need not be'separately bonded if they are
electrically continuous with the lightning protection system through the steel framework.
Ie)
(d)
(QI
Note: i) Lightning conductor fixings should be purpose-made for each size of strip; dimension a in Figure (e)
should be equal to the thickness of the strip and should be equal to the width plus 1.3mm a for
expansion. Conductors of circular section should he similarly· treated.
ii) All fixings should be securely attached to the structure; mortar joints should not be used.
HC
(
\
/ --/\/ I
--- GL~///////////// / /' ../'"II I.\ I
I \ I
He
.•..•.•.••
/
ZP
\ GL
0\
/'".•.........
lbl Horllonttl tlr t.rmlnttlon
Ilvtl
tt ground
" --- prottctlon •.•.•....••
PI.n vl.w
01 lont 01
/ ,.- - .......•••.•...
-"'"
'"
/ ZP ZP \
{ vC vC \
1"11" view \ o 0 J
protection
.t ground
01 Ion. 01 .
,...,
> <
{ o
ve
o
ve
,
\ /
--
Icl Four vortlcol conductors showing protlctlVl .ngl ••
.nd •• socltted Ion •• 01 protection.
~-
\ ZP ZP /
"-.. . ../".... ./
Figure 7.2 Protective angles and zones of protection for various forms of air termination·
2 Rod holdliitl
€==
.CEP~:
'Q
u
13
4 D_n conductor
a Horlzontl' conductor
a Tilt lolnt
-$-
7 Elnh Ilectrodl
6Ql Ib6.
6
• EII'th tod 'A' cllmp
7
9 Rod hOUllnl
III Chimney. '"II thin 1.5 m dlomettr
It top.ond 20 m hil"
10 Cond"ctor clip
11 cOronll bind
12 Bond to CI" 'ron cap II
.'tornatl •• to coronll bind 1111.
(bl 60 m bricl(ltlck 13 Junction cllmp
Note This figure, does not apply to reinforced concrete chimneys where the reinforcing bars can be used as down
conductors
Reinforced
concrete structure,
PVC coping with
Bond to metal conducting roof
suspended ceiling
Detail
showing
item 4
Key 1 Handrail bond
2 Reinforcing bond
3 Coping bond
4· Non-ferrous bonding point (built-in)
Figure 7.5 Examples of air terminations and down conductors using handrails, metal copings and
reinforcingbars.
Beam
Note: Minimum dimensions when a metallic roof covering is used as part of the air termination network are as
follows:
Figure 7.6 Air termination for flat roof sbowing connection to standing seamjoint when
a metallic roof is used as part of tbe air termination network
HC ,
/:s:j
Ie) Elevation .howing protective .ngle
l~",
'"
"
HC \
I II
I ,
HC
. II I
HC
'Oml mall.l
L 20m /
He
/
___ ZP_ --_/
Ib) Plan .howlng zone of protection at ground level
Note: i) If S> 10+ 2H, additional longitudinal conductors are required so that the distance between conduc~rs
does not exceed lO:Om.
ii) If the length of the roof exceeds 20.0m, additional transverse conductors are required.
iii) Down conductors are omitted for clarity.
Figure 7.8 Air terminations for large areas of roof various profiles
16 m
DeL
(1) (2) (3)
Note: The protective angle provided by the ridge conductor in each case is as follows:
(i) protective angle up to 45° : ridge conductor is sufficient with connection to metallic gutters; number of
down conductors=72/20=3.6 (say4).
(ii) protective angle over 45~: air termination mesh (maximum IO.Om x (IO+2H)); ridge and eaves
conductors provide approximate roof mesh 6.0m x lQ.Om;number of down conductors=40/20=2.
(iii) situation as for (ii) but metallic gutters used in lieu of eaves conductor; number of down conductors
=64/20=3.2 (say4).
Vertical air
terminatinn
Conductor 'or
strip rOd or
metallic gulter
Rfdge conductor
D.t.1I
fixed below tile
-'e~el (see detail)
Figure 7.9 Air terminations and concealed conductors for buildings less 20.0m high with
stopping roofs
, "-
'.....-
,.. ,,- ,,-
View from B
/I -. -#---r
Il-oc
II DC
A
112
.. 6m .1
12 m
I
[J
fa Dc"1
t [J I Hell II
Perimeter ••24 + 24 + 12 + 12 •• 72 m •
Number of down conducton rel.1\Iired
72/20 ••4.
Note: i) An.air tennination along the outer perimeter of the roof is required and no part should be more than
5.0m from the nearest horizontal conductor, except that an additional 1.0m may be allowed for each
metre by which the part to be protected is below the nearest conductor.
ii) Horizontal conductors are not necessary on the parapets of the light well; a zone of protection of 60· is
provided by the two adjacent horizontal conductors for structures less than 20.0m high. This principle
does not apply to taller structures.
ii) Where PVC covered horizontal air tennination conductors are used, bare vertical rods O.3m high should
be fixed at each intersection and at intennediate positions along the horizontal conductors spaced no
more than 10 apart.
Figure 7.11 Air terminations and down conductors for flat roof buildings where the air
termination conductors have a PVC oversheath
Note: The air tennination network for a tan reinforced concrete or steel framed structure should be as fonows:
(a) Horizontal conductors on roofs from a IO.Om x 20.0m network.
(b) There are bonds to steelwork at corners, at 20.0m intervals around the periphery and on the tower O.5m
above the lower roof level.
(c) Key bonding to the building steelwork.
Roof conductor
*
represents a bond to roof steelwork.
Note: i) The horizontal conductor mesh size should be 5.0m x 1O.Om or smaller, according to the risk.
ii) For clarity, down conductors are omitted.
Figure 7.13 Air termination network with horizontal conductors for structure with
explosive or highlYJlammable contents
Sm
,
9,I, ,I
,I!
.9
9t
Ii, ,
I9
,I, I
I' -.
Koy
Note: i) The air termination network should have a 1O.Oll} x 20.0m mesh. For structures below 20.0m hight, there
should be down conductors every 20.0m of periphery and for structures over 20.0m high, every 10.0m
of periphery; horizontal conductors should be every 20.0m from the top.
ii) Metal roofs may be suitable as air terminations (see Table 7.5 and Figure 7.17).
iii) On shingle spires, metallic soakers and gullies should be bonded at the top and bottom.
~Earth electrode~
lat Elevation
Protect.ed building
(b} Plan
Kay
:'\\
'II- \
Protected
building \
\
\
(el End .I ••.• llon showing zones 01 prote<:tlon
Note: i) Where two or more suspended horizontal conductors are employed, a protective angle of 45° may be
used in the space bounded by the conductors. Elsewhere, the protective angle is limited to 30°.
ii) To prevent flashover between mast/conductor and protected building, the minimum clearance distance
has to be 2.0m or as under above governed by whichever is the greater. This clearance has to be as
above under maximum sag conditions
Figure 7.15 Air termination with twin suspended horizontal conductors & zone of
protection for structure with explosive or highly flammable contents
R •• RilclillS of bolnd.
8 inchus (203 mOll minimlim.
•• •
•• • ••
i
L
-----. .••
• Itl·
• ,I.• • N
•
•
:LJ=
1.1 11/
••
•• •
ldl
t T3
Note: i) The down conductors may be natural part of the building framework or added strips or rods on external
faces.
ii) On structures exceeding 20.0m in height, down conductors should be spaced at not more than 1O.Om
apart.
Figure 7.17 Pattern of down conductors for various forms of tall building
l ~
SECTION 7: EARTHING, BONDING AND LIGHTENING PROTECTION
ad maximum Exceeding ad
, d" i
"~
I
(a Permissible arrangement (bl Arrangamant that is not permissible
permissible
Not --tII ~Permisslble
I
t
I
lcl Permissible melhod of taking conductor ldl Routlli for, down conductor" in a building
through a pllrapat wall with cantilevlIrtld uppllr lIoon
A= o.6~m mini~um
t
B= 3.0P m mini~Um
.
Figure 7.19 Earthtng in ~oiBt
Clay ·~oil.
Down conductors
lin these caSes
steel rei,. forc ing
or steel frame
of building I
'I
11l
"
Fig ••.• 7.20 Ligbtning protedio. system ror tall b.ildings (over 20.0m bigb) sbowing air termi.atinns. down cond.cto •.••bonds to projectinns above roor
ELECTRICAL INSTALLATION OF BUILDINGS
ternate configuration
A =10.610 mminimum
a = 13.00 m minimum
,/ ,/
--<-
'",,-
Earth
'''-
plate .
Loop conductor
..
~ 0'
. 0
•
, .0 o ",
."
" 0
. 0:. b
Concrete 0,,' o
, '
o . 0 • ,
.. ..
,~' , , .
• D ,0
. ,
b • " ,P ,
,~
.'0
,0
1ft}!..-~/;~,??-.~/.;?·:~~~,~:';:~:i'·"
. ~'.'" ,4 "-' :*:1.'
" ., 1I ': 0111 0: ,' 0, .'
Asphalt
Asphalt /"
Concrete
.0 ?, 'n
. 6' :. <:>
.'"
Figure 7.23 Example of an earth electrode seal for use within a tanked structure
~
SECTION 7: 'EARTHING, BONDING AND LIGHTENING PROTECTION
I,
ExterMl down
conductor..-..-
For Test
cavityJolallS
nt~
Lightning protection
earth termination netv~ " "
Electr~city cable ,,.
Water , ...-, t k I \0" ( •••• ' \ ... 11,.0: ,
,, ,,.
l' J',.,'"
.'
..i- ,,~..,.....
,,,.., . ,.. I \~
SYSTEM DESIGN
GENERAL CONSIDERATIONS
The structure or, if it has not been built, the drawings and specifications should be examined
taking into account the recommendations of this Section.
Modern buildings use metal extensively in their structure and there is considerable benefit in
utilizing such metal parts to maximize the number of parallel con~ucting paths. Often the
lightning protection will be improved, worthwhile cost savings may result and the aesthetic
appearance of the structure preserved. However, it should be borne in mind that a lightning
strike to such a metal part, especially if it is beneath the surface, may damage the covering and
cause masonry to fall. This'risk can be reduced, but not eliminated, by a surface-mounted
lightning protection system.
Examples of metal parts which should be incorporated into lightning protection systems are steel
frames, concrete reinforcing bars, metal in or on a roof, window rails and handrails. Some metal
within a structure may be used as a component of the lightning protection system; for example, .
sheet piling being in contact with the general mass of earth, may be used as an earth electrode
and is unlikely to be improved upon by the addition of rods or tapes.
The whole structure should be provided with a fully interconnected lightening protection system;
i.e., no part of the structure should be protected in isolation.
B.t GENERAL
Consultation should take place between the designer of the lightning protection s'ystem and the
interested parties indicated in Clauses B.2 through B.6 before and during all stages of design.
b) General areas available for earth tennination networks and reference earth electrodes.
d) Extent of the work and the division of responsibility for primary fixings to the
structure, especially those affecting the water-tightness of the fabric, chiefly roofing.
e) Materials(s) to be used in the structure, especially for any continuous metal, e.g.
stanchions or reinforcing.
g) Details of all metallic service pipes, rain-water system, rails and the like entering or
leaving the structure or with the structure which may require bonding to the lightning
protection system.
h) Extent of any buried services which could affect the siting of the earth tennination
network(s).
i) Details of any equipment, apparatus, plant or the like to be installed within or near
the building and which require bonding to the lightning protection system.
Agreement should be reached on the bonding of services to the lightning protection system.
Because of the introduction of new materials and practices, reliance should not be placed on
agreements reached for other structures.
b) routes and materials(s) for construction of ducts and sealing at floors if internal
conductor are being considered;
Agreement should be reached on the need to bond antenna supports and screens of cables to the
lightning protection system.
B.6 BUILDER
a) the form, positions and numbers of primary fixings to be provided by the builder;
d) whether any components of the lightning protection system are to be used during the
construction phase, e.g. the permanent earth termination network could be used for
earthing cranes, railway line, scaffolding, hoists and the like during construction;
e) for steel framed structures, the numbers and positions of stanchions and the form of
fixing to be made for the connection of earth terminations;
f) whether metallic roof covering, where used, are suitable as part of the lightning
protection system and the method of attachment of conductor to earth;
g) the nature and location of services entering the structure above and below ground
including railway lines, crane rails, wire ropeways, conveyor systems, television and
radio antennas and their metal supports, metal flues, and flue-liners;
h) the position and number of flag-masts, roof level plant rooms (i.e., lift motor rooms,
ventilating, tanks and other salient features;
i) the construction to be employed for roofs and walls in order to determine appropriate
methods of fixing conductor, specifically with a view to maintaining the
weather-tightness of the structure;
Note: The same general consideration applies to the reference earth electrode for use in initial and
periodic testing.
k) the provision of holes through the structures, parapets, cornices, etc to allow for the
free passage of the down conductor;
I) the provision of bonding connections to a sted frame, reinforcement bars and other
metal;
m) the most suitable choice of metal for the conductor taking account of corrosion,
especially at bimetallic contacts;
0) the preparation of a drawing incorporating the above details and showing the positions
of all conductors and of the main components.
8.1 SCOPE
(1) This Section applies to all wiring installation operating at 0.6/1.0kV or less except for:
(1) The following references contain provisions which, through reference in .this text, constitute
provisions of the Ethiopian Building Code Standard on Electrical Installation of Buildings.
(a) C22.1:1992 Canadian Electrical Code Part I, Safety Standard for Electrical
Installation, Sixteenth Edition
(b) BS 767:1992 The electricians Guide to the 16th Edition of the lEE Wiring
Regulations, Second Edition, 1993
(2) The Provisions in (1) above notwithstanding, the use of another method is not precluded
provided that compliance with this Code is maintained
(4) Non-sheathed cables for fixed wiring shall be enclosed in conduits, ducting or trunking;
however, this provision does not apply to a protective conductor.
(1) No electrical equipment, unless specifically approved for the purpose, shall be installed in
ducts used to transport dust, loose stock, or flammable vapours.
(2) No electrical equipment, unless specifically approved for the purpose, shall be installed in
any duct used for vapour removal or for ventilation of commercial-type cooking equipment.
(1) Direct buried conductors, cables, or raceways shall be installed to meet the minimum c?ver
requirements shown in Table 8.1.
Minimum cover means the distance between the top surface of the conductor, cable, or raceway and the finished
grade.
(2) The minimum cover requirements shall be permitted to be reduced by IS0.0mm where
mechanical protection is placed in the trench over the underground installation.
(3) Mechanical protection shall consist of one of the following and, when in flat form, shall
be wide enough to extend at least SO.Omm beyond the conductor, cables, or raceways on each
side:
(4) Raceways or cables, if located in rock, may be installed at a shallower depth entrenched into
the rock in a trench not less than IS0.0mm deep and grouted with concrete to the level of the
rock surface.
(5) Raceways may be installed directly beneath a concrete slab at grade level provided the
concrete slab is not less than a nominal 1OO.Ommin thickness, the location is adequately marked,
and the raceway will not be subject to damage during or after installations.
(6) Any form of mechanical protection which may adversely affect the conductors or cable
assemblies shall not be used.
(7) Backfill containing large rock, paving materials, cinders, large or sharply angular substances,
or corrosive material shall not be placed in an excavation where such materials may damage
cables, raceways, or other substructures prevent adequate compaction of fill, or contribute to
corrosion of cables, raceways, or other substructures.
(1) Where conductors other than those used to fumish energy to the lift or dumbwaiter are
installed in hoistways, they shall be from mineral-insulated cable or armoured cables or be run
in rigid or flexible metal conduit or electrical metallic tubing.
(2) The cable, conduit, or tubing referred to in (1) above shall be:
(b) arranged so that terminal-outlets or junction boxes open outside the hoistway except that
pull boxes may be installed in long runs for the purpose of supporting or pulling in
conductors.
(3) (a) Main feeders for supplying power to elevators and dumbwaiters shall be installed outside
the hoistway.
(b) Only such electric wiring, raceways, and cables used directly in connection with the
elevator or dumbwaiter, including wiring for signals, for communication with the car,
for lighting, heating, air conditioning and ventilating the car, shall be permitted inside
the hoistway.
8.4 CONDUCTORS
(1) Conductors installed in any location shall be suitable for the condition of use as indicated
in Annex B of Section 4 for the particular location involved and with particul.ar respect ..to the
follwing
(a) moisture
(b) corrosive action
(c) temperature
(d) degree of inclosure
(e) mechanical protection.
(1) The minimum internal radii of bends in conductors shall be as indicated in Table 8.2
Table 8.2 Minimum internal radii of bends in cables for fixed wiring
Mineral-insulated cables may be bent at a minimum radius of three times the cable diameter provided that they
will only be bent once.
Note: i) The factor shown in the table is that by which the overall cable diameter must be multiplied to give the
minimum inside' radius of the bend.
ii) The figutes in brackets apply to unsheathed single-core stranded pye cables when.installed in conduit,
trunking or ducting.
(1) Unless made with solderless wire connectors, joints or splices in insulated conductors shall
be soldered, but they shall first be made mechanically secured.
'.
(2) Joints or splices shall be covered with an insulation equivalent to that on the conductors
being joined.
(4) Splices in underground runs of cable, if required due to damage to the original installation,
may be made:
(a) in junction boxeswhich are located at least l.Om above grade and secured to buildings
or to stub poles and suitably protected from mechanical damage;
(b) notwithstanding the requirements in (3) above, by means of splicing devices or materials
(kits) acceptable for direct earth burial.
,
I
(1) Conductors shall be supported so that no injurious strain is imposed on the terminals of any
electrical apparatus or devices or on joints or taps. Table 8.3 shows guidance on methods of
support.
Horizontal
Vertical
Vertical
550
1500
450
800
400
900
600
2000
121)0
I
1- 250
400
350
300
MBximum sp,cing of clips [mm]
Horizontal
I: Min",f.insul,tBd c,bllS I ShllthBd c,bllS
~
Note: For the spacing of supports for cables of overall diameter exceeding 40.0mm. and for single-core cables
having conductors of cross-sectional area 300.0mm2 and larger, the manufacturer's recommendations
should be observed. '.
.(L) Sheathed cables clipped direct to or lying on non-metallic surface shall be installed in
accordance with Installation Method 1 (see Annex A).
(1) Spacing between conductors and adjacent surfaces shall be as indicated in Installation
Methods 12 and 13 (see Annex A).
(2) In all locations, a separation of at least 25.0mm shall be maintained between conductors and
adjacent metal piping or conducting materials.
(2) Conductors supported on solid knobs shall be securely tied thereto by tie wires having
insulation of the same type as that on the conductors which they secure.
(1) Sheathed and / or armoured cables installed in accessible positions and supported by clips
shall not exceed the appropriate spacing value stated in Table 8.3.
(I) Where conductors are supported on or in close proximity to the exterior surfaces of
buildings, they shall be installed and protected so that they shall not be hazardous to persons or
be exposed to mechani<;:al injury and they shall not, without special permission, be located at a
height less than 4.5m from the ground.
(1) Conductors which pass over roofs shall be located or guarded so that they cannot be reached
by a person standing on a fire escape, flat rooI, or other portion of a building.
(2) Such conductors in (1) above shall at least be 2.5m above the highest point of a flat roof or
a roof that can be readily walked upon and at least 1.0m above peaked roofs or the highest point
of such roofs that can be readily walked upon; however, by special permission, they may be
located less than 2.5m, but not less than 2.0m, .above the highest point of a flat roof or roofs so
that the latter can be readily walked upon.
(1) The conductors of a power supply system attached to the exterior surfaces of buildings shall
be at least 300.0mm from the conductors of a ~ommunication system unless one system is in
conduit or is permanently separated from other systems.
,,
"
.~
~ .
(1) Bare conductors shall not be used as main risers or feeders in buildings unless, special
permission is obtained.
Note: i) Where flat bus bars 6.25mm or less in thickness are used, the continuous current rating shall not
exceed 1.6A/mm2 of cross-sectional area of copper bus bar or 1.12A/mm2 in the case of aluminium
bus bars.
ii) Bus bar supports shall be spaced not more than 750.0mm apart, with minimum clearance across
insulating surface between bars of opposites polarity of not less than 50.0mm, and 25.0mm between
bus bars and any earthed surface.
(1) There shall be no more than 12 outlets on any 2-wire branch circuit except as permitted by
other Sections of this Code.
(2) Such outlets in (1) above shall be considered to be rated at not less than 1.0A per outlet
except as permitted by (3) below.
(3) Where the connected load is known, the number of outlets may exceed 12 provided the load
current does not exceed 80% of the rating of the overcurrent device protecting the circuit.
(1) A box or an equivalent device shall be installed at every point of outlet, switch or junction
of conduit and at every point of outlet and switch of concealed kllob-and-tube work.
(2) Nonmetallic outlet boxes shall not be used in wiring methods using metal raceways,
armoured or metal sheathed cable, except where the boxes are provided with bonding connection
between all conductor entry openings.
(4) At least 150.0mm of free conductor shall be left at each outlet for making of joints 'or
connection of fixtures unless the conductors are intended to loop through lamp holders, socket
outlets, or similar devices without joints.
(5) Ceiling outlet boxes in concrete slab construction shall have knockouts spaced above the free
or lower edge of the boxes a distance of at least twice the diameter of the steel reinforcing bars
so that conduit entering the knockouts shall clear the bars without offsetting.
(6) Boxes and fittings shall be firmly secured to studs, joists or similar fixed structural units.
(1) Boxes shall be of sufficient size to provide usable space for all insulated conductors
contained in the box.
(2) Conductors which are connected to different power or distribution transformers or other
different sources of voltage shall not be installed in the same box, cabinet or fitting.
(1) Where conductors are run from the ends of conduit, armoured cable surface raceways or non
metallic sheathed cable to appliances or open wiring installation, an outlet fitting or terminal
fitting may be used instead of the box required in Clause 8.8.2, and the conductors shall be run
without splice, tap or joint within the fitting.
(2) The fittings in (1) above shall have a separately bushed hole for each conductor.
(3) The fittings in (1) above shall not be used at outlets for fixtures.
(1) Every cable operating at low voltage shaH be selected in accordance with Section 4 of this
Code.
(2) The method of installation of cables and conductors shall be subject to the provision of
Clause 8.3.1.
Note: i) The methods of installation distinguished by bold type are reference methods for which the current-
carrying capacity given in Annex B, Tables B.I through B.45, Section 4, have been determined.
ii) For the other methods, an indication is given of the appropriate reference method having values of
current-carrying capacity which can safely be applied.
Installation 2 3
for 4determining
method Appropriate current-carrying
Reference Method capacity
s
Sheathed
on a non-metallic
cables clipped
surface'.direct to or lying : ~
Cables embedded direct in building materials:
11~ J~ Method 1
tThe wall is assumed to consist of an outer weatherproof skin, thermal insulation and an inner skin of a plaster board
or a wood-like material having a thermal conductance not less than IOw/m2K. The conduit is fixed so as to be close
to, but not necessarily touching, the inner skin. Heat from the cables is assumed to escape through the inner skin
only.
p
plaster or the like (other than
thermally insulating materials)
..
In trunking:
On trays:
11 Sheathed cables on a perforated
cable tray, bunched and
unenclosed. A perforated cable Method 11
tray is considered as a tray in
which the holes occupy at least
30% of the surface area
-----------
Cables in building voids:
Cable In trenches:
9.1 SCOPE
(1) This Section covers the protection and control of electrical circuits and apparatus installed
in accordance with the requirements of this Code.
(I) The following references contain provisions which, through reference in this text, constitute
provisions of the Ethiopian Building Code Standard on Electrical Installation of Buildings.
(a) C22.1:1992 Canadian Electrical Code Part I, Safety Standard for Electrical
Installation, Sixteenth Edition.
(1) Every electrical apparatus and unearthed conductors shall be protected by one or more
devices as may be necessary for automatic and/or manual interruption of the supply in the event
of any fault and shall be provided with:
(a) protection against fault current to break any fault current in a circuit before such current
causes danger due to thermal or mechanical effects produced in those conductors or the
associated connection;
(b) protection against overload current to break any such current flowing in the circuit
conductors before such a current causes a temperature rise detrimental to insulation,
joints, termination or the surroundings of the conductors;
(c) protection against under-voltage which when necessary will open the circuit, where a
reduction in voltage, or loss and subsequent restoration of voltage could cause danger;
(d) manually-operable control device which will safely disconnect all unearthed conductors
of the circuit at the point of supply simultaneously; and
(e) protection against earth fault in accordance with Clause 9.4.2.
(1) Circuit breakers, fuses, and switches shall be of type and ratings acceptable to the department
in charge of inspection.
(2) Overcurrent protective devices shall ensure safe operation and shall have interrupting
capacity sufficient for the voltage employed and for the anticipated fault current which mllst be
interrupted.
(1) Each unearthed conductor shall be protected by an overcurrent device at the point w.?ere it
receives its supply of current and at each point where the size of conductor is decreased, except
that such protection may be omitted where:
(a) the overcurrent device in a larger conductor properly protects the smaller conductor;
(b) the smaller conductor is not over 3.0m long and does not extend beyond the switchboard,
panel board, control device which it supplies; or
(c) the smaller conductor has an ampacity not less than one-third that of the larger conductor
from which it is supplied.
(2) The rating or setting of overcurrent devices shall not exceed the allowable ampacity of the
conductors which they protect except:
(a) where a fuse or circuit breaker having a rating or setting of the same value as the
ampacity of the conductor is not available, the ratings or settings given in Table 9.1 may
be used;
(b) in case of equipment wire, flexible cord, and tinsel cord, which will be considered as
being protected by 16.0A overcurrent devices; or
(c) as provided for by other Clauses of this Code.
(3) Overcurrent devices shall be enclosed in cutout boxes or cabinets unless they form a part of
an approved assembly which affords equivalent protection, or unless mounted on switchboards,
paneboards, or controllers located in room or enclosures free from easily ignitible material and
dampness, and accessible only to authorized persons.
(4) Overcurrent devices shall not be connected in parallel in circuits of 1000.OV or less unless
otherwise they are factory-assembled in parallel as a single unit.
(1) Earth-fault protection shall be provided to de-energize all normally earthed conductors of a
faulted circuit in the event of an earth fault in those conductors as follows:
(a) in solidly earthed circuits rated more than 230.0V-to-earth, less than 1000.OV phase-to-
phase and 1000.OA or more; and
(b) in solidly earthed circuits rated 230.0V-to-earth or less and 2000.0A or more.
(2) The maximum setting of the earth-fault protection shall be l200.0A and the maximum time
-
delay shall be 1.Os for earth fault currents equal to or greater than ~3000.0A.
(3) The ampere rating of the circuits referred to in (1) above shall be considered to be:
(a) the rating of the largest fuse that Can be installed in a fusible disconnecting device;
(b) the highest trip setting for which the actual overcurrent device installed in a circuit
breaker is rated or can be adjusted; or
,)c) the ampacity of the main. conductor feeding the devices in cases where no main
disconnecting device is provided. '
J..
ELECTRICAL INSTALLATION OF BUILDINGS
9.5 FUSES
(1) Only fuses and fuse holders of proper rating shall be used, and no bridging or short
circuiting of either component shall be permitted.
(2) Where plug fuses are used in branch circuits, they shall be of such a type and so installed
that they are non-interchangeable with a fuse of larger rating.
(3) A fuse having a fuse link which is likely to ·be removed or replaced while the supply is
connected shall be of a type such that it can be removed or replaced without danger.
(2) Indication shall be provided at the circuit breaker and at the point of operation to show
whether the circuit breaker is open or closed.
(3) Circuit breakers shall open the circuit in all unearthed conductors by the manual operation
of a single handle and by the action of overcurrent.
(4) Circuit breakers shall be of such design that any alteration by the user of either the tripping
current or the time will be difficult.
(5) 'circuit breakers shall be equipped with tripping elements as specified in Table 9.2.
(1) Control devices shall have'ratings suitable for the connected load of the circuits which they
control and, with the exception of isolating switches, shall be capable of safely establishing and
interrupting such loads.
(2) Control devices used in combination with overcurrent devices or overload devices for the
control of circuits or apparatus shall be connected so that the overcurrent or overload devices
will be dead when the control device is in the open position, except where this is impracticable.
(3) Control devices, with the exception of isolating switches, shall be readily accessible.
(4) Control devices, unless located or guarded so as to render them inaccessible to unauthorized
persons and to prevent fire hazards, shall have all current-carrying parts in enclosures of metal
or other fire-resisting material.
(5) Where electrical equipment is supplied by two or more different transformers or other
sources of voltage, then:
(a) a single disconnecting mean~, which will effectively isolate all unearthed conductor
supplying the equipment, shall be provided integral with or adjacent to the equipment;
or
(b) each supply circuit shall be provided with a disconnecting means integral with or
adjacent to the equipment, and the disconnecting means shall be grouped together.
9.8 SWITCHES
(1) Single-throw knife switches shall be mounted with their bases in a vertical plane so that
gravitational force will not tend to close them.
(2) (a) Double-throw knife switches may be mounted so that the throw will be either vertical
or horizontal.
(b) If the throw in (1) above is vertical, a positive locking device or stop shall be provided
to ensure that the blades remain in the open position when so set unless it is not intended
that the switch be left in the open position.
(3) Manual single-throw switches, circuit breakers, or magnetic switches, shall be connected so
that the bases or moving contacts will be dead when the device is in the open position except
when other conditions make this requirement unnecessary. '
(2) Portable appliances need not be equipped with additional control devices where the
appliances are:
(3) Where switches are used to control an outlet or outlets from more than one point, the
switches shall be wired and connected so that the earthed conductor runs directly to the outlet
or outlets controlled by the switches.
(4) Except for panel boards where more than 90% of the overcurrent devices supply feeders or
motor branch circuits, every panel board shall be protected on the supply side by overcurrent
devices having a rating not greater than that of the panel board.
(5) Transfer equipment for standby power systems shall prevent the inadvertent interconnection
of normal and standby sources of supply in any operation of the transfer equipment.
Ampacity of 63
80
40
100
16
20125
350
400
450
32
400
600
25
32
50
100
200
110
150
175
225
250
300
500
600
200
16
50
2
40
63
100
150
175
250
500
Circuit 0breaker
Rating or setting permitted
Fuse [A]
in
oneany
one ininconductor
each except
each phase,
phase toa neutral
not For neutral
conductor
circuit or
be 2-wire
3-wire,
5-wire,
4-wire,
System 2
a.c. earthedtt
32-phase
conductor
earthed
or
1-phase
3-phase
devices
4--wire,2-phase
protection Kind
d.c.,
a.c.
t2-phase
1-phase
cqpnected
3-phaseconductor
a.c.,
a.c.
such
a.c., of
unearthed
or motor
unearthed
d.c.
d.c.,
with
a.c.
in
or
as any
trip or
with
d.c.
earthed
unearthed or
withwith Number
oneForormotor
earthed
neutral
coils neutral
conductor
relays, and location of overload
overload protection
1
2-trip coils, one in each outside
arthed 4-trip coils, one in each unearthed
t This will not preclude the use of other arangements which will provide equivalent protection.
tt This will not prevent the use of one single-pole circuit breaker in each conductor for the protection. of an unearthed 2-wire circuit.
SECTION 10
CLASS 1 AND CLASS 2 CIRCUITS
10.1 SCOPE
(1) This Section covers remote-control, signalling and power-limited circuits that are not integral
parts of a device or an appliance.
(2) This Section does not apply to communication circuits that are dealt with in Section 23.
Note: The circuits described in this Section are characterized by usage and power limitation which differentiate
them from electric light and power circuits and, therefore, alternative requirements to'those of other relevant
Sections of this Code with regard to minimum wire sizes, de-rating factors, overcurient protection, insulation
requirements, wiring method, and material are deemed necessary.
(1) The following references contain provisions which, through reference in this text, constitute
provisions of the Ethiopian Building Code Standard on Electrical Installation of Buildings.
(a) NFP A70/NEC: 1986 National Fire Protection Association! American National Electrical
Code, 1987 Edition.
(b) C22.I:1992 Canadian Electrical Code Part I,Safety Standard for Electrical
Installations, Sixteenth Edition.
10.3 CLASSIFICATION
10.3.1 General
{i) CirCUItscovered by this Section are those portion of the wiring system between the load side
of the overcurrent device or the power-limited supply and all connected equipment, and shall be
Class 1 or Class 2 as defmed below:
(a) Class 1 - Circuits which are supplied from sources having limitation in accordance
with Clause 10.4.1.
(b) Class 2 - Circuits which are supplied from sources having limitation in accordance
with Clause '10.5.1.
(1) Circuits which are neither remote-control circuits nor signal circuits, but which operate at
not more than 30.0V where the current is not limited in accordance with Clause 10.5.1 and
which are supplied from a transformer or other device restricted in its rated output to 1000. OVA
shall be clasefied as extra-low-voltage power circuits and shall be considered to be Class 1
circuits.
(1) Circuits which are neither remote-control circuits nor signal circuits but in which the current
is limited in accordance with Clause 10.5.1 shall be clasified as low-energy power circuits and
shall be considered to be Class 2 circuits.
(1) Where the circuits or apparatus within the scope of this Section are installed in hazardous
locations, they shall also comply with the applicable Clauses of Section 12.
(1) Where the failure to operate a remote-control circuit to a safety control device v rill introduce
a direct fire or life hazard, the remote-control circuits shall be deemed to be a Class 1 circuit.
(1) Class 1 circuits shall not be run in the same cable with communication circuits.
(2) Class 2 remote-control and Signal Circuits or parts thereof which use conductor in a cable
assembly with other conductors forming parts of communication circuits are, for the purpose of
this Code, deemed to be communication circuits and shall conform to the req~irements of
applicable Clauses of Section 23.
•
SECTION 10: CLASS 1 AND CLASS 2 CIRCUITS ----
10.4 CLASS 1 CIRCUITS
(1) Class 1 extra-low-voltage power circuits shall be supplied from a source having a rated
output of not more than 30.0V and 1OOO.OV A.
(2) Class I remote-control and signal ~ircuits shall be supplied by a source not exceeding
600.0V.
(1) The equipment and conductor of Class I circuits shall be installed in acc?rdance with the
requirements of other appropriate Sections of this Code, except as provided in\Clauses 10.4.5
through 10.4.10.
(1) Conductors of Class 1 circuits shall be protected against overcurrent in accordance with
Section 9 of this Code, except:
(a) where other Clauses of this Code specifically permit or require other overcurrent.
protection; or
(b) where the conductors are of 1.0mm2 copper and extend beyond tIle equipment enclosure,
they shall be protected by overcurrent devices rated at a maximum of 5.0A and 10.0A,
respectively.
(2) Where overcurrent protection is. installed at the secondary terminals of the transformer and
the transformer is suitably enclosed, no overcurrent protection is required on the primary side
othttr than the normal overeurrent protection of the branch circuit supplying the transformer.
(1) In Class 1 circuits, the overcurrent devices shall be located at the point where the conductor
to be protected receives its. supply.
(2) The overcurrent device may be an integral part of the power supply.
(1) Copper conductors smaller than 2.5mm2 may be used in Class 1 circuits if:
~
(a) installed in a raceway;
(b) installed in a cable assembly; or
(c) within a flexible cord in accordance with Section 4.6.
(2) Subject to the conditions specified in (1) above, conductors shall not be smaller than:
(1) Where conductors larger than 1.5mm2 copper are used in a Class 1 circuit, they shall be of
any type shown in Annex B of Section 4.
(2) Where conductor of 1.0mm2 or 1.5mm2 copper are used in a Class 1 circuit, they shall be
equipment wire of the type suitable for such use as shown in Annex B of Section 4.
(1) Different Class 1 circuits shall be permitted to occupy the same enclosure, cable or raceway
without regard to whether the individual circuits are alternating current or direct current,
provided all conductors are insulated for the maximum voltage of any conductor in the
enclosure, cable or raceway.
(2) Power supply conductors and Class 1 circuit conc'uctors shall not be permitted in the same
enclosure, cable, or raceway except when connected to the same equipment; and all conductors
are insulated for the maximum voltage of any conductor in the enclosure, cable, or raceway.
(1) Where mechanical damage to a remote-control circuit would result in a hazardous condition
all conductors of such remote-control circuits shall be installed in conduits, electrical metallic
tubing, or be otherwise suitably protected from mechanical injury or other injurious condition
such as moisture, excessive heat or corrosive action.
(I) Class 1 circuits which extend aerially beyond a building shall comply with the requirement
of Section 8.6.
(1) Class 2 circuits, depending upon the voltage, shall have currents limited as follows:
a) 0 to 20. OV: Circuits in which the open-circuit voltage does not exceed 20.0V shall have
overcurrent protection rated at not more than 5.0A except that overcurrent protection·.
shall not be required where the current is supplied from:
i) primary batteries which, under short circuit, will not supply a current exceeding
7.5A after 1.0min;
ii) a Class 2 circuit transformer;
iii) a device having characteristics which will limit the current under normal operating
conditions or under fault conditions to a value not exceeding 5.0A; or
iv) a device having a Class 2 output.
b) Over 20.0V but not exceeding 30.0V: Circuits in which the open-circuit voltage exceeds
20.0V, but does not exceed 30.0V, shall have an overcurrent protection rating not
exceeding lOON amperes, where V is the open-circuit voltage, except that the,
overcurrent protection shall not be required where the current is supplied from:
i) primary batteries which under short circuit will not supply a current exceeding 5.0A
after 1.0min;
ii) a C;:lass2 circuit transformer;
iii) a device having characteristics which will limit the current under normal operating
conditions or under fault conditions to a value not exceeding lOON amperes, where
V is the open-circuit voltage; or
iv) a device having a Class 2 output.
ETHIOPIAN BUILDING CODE STANDARD EBCS-10 1995 249
ELECTRICAL INSTALLATION OF BUILDINGS
c) Over 30. OJ' but not exceeding 60.0.,,: Circuits in which the open circuit voltage exceeds
30.0V. but does not exceed 60.0V, shall have an.,overeurrent protection rating not
exceeding lOON ampers, where V is the open-circuit voltage, except that the overcurrent
pro~ection shall not be required where the current is supplied from:
d) Over 60.0'" but not exceeding J 50.0.,,: Circuits in which the open-circuit voltage exceeds
60.0V, but does not exceed ISO.OV, shall have an overcurrent protection rating not
exceeding lOON amperes, where V is the open-circuit voltage, and, in addition, shall be
equipped with current-limiting means other than overcurrent protection, which will limit
the current, either under normal operating conditions or under fault conditions, to a value
not exceeding lOON amperes, where V is the open-circuit voltage.
(2) Transformer devices supplying Class 2 circuits shall be restricted in their rated output to not
exceeding I OO.OVA.
(3) A device having energy-limiting characteristics may consist of a series resistors of suitable
rating or other similar device.
(4) A Class 2 power supply shall not be connected in series or parallel with another Class 2
power source.
(1) In Class 2 circuits, the coriductors and equipment on the supply side of overcurrent
protectidh, transformers, or current-limiting devices shall be installed in accordance with the
requirements of other appropriate Sections of this Code.
10.5.3 Marking
(1) A Class 2 power supply unit shall have permanent markings which shall be readily visible
after installation to indicate the class of supply and its electrical rating.
(2) The overcurrent protection may be an integral part of a transformer or other power-supply
device.
(1) Overcurrent devices shall be located at the point where the conductor to be protected receives
its supply.
(1) Conduct<;.}[Sfor use in Class 2 circuits shall be of the type suitable for the application as
indicated in Annex B, Section 4.
(2) The maximum allowable current shall be as listed in Annex B, Section 4, for sizes 1.5mm2
and smaller, but in no case shall it exceed the current limitations of Clause 10.5.1.
(1) Conductors of Class 2 circuits shall be separated at least 50.0mm from insulated conductors
of electric lighting, power or Class 1 circuits operating at 380.0Y or less, and shall be separated
at least 600.0mm from any insulated conductors of electric lighting, power or Class 1 circuits
operating at more than 380.0Y unless for both conditions effective separation is afford by use
of:
a) metal raceways for the Class 2 circuits or for the dectric lighting, power and Class 1
circuits subject to the metal raceway being bonded to earth;
b) metal sheathed or armoured cable for the electric lighting, power and Class 1 circuit
conductors subject to the sheath or armour being bonded to earth;
c) nonmetallic sheathed cable for the electric lighting, power and Class I circuits operating
at 380.0Y or less; or
d) nonmetallic conduit, electrical nonmetallic tubing, insulated tubing or equivalent, in
addition to the insulation on the Class 2 circuit conductors or the electric lighting, power
and Class 1 circuit conductors.
(2) Where the electric lighting or power conductors are bare, all Class 2 circuit conductors in
the same room or space shall be enclosed in a metal raceway that is bonded to earth and 110
opening, such as an outlet box, may be located within 2.0m of the bare conductors if up to and
including 15.0kY or within 3.0m of bare conductors above 15.0kY.
(3) Unless the conductors of the Class 2 circuits are separated from the conductors of electric
. lighting, power and_Class 1 circuits by an acceptable barrier, the conductors in Class 2 circuits
shall not be placed in any raceway, compartment, outlet box, junction box or similar fitting with
the conductor of electric lighting, power or Class I circuits.
10.5.8 Conductors of Different Class 2 Circuits in the Same Cable, Enclosure, or Raceway
0) Conductors of two or more Class 2 circuits shall be permitted within the same cable,
enclosure or raceway provided all conductors in the cable, enclosure, or raceway are insulated
for the maximum voltage of any conductor.
(1) Conductors of a Class 2 circuit extending through a fire separation shall be so installed as
to limit fire spread.
(1) Class 2 conductors mld cable installed in a vertical shaft or hoistway shall comply with the
requirements of Section 18.
(1) Class 2 conductors and equipment shall not be placed in ducts or plenum chambers except
as permitted by Clause 8.3.2.
(1) Equipment located on the load side of overcurrent protection, transformers, or current-
limiting devices for Class 2 circuits shall comply with the following:
a) For Class 2 circuits operating at 30.0V or less, alternating current or direct current, it
shall be acceptable for the particular application.
b) For Class 2 circuits operating at more than 30.0V, alternating current or direct current,
it shall be arranged so that no live parts are accessible to unauthorized persons.
(2) Notwithstanding the provisions of (Ia) above, lighting fixtures and thermostats incorporating
heat anticipators, located on the load side of overcurrent protection, Class 2 transformers, or
current-limiting devices shall be approved when connected to Class 2 circuits operating at 30.0V
or less.
(1) Where Class 2 circuits extend beyond a building and are run in such a manner as to be
subjected to accidental contact with lighting or power conductors operating at a voltage
exceeding 380.0V between conductors of the Class 2 circuits, they shall also meet the
requirements of Section 23.
(2) Direct buried Class 2 circuits shall maintain a minimum horizontal separation of 300.0mrrl
from other underground systems except when installed in accordance with (3) below.
(3) Direct buried Class 2 circuits may be placed at random separation in a common trench with
power circuits which are for the sole purpose of supplying power to the Class 2 circuits provided
that the Class 2 circuit is in a metal sheathed' cable, with sheath bonded to earth, the power
circuit operates at 750.0V or less, and all conductors are insulated for the maximum voltage of
any conductor in the trench.
11.1 SCOPE
(1) This Section applies to the installation of the following electric equipment:
(1) The following references contain provisions which, through reference in this text, constitute
provisions of the Ethiopian Building Code Standard on Electrical Installation of Buildings.
(a) NFP A 70/NEC: 1986 National Fire Protection Association! American National
Electrical Code, 1987 Edition.
(b) C22.1: 1990 Canadian Electrical Code, Part 1, Safety Standard for Electrical
Installations, Sixteenth Edition.
11.3 GENERAL
../
(1) Fusible equipment shall employ low-melting-point fuses when connected to conductors
whose ampacity is based on Annex B of Section 4, unless equipment using other types of fuses
is marked as being suitable for such use.
(1) Wherever a device having an identified terminal or leads is connected in a circuit having
identified conductors, the identified conductors shall be connected to the identified terminal or
lead.
(1) Where there is a combustible surface directly under stationary or fixed electrical equipmentl
that surface shall be covered with a steel plate at least 1.6mm thick and which shall extend at
least 150.0mm beyond the equipment on all sides, if:
(1) Yentilated enclosures shall be installed in such a manner that ventilation is not restricted.
(1) Non-portable electric heating and cooking appliances shall be installed so that the danger
of igniting nearby combustible materials is reduced to a minimum.
(2) The input to portable electric heating and cooking appliance for use on nominal 230.0Y
branch circuits protected by overcurrent devices rated or set at not more than 16.0A shall not
exceed 1500.0W at 230.0Y.
(1) Every electric· heating and cooking appliance rated at more than 1500.0W shall be supplied
. from a branch circuit used solely for one appliance except that more than one appliance.may be
connected to a single-branch circuit provided that following is used:
a) A multiple-throw, manually-operated device that will permit only one such appliance to
be energized at one time; or
b) An automatic device that will limit the total load to a value that will not cause operation
of the overcurrent device protecting the branch circuit.
(2) Every electric heating and cooking appliance rated at more than 1500.0W shall be controlled
by an indicating switch which may be in the circuit or on the appliance except that:
a) if the rating of the appliance does not exceed 32.0A, an attachment plug and socket
outlet may be used instead of a switch; and
b) if the appliance has more than one individual heating element each controlled by a
switch, no main switch need be provided.
Note: For the purposed of this Clause, two or more separate built-in cooking units, together with their overcurrent
devices, ar~ considered as one appliance.
(1) All electric power for heating and associated equipment operating in connection therewith
shall be obtained from a single-branch circuit which shall be used for no other purpose.
(2) A suitable disconnecting means shall be provided for the feeder or branch circuit.
(1) Power supply conductors or cables run from well-head to the pump (deep well submersible
pump) shall be:
(2) The area around the submersible pump installed in lakes, rivers and streams shall be
protected from access by the public by fencing, cribbing or isolation and so marked.
(1) The wiring method for stationary motors shall be in accordance with the applicable
requirements of Section 8.
(1) Connections to portable motots shall be permitted with flexible cord which shall have a
serviceability not less than that of extra-hard usage cord unless the motor forms part of a
motor-operated device.
(1) Supply conductors to a motor connection box shall have an insulation temperature ratings
equivalent to or greater than those provided in Table 11.1 unless the motor is marked otherwise
and their ampacity based on a 75°C conductor insulation rating when 90°C wire is used as circuit
conductors to the motor.
(2) Where Table 11.1 requires insulation temperature ratings in exc~ss of 75°C, the motor
supply conductors shall not be less than 1.2m long and shall terminate in a location not less
than 600.0mm from any part of the motor except that, for motors rated 100.0hp or larger, their
terminations shall be not less than 1.2m from any part of the motor.
(3) For ambients higher than 30°C, the supply conductor insulation rating shall be increased at
least by the difference between the ambient and 30°C.
(1) The conductors of a branch circuit supplying a continuous-duty motor shall have an
ampacity not less than 125% of the full-load current rating of the motor.
(2) The conductors of a branch circuit supplying a non-continuous-duty motor shall have an
ampacity not less than the current value obtained by multiplying the full-load current rating of
the motor by the applicable percentage given in Table 11.2 for the duty involved.
(3) Notwithstanding the Provisions of (1) above, conductor ampacities shall be permitted to be
selected from Table 11.5 using the full-load current rating for a continuous duty motor.
(4) Tap conductors supplying individual motors from a single set of branch circuit overcurrent
device supplying two or more motors shall have an ampacity of at least equal to that of the
branch circuit conductors except that where the tap conductors do not exceed 7.5m in length,
they shall be permitted to be sized in accordance with (1) or (2) above provided the ampacity
so determined is not less than % of the ampacity of the branch circuit conductors.
(1) Conductors supplying a group of two or more motors shall have an ampacity equal to or
exceeding:
(a) 125% of the full-load current rating of the motor having the largest full load clllTCnt
rating plus the full load current ratings of all the other motors in the group where all
motors' in the group are continuous-duty motors;
(b) the total of the calculated currents determined in accordance with (a) above for each
motor where all motors in the group are non-continuous-duty motors; or
(c) the total of the following where the group consists of two or more motors of both
continuous and non-continuous-duty types:
i) 125% of the current of the continuous-duty motor having the largest full load
current rating;
(ii) the full-load current ratings of all other continuous duty motors; and
(iii) the calculated current determined in accordance with (2) below for the non-
continuous duty motors.
(2) Where the circuitry is so interlocked as to prevent all motors of the group from running at
the same time, the siLe of the conductors feeding the group shall be permitted to be determined
for the motor, or group of motors operating at the same time, having the largest rating selected
as determined in (1) above.
(3) Demand factors shall be permitted to be applied if the character of the motor loading
justifies reduction of the' ampacity of the conductor to less than the ampacity specified in (1)
above provided that:
(a) the conductors have sufficient ampacity for the maximum demand load; and
(b) the rating or setting of the overcurrent devices protecting them is in accordance with
11.7.2.3(4) below.
(l) Where a feeder supplies both motor loads and other loads, the ampacity of the conductors
shall be calculated in accordance with 11.7.1.4 and 11.7.1.5 plus the requirements of the other
loads.
(2) The ampacity of a tap from a feeder to a single set of overcurrent devices protecting a motor
branch circuit shall not be less than that of the feeder, except that the ampacity of the tap shaH
be permitted to be calculated in accordance with 11.7.1.4 and 11.7.1.5 if the tap:
(1) Conductors connecting the secondaries of wound rotor motors to their controllers shall have
ampacities not less than:
(a) 125% of the rated full load secondary current for continuous-duty motors; or
(b) the percentage of rated full lmid specified in Table 11.2 for non-continuous-duty
motors.
(2) Ampacities of conductors connecting secondary resistors'to t_heircontrollers shall not be less
than that determine<i by applying the appropriate percentage in Table 11.3 to the maximum
current which the devices are required to carry.
,-
(1) Each unearthed conductor of a motor branch circuit shall be protected by an overcurrent
device complying with the following:
(a) A branch circuit supplying a single motor shall be protected, except as permitted by (c)
below, by using an overcurrent device of rating not to exceed the values in Table 11.4
using the rated full load current of the motor;
(b) notwithstanding (a) above, Table 11.5 shall be permitted to be used to select the size
of overcurrent devices required for a motor where the full load current rating of the
motor is shown in the Table;
(c) instantaneous trip (magnetic only) circuit interrupters shall be permitted where applied
in accordance with 11.7.2.5;
(d) where the overcurrent devices as determined in (a) above will not permit the motor to
start, the rating or setting of the overcurrent device shall be permitted to be increased
as follows:
(e) for a branch circuit supplying two or more motors, the rating or setting of the
overcurrent device shall not exceed the maximum value permitted by 11.7.2.4.
(1) Where the characteristics and rating or setting of a branch circuit protective device are
specified in the marking of motor CGntrol equipment, they shall not be exceeded,
notwithstanding any greater rating or setting permitted by 11.7.2.1.
(1) For a feeder supplying motor branch circuits only, the rating or setting of the feeder
overcurrent deviee shall not exceed a maximum value calculated by determining the maximum
rating or setting of the overcurrent device pem.itted by 11.7.2.1 for that motor which is
permitted the highest rated overcurrent devices of any motor supplied by the feeder, and adding
thereto the sum of the full load current ratings of all other motors which will be in operation at
the same time.
(2) (i) Where a feeder supplies a group of motors, two or more of which are required to start
simultaneously, and the feeder overcurrent devices as set in accordance with (1) above
are not sufficient to allow the motors to start, the rating or setting of the feeder
overcurrent devices shall be permitted to be increased as necessary to a maximum.
(ii) Notwithstanding the Provisions of (i) above, the permitted increase shall not exceed
the rating permitted for a single motor having a full load current rating not less than
the sum of the full load current ratings of the greatest number of motors which start
simultaneously, provided this value does not exceed 300% of the' ampacity of the
feeder conductors.
(3) Where a feeder supplies one or more motor branch circuits together with other loads, the
required overcurrent protection shall be determined by calculating the overcurrent protection
required for the motor .circuits and adding thereto the requirements of the other loads supplied
by the feeder.
(4) Where a demand factor has been applied as permitted in 11.7.1.5(3b), the rating or setting
of the overcurrent devices(s) pfotecting a feeder shall not exceed the ampacity of the feeder,
except as permitted by applicable Clauses of Section 8.
(1) Two or more motors shall be pennitted to be grouped under the protection of a single set
of branch circuit overcyrrent devices having a rating or setting calculated in accordance with
11.7.2.3(1) provided that the protection conforms to one of the following:
(a) The ratings or settings of the overcurrent devices do not exceed 16.0A; or
(b) Protection is provided for the control equipment of the motors by having the branch
circuit overcurrent devices rated or set at:
(i) values not in excess of those marked on the control equipment for the lowest rated
motor of the group, as suitable for the protection of that control equipment; or
(ii) in the absence of such markings, values not in excess of 400% of the full-load
current of the lowest rated motor.
(c) The motors are used on a machine tool or woodworking machine; and
(i) the control equipment is arranged so that all contacts which open the motor's
primary circuits are in enclosures, either forming part of the machine base or for
separate mounting, having a wall thickness not less than 1.69mm for steel,
2.40mm for malleable cast iron, or 6.30mm for other cast metal, having hinged
doors with substantial catches, and having no openings to the floor or the
foundation on which the machine rests; and
(ii) the ratings or settings of the overcurrent devices do not exceed 200.0A at 230.0V
or less, or 100.0A at voltages from p1.0V to 750.0V.
(1) Instantaneous trip circuit interrupters, when used for branch circuit protection, shall be:
(a) part of a combination motor starter or controller that also provides overload protection;
and
(b) rated or adjusted, for an a.c. motor, to trip at not more than 1300% of the motor full-
load current or at not more than 215% of the motor locked rotor current, where given,
except that ratings or settings for trip current need not be less than 16.0A; or
(c) rated or adjusted, for a d.c. motor rated at 50.0hp or less, to trip at not more than 250%
of the motor full load current, or for a d.c. motor rated at more than 50.0hp, to trip at
not more than 200% of the motor full-load current.
(1) The branch circuit conductors and control equipment of each motor shall have overload
protection, except as permitted by 11.7.3.5
(a) a separate overload device which is responsive to motor current and which shall be
permitted to combine the function of overload and overcurrent protection if it is capable
of protecting the circuit and motor under both overload and short circuit conditions,
(b) a protective device, integral with the motor and responsive to motor current and
temperature, provided such device will protect the circuit conductors and control
equipment as well as the motor.
(2) Fuses used as separate overload protection of motors shall be timedelay fuses.
(2) Except by special permission, where current-responsive devices are used for the overload
protection of 3-phase motors, such devices shall comprise of three current-responsive elements
which shall be:
(a) connected directly in the motor circujt conductors as required by (1) above; or
(b) fed by two or three current transformers so connected that all 3-phases will be protect~d.
(1) Overload devices responsive to motor current shall be rated or selected to trip at not more
than the following:
(a) 125% of the full-load current rating of a motor having a marked service factor of 1.15
or greater; or
(b) 115% of the full-load current rating of a motor which does not have a marked service
factor or where the marked service factor is less than 1.15.
(2) Notwithstanding the Provisions of (1) above, Table 11.5 shall be applicable to determine
the type of the overcurrent device required for motors having a service factor of 1.15 or greater
where the full-load current rating of the motor is listed in the Table.
(3) Where a motor overload device is so connected that it does not carry the total current
designated on the motor nameplate, such as for wye-delta starting, the percentage of motor
nameplate current applying to the selection or setting of the overload device shall be clearly
marked on the motor starter or shown in the motor starter manufacturers overload selection table.
(1) Overload protection shall not be required for motors complying with any of the following:
(a) A manually started motor rated at 1.0hp or less that is continuously attended while in
operation, which is on a branch circuit having overcurrent protection rated or set at not
more than 16.0A or on an individual branch circuit having overcurrent protection as
required by Table 11.5 if it may be readily determined from the starting location that
the motor is running.
(b) A motor constructed so that it cannot be overloaded.
(c) A motor whose operating requirements are such that it is impracticable to obtain proper
overload protection.
(d) An automatically startable motor having a rating of 1.0hp or less forming part of an
assembly equipped with other safety controls that protect the motor from damage due
to stalled-rotor current and on which a nameplate, so located as to be visible after
installation, indicates that such protection features are provided.
(1) Overload protection shall be permitted to be shunted or cutout ofa circuit during the starting
period, provided that the device by which the protection is shunted or cutout cannot be left in
the starting position and that the overcurrent device is in the motor circuit during the starting
period.
(]) Where automatic restarting of a motor after a shut down on overload could cause injury to
persons, the overload or overheating devices protecting the motor shall be so arranged that
automatic restarting cannot occur.
(I) Each motor shall be provided with means of overheating protection except as permitted by
11.7.3.10.
(I) Overheating protection, where required by 11.7.3.8, shall be provided by devices integral
with the motor and responsive to both motor current and temperature or to motor temperature
only, and shall be arranged to cut off power to the motor or, by spacial permission, to activate
a warning signal when the temperature exceeds the safe limit for the motor.
(2) Motors with inherent overheating protection acceptable under (l) above shall be marked to
indicate that they are thermally protected or impedance protected.
(a) where the motor circuit requires no overload protection under 11.7.3.5; or
- (b) where overload protective devices required by 11.7.3.2 adequately protect the motor
against overheating due to excess current and the motor is in a location where:
(i) ambient temperatures are not more than 100e higher than those at the location of
the overload devices; and
Oi) dust or other conditions will not interfere with the normal dissipation of heat from
the motor.
(1) Motors shall be disconnected from the source of supply in case of low voltage by one of
the following means unless it is evident that no hazard will be incurred through lack of such
disconnection:
(a) A motor control device shall provide low-voltage protection when automatic restarting
is liable to create a hazard.
(b) The motor control device shall provide low-voltage release when it is necessary or
desirable that a motor stops on failure or reduction of voltage and automatically restart
on return of voltage.
(1) The protection specified in 11.7.4.1 shall be permitted to be applied to a feeder or branch
circuit supplying a group of motors, in which case the individual motors need not. be so
protected, provided the means for manually resetting a low-voltage protective device shall be
within sight of all machines supplied by a feeder or branch circuit and so located that the
operator can visually assure himself that safe re-energization of the feeder or branch circuit is
possible.
11.7.5 Control
(1) Except as permitted by (3) below, each motor shall be provided with a motor starter or
controller for starting and stopping it and having a rating, in horsepower, not less than the rating
of the motor it serv~s.
(2) A motor controller need not open the circuit in all unearthed conductors to a motor unless
it also serves as a disconnecting means.
(3) The motor starter or controller specified in (1) above shall not be required for motors
applied as follows:
(a) A singlephase portable motor rated at Y3hp or less, connected by means of a socket
outlet and attachment plug rated not in excess of 16.0A, 230.0V.
(b) A motor controlled by a manually operated general-use switch having an ampere rating
not less than 125% of the full load current rating of the motor.
(c) A two-wire potable a.c. or d.c. motor having a rating not in excess of Y3hp, 230.0V
controlled by a horsepower rated singlepole motor switch.
(1) A motor controlled manually, either directly or by a remote control ofa motor starter, shall
have the means of operation by the controller so located:
(a) that safe operation of the motor and the machinery driven by it is assured, or the motor
and the machinery shall be guarded or enclosed so as to prevent accidents due to contact
of persons with live or moving parts; or
(b) where compliance with (a) above is not practicable because of the type, size or location
of the motor or machinery and its parts, devices shall be provided at each point where
the danger of accidents exists whereby the machine or parts of the machine may be
stopped in an emergency.
(1) Manual motor starters having different starting and running positions shall be constructed
so that they cannot remain in the starting position.
(2) Magnetic motor starters having different starting and running positions shall be constructed
so that they cannot remain in the starting position under normal operating conditions.
(I) When power for a control circuit for a.motor controller is obtained conductively from an
earthed system, the control circuit shall be so arranged that an accidental earth in the wiring
from the controller to any remote or signal device will not:
(1) Except as permitted by (2) and (3) below, separate disconnecting means shall be provided
for:
(a) each motor branch circuit,
(b) each motor starter or controller, and
(c) each motor.
(2) A single disconnecting means shall be pennitted to serve more than one of the functions
described in (1) above.
(3) A single disconnecting means shall be pennitted to serve two or more motors and their
associated starting and control equipment grouped on a single branch circuit.
(4) Disconnecting means or the means for operating them shall readily be accessible.
11.8.1 General
(1) The provisions of Section 11.7 for overload, overheating and control of motors shall apply
to electric motor driving air conditioning and refrigerating equipment.
(1) A room air conditioner s.hall be considered as a single motor unit in detennining its branch-
circuit requirements when all the following conditions are met:
(2) The total marked rating of a cord-and-attachment plug-connected room air conditioner shall
not exceed 80% of the rating of a branch circuit where no other loads are supplied.
(3) The total marked rating of a cord-and-attachment plug-connected room air conditioner shall
not exceed 50% of the rating of a branch circuit where lighting units or other appliances are also
supplied.
(1) An attachment plug and socket outlet are permitted to serve as disconnecting means for a
single-phase room air conditioner rated 230.0Y or less if:
(a) the manual controls on the room air conditioner are readily accessible and located within
2.0m of the floor; or
(b) an approved, manually operable switch is installed in a readily accessible location within
sight from the room air conditioner.
(1) Where a flexible cord is used to supply a room air conditioner, the length of such cord shall
not exceed 2.0m for a nominal 230.0Y rating.
(I) Batteries with exposed live parts shall be kept in a room or an enclosure accessible only to
authorized personnel.
(2) Storage batteries shall not be subjected to ambient temperatures greater than 4SoC or less
than the freezi~g point of the electrolyte.
(1) Battery trays, racks and other surfaces on which batteries are mounted shall be:
a) level,
b) protected against corrosion from the battery electrolyte,
(3) Battery cells having conductive containers shall be installed on non-conductive surfaces.
(4) Sealed cells and multi-compartment sealed batteries having conductive containers shall have
an insulating support if a voltage is present between the container and earth.
(5) Cells and multi-compartment vented stage batteries, with covers sealed to containers of non-
conductive, heat resistant material, shall not require additional insulating support.
(6) Batteries having a nominal voltage greater than 230.0V and with cells in rubber or
composition containers shall be sectionalized into groups of 230.0V or less.
11.9.5 Wiring
(l) The installation of wiring and equipment in a battery room shall be in accordance with the
requirements of a dry location.
(2) The wiring between cells and batteries and between the batteries and other electrical
equipment shall be:
c) the conductor shall issue from the raceway through a substantial glazed insulating
bushing;
d) at least 300.0mm of the conductor shall be free from the raceway where connected to
a cell terminal; and
e) the raceway exit shall be at least 300.0mm above the highest cell terminal to reduce the
electrolyte creepage or spillage entering the raceway.
Table 11.1 Minimum temperature rating for the insulation of motor supply conductor [0C]
(Based on ambient temp.erature of 30°C)
H75
B
F
90
90
110
110 75 Insulation class rating
A
ventilated
Table 11.2 Conductor sizes for motors for different service requirements
60-
rating
-
85
120
95
140
150
90
200 minute 85Percentage
110 110 of nameplate 30-and
current rating of
eg ousminute
Continu
rating
Operating
turntables,
Freight motor
etc.valves,
Rolls, ore-and raising' or lowering
coal-handling
Intermittent
Varyng
Periodicduty duty and passenger elevators,
duty
Carrying capacity of
I conductors In percent of
Resistor duty classification Duty cycles
full-load secondary
circuit
Table 11.4 Rating or setting of overcurrent devices for the protection of motor branch circuits
(Except as permitted in Table 11.5 where 16-A overcurrent protection for motor branch circuit conductors exceeds
the values specified in here)
Alternating Current
Note: (i) The ratings of fuses for the protection of motor branch circuits as given in Table 11.5 are based upon
fuse ratings appearing in the Table above, which also specifies the maximum settings of circuit
breakers for the protection of motor branch circuits.
(H) Synchronous motors of the low-torque, low-speed type (usually 450.0rpm, or lower) such as are
used to drive reciprocating compressors, pumps, etc., and which start up unloaded, do not require
a fuse rating or circuit breaker setting in excess of 200% of full-load current.
(Hi) For the use of instantaneous trip (magnetic only) circuit interrupters in motor branch circuits, see
11.7.2.5.
l
Table 11.5 Sizes of conductors, fuse ratings, and circuit breaker settings for motor overload protection and motor circuit overcurrent protection
(This Table is based on Table 11.4 and a room temperature of 30°C).
I breaker
Breaker
breaker
Non-time
Non-timeMaximum Starting)
Fuses
20
30
25
20
40
35
15
20
delay conductor
5.00
1.25
15
2.50
15
1513.75
2018.75
2017.50
15
15 1.125
13.75
1'516.25
12.50
10.00
15.00
11.25
12.50
13.75
15.00
1.25
30
45
25
40
10.00
6.251.125
2.25
17.50
7.507
8.758
7.50
8.75
20
25 rating
925 ofofof
allowable
fuses Maximum
Timedela
Time
overload
devices
18.75
3.75
6.25
5.00
16.2517.5
10
1
15
4.5
3.5
5.6
Minimum
ampacity
yy"O"
"0""0"
setting
2.25
delay Overload d.c.
delay Starting) or wound
protection
squirrel
Single rotor
for cage
phase,
Overcurrent a.c.
and
all synchronous
Type types and
for motor
protection circuitsallowable
maximum [A] rating of fuses and
15 fuses
Circuit (Full
.F·5
Circuit Reactor
voltage, Resistor and
(Autotransformer
Squirrel and Maximum
Star-Delta allowable setting of circuit breakers of the time-limited
cage and Synchronous
Fuses motor [A]
Table 11.5 Sizes of conductors, fuse ratings, alld circuit breaker settings for motor overload protection and motor circuit overcurrent protection (conte' d)
(This Table is based on Table 11.4 and a room temperature of 30°C).
100 Non-time
40II ..II delaydelay
Non-time
fuses
rating (Autotransformer and Star-Delta
100
70
60
40
45
50
50
70
40
30
60
30 50.0
21.25
22.50
80
30.0
32.5
30.0
32.5
5045.0
4040.0
4037.5
70
80
60
35
25 125
110
100
23.75
90
47.5
45.0
42.5
40.0
37.5
35.0
47.5
42.5
35.0
60
25.00
60
27.5
27.5
20.00
20.00
50
Timedela
Time
Fuses
yy"O"
"0" 20 of of
allowable
50.0 50
overload
devices
fuses Minimum
conductor
30
45
40
35
25
25
17.5
Maximum
"0"
ampacityof fuses Overload d.c. or wound
protection rotor
forcage a.c.
) and
23.75
20
25.00 I setting
(Full Reactor
Circuit
Circuit
breaker
Circuit
Breaker
breaker voltage, Starting)
Resistor
Squirrel
Overcurrent
Maximum
and cage squirrel
Single
and Synchronous
protection
allowable
phase. Type
all for andmaximum
setting
motor
synchronous
types circuitallowable
ofcircuits breakers
[A] rating
of the oftime-limited
Starting)
fuses and
Fuses 50
Table 11.5 Sizes of conductors, fuse ratings, and circuit breaker settings for motor overload protection and motor circuit overcurrent protection (conte'd)
(This Table is based on Table 11.4 and a room temperature of 30°C).
Non-time
delay Starting)
(Autotransformer and
Fuses
fuses
Timedela
70
100
'175
100
125
60
125 Time
200
77.5
7072.5
110
100
7067.5
1-00
150
70
200
80
90
175
125
110
150
90
80
70
175
100.0
225
250
175
150
125
75.0
77.5
8
65.0
62.5
87.5
9
97.5
250
100.0
60.0
57.5
55.0
52.5
67.5
65.0
62.5
82.5
60.0
57.5
55.0
70.0
72.5
75.0
80.0
85.0
87.5
90.0
92.5
97.5
52.5
95.0
7070.0
delay"D"
yy"D"0.0
2.5
5.0
"D".7
6
8Maximum
Non-time
9rating
60
500 ofof
allowable
overload
devices
conductor
Maximum
Minimum
90
setting
ampacityof fuses Starting)
fuses
Reactor
(Full voltage, Overload
Resistor d.c.
and for Star-Delta
or Maximum
wound
protection
Single
squirrel rotor
phase,
cage
Overcurrent a.c.
all synchronous
and
allowable types
protection
Type and
setting
for maximum
motorofcircuits
circuitallowable
breakers
[A] rating
of the oftime-limited
fuses and
breaker
breaker
Breaker
Circuit
Circuit Squirrel cage and Synchronous
Fuses
Table 11.5 Sizes of conductors, fuse ratings, and circuit breaker settings for motor overload protection and motor circuit overcurrent protection (conte'd)
(This Table is based on Table 11.4 and a room temperature of 30°C).
Non-time
delay Starting)
(Autotransformer and
350
225
225
300
200
250
300
125
150
175
200
225
150
175
125
200
150
1751
450
169.0
175.0
75.0
69.0
107.5
105.0
102.5
110.0
112.5
115.0
117.5
120.0
122.5
400
250
102.5
350 Maximum
Non-time
87.5
175
rating
187.5
181.5
105.0
162.5
125.0
137.5
150.0
107.5
110.0
112.5
115.0
117.5
131.5
120.0
122.5
156.5
144.0
25.0
37.5
56.5
44.0
Timedela
Time
yy"D" 90 of of
allowable
overload
fuses
Fuses81.5
conductor
Minimum
150
50.0
100
110
125
devices
300Maximum
31.5
62.5
setting
delay"D"
"D"
ampacltyof fuses
fuses Overload d.c. or wound
protection for Star-Delta
rotor a.c.
~50
Breaker Reactor Starting)
(Full voltage,
breaker
breaker
Circuit
Circuit Resistor andcage Maximum
Squirrel
Overcurrent
squirrel
Single allowable
cage
phase,
and Synchronous
Type
protection
and for
setting
motor
all synchronous
types maximum
and of circuits
circuit allowable
breakers
[A] rating
of the oftime-limited
fuses and
Fuses
Table 11.5 Sizes of conductors, fuse ratings, and circuit breaker settings· for motor overload protection and motor circuit overcurrent protection (conte'd)
(This Table is based on Table 11.4 and a room temperature of 30°C).
Non-time
400
450 delay
Non-time Maximum
-Maximum (Autotransformer
Starting)
Overlo::.ld protectionand
forStar-Delta
fuses
Fuses
225
250
300
250
250
350
450
400
600500
500
600
500
300
300
350
500
350 200
206
219
225
238
231
244
delay"D"194
250
263
200
194
206
213
219
225
231
244
238
250
263
275
275
313
313
288
288
300
300
limedela
lime
213
yy"D"
"D" 200
225rating
allowable
overload
devices
conductor
Minimum
175
250
300
setting
ampacltyof ofof
fuses Starting)
fuses d.c. or Maximum
wound
squirrel
Single rotor
cage
Overcurrent
phase,a.c.
andall synchronous
allowable
Type
protection
types
for
setting
motor
and
maximum
ofcircuits
circuitallowable
breakers
[A] rating
of the oftime-limited
fuses and
breaker
breaker
Breaker
Circuit
Circuit(Full Reactor
voltage. Resistor and
Squirrel cage and Synchronous
Fuses
Table 11.5 Sizes of conductors, fuse ratings, and circuit breaker settings for motor overload protection and motor circuit overcurrent protection (conte'd)
(This Table is based on Table 11.4 and a room temperature of 30°C).
---Non-time
----
~
-400425
-delay
Non-time
'- (Autotransformer
Starting) and
500
600
500
600
'400Fuses
fuses
350336
500450
500475
500500
600
450
600
400
500
delay.
~OO500 -overload
yy''O"-325
Time
400375'·
400400 3625
625
325
350
363
375
400
425
450
475
500
550
600
600
350
575
5~5
"0. 600
63
450
300
350
400
575
500
336
525
550 Maximum
ratingFuses
conductor
Tlmedela Maximum
allowable
Minimum
devices
setting
ampacltyof ofof
fuses
fuses Overload
(Full Reactor
"0"
voltage, Starting)
d.c.
protection
Resistor and for Star-Delta
or Maximum
wound rotor
Overcurrent
squirrel
Single cage
phas~, a.c.
protection
and maximum
all synchronous
Type
allowable types
for and
motor
setting circuitallowable
ofcircuits [A]
breakers rating
of the oftime-limited
fuses and
breaker
Breaker
breaker
Circuit
Circuit Squirrel cage and Synchronous
SECTION 12
HAZARDOUS LOCATIONS
12.1 SCOPE
(1) This Section applies to hazardous locations in which electrical equipment and wiring
are subject to the conditions classified as follows:
(a) Class I locations in which flammable gases or vapours are or may be present in
the air in quantities sufficient to produce explosive or ignitible mixtures;
(b) Class II location which are hazardous because ofthe presence of combustible or
electr.ically conductive dusts; and
(c) Class III locations which are hazardous because of the presence· of easily ignitible
fibres or flyings, but in which such fibres or flyings are not likely to be in
suspension in the air in quantities sufficient to produce ignitible mixtures.
(l) The following reference contains provisions which, through reference in this text, constitute
provisions of the Ethiopian Building Code Standard on Electrical Installation of Buildings.
(a) C22.1:1990 Canadian Electrical Code, Part 1, Safety Standard for Electrical
Installations, Sixteenth Edition.
12.3 CLASSIFICATION
(b) I
Division 2, comprising Class locations in which:
(i) flammable volatile liquids, flammable gases or vapours are handled, processed,
or used, but in which the liquids, gases, or vapours are normally confined
within
\ closed containers or closed systems from which they can escape only as
a result of accidental rapture or breakdown of the containers or systems or the
abnormal operation of the equipment by which the liquids or gases are
handled, processed, or used; or
(ii) hazardous concentration of gasses or vapours are normally prevented by
positive mechanical ventilation, bu.twhich may become hazardous as the r~sult
of failure or abnormal operation of the ventilating equipment; or
(iii) the IQcation is adjacent to a Class I, Division 1 location, from which a
hazardous ~ncentration of gas~es or vapours could be communicated, unless
such communication is prevented by adequate positive-pressure' ventilation
from a source of clean air, and effective safeguards against ventilation failure
are provided.
b) Division 2, comprising Class.II locations in which combustiBle dusts are not normally
in suspension in air or likely to be thrown into suspension by the normal or
abnormal operation or the failure of equipment or apparatus in quantities sufficient
to produce explosive or ignitible mixtures, but in which:
(1) Class III locations shall be divided into two divisions as follows:
b) .Division 2, comprising Class III locations in which readily ignitible fibres other fhan
those in process of maI}.ufactureare stored or handled.
(1) Where electrical equipment is required by this Section to be approved for the class of
location, it shall also be approved for the specific gas, vapour, or dust that will be present.
(2) Such approval in (1) may be indicated by one or more of the following atmospheric-
gI:oup designations which have been established for the purpose of testing and approval:
12.4.2 Marking
(1) Electrical, equipment approved for use in hazardous locations shall be marked to
indicate the class and for Classes I and II locations the group, or the specific gas, vapour
or dust for which the equipment has been approved .
•
(2) Electrical equipment approved for use in Class I hazardous locations may be tJ1arked
with:
Temperature T6
T3A
T4
T3C
T5
T4A
T38 Max.
Max. external
external
100
200
85
180
165
160
135
120
215
230
450
300
280
260
Temperature
oode
temperature
temperature [0C]
[0C]
.
282 EBCS-10 1995 ETHIOPIAN BUILDING CODE STANDARD
SECTION 1 H RDOUS LOCATIONS
Group A - 28O"C
Group B - 28O"C
Group C - 160"C
Group D - 215°C
(5) slectrical equipment approved for operation at ambient temperatures exceeding 40"C
shall, in addition to the marking specified in 12.4.2 be marked with the maximum ambient
temperature for which the equipment is approved, and the maximum external temperature
of the equipment as referred to in (2) and (3) above.
(2) Service equipment, panelboards, switchboards, and similar electrical equipment shall,
'where practicable, be located in rooms or sections of the building in which hazardous
conditions do not exist.
(1) Where walls, partitions, floors or ceilings are used to form hazard-free rooms or
sections, they shall be:
a) of substantial construction;
b) built of or lined with noncombustible material; and
c) such as to ensure that the roo~ or section will remain free from hazards.
(1) Cable trays shall not be used to support cables in hazardous locations except where:
a) the type of cable is approved iil Clauses of this Section for use in the particular
hazardous location; and
b) there can be no hazardous accumulation of combustible process dust or fibre in or
upon the cable; the cable tray or the supports.
(1) Transformers and electrical capacitors which contain a combustible liquid that will burn
shall be installed in electrical equipment vaults in accordance with applicable Clauses of
Section 11.
(1) Where practicable, meters, instruments and relays, including kilowatt-hour meters,
instrument transformers and resistors, rectifiers and thermionic tubes shall be located
outside the hazardous locations.
(2) Where it is not practicable to install meters, instruments, and relays outside Class I,
Division 1 locations, they shall be approved for Class I locations.
(1' Switches, motor controllers, circuit breakers and fuses, including push buttons, relays,
and similar devices shall be provided with enclosures; the enclosure in each case, together
with the enclosed apparatus, shall be approved as a complete assembly for use in Class I
locations.
(1) Motors, generators and other rotating electrical machines shall be approved for Class
I locations.
(1) The wiring method shall be threaded rigid-metal conduit or cables approved for
hazardous locations with associated cable glands approved for the particular hazardous
location.
(2) All boxes, fittings, and joints shall be threaded for connection to conduit or cable
glands, and shall be explosion-proof with boxes and fittings approved for Class I locations.
(3) Threaded joints shall have at least five full threads fully engaged and running threads
shall not be' used.
(4) Cables shall be installed and supported in a manner to avoid tensile stress at the cable •
glands.
(5) Where it is necessary to use flexible connections at motor terminals and similar places,
flexible fittings of the explosion-proof type and approved for the location shall be used.
(6) Seals shall be provided in conduit or cable systems to prevent the passage of gases,
vapours, or flames from one portion of the electrical installation to another through the
system.
(1) Fixtures for fixed and portable lighting shall be approved as complete assemblies for
Class I locations and shall be clearly marked to indicate the maximum wattage of lamps for
which they are approved.
(2) Boxes, box assemblies or fittings used for the support of lightiRg fixtures shall be
approved for the purpose and for Class I locations.
(2) Cable shall be installed and supported in a manner to avoid tensile stress at the cable
glands.
(3) Where it is necessary to use flexible connection at motor terminals and similar places,
flexible metal conduit may be used.
(5) Seals shall be provided in conduit or cable systems to prevent the passage o(gases,
vapours, or flames through the system from one portion of the electrical installation to
another.
(1) Motors, generators, and other rotating electrical machines, in which are incorpor~ted
arcing or spark-producing components or integral resistance devices, shall be approved for
Class I, Division 2 locations unless the arcing or spark-producing components or integral
resistance devices are provided with enclosures approved for Class I locations.
(2) Motors, generators, and other rotating electrical machines which do not incorporate
arcing or spark producing components or integral resistance devices may be of the open or
non-explosion-proof type.
b) approved as complete assemblies for Class I, Division 2 locations and shall be clearly
marked to indicate the maximum wattage, voltage, and specific type designations
of the lamps for which they are approved.
(2) Pendent fixtures shall be suspended by threaded rigid conduit systems or by other
approved means.
(3) Starting and control equipment for electric-discharge lighting equipment shall be
pr0v.ided with enclosures approved for the location.
(1) Transformers and electrical capacitors which contain a combustible liquid shall be
installed in electrical equipment vaults in accordance with applicable Clauses of Section 11,.
(1) Switches, motor controllers, circuit breakers and fuses, including push buttons, relays,
and similar devices, shall be provided with a dust-tight enclosure approved for Class II
locations.
(1) Motors, generators and other rotating electrical machines shall be approved for Class
n locations.
(1) The wiring method shall be threaded rigid metal conduit or cables approved for
hazardous locations with associated cable glands approved for the particular hazardous
location.
(2) Boxes, fittings and joints shall be threaded for connection to conduit or cable glands
and boxes and fittings shall be approved for Class II locations.
(4) Where flexible connections are necessary, they shall be provided by:
(5) Where flexible connections are subject to oil or corrosive conditions, the insulation of
the conductors shall be of type approved for the condition or shall be protected by means
ofa suitable sheath.
(6) Where a raceway provides communication between enclosures one of which is required
to be dust-tight and the other not, the entrance of dust into the dust enclosure through the
raceway shall be prevented by:
12.6.1.5 Lightingfixtures
(1) Fixtures for fixed and portable lighting shall be approved as complete assemblies for
II
Class locations and shall be clearly marked to indicate the maximum wattage of lamps
for which they are approved.
(2) Pendent fixtures shall be suspended by threaded rigid conduit stems or chains with
approved fittings or by other approved means which shall not include a flexible cord as the
supporting medium, and threaded joints shall be provided with set screws or other effective
means to prevent loosening.
(3) Boxes, box assemblies or fittings used for the support of lighting fIxtures shall be
approved for the purpose.
(1) Transformers and electrical capacitors which contain a combustible liquid shall be
installed in electrical equipment vaults in accordance with applicable clauses of Sections 11.
(1) In locations where dust from magnesium, aluminum, aluminum bronze powders, or
other metals of similar hazardous characteristics may be present, switches, motor
controllers, circuit breakers, and fuses shall have dust-tight enclosures approved for such
locations.
(1) Motors, generators and other rotating electrical machinery shall be:
(2) Cables shail be installed and supported in a manner to avoid tensile stress at the cable
glands.
(2) Pendent fixtures shall be suspended by threaded rigid conduit stems or chains with
appro.ved fittings, or by other approved means, which shall not include flexible cord as the
supporting medium.
(3) Boxes, box assemblies or fittings used for the support of lighting fixtures shall be
approved for that purpose.
(4) Starting and control equipment for mercury-vapour and fluorescent lamps shall conform
to the requirment of 12.6.2.2.
(1) Switches, motor controllers, circuit breakers and fuses, including push buttons, relay~
and similar devices, shall be provided with tight enclosures designed to minimize entrance
of fibres and flyings, and which shall:
a) be equipped with telescoping or close fitting covers, or with other effective means
to prevent escape of sparks or burning material; and
b) have no openings, such as holes for attachment screws, through which, after
installation, sparks or burning material might escape, or through which exterior
accumulations of fibres or flyings or adjacent combustible material might be ignited.
(1) Except as provided in (2) below, motors, generators and other rotating electrical machinery
shall be:
(2) Where only moderate accumulations of lint and flyings are likely to collect on or in the
vicinityof a rotating electrical machine and the machine is readily accessible for routine
cleaning and maintenance, there may be installed in the location:
(3) Motors, generators and other rotating electrical machinery of the partially enclosed or
splash-proof type shall not be installed in Class III locations.
(1) The wiring method shall be threaded rigid metal conduit or cables approved for
hazardous locations with associated cable glands approved for the particular hazardous
location.
(2) Boxes and fittings in which taps, joints or terminal connections are made shall:
b) have no openings, such as holes for attachment screws, through which after
installation, sparks or burning material might escape, or through which adjacent
combustible material might be ignited.
(3) Cables shall be installed and supported in a manner to avoid tensile stress at the cable
glands.
(4) Where it is necessary to use flexible connections, the provisions of 12.6.1.4(4) and
12.6.1.4(5) shall apply.
a) provide enclosures, for lamps and lampholders, which shall be designed to minimize
entrance of fibres and flying objects and to prevent the escape of sparks, burning
material, or hot metal;
b) be clearly marked to indicate the maximum wattage lamp which may be used •
without exceeding a maximum exposed surface temperature of 165°C under Rormal
conditions of use.
(2) Lighting fixtures which may ~e exposed to phystcal damage shall be protected by a
suitable guard.
(4) Boxes, box assemblies or fittings used for the support of lighting fixtures shall be
approved for that purpose.
(1) Storage battery charging equipment shall be located in a separate room built or lined
with substantial noncombustible materials so constructed as to adequately exclude flyings
or lint, and shall be well ventilated.
(1) The wiring method in Class III, Division 2 locations shall conform to 12.7.1.4 except
that in sections, compartments or areas used solely for storage and containing no
machinery, open wiring on insulators, in accordance with applicable Clauses of Section 8,
may be used, provided that, where conductors are installed elsewhere other than in roof
spaces and remote from physical damage, they shall be protected by running board not less
than 19.0mm thick or other acceptable means.
(1) Switches, motor controllers, circuit breakers, and fuses shall conform to the requirement
of 12.7.1:2.
(1) Motors, generators, and other rotating electrical machinery shall be:.
(2) Motors, generators or other rotating electrical machinery of the partially enclosed
or splashproof type shall not be iI)Stalledin Class III locations.
13.1 SCOPE
(1) This Section applies to electrical apparatus and wiring installed in the following
facilities:
a) Gasoline dispensing and service stations, and other locations where gasoline or other
similar volatile flammable liquids are dispensed or transferred to fuel tanks of self-
propelled vehicles.
b) Commercial garages, repair houses and storage where service and repair operations
of vehicles of the type described in (a) above are carried out and in which more
than three such vehicles are, or may be, stored at anyone time.
c) Residential storage garages in which not more than three vehicles of the type
described in (a) above are, or may be, stored, but which will not normally be used
for service or repair operations.
d) Bulk storage plants where gasoline or other similar volatile flammable liquids are
stored in tanks having an aggregate capacity of one-car-Ioad or more, and from
which such products are distributed (usually by tank truck).
e) Finishing processes where paints, lacquers or other flammable finishes are regularly
or frequently applied by spraying, dipping, brushing or by other means, and where
volatile flammable solvents or thinners are used or where readily ignitible deposits
or residues from such paints, lacquers, or finishes may occur.
t) Aircraft hangars used for storage or servicing of aircraft in which gasoline jet fuels,
or other volatile flammable liquids, or flammable gases, are used; but shall not
include those locations used exclusivelyfor aircrafts that have never contained such
liquids or gases, or which have been drained and properly purged.
(1) The following references contain provisions which, through reference in this text, constitute
provisions of the Ethiopian Building Code Standard on Electrical Installation of Buildings.
(1) The space within a d~penser enclosure upto 1.2m vertically above its base including the
space below· the dispenser which may contain electrical wiring and equipment shall be
e<;>nsideredto be Class I, Division 1 location.
(2) The space within a nozzle boot of a dispenser shall be considered to be a Class I
Division 1 location.
(3) The space within 450.0mm horizontally from the Division 1 location within the
dispenser enclosure as specified in (1) aoove shaU be considered to be a Class I, Division
1 location.
(4) In an outside location, any area beyond the Class I, Division 1 area within 6.0m
horizontally from the exterior enclosure of any dispenser shall be considered a Class I,
Division 2 location, which will extend to a level 4~O.Ommabove driveway or ground level.
(5) In an outside location, any area beyond the Class I, Division 1 location and within 3.0m
horizontally from any tank fillpipe shall be considered a Class I, Division 2 'location which
shall extend upward to a level 450.0mm above driveway or ground level.
(6) Electrical wiring and equipment, any portion of which is below the surface of areas
defined as Class I, Division 1 or Division 2 in (1), (3), (4) or (5) above shall be considered
to be within Class I, Division 1 location which shall extend at least to the point of
emergence above grade.
(7) Areas within the vicinity of tank ventpipes shall be classified as follows:
a) The spherical volume within a 900.0mm radius from point of discharge of any tank
ventpipe shall be considered a Class I, Division 1 location and the volume between
the 900.0mm to 1.5m radius from point of discharge of a vent shall be considered
a Class I, Division 2 location.
b) For any vent that does not discharge upward, the cylindrical volume below both the
Division 1 and Division 2 locations extending to the ground shall be considered as
Class I, Division 2 location.
c) The hazardous area shall not be. considered to extend beyond an unpierced wall.
a) The area within any pit or space below grade or floor level shall be considered a
Class I, Division 1 location unless the pit or space is beyond the hazardous areas
specified in (4), (5), (6), (7) above in which case the pit or space shall be considered
a Class I Division 2 location.
b) The area within the entire lubrication room up to 50.0mm above the floor or grade,
whichever is the higher, and the area within 900.0mm measured in any direction
from the dispensing point of a hand-operated unit dispensing volatile flammable
liquids shall be considered a Class I, Division 2 location.
(1) Electrical wiring and equipment within the hazardous areas defined in Clause 13.3.1
shall conform to the requirements of Section 12.
(2) Where dispensers are supplied by rigid metal conduit, flexible fittings of the explosion-
proof type approved for the location shall be used between the conduit and the junction box
of the dispenser in addition to any sealing fittings and unions that may be required pursuant
to the provisions of Section 12.
(3) Each circuit leading to or through a dispensing pump shall be provided with a switching
means which will disconnect simultaneously from the source of supply all unearthed
conductors of the circuit.
(4) All non-current-carrying metal parts of dispensing pumps, metal raceways and other
electrical equipment shall be bonded to earth in accordance with Section 7 of this Code.
(1) Wiring and equipment above hazardous areas· shall meet the requirements and
provisions of Clauses 13.4.3 and 13.4.4 of this Section.
(1) For each floor at or above grade, the entire area up to a level 50.0mm above the floor
shallbe considered to be a Class I, Division 2 location.
(2) For each floor below grade, the entire area up to a level 50.0mm above the bottom of
outside doors or other openings which are at or above grade level shall be considered to
be a Class I, Division 2 location except that, where adequate mechanical ventilation is
provided,the hazardous location shall extend up to a level of only 50.0mm above each such
floor.
(3) Any pit or depression below floor level shall be considered to be a Class I, Division 2
locationwhich shall extend up to the floor level.
(4) Adjacent areas in which hazardous vapours are not likely to be released such as
stockrooms, switchboard rooms, and other similar locations having floors elevated at least
50.0mmabove the adjacent garage floor, or separated therefrom by tight curbs or partitions
at least 50.0mm high, shall not be classified as hazardous.
(1) Within hazardous areas as defined in Clause 13.4.1, wiring and equipment shall
conform to the requirements of applicable Clauses of Section 12.
(1) All fixed wiring above hazardous areas shall be carried out in accordance with the
provisions of Section 8 and suitable for the type of building and occupancy.
(2) For pendants, flexible cord of the hard-usage type shall be employed.
(3) For connection of portable lamps, portable motors, or other portable utilization
equipment, flexible cord of the hard-usage type shall be used.
(1) Fixed equipment which is less than 3.6m above the floor level and which may produce
arcs, sparks, or partiCles of hot metal such as cutouts, switches, charging panels, generators,
motors or other equipment (excluding socket outlets, lamps and lampholders) having make-
and-break or sliding contacts, shall be of the totally enclosed type or so constructed as to
prevent escape of sparks or hot metal particles.
(2) Lamps and lampholders for fixed lighting and that are located over lanes through which
vehicles are commonly driven or which may otherwise be exposed to physical damage shall
be located not less than 3.6m above floor level unless of totally enclosed type or so
constructed as to prevent escape of sparks or hot metal particles.
(1) Where the lowest floor is at or above adjacent grade or driveway level, and where there
is at least one outside door at or below floor level, the garage area shall not be classified
as a hazardous location.
(1) Where the lowest floor is below adjacent grade or driveway level, the following shall
apply:
a) The entire area of the garage or of any enclosed space which includes the garage
shall be classified as a Class I, Division 2 location and will extend up to a level
50.0mm above the garage floor.
b) Adjacent areas in which hazardous vapours or gases are not likely to be released,
and having floors elevated at least 50.0mm above the garage floor, or separated
therefrom by tight curbs or partitions at least 50.0mm high shall not be classified as
hazardous.
13.5.3 Wiring
(1) Wiring above the hazardous locations shall conform to the provisions of Section 8.
(2) Wiring in the hazardous location shall conform to the provisions of Section 12.
(1) Neas containing pumps, bleeders, withdrawal fittings, metres and similar devices wliich
are located in pipelines handling flammable liquids under pressure shall be classified and
comply with the following:
i) design of the ventilation systems takes into account the relatively high relative
density of the vapours;
ii) where openings are used in outside walls, they are of adequate size and located
at floor level unobstructed except by louvres or coarse screens; and
b) Indoor areas not ventilated in accordance with (a) above shall be considered
Class I, Division 1 locations within a 15m distance extending in all directions from
the exterior surface of such devices as well as 7.5m horizontally from any surface of
the device and extending upward 900.0mm above floor or grade level.
(2) Areas where flammable liquids are transferred shall be classified as follows:
b) Where positive and reliable mechanical ventilation is not provided in indoor areas
in which flammable liquids are transferred to individual containers, such areas shall
be considered to be a Class I, Division 1 location.
(3) Areas in outside locations where loading and unloading of tank vehicles and tank cars
take place shall be classified as follows:
a) The area extending 900.0mm in all'directions from the dome (when loading through
an open dome) or from the vent (when loading through a closed dome with
atmospheric venting) shall be considered a Class I, Division 1 location.
b) The area extending between a 900.0mm and a 15m radius from the dome (when
loading through an open dome) or from ,the vent (when loading through a closed
dome with atmospheric venting) shall be considered a Class I, Division 2 location.
c) The area extending within 900.0mm in all directions from a fixed connection used
in bottom loading or unloading, loading through a closed dome with atmospheric
venting, or loading through a closed dome with a vapour recovery system shall be
considered a Class I, Division 2 location except that, in the case of bottom loading
or unloading, this classification shall also be applied to the area within a 3.0m radius
from point of connection and extending 450.0mm above grade.
(4) Area within the vicinity of above-ground tanks shall be classified as follows:
a) The area above the roof and within the shell of a floating-roof type tank shall be
considered a Class I, Division 1 location.
i) the area within 3.0m from the shell ends, and roof of other' than a floating-roof
shall be considered a Class I, division 2 location; and
ii) where dikes are provided, the area inside the dike and extending upwards to the
top of the dike shall be considered to be a Class I, Division 2 location.
c) The area within 105m of vent opening and extending in all directions shall be
considered a Class I, Division 1 location.
d) The area between 105mand 3.0m of a vent opening and extending in all directions
shall be considered a Class I, Division 2 location.
a) Any pit or depression, any part of which lies within a Division 1 or Division 2
location, unless provided'with positive and reliable mechanical ventilation, shall be
considered a,Class I, Division 1 location.
b) Any such areas as in (a) above, when provided with positive and reliable mechanical
ventilation, shall be considered a Class I, Division 2 location.
(6) Garages in which tank vehicles are stored or repaired shall be considered to be a Class
I, Division 2 location up to 450.0mm above floor or grade level.
(7) Buildings such as office buildings, boiler rooms, etc which are outside the limits of
hazardous areas as defined herein and which are not used for handling or storing volatile
flammable liquids or containers for such liquids shall not be considered to be hazardous
locations.
(1) All electrical wiring and equipment in hazardous areas defined in Clause 13.6.1 shall
conform to the requirements of Section 12.
(1) Wiring installed above a hazardous location shall conform. to the requirements of
Section 8 and be suitable for the type of buildings and occupancy.
(2) Fixed equipment which may produce arcs, sparks or particles of hot metal, such as
lamps and lampholders, cutouts, switches, socket outlets, motors or other equipment having
make-and-break or sliding contacts, shall be of the totally enclosed type or so constructed
as to prevent the escape of sparks or hot metal particles.
(3) Portable lamps or utilization equipment and the flexible cords supplying them shall
conform to the requirements of Section 12 for the class of location above which they are
connected or used.
(4). All non-current-carrying metal parts of equipment and raceways shall be bonded to
earth in accordance with Part I of Section 7 of this Code.
b) All space within 6.0m horizontally in any direction, and extending to a height of
900.0mm above the goods to be painted, from spraying operations that are more
extensive than touch-up spraying and not conducted within the spray booth.
c) All space within 6.0m horizontally in any direction from dip tanks and their drain
boards, such space extending to a height of 900.0mm above the dip tank and drain
board.
d) All other spaces where hazardous concentrations of flammable vapours are likely to
occur.
(2) For spraying operations within an open face spray booth, the extent of the Class I,
Division 2 hazardous location shall be not less than the following:
b) Where the ventilation system is not interlocked with the spraying equipment so as
to make the spraying equipment inoperable when the ventilation system is not in
operation, the space shall extend at least 3.0m from the open face or front of the
.spray booth.
(3) All space within the room, but beyond the limits for Class I, Division 1 location as
classified in (1) above for extensive open spraying; for dip tanks and drain boards and for
other hazardous operations, shall be considered to be Class I, Division 2 location.
(4) Adjacent areas which area cut off from the defined hazardous area by tight partitions
without communicating openings, and wi~hinwhich hazardous vapours are not likely to be
released, shall be classified as non-hazardous.
(5) Drying and baking areas provided with positive mechanical ventilation to prevent
formation of flammable concentration of vapours and provided with effective interlocks to
de-energize all electrical equipment not approved for Class I locations, in case the
ventilating equipment is inoperative, may be classified as non-hazardous.
(6) Notwithstanding the requirements of (lb) above, where adequate mechanical ventilation
with effective interlocks is provided at floor level:
a) the space within 900.0mm horizontally in any direction from the goods to be painted
and such space extending to a height of 900.0mm above the goods to be painted
shall be considered a Class I, Division 1 location; and
b) all space between a 900.0mm and 105mdistance above the goods to be painted and
all space within 6.0m horizontally in any direction beyond the limits for Class I,
Division 1 location shall be considered a Class I, Division 2 location.
(7) Notwithstanding the requirements of (2) above where a baffle of sheet metal of not less
than 1.25mm is installed vertically above the front face of an open-face spray booth to a
height of 900.0mm or to the ceiling, whichever is lower and extending back on the side
edges for a distance of 105m,the space behind this baffle shall be considered to be a non-
hazardous location.
(1) All electrical wiring and equipment within the hazardous areas as defined In
Clause 13.7.1 shall conform to the requirements of Section 12.
(2) .Unless specifically approved for both readily ignitable deposits and flammable vapour
location, no electrical equipment shall be installed or used where it may be subject to a
hazardous accumulation of readily ignitable deposits or residue.
(3) Illumination of readily ignitable area through panels of glass or other tr~nsparent or
translucent materials is permissible only where:
a) not be used within a hazardous area during operation of the finishing process;
b) be of a type specifically approved for Class I locations when used during cleaning
or repairing operations.
a) totally enclosed and gasketted lighting may be used on the ceiling of a spray room
where adequate and positive mechanical ventilation is provided; and
b) infra-red paint-drying units may be utilized in a spray room if the controls are
interlocked with those of the spraying equipment such that both operations cannot
be performed simultaneol,lsly;and if portable, the paint and the drying unit shall not
be brought into the spray room until the spraying operations have ceased.
(1) All fixed wiring above hazardous area shall conform to the provisions of Section 8.
(2) Equipment which may produce arcs, sparks, or particles of hot metal, such as lamps and
lampholders for fixed lighting, cutouts, switches, receptacles, motors or other equipment
having make-and-break or sliding contacts, where installed above a hazardous area or above
an area where freshly finished goods are handled, shall be of the totally enclosed type or
so constructed as to prevent the escape of sparks or hot metal particles.
(3) All metal raceways and all non-current-carrying metal portions of fixed or porta~le
equipment, regardless of voltage, shall be bonded to earth in accordance with ,Part I of
Section 7 of this Code.'
(1) Any pit or depression below the level of the hangar floor shall be considered to be a
Class I, Division 1 location which shall extend up to the floor level.
(2) The entire area of the hangar, including any adjacent and communication areas ~ot
suitably cut off from the hangar shall be considered to be Class I, Division 2 location up to
a level 450.0mm above the floor.
(3) The area within 105m horizontally from aircraft power plants, aircraft fuel tanks, or
aircraft structures containing fuel shall be considered to be a Class I, Division 2 location
which shall extend upward from the floor to a level1.5m above the upper surface of wings
and of engine enclosures.
(4) Adjacent area in which hazardous vapours are not likely to be released, such as stock
rooms, electrical control rooms, and other similar locations, may be classified as non-
hazardous when adequately ventilated and when effectively cut off from the hangar itself
in accordance with the provisions of Section 12.
(1) All fixed and portable wiring and equipment which is or may be installed or operated
within any of the hazardous locations defined in Clause 13.8.1 shall conform to the
requirements of Section 12.
(2) All wiring installation in or under the hangar floor shall conform to the requirements
for Class I, Division 1 locations.
(3) Wiring systems installed in pits or other spaces in or under the hangar floor shall be
provided with adequate drainage and shall not be placed in the same compartment with any
other service except piped compressed air.
(4) Attachment plugs and socket outlets in hazardous locations shall be explosion-proof?r
shall be so designed that they cannot be energized while the connections are being made
or broken.
(1) All fixed wiring in a hanger not within'a hazardous area as defined in Clause 13.8.1
shall be installed in metal raceways or shall be armoured cable, Type MI (Mineral-
Insulated) cable, or aluminium sheathed cable, except that wiring in a non-hazardous
location as set out in 13.8.1(4) may be of any type recognized in Section 8 as suitable for
the type of building and the occupancy.
(2) For pendants, flexible cord of the hard-usage type and containing a separate bonding
conductor shall be used.
(3) For portable utilization equipment and lamps, flexible cord approved for hard usage
and containing a separate bonding conductor shall be used.
(4) Suitable means shall be provided for maintaining continuity and adequacy of bonding
between the fixed wiring system and the non-current-carrying metal portions of pendant
fixtures, portable lamps and other portable utilization equipment.
(1) In locations other than those described in Clause 13.8.1, equipment which is less than
3.0m above wings and engine enclosures of aircraft and which may produce arcs, sparks, or
particles of hot metal, such as lamps and lanipholders for fixed lighting, cutouts, switches,
socket outlets, charging panels, generators, motors or other equipment having make-and-
break or sliding contacts, shall be of totally-enclosed type or· so constructed as to prevent
escape of sparks or hot metal particles, except that equipment in areas described in
13.8.1(4) may be of general purpose type.
(2) Lampholders of metal-shell-fibre-lined types shall not be used for fixed lighting.
14.1 SCOPE
(1) This Section of the Code applies to the installation of electrical wiring and equipment
within patient care areas of hospitals and those portions of the ele~trical systems of
hospitals designated as essential electrical systems.
14.2 NORMATIVEREFERENCES
(l) The following references contain provisions which, through reference in this text, constitute
provisions of the Ethiopian Building Code S~dard on Electrical Installation of Buildings: .
14.3· DEFI~ITIONS
(1) For the purpose of this Section, in addition to the terms defined in Section 1, the
following definitions shall apply:
anaesthetizing location any area of a health care facility where the induction and
maintenance of..general anaesthesia are routinely carried out in
the course of the examination or treatment of patients.
appUed part the part or parts of medical electrical' equipment including the
patient leads which come intentionally into contact 'Wi.,ththe
patient to be examined or treated.
body contact an intentional contact at the skin surface or internally, bur not
directly to the heart.
casual contact contact by voluntary action with a device that has no applied
part. and is not intended to be connected to a patient.
critical care area a patient care area in which anaesthetics are administered, or in
which cardiac contact between a patient and medical electrical
equipment is frequent or normal.
delayed vital branch that portion of an essential electrical" system'in which the
circuits require power restoration within 2.0min.
essential electrical system an electrical system which has the capability of restoring and
sustaining a supply of electrical energy to specified loads in the
event of a loss of the normal supply of energy.
hazard index for a given set of conditions in an isolated power system, the
current, expressed in milliamperes and consisting of resistive
and capacitive leakage and fault currents, that would flow
through low impendence if the low impendence were to be
connected between either isolated conductor and ground.
intermediate care area a patient care area in which body contact between a patient and
medical electrical equipment is frequent or normal.
line isolation monitor a device which measures and displays the total hazard index on
an isolated electrical system, and provides warning when the
index reaches a preset limit.
normal supply the main electrical supply into a building or building complex,
and may consist of one or more consumer services capable of
supplying all loads in the building complex.
patient care area an area intended primarily for the prqvision of diagnosis,
therapy, or care.
patient care location a zone in a patient care area which has been pre-selected for
the accommodation of a patient bed, table, or other supporting
mechanism, and for the accommodation of equipmentlnvolved
in patient treatment, and which includes the space within the
room 1.5m beyond the perimeter of the bed in its normal
location and to within 203m of the floor.
patient car~ location bonding point a common bus at a patient care location, that is
bonded to earth, and that serves as a common point
t6 which equipment and other bonding connections
can be made by means of a group of-jacks.
total hazard index the hazard index of a given isolated system with all appliances,
including the line isolation monitor, connected.
(1) The·branch circuits supplying socket outlets and permanently connected equipment in
basic care areas shall be supplied from an earthed distribution system.
(2) A branch circuit which supplies socket outlets or permanently connected medical
electrical equipment within a patient care location shall only supply loads within such
location.
(3) All branch circuits for a patient care location shall be supplied from a single
panelboard, except branch circuits intended to be part of an essential electrical 'system,
which shall then be permitted to be supplied from two panelboards, one of which is part
of the essential system.
(2) All socket outlets and other permanently connected equipment shall be bonded to earth
by copper equipment bonding conductors, sized not smaller than the minimum size required
for circuit conductors and, except as permitted by the supplying authority, run with the
circuitconductors in accordance with the following:
a) Each multi-wire branch circuit shall be provided with its own equipment bonding
conductor.
b) Except as permitted by (c) and (d) below, each 2-wire branch circuit supplying- a
socket outlet at a patient care location shall be provided with its own equipment
bonding conductor.
c) When the socket outlets at a patient care location are supplied from two 2-wire
branch circuits in the same raceway, a single equipment bonding conductor shall be
- permitted to be shared by the two circuits.
d) When socket outlet intended for a pair of adjacent patient care locations are
supplied by three 2-wire branch circuits and one of the circuits is intended to be
shared by both patient care locations, the three circuits shall be permitted to share
two equipment bonding conductors.
(3) Equipment bonding conductors required by (2) and (5) below shall terminate either at
the panelboard supplying the branch circuits to the patient care location from which they
arise or on an earthing bus which is bonded to that panelboard.
(4) Each item of 3-phase equipment shall be bonded to earth with an equipment bonding
conductor which is:
a) sized in accordance with Part I of Section 7 of this Code, but in no case smaller than
4.0mm2; and
b) connected to its own terminal at the equipment and the panelboard.
,
(5) Exposed non-curr9nt-carrying metal parts of communication, radio or television
equipment, other than telephone sets, at a patient care location, if they could become
energized, shall be bonded to earth by:
(1) Socket outlets intended for a given patient-care location shall be located so as to
minimize the likelihood of their inadvertent use for a patient-care location for which they
are not intended.
(2) Socket outlets which are located in areas that are routinely cleaned using liquids which
normally splash against the walls shall be installed not less than 300.0mm above the floor.
(3) Socket outlets located in bathrooms or washrooms within a patient care area shallbe
located:
a) adjacent to the wash basin, and
b) outside of any bathtub enclosure or shower stall.
(4) Socket outlets which are located adjacent to a washbasin in a patient care area shall be
protected by an earth fault circuit interrupter of the Class At type.
(1) The branch circuits supplying spcket outlets and other permanently connected
equipment in intermediate or critical care areas. shall be supplied from either an earth
system meeting the requirements of Section 14.4 or an isolated system meeting the
requirements of Section 14.6, except that all branch circuits, other than those supplying
multiphase equipment, shall be 2-wire circuits.
(1) Bonding to earth in intermediate and critical care areas shall conform to Clause 14.4.2
whether the supply is derived from an earthed or an isolated system.
t For definition of Class A earth-fault circuit interrupter, refer to Clause A.2, Annex A, Section 25.
(2) Where more than one single-phase isolated pow~r system serves a single location, the
earthing busses of all of these systems shall be bonded together with a copper bonding
conductor:
(2) Any disconnecting means controlling an isolated circuit shall safely and simultaneously
disconnect all unearthed conductors.
(3) A single-phase isolated system shall include automatic means (a line isolation monitor),
with an indicator located where visible to persons using the system, to monitor the
impedance-to-earth of the system together with any loads connected to it.
(5) A single-phase isolated system which supplies only a single load via a single branch
circuit shall meet the requirements of (1) through (3) above except that:
(1) An essential electrical system shall comprise those circuits that supply loads designated
by the hospital administration as being essential for the life safety and care of the patient,
and the effective operation of the hospital.
(2) An essential electrical system shall comprise at least a vital branch, and may also
include a delayed vital branch.
(3) The wiring of the essential electrical system shall be kept entirely independent of all
other wiring and equipment and shall not enter a ftxture, raceway, box or cabinet occupied
by other wiring except where necessary as in:
a) The switching means shall be mechanically held and the operation shall be by direct
manpower or by electrical remote manual control utilizing control power from the
supply to which the load is being transferred.
(4) The vital and delayed vital branches shall be connected to the emergency power supply
by means of one or more automatic transfer switches.
(1) An emergency supply shall be one or more generator sets driven by a prime mover and
located on the hospital premises in a fire-resistant enclosure or room, and in such a manner
as to minimize the possibility of flooding and damage.
(2) The prime mover of the generating set, as specified in (1) above, shall be capable of
operating independently of supplies of water and fuel from public utilities.
(3) A fuel supply sufficient to operate the prime mover under full load for at least 24.0hrs
shall be stored on the site.
15.1 SCOPE
(1) This Section applies to installation of interior and exterior lighting equipment.
15.2 NORMATIVEREFERENCES
(1) The following references contain provisions which, through reference in this text, constitute
provisions of the Ethiopian Building Code Standard on Electrical Installation of Buildings.
15.3.1 General
15.3.1.1 Material
(1) Material of lamps shall confirm, as regards the type of lamp, mechanical qualities and
insulation resistance, to applicable IEC or other international standards.
(1) Luminaires shall be constructed from such material and so finished that their s·afety,
performance or appearance does not deteriorate significantly during normal life when they
are operated in the condition for which they are designed.
15.3.1.3 Voltage
(1) Branch circuit voltages shall not exceed 230.0V -to-earth in dwelling units; and in other
than dwelling units, voltages shall not exceed the voltage-to-earth of nominal system 380.0V.
Note: Where 380.0V line-to-line system is used, the control switch shall be of double-pole type and the
luminaire shall be earthed.
15.3.1.4 Pro.tection
(4) High intensity discharge (HID) luminaries shall not be connected to a branch circuit
protected by overcurrent devices rated or set at more than:
~ 20.0A where the input voltage to the luminaire is not more than 230.0V nominal,
but not exceeding 380.0V nominal; and
b) 16.0A where the input voltage is above 380.0V nominal.
(1) Luminaries and lampholders shall be placed or guarded in such a manner as to prevent
ignition of any combustible materials.
(2) Any shade or guard used for the purpose in (1) above shall be, besides limiting the
temperature to which the combustible material may be subjected, suitable to withstand the
heat from the lamp.
a) shall be located on the ceiling or on the front wall above the door of the closet
unless mounted on the trim of the ,sidewalls of the doorway and approved for the
application; and
b) shall not be of pendant type.
(1) Luminaries in damp or wet locations shall be approved for such locations and be so
marked.
(1) A light fitting connected to an installation by means other than a socket outlet shall be
controlled by a switch which shall be arranged to disconnect all the supply conductors.
(2) The switch required by (1) above shall be separate from lighting fitting and in a readily
accessible position subject to the provisions (3) and (5) below, where applicable.
(5) Where lighting fittings are installed over readily combustible material, every light fitting
.shall be controlled by an individual wall switch.
(6) Where st~irway in a dwelling unit has risers, the lighting shall be controlled by
intermediate wall switches or their functional equivalent located at the head .and foot of the'
stairway.
(1) Luminaries, lampholders, and rosettes shall be installed so that no live part is exposed
to contact while they are in use.
(2) Where lampholders and switches have exposed accessible terminals, ,they shall not be
installed in metalluminaire canopies or in open bases of portable lamps.
15.3.3.2 Supports
(2) Where a luminaire weighs more than 30.0N or exceeds 40.0cm in any dimension, it
shall not be supported by the screw shell of the lampholders.
(3) Where a non-metallic outlet box of thermoplastic material, such as, for example, P.V.C,
is used to suspend a luminaire, care shall be taken to ensure that the temperature of the
box does not exceed 600Cj and the mass suspended shall not exceed 30.0N.
(4) Where the weight of a luminaire does not exceed lOO.ON,it shall be permitted to be
supported by an outlet box that is mounted on a bar hanger.
(5) Where a luminaire weights more than lOa. ON,it shall be suspended independently of
the outlet box, or by means of an acceptable fixture hanger with integral outlet box.
(1) Every outlet box used with lighting equipment shall be provided with a cover or covered
by a luminaire canopy lampholder, rosette, or other device.
(1) The recessed portion of every enclosure of a recessed luminaire shall be at least
12.5mm from combustible material at every point other than at a point of support.
(2) Every recessed luminaire shall be,so installed that any adjacent combustible material
is not subjected to temperature in excess of 90oe. •
(3) Recessed luminaries shall not b,e used when blanketed with thermal insulation unless
the luminaries are marked and approved for this use.
(1) Where a rigid luminaire or lampholder is located at a height of less than 2.1m above
the floor and is readily accessible, the luminaire or lampholder shall be protected from
mechanical injury by a guard or by location.
(1) Where luminaries are installed in gymnasiums or similar locations where the lamps are
normally exposed to damage from flying objects, the lamp shall be guarded by one of the
following means:
(1) Branch circuit conductors run through a luminaire shall be contained in a raceway
which is an integral part of the luminaire except that the conductor of a 2-wire, 3-wire, or
4-wire branch circuit supplying the luminaire may be carried through:
(2) Ballasts located within luminaries shall be deemed to be sources of heat and' the
conductors supplying the l\lminaries shall:
(1) AIl electrical wiring on or within -aluminaire, -beside ensuring its electrical safety, shall:
(1) Notwithstanding the requirements of Section 4 with regard to the colours used for
identifying conductors, a continuous-coloured tracer in the braid ~f individual braided
conductor shall be permitted for the supply conductors of a luminaire.
(1) Luminaries shall be wired with a conductor at least O.5mm2 cross sectional area, having
insulation suitable for voltage and temperatnre to which the conductors may be subjected.
(1) Stranded conductors shall be used on chain-type luminaire and other movable parts of
lighting equipment.
(2) Conductors shall be arranged so that the weight of the luminaire or that of the movable
parts do.es not place undue tension on the connections.
(3) All conductors which supply movable parts of lighting equipment shall be protected
against mechanical injury.
(1) Where pendant conductors are longer than 900.0mm, they shall be twisted together.
(1) Conductors for wiring recessed luminaire, branch circuit and tap connection shall have
insulation suitable for the temperature encountered.
(2) Branch circuit conductors shall be permitted to be run directly to the luminaire.
a) not be smaller than 1.0mm2 copper run in a factory-installed raceway or, if raceway
is provided but not factory assembled, smaller than 2.5mm2;
b) extend at least 1S0.0mm from the raceway; and
c) be installed in a raceway extending at least 450.0mm but not more than 2.0m from
the luminaire, and terminate in an outlet box located not less than 300.0mm from
the luminaire.
(4) The outlet box referred in (3c) above shall be accessible, and if access is through the
opening for mounting the luminaire or through some other opening in the ceiling, this
opening shall be not less than 200.0mm x 200.0mm and the outlet box shall be mounted
within 350.0mm of the opening.
(5) A supply connection box forming part of an approved luminaire assembly shall be
accessible, and if access is through the opening for mounting the luminaire, the following
requirements shall be met:
b) The cover of the supply connection box shall be capable of being removed by hand
tool held below ceiling.
(6) Branch-circuit conductors shall not pass through the supply connection box forming
part of an approved luminaire assembly unless the luminaire is approved and marked for
the purpose.
(1) Branch-circuit conductors having insulation suitable for 90°C shall be used for the
wiring of all ceiling outlet boxes on which a luminaire is, or may be, mounted; and the
ampacity of 90°C wire shall be limited to the ampacity of 60°C wire.
(1) Where show-window luminaries are closely spaced, they shall be permitted to be
connected to c;. conductor suitable for the purpose which is listed in Annex B of Section 4
with a temperature rating of not less than 125°C.
15.3.5.1 General
15.3.5.2 Lampholders
(1) Where centre-contact screw lampholders are connected to a source of supply having
an earthed neutral conductor, the outer or screwed contact shall be connected to that·
conducfor.
(2) Where lampho"lders in (1) above are used in circuits having neither pole connected with
earth or in any damp situation in which they can readily be touched by a person in contact
with or standing on earthed metal, they shall be provided with a protective shield of
insulating material or shall be placed or safeguarded so that neither the lamp cap nor the•
oute,r or screwed contact of the lampholder can inadverntly be touched when the l~mp cap
is engaged with the contact.
15.3.6.1 Transformer
(1) Luminaries which employ fluorescent lamps shall have thermally protected ballasts
except where the ballasts are of the simple reactance type.
(1) Reactors, capacitors, resistors, and other auxiliary equipment shall be:
a) enclosed within the liminaire,
b) enclosed within an accessible, permanently installed, metal cabinet where remote
from the luminaire, or
c) acceptable for use without an additional enclosure.
(2) The metaJ cabinet, if not part of the luminaire, shall be installed as close as possible
to the luminaire.
(3) Where display cases are not permanently installed, no part of a secondary circuit shall
be included in more than one case.
15;~.6.4 Control
(1) The luminaries. and lamp installations shall be CQp.trolledby a switch, circuit breaker,
or contact.or.
a) have a current rating of not less than twi~ the C\lfrent rating of the lamps or
transformers;
b) be a type approved with the assembly; or
c) be a manually-operated general use 380.0V a.c. switch.
15.4.1 General
15.4.1.1 Hazard
(1) Luminaire which employ fluorescent lamps shall hwe thermally protected ballasts
except where the ballasts are of the simple reactance type.
15.4.2.1 General
(1) Clause 15.4.2 shall apply to permanent, outdoor installations of floodlights of 300.0W
or larger where the floodlights are mounted on poles or towers.
(1) Service equipment shall comply with Section 5 of this Code; and where indoor
installation is installed outdoors, it shall be installed in an acceptable weather-proof
enclosure.
(2) Conductors buried directly in the earth shall be of types suitable for use in wet
locations ..
(3) Suitable corrosion-resistant protection shall be provided for aluminIum sheathed cables
and aluminium conduits, and also for mineral-insulated cable, if used where materials
coming into contact with the cable may have a deteriorating effect on the sheath.
(1) All electrical equipment on a pole shall be controlled by a switch which can be locked
in the "Off' position, and each pole shall be provided with a prominent sign warning against
climbing the pole until the switch is "Off' unless all conductors and live parts other than
those used for pole-top wiring are guarded against accidental contact in one of the
following ways:
b) The conductors and live parts are kept at least 1.0m from the climbing ladder or
climbing step.
c) Barriers are provided between conductors or live parts, or both, and the climbing
ladder so as to prevent a likelihood of contact by the climber.
(2) Conductors running up the centre of poles shall be supported so as to prevent jnjury
to the conductors inside the pole and so as to prevent undue strain on the conductor where
they leave the pole.
(3) Where vertical conductors, cables, and earthing conductors are within 2.5m oflocations
accessible to unauthorized persons, they shall be provided with a covering which gives
acceptable mechanical protection.
(4) On wood poles, for earthing conductors from lightning arresters, the protective covering
specified in (3) above shall be of wood moulding or other insulating material giving
equivalent protection.
(5) Where there is more than one branch circuits on a pole top, the feeders shall be run
to a distribution panelboard which shall be either weather-proof or installed in a weather-
proof enclosure.
Note: The panelboard may be omitted where there are two branch circuits on a 230/380.0Y circuits with a
common neutral lineand where there are three branch circuits on a 230/380.0Y, 3-phase, 4-wire circuits.
(6) Pole-top branch circuit wiring, exclusive of leads approved with floodlights to which
they are connected, shall be run:
(7) There shall be no joints or splices concealed within conduit; but open taps and joints
may be made in pole-top exposed wiring provided the joint or lap is given insulation
equivalent to that on the conductors jointed.
a) If mounted on floodlight poles, all live parts shall be guarded as required by (1)
above.
b) If mounted on poles, the bottom of the transformer shall be at least 5.0m above
locations accessible to unauthorized persons.
c) If located on platforms on the ground, they shall be completely enclosed so as to
prevent access by unauthorized persons or they shall be surrounded by a protecting
fence.
(11) Except for isolated metal parts such as cross bars, bolts, insulator pins, and the like,
all non-current-carrying metal parts of the electrical equipment at the pole-top shall be
bonded together and, if within reach of any earthed metal, they shall be earthed.
15.4.3.1 General
(l) Clause 15.4.3 shall apply to exposed wiring for permanent outdoor lighting other than
floodlighting where the circuits are run between buildiilgs, between poles, or between
buildings and poles.
15.4.3.2 C7olUiuctors
(1) Conductors shall be stranded copper, not less than 2.5m2, and shall be:
(1) Conductors shall be securely attached to insulators at each end of the run if a
messenger is not used and at the intermediate points of support, if there are any.
15.4~3.3.2Type of insulator
(1) Insulators at the ends of runs shall be of the strain type unless the conductors are
supported by messenger cables.
(1) Conductors supplying lamps in parking lots, used-car lots, drive-in establishments and
similar commercial areas shall be maintained such that the conductors or the bottom of a
lamp fed from the conductors, whichever is lower, shall have a clearance of not less than
4.0m above grade at any point in a run, except that where a driveway or through fare exists,
this clearance shall not be less than 4.0m.
(1) Conductors and lampholders shall be maintained at a distance not less than 1.0m from
any combustible material except for branch circuit conductors at the point of connection
to buildings or poles.
(1) Conductors shall be separated at least 300.0mm from each other by means of insulating
spacers at intervals of not more than 4.5m unless the conductors are secured t9 and '
supported by messenger cables.
15.4.3.7 Lampholders
c) have, when with permanently attached leads, the connection to the circuit wires
staggered where a cabled assembly is used.
i) if lampholders having permanently attached leads are used, and the span·
exceeds 12.0m; and
ii) in all cases where lampholders having termination which puncture the insulation
are used;
b) shall be securely attached at each end of the run and shall be earthed.
(1) Messenger cables shall be of galvanized steel, copper-coated steel, or stainless steel, and
shall be of a stranded construction with no less than seven strands.
(2) The effective ultimate strength of a messenger cable shall not be less than 3 times the
calculated maximum working load and in no case shall the individual strands be less than:
(1) Branch circuits shall be protected by overcurrent devices rated at not more than 32.0A.
(2) The total load on a branch circuit shall not exceed 80% of the rating or setting of the
overcurrent devices.
LIGHTING COLUMNS
Lighting column a support intended to hold one or more lanterns, consisting of one
of more parts: a post, possibly an extension piece and, if necessary,
a bracket. It does not include columns for catenary lighting.
nominal height the distance between the centreline of the point of entry of the
lantern and the intended ground level for a column planted in the
ground, or the flange plate, for a column with a flange plate as
shown in Figure A.i.
post-top columna straight column without bracket to support the lantern (post-top
lantern) directly.
bracket projection horizontal distance from the point of entry to the lantern to a
vertical line passing through the center of the cross section of the
column at the ground level as shown in Figure A.2.
w
The shape
of the bracket
is not speCified
,in this standard
'.
Figure A.2 Bracket projection
bracket fixing the connecting part on a column for securing a separate bracket. It
may be of the same size or a different cross section from the column.
lantern fixing the connecting part on the end of a post-top column or of a bracket
for securing a lantern. It may be the end of the column or the
bracket itself or an additional part having the same or a different
cross section from the column or bracket.
lantern fixing angle angle between the axis of the lantern fixing and the horizontal.
cable entry slot opening in a column below ground for cable entry.
planting depth the length of a column below the intended ground level as shown in
Figure A.3.
J!Y'~
,,',---,,'
)
base plate plate below ground level fixed to a planted column sinking into the
ground and to help prevent the column overturning as shown in
Figure A.4.
Base plate
flange plate a plate with an opening for cable entry, attached rigidly to a column
which is surface mounted, to allow it to be secured to a concrete
foundation or other structures as shown in Figure AS.
)
.~.
Flange plate
A.2.t Requirements
The dimensional requirements are specified except that the connection dimensions in
Clause A2.7 represent a recommended choice.
Nominal
...----_.
--.----_
------
---- -------.----
,_.~_.20
h...
18
15
12--
85
46
huillht
__ __
•• _ ••••• _ On_ •••••• .•...
___ .
3
10
·01 J~
w
Connection dimensions (see clause AZ.?)
Lantern fixing angle 5° or 15°
The shape
of the bracket
Is not specified
'\
in this standard
h
Nomine'
helohl
Projection
wll
to18
1B52
615
0.75
1,25
2
3
m~
~
Typo B1
For clause
see A1.5
base plate
Type B2 Type B3
For flange plate
see clousa AZ.t:
--~ ~
.'\ \
),
--- /"
// ~I
I
.._----
a
-._-~---
- • b
130
1'00
120
85
100
115
75
1301)
951)
1301)
600
400 500
- 900')
600
500
300
200
6801)
6801)
@J I
F''Jwe. A2·3
Position of door4) and cable entry slot
-.-
,50
l aa I~
........
-9
a 1.01
Fl! - -:~T II '>_, aUl
.-
1=lt'H~ A2.""
Dimensions of cutout
A.2.S Column foundation, planting depth and base plate (din .sians in rnillirnetres)
Nominal --
1700
2000
1000
600
-- -
mh 8
6
haight --
1500
1200
1500
1000
1200
1500
1200
1800
1000
300
2500
800
e1)
Planting dapth
10
18
15
12 20 <5
300 X 300
or
400 x 400
.~
1) The planting depth. e, shall be selected from the values given in the table taking into consideration the
calculations made before hand and the ground conditions.
j~
t'
, I
\ )
.~
/ /
c: I
III
-'J
L...
'
figure A2.B d2
Ii
300
sll 400 r M27 33 d2
22
400
30
500
700 ,11
500 h 300
200
M18
M24
d,1) 8
400
a260
c10 min.
400 M18
d,l1 min.
m M27
,20 ,I
! M24
" 12
<20 < 5
~l -;t 102
/tlO
-.---
76
dlJ1 13070
250
'1
(2 )
Fiuuro A 2.',1 Figure A2·~ b
Post top !;.oterns
} 60
42
d2J1
250
-- 100
100
'2
,
Figure
Figurll AZ.IOb
r
i {,!
+ 'x •.•
cu( .. j E
-l::: •• ~"I\II .
~\'\ \."I ~I I\
.
\
\ !
Lt
1) See clause A.2.1.
2) This design does not apply to concrete columns.
3) Diameters of steel spigots should be as given in ISO 64-1974 "Steel tubes, outside diameters" for steel
tubes of the nearest size.
16.1 SCOPE
(1) This Section describes the essentials of the fire alarm systems and applies to the
installation of local fire alarm systems and fire pumps.
(1) The following references contain provisions which, through reference in this text, constitute
provisions of the Ethiopian Building Code Standard on Electrical Installation of Buildings.
16.3 DEFINITIONS
(1) In addition to the terms defined in Section 1, the following definitions shall apply in
this Section:
alerting facility a facility which issues the fire alarm - e.g., by means of audible
and visual signalling devices - and which is not contained in the
fire alarm control and indicting panels.
automatic fire alarm system a system which detects the occurrence of fire in its incipient
stage and immediately signals this without human intervention.
automatic fire detector a part of a fire alarm system which, either continually or at periodic
intervals, observes a suitable physical and/or chemical identifier for
detecting a fire in the monitored area.
fire identifiers physical variables which are subject to measurable changes in the
environment of a fire in its incipient stage; e.g. rise in temperature,
smoke, flame radiation.
fire alarm signal a signal which alerts the fire fighting forces.
fire alarm system the entirety of the equipment and parts, matched for correct
interaction, used in a fire alarm system.
alarm box cdntrol room a facility from which the necessary fire fighting measures can be
initiated at all time.
false alarm a fire alann signal' caused by technical malfunctions in the fire
alann system (alann resulting from disturbance) or spurious alanns
resulting from the fire detector being "mislead".
non-automatic (manual) fire alarm devices alarm devices which can be used to initiate the
fire alann signals manually.
16.4.1 General
16.4.1.1 Design
a) the earliest possible definite warning of fire (i.e., avoiding false alann) is given to all
personnel immediately concerned;
b) it is capable of indicating the locality of the origin of the fire alann as to facilitate the
safe evacuation of the premises and to direct fire fighters; and
c) it performs its function with great reliability.
(1) The equipment, wiring and use of the fire alann system shall be exclusive to that system
and its power supply shall be provided independently from those for any other equipment.
(1) The audible and visual alann signals shall be used solely for the fire alann purpose, and
these signals shall not reset automatically.
(1) The fire alann and associated indicating panel shall be sited where they can be undet
constant observation when the premises are occupied and shall be accommodated in a room:
b) that provides adequate protection against ambient influences which could impair
operations; e.g. vibration, smoke, dust, gasses, vapour, etc. produced by ma.chinery, etc;
and
c) that has room climate suitable for proper operation of the fire alarm control and
indicating panel.
(1) If it is necessary to install the fire alarm equipment or wiring in situation where Jhere may
be an explosive or flammable atmosphere, the applicable Clauses of Section 12 shall be
observed.
16.4.2.1 General
(1) The design of a fire alarm circuit shall provide facilities for rapid and reliable transmission
of initiated signals when manual call points or detectors are operated and when specified faults
occur to control and indicating equipment.
(1) For sake of reliability, the number of circuit elements in the fire alarm system on which
alarm actuation depend shall be kept to a minimum.
(1) Any resultant signal shall be transmitted by the simplest possible circuitry to sounders and
other indicating equipment and to any equipment which is to be operated by the fire alarm
system; e,g. fire extinguishers, fire protection traps, local plant facilities, etc.
(1) Where chances of malfunction are high in a fire alarm system, discriminatory circuit shall
be incorporated in the system so that false alarms are identified.
(1) Except in buildings where fire can be located without delay, the fire alarm system shall
include an indication panel designed to show clearly the location of the origin of the alatm.
Note: To meet this requirement, suitable zones should be defmed throughout the building so that all the detectors
and/or manual call points in anyone zone are connected to an indicator exclusive to that zone.
16.4.3.1 General
(1) A manual call point shall be operated by a spring-loaded switch w~ich is held in
"non-alarm" position and protected from accidental operation by a cover usually of glass.
Breaking this glass cover releases the switch to an "alarm" position and the system starts to
operate. "1li :
a) be constructed of pressed metal, cast metal, or plastic materials so that they will not be
adversely affected' by the ambient temperature;
b) be rigid enough in construction to withstand the abuse to which they are likely to be
subjected, without deterioration or reduction in their ability to operate effectively when
required to do so;
c) have contacts that are capable of operating satisfactorily during the design life of the
installation;
d) be co loured "signal red" over at least 50% of their visible area;
e) have replaceable glass cover·; breaking the glass shall automatically operate the call
point, and shall include description'ofthe method of operation" by a concise inscription
• It is recognized that there are situations, e.g. food processing areas, where this type of call point is
unacceptable and there may be no alternative to using a suitable manual call point of the toggle-switch type with
safeguards against accidental operation.
The method of operation in an installation should be identical unless there is special reason for
variation.
including the word "FIRE" on case, or by a suitably inscribed plate behind the glass
cover; and
f) incorporate means whereby satisfactory operation may be readily and individually tested;
e.g. by opening the front by means of a special key.
16.4.3.3 Stricker
(1) A striker shall be provided adjacent to the call point to facilitate breaking the glass.
16.4.3.4 Placement
a) so located that no person need travel more than 30.0m from any position within the
premises in order to give fire alarm; .
b) located on the exit routes and, in particular, on the floor landing of staircases and on
exits to the street; and\~
c) fixed at a height of 104m above the floor at easily. accessible, well illuminated and
conspicuous positions free from obstruction.
(1) Where manual call points are incorporated in an automatic fire alarm system, they shall be·
included in such a way that the operation qf anyone of them produces the same effects as
though fire had been detected by a fire detector in the same zone.
16.4.4.1 General
(1) When selecting the type of detectors, the probable development of fire in the incipient stage,
the room height, the ambient conditions and all sources of spurious alarms in the areas to be
monitored shall be taken into consideration.
Note: The task of fire detectors is to detect a fire wherever possible in its incipient stage and signal this
automatically to an emergency service.
(1) If development of a smoldeJ;ing fire is anticipated in the incipient stage of fire (intense
smoke generation, very little or no flame radiation), smoke detectors shall be .used.
(2) If a rapid development of the fire is anticipated as early as in the incipient stage of a fire
(intense heat generation, intense flame radiation, and generation of smoke), smoke detectors, heat
detectors, flame detectors, or combinations of the various types of fire detectors shall be used.
Note: The fact is that combustion is not always accompanied by flame and the reflected radiation effect restricts the
application of flame detectors.
(3) Jf smoke damage is anticipated as early as the incipient stage of a fire owing to )'oom
occupancy (risk to human life, materials and goods sensitive to smoke), smoke detectors shall
be used.
(4) If a very rapid development of the fire is anticipated with a high degree of probability, an
automatic extinguisher system shall be considered.
(5) If it is not possible to predict or anticipate the development of a fire in the alarm ar~~
special investigation shall be conducted to assist in selecting the particular type of required fire
alarm detectors.
16.4.5.1 Monitoring
(1) Building and installation complexes shall be monitored or covered completely and each
effectively enclosed space shall be considered separately for this purpose in accordance with the
limits of spacing for the types of detectors concerned.
Notes: i) If, for some reason a fIre alarm system is not installed throughout a building or a related series of
buildings, the criterion shall be that the system will cover all of an area having physical boundaries of
such a nature as to provide adequate fIre separation or all of an area surrounded by sufficient open
space; e.g. roads, to provide adequate fIre separation.
ii) Voids not more than 800.0mm in height need not necessarily have independent monitoring.
Hi) Small lavatories and water closets need not have independent monitoring but; may rely upon that
provided in a lobby common thereto.
(1) Rooms divided into sections by walls, partitions or storage racks reaching 300.0mm of the
ceiling or where goods might be stacked in defined areas to a corresponding height, shall have
detectors for each section or passageway.
(1) Hoists, elevators and similar flue-like openings shall be monitored by detectors at the top.
16.4.5.4 Staircases
(l) Due to the requirements of the use to which any room, space, area or void is to be put or
to its structural features, installation of additional detectors shall be considered.
(1) Generally, the inter-relationship between the suitability of the various types of fire detectors
and room height indicated in Table 16.1 shall be observed.
(1) Heat sensitive point detectors shall be mounted so that their heat sensitive elements are
positioned not less than 25.0mm and not more than l50.0mm below the ceiling or the underside
of the roof.
Cat...
detectors Flame
w
Cat.
WW
RW
W
RW
W RRR detector
R 1 W
RR
R 2 Heat detectors
Cat. 3
Room height
(1) The spacing limits indicated on Table 16.2 shall be observed in sitting detectors.
(2) Notwithstanding the requirement in (1) above, the maximum spacing between detectors
cannot apply in all directions since the area limit shall be observed, but detectors shall not be
mounted closer than 500.0mm to any outside walls, separating walls or dividing partitions.
In15.0
In
3.5
7.5
In 10.0
corridors
corri.dors
Maximum
generalapart between
(horizontal)
centers
from dlatance
any Maximumpartitions
[m] or dividing
outside walls, (horizontal)
[m] distance
separating walls
In general
• In special buildings such as churcheli, mosques, museums and castles, it may be that detectors can only
be arranged at a great height unper certain circumstances. This will mean that an early fire warning cannot be
guaranteed. This render the use of the fire alarm less worthwhile .
•• Detectors are sub-divided into three response categories in line with the differing ceiling heights.
Sensitive detectors (e.g. detectors of response category 1) may be used for high ceiling.
16.4.6.3 Ceiling
(1) Where ceilings are crossed by beams, girders or other structural features having a depth of
·500.0mm or more, at least one detector shall be installed in each "pocket" fonned between such
features, and these detectors shall not be less than 500.0mm from any beam, guider or wall.
(1) One row of detectors shall be sited along the apex of each roof or bay; these and any further
detectors needed to cover the area shall be spaced in accordance with 16.4.6.2.
(1) Detectors shall be so sited that at least one on each floor is suitably placed within 105m of
hoists, elevators, stairways, well-holes, and similar openings to the floor above.
(1) Detectors fitted in lantern lights shall be protected from direct sunlight; fixed-tern perature- '.
type detectors shall be used in such location.
Note: Such locations are liable to rapid temperature variations due to combin/ltion of solar and internal heating and,
thus, ftxed-temperatere-type detectors are recommended.
(1) Where high and/or suddenly rising temperature owning to natural conditions or conditions
resulting from nonnal operation are likely, fixed-temperature detectors shall be used.
(2) The static response temperature of the detector section shall lie between lOoe and 35°C
abov.e the maximum temperature which can occur in the vicinity of the detector; and the
maximum temperature setting shall not exceed 88°e.
(1) If detectors have to be fitted where they will be subject to shock and/or vibration and may
also experience rapid temperature changes (e.g., in covering hoist apertures), a fusible alloy
fixeQ.-temperature-type shall be used.
Note: Vibration coinciding with rising, although not dangerously rising, temperature could induce false alanns from
other types.
(1) These detectors are affected by the same phenomenon as the point detectors, and the
recommendations given in Clause 16.4.6 shall be complied with.
16.4.9.1 General
(1) Smoke detectors shall normally be sitted at the highest parts of the enclosed areas, and shall
be mounted so that their sensing area is not less than 25.0mm or more than 600.Omm below roof
ceiling, except as may be indicated by site tests.
(1) The sitting of smoke detectors shall be arranged to take the effects of heat barrier.
Note: Wann air naturally collec~ under ceiling and in the apices of pitched roofs .. In some circumstances, this
wann air can form what is usually known as heat barrier to the products of combustion rising from fire which
is producing little change in the ambient condition. The combustion products from such a fire will spread out
below the heat barrier in the same way as they do beneath a ceiling or an apex of pitched roof.
(1) Factors affecting the sitting, number, etc. of the smoke detectors shall be considered
carefully and the necessary measures shalL be taken.
Note: Among facts which can establish temporary or permanent conditions which have their effect on the sitting
of smoke detectors are various forms of overhead heating, air-cooled equipment, roof or ceiling of unusual
shape, lofty buildings, staircases, canteen and restaurant, plant rooms, ambient air currents.
16.4.10.1 General
(2) In case of an automatic system, an additional sounder outside the building (preferably near
five brigades access) shall be installed.
a) Their type, number and location shall be such that the alarm is distinct from the
background noise in every part of the premises.
b) Their noise shall be quite distinct from any other sounders likely to be heard.
c) Alarm sounders of the same kind on a particular installation shall produce a similar
sound.
(1) Where a general alarm is undesirable (e.g. department stores, entertainment places,
hospitals), the alarm system shall be restricted to the provision of sounders out of the hearing
of the public or patients.
(2) The sounders should be supplemented by an adequate number of visual signals throughout
the premises for staff recognition only and/or by discrete special alerting facilities.
(1) Silencing switches shall only be installed for transferring an alarm or fault warning to a
supervisory sounders, and shall be so arranged as to put out of service the smallest practicable
number of manual call points and detectors.
(2) The operation of a silencing switch shall neither cancel the indications of the alarm or fault
on any indicator concerned while an alarm or fault condition exists nor prevent the proper
receipt of alarms or fault warnings on any circuit other than those with which the silencing
switch is associated.
(1) Where it is desired to distinguish between an alert and an evacuate signal, a two-stage alann
shall be used in which the first type of signal indicates an alert and the second type indicates a
need to evacuate the locality.
(2) The operation of a sounder shall not be prevented by a defect in a visual signal or
vice versa.
(3) In situations where a normal type of alarm sounder may be ineffective, e.g. where the
background noise is excessive or where the occupants are deaf, visual signals such as rotating
beacon lamps shall be used in addition.
a) alarm of fire is automatically transmitted over the public addr~ss system, taking priority
and over-riding every other facility and circuit conditions of the public address system;
b) other signals such meal-break, start and stop work, are not at any time broadcastby the
public address equipment in a manner which can be confused with a fire alarm signals;
c) during alarm conditions, all microphones are automatically disconnected, except one
designated a "fire microphone" which is retained in circuit so that it can be used for
announcements and instructions relating to the fire;
d) the power supply, cabling and wiring of the system shaH comply with the requirements
of this Section.
16.5 CABLESANDWIRING
16.5.1 Cables
16.5.1.1 General
(1) Cables shall have copper conductors and the cross-sectional area of the conductors shall be
selected on the basis of the current consumption of the equipment used and the line length.
(1) The insulation resistance of the individual cable with respect to earth shall at least be
400.0Kohm.
16.5.1.4 Suitability
(1) Cables shall be suitable for the purpose of the type listed in Annex B of Section 4.
(2) Notwithstanding the requirements in (I) above, cables smaller than 2.5mm2 installed in
raceway shall be equipment-wire type.
16.5.2.1 Installation
16.5.2.3 Segregation
(1) The conductors shall be installed so as to be entirely exclusive to a fire alarm installation
and the wiring of the alarm system shall be segregated from the wiring of any other circuits and
shall not enter a fixture, raceway, box or enclosure occupied by other wiring, except as may be
necessary for connection to:
(1) Fire-alarm wiring shall be spaced at least 50.0mm away from the circuits of any other
service.
(2) Notwithstanding the requirements in (1) above, where crossings are unavoidable, a bridge-
of suitable non-combustible insulating material, at least 6.0mm thick, shall be securely fitted to
maintain path in air of 50.0mm between circuits.
(1) All conductors contained in the same rl},cewayor cable shall be insulated for the highest
voltage in the raceway or cable.
(1) In order to reduce the likelihood of damage to fire-alarm cables by fire, main fire alann
wiring shall avoid lift wells, staircase, and other flue-like opening.
(1) If necessary, special measures shall be taken to protect the fire-alarm networks against
disruptive electrical influences (electrical interferences) resulting from lightning strike, switching
on high-power loads, electrical sparks of all types and electromagnetic waves.
(2) Any necessary connection point must be soldered or established using another very reliable
mechanical method.
(1) Exposed non-current-carrying metal parts of electrical equipment, including outlet boxes,
conductors, raceway, and cabinets, shall be bonded to earth in accordance with Section 7.
(1) Where a non-metallic wiring system is used, a bonding conductor shall be incorporated in
each cable and shall be sized in accordance with applicable Clauses of Section 7.
(1) The operating voltage of a fire alarm system shall not exceed 230.0V nominal whether
between conductors or· to earth.
(1) Two mutually independent power sources shall be provided for powering a fire alarm
system. The sources shall be:
Notes: i) Only batteries that are suitable for stationary operation and trickle-charging must be used.
ii) Where no mains supply is available, a primary battery may be used for powt:ring fire alarm systems
provided that a second similar battery in operational condition is held in reserve at all times.
16.7.3.1 General
a) be dimensioned such that unrestricted bperation of the system and the altering facilities
is guaranteed; and
b) also be able to supply the trickle charge current for the battery when the system is in
normal operating condition.
(1) A fire-alarm system shall be supplied by its own separate circuit connected as close as
practicable (without violating other Clauses of this Code) to:
16.7.3.3 Fusing
(1) A fire alarm's separate circuit shall be provided with its specially marked overcurrent device
, and disconnecting means which shall be clearly identified in a permanent, conspicuous and
)
legible manner as a fire alarm system; and the disconnecting means shall be co loured red and
lockable in the "ON" position.
(1) The charging facility shall be dimensioned such that it if capable of recharging a battery,
the charge state of which has dropped to the cut-off voltage, automatically to 80% of its nominal
voltage within a maximum period of 24 hours.
16.7.3.5 Interruption
(1) There shall be no possibility of the fire alarm system power supply being' interrupted as a
result of other plant facilities being switched off.
16.8.1 Conductors
(1) Conductors shall be of copper and shall have their ampacity in accordance with Section 4
and the requirements of the pump motor.
16.8.3.1 Box
(1) Where fire-pump equipment is connected to a consumers' service, a separate box for the fire
pump equipment shall be permitted.
(1) A service box for the fire pump equipment shall be permitted to be located remote from
other service box.
16.8.3.3 Labelling
(1) A service box for fire pump equipment shall be labelled in a conspicuous, legible, and
permanent manner with the letter "FIRE PUMP".
16.8.4 Protection
(1) The rating or setting of the over-current protection for feeders and branch circuits shall be
permitted to be selected to carry locked-rotor current of the motor(s) plus the rated current of
associated equipment on the circuit.
Note: Where the locked-rotor current is not marked on a motor, 600% of the rated current shall be considered to
be the locked-rotor current.
(1) The instantaneous short circuit characteristic shall be permitted to be selected or set at a
minimum of the normal load current of the associated equipment on the circuit plus 12 times
the full load current of the motor(s).
(1) The branch circuit conductors and control conductors or equ~pment of a fire pump shaU not
require overload or overheating protection and shall be permitted to be protected by the motor
branch-circuit over-current device(s).
Designations
...'H1i'
,"o...t- ~.
~,
..
'"V,
'"
VI
'M
on
,..... H
~I ,
""
'" l~ r:..
'8" I~/////~
'8' '8'
'8'
." 'if
g>---'ij'
II"joIN'
'"
In'''" '"
lilT •••"
1Il
Figure A.2 Example - Automatic fire alarm systems with non-automatic fire alarm
device
Jl4
r
)111
liS
2110 i.
4/1 (j.il
Jl12·
0 f, ~14
<'>
:i/lS
ll/ll I
III ..,ll~
Jll f, 1I1
IIG
1/1
1/4
.
III III
, ,I
II? , In 0 ~"IUMn.
'II '''fI'cIt IIwll
IIIUO '01{1
- - - ~ 11.".101
'II"
___ -0 t::t
)IlL)
Ilu,n MMII,,,.,
1111"' 102 - IU4IMAt
w.lIt
- - - -«£? lI.n
1"1 ~I (1l1l.lIn
,--- Rus.
--~----:
Fiu O'~'f1ftl~.~
(FWI
uE: 'lull,1 Pil'" IIPTI
IUI.I.,nlll"dt
hhln. COM'Clio"
ISA
Figure A.3 Installation plant of a fire alarm system with block circuit diagram
B.1.1 Introduction
Whilst there are but two basic call point control circuits, i.e. 'open circuit' and 'closed circuit',
simple definition of each can be misleading because, in practice, there are employed numerous
variations and combinations of each circuit.
The type of Circuit to be used should be determined by careful consideration of the functions
required from the fire alarm system in the particular building concerned, taking into account
simplicity, reliability, liability to damage, operational supervision, cost, environment and such
other relevant factors. It is unwise to assume, in general, that one type of circuit is better thl:!n
another.
Four simplified but typical, circuits are given below. Alarm and fault-sensing units may be
relays, solid-state circuits or similar devices; call points may have mechanical contacts, solid-
state circuits, variable-resistance devices, etc. It should be appreciated that many other circuit
arrangements are possible and the following circuits should in no way be considered other than
for the purpose of illustration.
B.1.2
Circuit I _ Open circu~ Alarm-sensing unit
o
1
. 0 supply
Figure B.I Open circuit
It
Open Circuit Call Point
Current flows when the call point contacts are closed, causing the alarm-sensing unit to operate
and initiate an alarm signal.
A broken connection/conductor will prevent a call point beyond the break from operating the
alarm-sensing unit.
A short-circuit between conductors will cause the alarm-sensing unit to operate, producing an
alarm signal.
Alarm-Sensing Unit
supply
o
Closed circuit call point
Current is n?rmally flowing through the cond~ctors and call points; the alarm-sensing unit is
hand operated.
When a call point's contacts are opened, the current is interrupted allowing the alarm-sensing
unit to release and initiate an alarm signal.
A short-circuit between conductors will allow the current to by-pass call points beyond the
short-circuit; thus, a call point beyond the short-circuit cannot interrupt the current and cannot,
therefore, initiate an alarm signal.
High-current '"
Limiting resistor.
Sensing Unit(alarm)
supply
The conductors are closed-circuit connected; a resistor limits the current through two sensing
units to a value sufficient to hold operated the low-current (faults) sensing unit, but insufficient
to operate the high-current (alarm) sensing unit.
Open circuit call points are connected across the conductors. Operation of a call point allows
the current to by~pass the resistor. The resultant increase in current operating the high-current
(alarm) sensing unit which initiates an alarm signal.
A broken connection/conductor will interrupt the current, releasing the low-current (fault)
sensing unit- which initiates a fault signal.
A short-circuit between conductors by-passes the resistor, the resultant increase in current
operates the high-current (alarm) sensing unit, which initiates an alarm signal.
/
/
The conductors are "closed circuit" connected, the open-circuit call points being wired in series,
their contacts being bridged by resistors. The values of the call point resistors and of the
limiting resistor are carefully chosen to ensure that the correct current flows in the circuit during
the various conditions of fault and alarm.
Under normal conditions, the current flowing in the circuit is sufficient to hold the low-current
(fault) sensing unit operational, but is insufficient to operate either the medium- or the high-
current alarm or fault-sensing units.
Operation of a call point by-passes its call point resistor. The resultant increase in current is
sufficient to operate the medium-current alarm-sensing unit, which initiates an alarm signal, but
is insufficient to operate the high-current fault-sensing unit.
A broken connection/conductor will interrupt the current, releasing the low-current fault-sensing
unit which initiates a fault signal.
A short-circuit between conductors by-passes the limiting resistor. The resultant increase in
current is sufficient to operate both the medium-current alarm and the high-current fault-sensing
units. The former's attempt to initiate an alarm signal is overridden by the latter and a fault
signal is initiated.
Study of the above circuits will indicate that each circuit has advantages and disadvantages.
Some of these are outlined in Clause B.2.
b.2.! Circuit 1
a) Advantages
b) Disadvantages
i) There will be no indication of a break in the circuit which may make some parts of
the system inoperative.
ii) A short-circuit between conductors will produce a false alarm.
B.2.2 Circuit:2
a) Advantages
b) Disadvantages
i) Current is consumed on stand-by; therefore, the size and cost of the battery and
charger will be increased.
ii) There will be no indication of a short-circuit between conductors which may make
some parts of the system inoperative.
iii) A broken connection or conductor will cause false alarm.
a) Advantages
b) Disadvantages
a) Advantages
b) Disadvantages
17.1 SCOPE
(1) This provisions of this Section apply to the installation of signs and outline lighting wherein
the source of light are:
a) incandescent lamps,
b) fluorescent lamps,
c) high-voltage luminous discharge tubes including neon tubes, and
d) high intensity discharge lamps.
Note: The word "sign", when used throughout this Section, includes those of the through-wall type.
17.2 NORMATI\%REFERENCES
(1) The following references contain provisions which, through reference in this text, constitute
provisions of the Ethiopian Building Code Standard on Electrical Installation of Buildings.
b) C22,1: 1990 Canadian Electrical Code, Part 1, Safety Standard for Electrical
Installation, Sixteenth Edition
17.3.1 Construction
(1) All signs and outline lighting apparatus, accessories, and fittings manufactured wholly or
in part in the field shall comply with the relevant requirements of:
(1) Each outline lighting installation and each sign other than the portable type shall be provided
with a disconnecting means which shall:
(1) Switches, flashers, and similar devices breaking inductive loads shall be either of a type
approved for the purpose or have a current rating of not less than twice the current rating of the
loads.
(1) Ballasts of the thermally-protected type shall be required for all signs and outline lighting
which employ fluorescent lamps except where the ballasts are of the simple reactance type.
(1) Circuits shall be arranged so that the load imposed by lamps and associated gears shall not
exceed 80% of the branch circuit overcurrent protection.
17.3.6 Location
(1) Signs and outline lighting shall be located so that all the following requirement are met:
a) Any person working thereon is not likely to come into contact with overhead conductors.
b) No part of the sign or its support will interfere with normal work operations performed
on electrical and communication utility lines.
c) No part of the sign or its support is in such proximity to overhead conductors as to
constitute a hazard.
17.3.7 Bonding
(1) All conductive non-current-carrying parts of the lighting installation shall be bonded to earth
in accordance with the requirements of Section 7 except for conductive parts of letters attached
to the building and illuminated from the rear.
(1) Sign leads which pass through the walls or partitions of the sign structure shall be protected
by non-combustible, moisture-absorption resisting bushings.
(1) Conductors for sign and outlying lighting shall be installed in accordance with the
requirement of Section 8.
(1) Fuseholder, flashers, etc. shall be enclosed in metal and shall-be accessible without the
necessity of removing obstructions or, otherwise, dismantling the sign.
17.4.1 Enclosure
17.4.1.1 General
(1) Enclosure for transformers, switches, timers, relays, sequencing units and other similar
devices shall be of metal or of heat and moisture resistant, non-combustible material.
17.4.1.2 Construction
(1) The enclosure shall be cC'nstructed to prevent the emission of flames or any burning or
ignited material.
17.4.1.3 Ventilation
(1) Openings for ventilation shall be arranged to comply with the requirement of 17.4.1.2 and
shall at least be 100.0mm from live parts.
17.4.1.4 Thickness
(1) Metal enclosures shall not be less than O.8mm thick and at the point where it is intended
that the supply connections be made, the enclosure shall be of not less than 1.6mm in thickness.
17.4.1.5 Marking
(1) Each enclosure housing a transformer shall be marked in accordance with the requirements •
of Clause 2.4.6.
(1) Doors or covers accessible to the general public and which give access to uninsulated parts
of indoor signs or outline lighting shall either be provided with interlock switches which, on the
opening of the doors or covers, disconnect the primary circuit or shall be fastened so that the
use of other than ordinary tools will be necessary to open them.
17.4.05 Transformers
(1) The rated secondary open-circuit voltage of transformers shall not exceed 15.0kV, except
as in (2) below.
(2) In end-earthed transformers, rated secondary open-circuit voltage shall not exceed 7.5kV.
.
f ••••.
(I) Transformers used outdoor shall be of the weather':'proof type or shall be enclosed in the
sign body or in a separate weather-proof box.
17.4.3.4 Installation
(1) Transformers shall be installed in such location that they are accessible and capable of being
removed and replaced.
(2) They shall be supported by attachment to the enclosure in which they are housed by at least
two studs or bolts.
(1) Each transformer shall be protected by an overcurrent device except that two or more
transformers may be protected by one ove-current device if their combined load does not exceed
12.0A.
a) transformer enclosure,
b) sign enclosure,
c) flexible metal conduit,
d) rigid conduit, or
e) other acceptable type of raceways except for surface raceways.
(1) High-voltage conductors may be run from the ends of gas tubes to the earthed midpoint of
transformers which have terminals at the midpoint.
17.4.4.3 Bends
(1) All high voltage conductors installed inside metal sign enclosures shall be of the
luminous-tube-sign type cables.
(1) In a metalic raceway and in a non-metallic raceway, cables not more than a total of 6.0m
and 16.0m, respectively, shall be run from transformer to other parts of the sign.
(1) Connection of high-voltage conductors to neon tubing outside the building or structure shall
be made by means of one of the following.
a) an electrode receptacle;
b) a direct connection in the neon tubing outside the building or structure wall provided that
not more than 1.0m of high-voltage wiring extends beyond the end of the raceway;
c) any other acceptable methods.
Note: The connection in (b) shall be electrically secure and provided with acceptable wrapping of insulating tape.
18.1 SCOPE
(1) This Section applies to the installation of electrical equipment for passenger, good's or
dual-purpose elevators (lifts), including dumbwaiters, escalators, movmg walks, freight platform
lifts, and elevating devices for the handicapped.
(1) The following references contain provisions which, through reference in this text, constitute
provisions of the Ethiopian Building Code Standard on Electrical Installation of Buildings.
a) C 22.1: 1990 Canadian Electric(il Code Part I, Safety Standard for Electrical
Installations, Sixteenth Edition.
18.3 GENERAL
(1) The nominal voltage used for lift operating control and signalling circuits, operating
equipment, driving machine motors, machine brakes, and motor generator sets shall not exceed
the following:
a) 380.0Y for operating control and signalling circuits and related equipment, including
door operator motors.
b) 750.0Y for driving motors, machine brakes, and motor-generator sets.
Exemption: Higher voltages shall be pennitted for driving motors of motor generator sets.
(1) All live parts of electric apparatus in hoistways, at landings or in or on the cars of lights and
dumbwaiters or in the well-ways or the landing of escalators, or moving walks shall be enclosed
to protect against accidental contact.
18.4 CONDUCTORS
(1) The conductors to the hoistway door interlocks from the hoistway riser shall be
flame-retardant and suitable for temperature of not less than 200°C.
(1) Travdling cables used as flexible connections between the lift car and the raceway shall be
of the types of lift cables or other approved type.
(1) All conductors in raceways, in or on the cars of lifts and dumbwaiters, in the well-ways of
escalators and moving walks, and in the machine room of lifts, escalators, and moving walks
shall have flame-retardant insulation.
(I) All conductors shall have an insulation voltage rating equal to at least the maximum nominal
circuit voltage rating of any conductor within the enclosure, cable or raceway.
(1) The minimum size of conductors used for lifts, dumbwaiters, escalators, and moving walk
wiring, other than conductors that forms an integral part of control equipment, shall be as follow:
(l) Conductors supplying lifts, dumbwaiters, escalator, or moving walk motors shall have an
ampacity of:
(a) if supplying single motor, not less than 150% of the motor full-load current rating.
(b) if supplying two or more motors, not less than 125% of the nameplate current rating
of the highest rated motor in the group plus the sum of the nameplate current ratings
of the remainder of the motors in the group.
18.5 WIRING
(l) Conductors located in hoistway, machine rooms and escalator well-ways, except travelling
cables, shall be installe~ in rigid metal conduit, electrical metallic tubing, or metal wireways,
except that flexible metal conduit or armoured cable shall be permitted only if not subjected to
mechanical damage.
Exemption: Mineral-insulated cable or aluminium-sheathed cable may be used if located so that there is no liability
of damage to the sheath.
(l) Conductors on lift and dumbwaiter cars shall be run in rigid metal conduit, electrical
metallic tubing, or wireways, except that:
a) short runs of flexible metal conduit or armoured cable may be used where they are
securely fastened in place and not exposed to oil or grease;
b) hard usage flexible cord shall be permitted to be used between fixed wiring on the car
and switching or sensing devices on the door or gate, and between the fixed car top
inspection light and an extension light controlled by the same switch, provided it is
securely fastened and so located as to not be subject to mechanical injury;
(1) In passenger lifts, at least one branch circuit shall be provided solely for the lighting and
accessories on each car.
(1) Where air conditioning units are installed on the car, they shall be supplied by separate
branch circuits.
(1) The overcurrent device protecting each branch circuit shall be located in the machine room.
(1) The sum of the cross-sectional area of the operating and control circuit conductors In
raceways shall not exceed 40% the interior cross-sectional area of the raceway.
18.6.2 Supports
(1) Supports for cables or raceways in a hoistway or in an escalator or moving walkways shall
be securely fastened to the guide rail or to hoistway well-way construction.
(1) Conductors for operating, control, power, signalling and lighting circuits of 600.0Y or less
shall be permitted to be run in the same travelling cable or raceway system if all conductors are
insulated for maximum voltage found in the cables or raceway system and if all live parts of the
equipment are insulated from earth for the maximum voltage.
(2) Such travelling cable or raceway in (1) above shall be pennitted to include shielded
conductors and/or one or more coaxial cable if such conductors are insulated for the maximum
voltage found in cable or raceway system. Conductors shall be pennitted to be covered with
suitable shielding for telephone, audio, video or higher frequency communication circuits.
(1) Main feeders for supplying power to lifts and dumbwaiters shall be installed outside the
hoistway (hoist shaft).
Note: Only wiring, raceways, and cables that are or form part of lift or dumbwaiter installation, including wiring
for signals, for communication with the car, for lighting, heating, air conditioning and ventilating th~ car,
for fire detecting systems, for pit pumps, and for heating and lighting the hoistway, shall be permitted inside
the hoistway.
(1) Electric equipment and wiring used for lifts, dumbwaiters, escalators, and moving walks in
garages shall comply with the requirements of Section 12 (Class I locations). Wiring and
equipment located on the underside of the car platfonn shall be considered as being located in
the hazardous area.
(1) Sidewalk lifts with sidewalk doors located exterior to the building shall have all electrical
wiring in metallic tubing and all electrical outlets, switches, junction boxes and fittings shall be
weather-proof.
18.7.1 Suspension
(1) Travelling cables shall be so suspended at the car and hoistway's ends as to reduce the strain
on the individual copper conductors to a minimum and shall be supported by one of the
following means:
c) by suspending from the supports by means that automatically tightens around the cable
when tension is increased for unsupported lengths upto 60.0m.
(1) In hazardous (classified) locations, travelling cables shall be of a type approved for
hazardous (classified) locations and shall be secured to explosion-proof cabinets.
(1) Travelling cable supports shall be so located as to reduce to a minimum the possibility of
damage due to the cable coming into contact with the hoistway construction or equipment in the
hoistway; and where necessary, suitable guards shall be provided to protect the cable against
damage.
18.7.4 Installation
(1) Travelling cable shall be permitted to be run without the use of raceway or conduit for a
distance not exceeding 1.8m from the first point of support on the lift car or hoistway wall
provided the conductors are grouped together and tapped or corded or in the original sheath.
(2) Travelling cables shall be permitted to be continued to lift control panels and to lift car and
machine room connections as fixed wiring provided they are suitably supported and protected
from damage.
18.8.1 General
(1) Lifts, dumbwaiters, escalators, and moving walks shall have a single means for
disconnecting all unearthed main power supply conductors for each unit.
(2) Where multiple driving machines are connected to a single lift, escalator, moving walk or
pumping unit, there shall be one disconnecting means to disconnect the motor(s) and control
devices.
(3) Where there is more than one driving machine in a machine room, disconnecting means
shall be number-marked to correspond to the number-mark of the driving machine which they
control.
18.8.2 Type
(1) The disconnecting means shall be an enclosed, externally operable, fused motor circuit
switch or circuit breaker to be locked in the open position.
(2) No provision shall be made to close the disconnecting means in (1) above from any other
part of the premises; nor shall circuit breakers be opened automatically by a fire alarm system.
18.8.3 Location
(1) Disconnecting means shall be located where they are readily accessible to qualified persons.
(1) Lifts. driven by polyphase alternating current shall be provided with a means to prevent
starting of the lift when:
(1) Hydraulic lifts powered by a polyphase alternating current motor shall be provided with the
means to prevent overheating of the drive system (pump and motor) due to phase-rotation
reversals or failure.
(1) Control and operating circuits and signalling circuits shall be protected against overcurrent
in accordance with the requirements of the relevant Clauses of Section 9.
18.9.2 Motors
(1) Duty on lift and dumbwaiter driving-machine motors and driving motors of motor-generators
used with generator field control shall be classed as non-continuous. Such motors shall be
protected against overcurrent in accordance with applicable Clauses of Section 11.
(1) Duty on escalators and moving-walk driving motors shall be classed as continuous. Such
motors shall be protected against overcurrent in accordance with applicable Clauses of
Section 11.
(1) Lifts, dumbwaiters, escalators, and moving walk driving machines, motor-generator sets,
motor controllers, and disconnecting means shall be installed in a room or enclosure set aside
for that purpose.
(2) The room or the enclosure in (1) above shall be secured against unauthorized access.
(1) Sufficient clear working space shall be provided around control panels and disconnecting
means to provide safe and convenient access to all live parts of the equipment necessary for
maintenance and adjustment.
18.11 EARTIllNG
(1) Metal raceways attached to lift cars shall be bonded to earthed metal parts of the car with
which they come into contact.
(1) For electric lifts, the frames of all motors, lift machines, controllers, and the metal
enclosures of all electric devices in or on the car or in the hoistway shall be earthed in
accordance with Section 7.
(1) For lifts other than electric and having any electric conductors attached to the car, the metal
frame of the car, where normally accessible to persons, shall be earthed in accordance with
Section 7.
18.11.4.1 Equipment
(1) Equipment mounted on members of an earthed structural metal frame of a building shall be
deemed to be bonded to earth.
(1) Metal car frames supported by metal hoisting cables attached to or running over metal
sheaves or drums of lift machines and affording metal-to-metal contact therewith shall be
deemed to be bonded to earth when the machine is bonded to earth in accordance with
Section 7.
18.12 OVERSPEED
(1) Under overhauling load conditions, a means shall be provided on the load side of each lift
power disconnecting means to prevent the lift from attaining a speed equal to the governor
tripping speed or a speed in excess of .125% of the lift rated speed, whichever is smaller.
(2) Overhauling load conditions shall include all loads upto rated lift loads for goods lifts and
all loads upto 125% for the rated lift loads for passenger lifts.
____ ~~~~~~~===~~~~========J.4
l
ELECTRICAL INSTALLATION OF BUILDINGS
(1) Motor generators driven by direct current motors and used to supply direct current for the
operation of lift machine motors shall be provided with speed-limiting devices that will prevent
the lift from attaining, at any time, a speed of more than 125% of its rated speed.
18.13.1 Supply
(1) A lift shall be permitted to operate from an emergency power supply in the event of normal
supply failure, provided the lift operates on such emergency power in accordance with the
emergency power system requirements of a recognized international safety code for lifts.
18.13.2 Disconnection
(1) The disconnecting means shall disconnect the emergency power service from the normal
power service.
(1) In the case of hydraulic lifts where emergency power is supplied from a second source for
lowering the car only, the disconnecting means shall be provided with an auxiliary contact that
is positively opened mechanically, the opening not being solely dependent on springs, and
connected in the control circuit to prevent movement of the car when the disconnecting means
is open.
18.14.1.1 Lighting
(1) Permanent provision of adequate artificial light shall be made in machine rooms of power
lifts.
(1) The machine room lighting switch shall be within easy reach of the entrance to the machine
room.
(1) At least one duplex (twin) socket outlet connected to 16.0A branch circuit supplying no
.othersocket outlets shall be installed in the machine room.
18.14.2.1 Luminaire
(I) -OneQf mote p.ennaAent luminaire equipped with a guar.d of metal, safety glass or suitable
plastic matedal shaH tbeprovided in aU pits.
The luminaires shall provide an illuminations level of at least lOO.O/x at the pit floor.
(I) A Hghtswitchshall 'be 'provided ,and shall be located so as lobe accessible from the pit
access door.
(1) At least one twin socket outlet connected to a 1'6:0A branch circuit supplying no other
socket outlet shall ,be installed in .each ;pit.
THEATRE INSTALLATION
19.1 SCOPE
(1) This Section applies to electrical equipment and their installations in buildings or parts' of
a building designed, intended, or used for drama, opera, motion picture, or other shows.
(1) The following reference contains provisions which, through reference in this text, constitute •
provisions of ,the Ethiopian Building Code Standard on Electrical Installation of Buildings.
a) C22.1: 1990 Canadian Electrical Code, Part 1, Safety Standard for Electrical
Installation, Sixteenth Edition.
(1) Wiring in stage and stage wing areas, orchestra pits, and projection booths shall be in rigid
metal conduit, armoured cable, lead-sheathed armoured cable, or aluminium-sheathed cable
except that:
(2) Surface raceways shall not be used on the stage side of the proscenium wall.
(3) Wiring in areas other than those listed in (1) above shall be in accordance with the
requirements of the appropriate Sections of this Code.
(4) Circuits for aisle lights located under seats may supply 30 outlets provided that the size of
lamp which can, be used with each outlet is limited by barriers or the equivalent to 25.0W or
less.
(2) Where a stage switchboard has exposed live parts on the back of the board, it shall be
enclosed by the walls of the building, by wire mesh grills, or by other acceptable methods.
19.4.1 Fuses
(1) All circuits leaving the switchboard shall have an overcurrent protection device connected
in each unearthed conductor.
\
/ /
19.4.3 Dimmers
(1) Dimmers shall be connected so as to' be dead when their respective circuit switches are
open.
(2) Dimmers which do Mt open the circuit may be connected in earthed neutral conductor.
(4) Dimmer faceplates shall be llf1'anged so thllta~cidental contact cannot readily be made with
the faceplate ContactS.
(1) Stage and galiery pockets shall be ~ontrolled from the switchboard.
19.4.5 Conductors
(1) Stage switchboards equipped with re's'istlve~'or transfortfied~typ'€ dimmer :switches ,shaH be
wired witheonductotshaving insulatio'nsuhable for the temperature generated therein; put in
no case shaH the design temperature be less than f2sot.
(2) Th'e conductors in (1) above shall have anampadty of hot less than that of the switch or
overcurtent device to which they are connected.
(3) Holes in the metal enclosure through which conductors pass shaH be bushed.
(4) The strands of the conductor shall be soldered together hefore they are fastened under!a
clamp or binding screw.
(5) Where a conductor of lO.Omm? or 'Of a larger size is connected toa terminal:
(1) portable switchboards shall be pla~ed within ~nclosure of substanti!ll construction; but they
may be arranged so that the enclosure is open during operation.
(2) Then~ shall be no live parts exposed wit.hin the, enclosure. ~x.cept thos~.on.dimmer faqeplates.
(1) Portable switchboards shall be supplied by means of flexible cord elf cable. of e.xtra"bard
usage type tenninating within the switchboard enclps\lre in an e~terncllly operated, en~loseQ~
fused master switch.
(2) The master switch in (1) llbove shall be arrMged so as tel cyt off qurr~l1t from all apparatus.
within the enclos\lre except the pilot light.
(3) The flexible cord or cable shall have sufficient ~apcity to carry the total load, CijITent of
the switchboard.
(4) The ampere-rating of the fuses of the m!lster switch shall not be greater than tile tQtlllloaQ
current of the swltehboCU'd.
19.6.1 FoptHght$
(1) Where footlights are wired in rigid metal conduit or electrical me.taJli9 tubing, every
lampholder shall b~ instllUed in an indivig)Jal outlet box.
(2) Where footlights are not wired in rigid metal conduit or electrical met/dUe tubing, the wiring
shall be installed in a metlll trough.
19.6.2 Metalwork
(1) The metalwork for footlights, borders, pro!!ceniu!ll sidelights, and strips shall not be les'"
than Q.8mm thick.
(2) The metalwork for bunches and portable strips shall be not less than O.5mm thick.
(1) The terminals of lampholders shall be separated from the metal of the trough by at least
13.0mm.
(1) Borders, proscenium sidelights, and strips shall be constructed so that the flanges of the
reflectors or other suitable guards protect the lamps from mechanical injury and from accidental
contact with scenery or other combustible material.
(1) Borders and strips shall be so suspended as to be electrically and mechanically safe.
(1) Conductors shall be soldered to the terminals of lampholders unless other suitable means are •
provided'to obtain positive and reliable connection under severe vibration. -,
(1) Where the lighting device are equipped with mogullampholders, the lighting devices shall
be constructed with double walls and with adequate ventilation between the walls.
(1) Foot, border, proscenium, and portable striplight fixtures assembled in the field shall be
wired with conductors having insulation suitable for the temperature at which the conductors will
be operated; but in no case shall the design temperature be less than 125°C.
(1) Branch circuits for footlights, border lights, and proscenium sidelights shall have overcurrent
protection in accordance with 15.3.1.4.
(1) Where. a pendent lighting device contains a lamp or group of lamps of more than IOO.OW
capacity, it shall be provided with a guard of not more than 13.0mm mesh so arranged as to
prevent damage from falling glass.
(1) Flexible cord or cable for border lights shall be of extra-hard-usage type.,
(2) The flexible cord or cable shall be fed from points on the grid iron or from other acceptable
overhead points; but they shall not be fed from side walls.
(3) The flexible cord or cable shall be arranged so that strain is taken from clamps and binding
screws.
(4) Where the flexible cord or cable passes through a metal or wooden enclosure, a metal
bushing shall be provided to protect the cord.
(5) Terminals or binding posts to which flexible cords or cables are connected inside the
switchboard enclosure shall be located so as to permit convenient access to them.
(1) Where the wiring to arc pockets is in rigid metal conduit or electrical metallic tubing, the,
end of the conduit or tubing shall be exposed at a point approximately 300.0mm away from the
pocket, and the wiring shall be continued in flexible metal conduit in the form of a loop at least
600.0mm long, with sufficient slack to permit the raising or lowering of the box.
(1) Socket outlets intended for the connection of arc lamps shall:
(2) Socket outlets intended for the connection of incandescent lamps shall:
(3) Plugs for arc and incandescent socket outlets shall not be interchangeable.
(1) Where stage flue dampers are released by an electrical device, the circuit operating the
device shall, in normal operation, be closed.
(2) The circuit shall be controlled by at least two single-pole switches enclosed in metal boxes
with self-closing doors without locks or latches.
(3) One switch shall be placed at the electrician's station and the other at a suitable place.
a) designed for the full voltage of the circuit to which it is connected, or resistance being
inserted;
b) located in the loft above the scenery; and
c) enclosed in a suitable metal box with a tight self-closing door.
(3) The stems of the fixtures shall be carried through to the back of the scenery and shall have
a suitable bushing on the end thereof.
(1) Joints in the wiring of string or festooned lights shall be staggered where practicable.
(2) Where the lamps of string or festooned lights are enclosed in paper lanterns, shades, or other
devices of combustible material, they shall be equipped with lamp guards.
(1) Flexible conductors for arc lamps, bunches, or other portable equipment shall be of extra-
hard-usage type cord or cable; but for separate miscellaneous portable devices operated under
conditions where the conductors are not exposed to severe mechanical injury, reinforced cords
of ordinary type may be used provided that they are protected by an overcurrent device rated
or set at not more than 16.0A.
(1) Portable equipment for stage effects shall be of a type acceptable for the purpose and shall ~
be so located that flames, sparks, or hot particles cannot come in contact with combustible
material.
20.1 SCOPE
a) the installation, operation and maintenance of emergency system and unit equipment
intended to supply illumination and to emergency systems intended to ~upply power,
where required by the authority having jurisdiction, and
(1) The following reference contains provisions which, through reference in this text, constitute
provisions of the Ethiopian Building Code Standard on Electrical Installation of Buildings.
a) C22.1: 1990 Canadian Electrical Code, Part 1, Safety Standard for Electrical
Installations, Sixteenth Edition.
20.3 GENERAL
20.3.1 Capacity
(1) Emergency systems and unit equipment shall have adequate capacity and rating to ensure
the satisfactory operation of all connected equipment when the general power supply fails.
20.3.2 Instruction
(1) Complete instructions for the operation and maintenance of the emergency system or unit
equipment which shall also specify testing at least once every month td ensure security of
operation, shall be posted on the premises in a frame under glass.
(1) When batteries are used as a source of supply, the batteries shall be kept:
20.3.4 Lamps
(1) Emergency lights shall be so arranged that the failure of one lamp will not leave the area
normally illuminated by it in total darkness.
20.3.5 Circuits
(1) No appliance or lamp, other than those req~ired for emergency purposes, shall be supplied
by the emergency circuits.
20.3.6.1 General
(1) The method of wiring, including that between unit equipment and remote lamps, shall be
in accordance with the provisions of Section 8.
20.3.6.2 Segregation
(1) The wiring shall be kept entirely independent of all other wiring and equipment and shall
not enter a fixture, raceway, box, or cabinet occupied by other wiring except, where necessary:
20.4.1 Supply
a) a storage battery of the rechargeable type having sufficient capacity to supply and
maintain the total load of the emergency circuits at not less than 91% of the full voltage
for the time period required by the authority having jurisdiction, but in no case less than
Y2hr, and be equipped with a charging means to maintain the battery in a charged
condition automatically.
Note: Automobile batteries and lead batteries not of the enclosed glass-jar type are not considered suitable.
iO.4.2 Control
(1) The current supply for emergency systems shall be controlled by an automatic transfer
switch which energizes the emergency system upon failure of the normal current supply and is
accessible only to authorized persons.
(1) No device capable of interrupting the circuit, other than the overcurrent device for the
current supply of the emergency system, shall be placed ahead of the branch circuit overcurrent
device.
(1) Every emergency system shall be equipped with audible and visual trouble signal devices
which give warning of derangement of the current source or sources and which indicate when
the emergency load is supplied from batteries or generators.
20.4.4.2 Wiring
a) they can be silenced, but a red-warning or trouble light shall continue to provide the
protective function, and
i) sound, thus indicating the necessity of restoring the s.ilencing switch to its normal
position, or
ii) reset automatically so as to sound for any subsequent operation 'of the emergency
system.
20.4.4.3 Voltagedrop
(1) The voltage drop in the wiring feeding lamps mounted remote from the 'currenfsupply shaH
not exceed 5% of the applied voltage.
20.S.1Mounting
(1) Each unit equipment shall be mounted with the bottom of enclosure not'less than 2.0m
above the floor wherever practicable.
Note: Unit equipment for 'emergency lighting is defined ,as an -item of equipment that:
i) is intended to provide automatically , in response to ,afailure of a power supply 'to which it is connected,
'specified ,light output and a specified amount of power for illumination purposes, for a specified period
of time, but in any case not :Iess than 30.0min;
ii) comptises,in 'a unit construction, a storage battery , 'charging means to maintain the battery in a charged
condition automatically, lamps, ·ot output terminals to which specifically listed lamps may be connected,
means to energize the lamps when the normal power supply fails and to de-energize the lamps when the
normal power supply is reStored, and means to indicate and test the operating conditions of the
equipment.
(1) Outlet point to which unit equipment is to be connected shall be not more than 1.5m.from
the location of the unit equipment.
(2) Where the above ratings are not exceeded, the unit equipment may be connected using the
flexible cord and attachment plug supplied with the equipment.
20.5.2.3 Installation
(1) Unit equipment shall be installed in such a manner that it will be automatically acthlated
upon the failure of the power supply to the normal lighting in the area covered by that unit
equipment.
20.5.2.4 Feeding
(1) Unit equipment shall be fed, where practicable, from the same panel board, and may be fed
from the same branch circuit which feeds the normal lighting in the area covered by that unit
equipment.
(1) The circuit conductors to lamps mounted remote from supply source shall be of such size
that the voltage drop does not exceed 5% of the marked output voltage of the unit equipment.
(1) The number of lamps connected to single equipment shall not result in a load that is in
excess of the watt output rating marked on the equipment for the required emergency period.
(1) The power supply for exit signs shall be provided from:
20.6.2 Wiring
(1) Exit signs shall be wired in accordance with the provisions of Section 8 of this Code.
21J. SCOPE
(1) This Section sets provisions and installation requirements that apply to motion-picture
studios, projection rooms, exchanges, factories and any building in which motion-picture
films, pyroxylin plastic and nitrocellulose x-ray and photographic films are manufactured,
projected, developed, printed, rewound, repaired or stored.
(1) The following r,eferencescontain provisions which, through reference in this text, constitute •
provisions ,ofthe Ethiopian Building Code Standard conElectrical Installat,ionof Buildings:
21.3 GENERAL
(1) The wiring method, unless specifiedofherwise in subclause·of'this Section, shall be rigid
conduit, steel electrical metallic tubing, or mineral-insulated cable.
(2) The wiring for stage-set lighting, stage. ,effects, electric equipment used as stage
properties, ,and other wiring not fixed as to location, shall 'be done with approved flexible
cords and cables.
(3) For portable lamps other than those used as properties in a motion-picture set on a
studio stage or similar location, the lamp holders shall be:
a) unswitched,
b) of composition or metal sheathed procelain, and
c) provided with a guard hook and handle.
(1) All lighting fixtures, except lamps forming an integral part of table equipment, shall be
of the totally-enclosed gasketted type.
(1) In rooms used for storage of pyroxylin plastic, no socket outlet or attachment plugs
shall be installed.
(2) .No electrical equipment other than that necessary for fixed lighting shall be installed
in film vaults.
(1) The wiring method in film-vault shall be rigid-conduit or mineral-insulated cable only,
with threaded joints at couplings boxes and fittings.
(2) Conduit or cable shall not run directly from vault to vault, but only form the switch to
the lighting fixture within the vault.
(3) Conduit shall be sealed off near the switch enclosure with a fitting and compound
approved for the purpose.
(l) Lighting fixtures in film vaults shall be of the explosion-proof type approved for the use
in Class I Group C hazardous locations and shall have metal cages or guards protecting the
globs.
j
~-L
(2) The fixtures in (1) above shall be located as close as practicable to the ceiling to avoid
their being damaged through handling of film containers.
(1) Fixtures shall be controlled by a double pole switch located outside the film vault.
(2) A red pilot light shall be provided to indicate when the switch is closed and shall be
located outside the film vault.
(3) Wiring shall be arranged so that, when the switch is off, all conductors within the film
vault will be dead.
(1) Incandescent lamps in projection rooms or booths shall be provided with a lamp guard
unless otherwise protected by noncombustible shades or other enclosures.
(1) Motor generator sets, frequency changers, transformers, rectifiers, rheostats, and similar
equipment for the supply or control of current to arc lamps or projectors shall be located
in a room separate from the projection room.
21.6.3 Ventilation
(1) Exhaust ventilation fans for the projection room shall be controlled from inside the
projection room.
(1) Motors and generators having brushes or sliding contacts, other than those used on
studio stages or those installed in accordance with Clause 21.6.2, shall be of approved dust-
tight or enclosed types.
22.1 SCOPE
(1) This Section of the Code applies to the installation of x-ray and other diagnostic
imaging equipment operating at any frequency. However, it does not specify safeguards
against direct, stray, or secondary radiation emitted by the equipment.
(1) The following references contain provisions which, through reference in this text, constitute
provisions of the Ethiopian Building Code Standard on Electrical Installation of Buildings:
22.3 DEFINITIONS
(1) For the purpose of this Section, in addition to the terms defined in Section 1, the following
definitions shall apply when referring to x-ray or computerized tomography equipment,
long-time rating a rating that is applicable for an operating period of5.0min or more.
momentary rating a rating that is applicable for an operating period of not more than
20.0s.
(1) High-voltage parts shall be mounted within metal enclosures that are bonded to eaith except
when installed in separate rooms or enclosures where a suitable switch shall be:
(2) High voltage parts of diagnostic imaging equipment shall be insulated from the enclosure.
(3) Conductors in the high voltage circuits shall be of the shock-proof type.
(1) Permanently connected diagnostic imaging equipment shall be connected to the power
source by means of a wiring method meeting the general requirements of this Code except that
equipment properly supplied by a bran~h circuit rated at not over 30.0A shall be permitted to
be supplied through a suitable attachment plug and hard-service cable or cord.
(2) Mobile diagnostic imaging equipment of any capacity may be connected to its power source
by ,suitable temporary connections and hard-usage cable or cord.
. (1) A disconnecting means of adequate capacity for at least 50% of the input required for the
momentary rating or 100% of the input required for the long-time rating of x-ray or·
computerized tomography equipment, whichever is greater, shall be provided in the supply
circuit in a location readily accessible from the radiation control.
(1) Capacitors fonning part of a diagnostic imaging equipment shall be provided with an
automatic means for discharging and grounding 11leplates whenever the transformer primary is
disconnected from the source of supply unless all current-carrying parts of the capacitors and of
the. conductors connected· therewith are:
a) at least 2.5m from the floor and .are inaccessible to unauthorized persons, or
b) within metal enclosures that are bonded to earth or within enclosures of insulating
material if within 2.5m of the floor.
22.8 CONTROL
(1) For stationary equipment, the low-voltage circuit of the step-up transfonner shall contain
an overcurrent device which:
(2) Where as in (I) above, the design of the step-up transfonner is such that branch fuses
having a current rating lower than that of the overcurrent device are required for adequate
protection for fluoroscopic and therapeutic circuits, they shall be added for the protection of
these circuits.
(3) For portable equipment, the requirements of (I) and (2) above shall apply; but, the
overcurrent device shall be located in or on the equipment except that no current-limiting device
is required when the high-voltage parts are within a single metal enclosure that is provided with
a means for bonding to earth.
(4) Where more than one piece of equipment is operated' from the same high-voltage circuit,
each piece or group of equipment, as a unit, shall be provided with a high-voltage switch or
equivalent disconnecting means.
(1) The ampacity of supply conductors and the rating of overcurrent protection devices shall not
be less than:
(2) Theampacity of conductors and the rating of overcurrent protection devices for two or more
branch circuits supplying x~ray or computerized tomography units shall not be less than:
a) the sum of the long-time current rating of all x-ray or computerized tomography units
which are intended to be operated at anyone time, or
b) the sum of SO% the mliximum momentary current rating for x-ray or ,computerized
tomography equipment on a radiographic setting for the two largest units plus 20% of
the maximum current rating of the other units.
22.10 .BONDING
(1) N on-current-carrying parts of tube stands, tables and other apparatus shall be bonded to
earth in accordance with the requirements of Part I" Section 7 of this Code.
23.1 SCOPE
(1) This Section applies to the installation of electrical communication systems including
infonnation processing systems.
(1) The following reference corttains provisions which, through reference In this text, constitute
provisions of the Ethiopian Building Code Standard on Electrical Installation of Buildings:
a) C221: 1990 Canadian Electrical Code Part 1, Safety Standard for Electrical
Installations, Sixteenth:'Edition.
23.3 GENERAL
.
23.3.1 Circuits in Communication Cables
(i) Radio and television circuits, remote control circuits, fire alarm circuits, or parts thereof
shall be:
(1) Where the wiring or electrical equipment within the scope of this Section' is installed in
hazardous locations as defined in Sections II, 12, or 14, it shall also comply with the applicable
Clauses of those Sections.
(1) Where transformers or other devices supplY current to a communication circuit from an -
electric' supply circuit, the transformers or other devices shall be of a type approved for the
service.
(1), Conductors shall be neatly arranged and'secured in place in a'convenient and workmanlike
manner.
(2) Raceways for communication circuitsihall be installed in accordance with the requirements
of Section 10 and, in case of metal, they shall be earthed in accordance with the provisions' of
Section 7.
23.4.2 Insulation
(1) Wire and cable used for communication system in a building shall be of the approved types
as specified in Annex B, Section 4 of this Standard.
(1) Where a conductor or cable is equipped with an outer metal covering, the covering shall be
earthed.
(1) The conductors of an electrical communication system in buildings shall be separated at least
50.0mm from any insulated conductor of a Class 1 circuit or an electric light or power system
operating at 380.0V or less, and shall be separated at least 600.0mm. from any insulated
conductor or an electric light or power system operating at more than 380.0V unless:
a) one system is in earthed metal raceways, metal sheathed cable, or earthed armoured
cable,
'b) the Class 1 circuit or electric light or power system operating at 380.0V or less utilizes
a nonmetallic sheathed cable or hard~llsage or extra-hard-usage flexible cord, or
c) both systems are permanently separated by a continuous, firmly fixed non-meta! raceway
in addition to the insulation of the conductors.
(2) Where the light or power conductors are bare, all communication conductors in the same
room or space shall be enclosed in an earthed metal raceway and no opening, such as an outlet
box, may be located within 2.0m of bare conductors of up to and including 15.0kV oLwithin
3.0m of bare conductors above 15.0kV.
(3) The conductors of an electrical communication system shall not be placed in any outlet box,
junction box, raceway, or similar fitting or compartment which contains conductors of electric
light or power systems or of Class I circuits (as defined in Section 10) unless:
a) the communication conductors are separated from the other conductors by an acceptable
partition, or
b) the power or Class 1 conductors are placed solely for the purpose of supplying power
to the communication system, or for connection to remote control equipment.
(4) The conductors of an electrical communication system in a building shall not be placed in
a shaft with the conductors of an electric light or power system unless:
a) the conductors of all systems are insulated and are separated by at least 50.0mm, or
b) the conductors of either system are encased in noncombustible tubing.
(1) Conductors of communication circuits extending through a fire separation shall be installed
so as to limit the spread of fire.
(2) All conductors, except travelling cables, shall be totally enclosed in continuous metal
raceway.
(3) Pullboxes required for communication interconnection shall be located outside the hoistway.
(1) Communication conductors shall not be placed in ducts or plenum chambers except as
permitted by relevant Clauses of Section 8.
(1) The interconnecting' cables used in data processing systems shall be permitted to eontain
power and communication conductors where SU9h cables are specifically approved for the
purpose.
(1) Where the ends of cables or conductors are not terminated on a device, they shall be capped
or taped.
23.4.11.1 General
(1) The provisions of Clause 23.4.11 apply to the installation of communication flat-cable-type
(CFC) systems which, together with the connecting devices, shall be approved or acceptable for
the purpose.
a) only under carpet squares not exceeding 7S0.0mm, and any adhesive used shall be of
release type;
b) as an extension Qf conventional wiring to serve areas or zones, and each run of wiring
from the transition point ~all not exceed IS.0m;
e) on floors heated in excess of 30°C only, if approved and identified for that purpose.
(1) Type CFC system wiring shall be covered with abrasion resistant tape, secured to the floor
so as to completely cover all cables, corners, and bare conductor ends.
23.4.11.5 Coverings
(1) Type CFC system wiring shall be permitted to cross over or under each other, and over or
under power supply system wiring provided there is a layer of earthed metal shielding between
the CFC and the power supply syste~ cables.
(1) Type CFC system wiring shall not be stacked on top of each other except as required to
enter the transition point.
(1) Type CFC system wiring equipped with.a metal shield shall be earthed.'
23.5 EQUIPMENT
(I) Communication equipment located in a bathroom shall be permanently fixed on the wall,
and shall be located so that no part may be reached or used from the bath or from the shower
enclosure; however, it shall be permitted to be actuated by means of a cord with an insulating
link. .
(1) Communication equipment and terminals shall not be placed in ducts, plenums, or hollow
spaces which are used to transport air nor in suspended ceiling areas except where a duct,
plenum, or hollow space is created by a suspended ceiling having lay-in panels or tiles;
connecting blocks which are a non-protective type may be installed provided they are placed in
an accessible enclosure.
(1) Communication circuits connected to a telecommunication network and having return path
via local earth or other circuitry which similarly could present a fire hazard, shall be provided
with a current-limiting device installed in or adjacent to the equipment of a type recommended
by the equipment manufacturer as suitable for the application, which will limit the current under
normal operating conditions and under fault conditions, to prevent fire hazards.
(1) The installation of overhead communication conductors on poles in proximity with power
conductors shall be established in conformity with the rules and regulations of the Ethiopian
Electric Light & Power Authority (EELP A.).
(1) Communication conductors passing over buildings shall be kept at least 2.5m above any roof
which may readily be walked upon.
(2) Communication conductors shall not be attached to the upper surfaces of roofs or be run
within 2.0m, measured vertically, of a roof without special permission.
(1) Separation of at least 2.0m shall, where practicable, be maintained between conductors of
communication circuits on buildings and lightning conductors.
(1) Where wires or cables are installed over or adjacent to swimming pools, they shall be paced
in accordance with the provisions of Clauses 25.4.2 and 25.4.3 of Section 25.
(1) Where communication conductors or cable assemblies are direct buried, the sheath shall be
suitable for direct burial and the conductor or cable assembly shall:
a) not be installed in the same vertical plane with other underground systems, except when
installed in accordance with (g) below;
c) not be less than 600.0mm deep, unless rock bottom is encountered at a shallower depth
in which case a minimum depth of 450.0mm shall be permitted, except that for service
wire under parkways and lawns, the depth may be reduced to 450.0mm;
d) be placed with a layer of sand 75.0mm deep, both above and below the cable, if in rocky
or stony ground;
e) not be less than 900.0mm deep under an area which is subject to vehicular traffic, except
that the depth may be reduced to 600.0mm when mechanical protection is provided,
which shall consist of:
i) treated plank at least 38.0mm thick or other acceptable material which shall be placed
over the conductor or cable after first backfilling with 75.0mm of sand or earth
containing no rocks or stones, or
ii) a conduit suitable for earth burial placed to facilitate cable replacement and to
minimize traffic vibration damage;
f) not be placed in a common trench involving random separation with power supply cables
or wires operating at over 750.0Y; and
g) have a metal sheath when placed in a common trench involving random separation with
power supply cables or wiring operating at 750.0Y or less, in which case the
communication conductor or cable assembly shall not cross under the supply cable~,.
(1) Where communication conductors or cable assemblies are placed in underground raceway
systems:
a) the raceway, including laterals, shall be separated from those used for the electric power
system by not less [han 50.0mm of concrete or 300.0mm of well-tamped earth;
b) the raceway shall be located to maintain minimum depth of 600.0mm in areas subject
to vehicular traffic and. 450.0mm in all other areas, except that where rock bottom is
encountered at a shallower depth, the raceway shall be encased in concrete;
c) the raceway shall not terminate in the same manhole, and the conductors or cable
assembly shall not be placed in the same manhole used for electric power system;
d) the cables shall not be placed in the same raceway containing electric lighting or power
supply cables; and
23.8 EARTHING
(1) Where cables, either overhead or underground, enter buildings, the metal sheath or shield
of the cable shall be bonded to earth as close as practicable to the point of entrance or shall be
interrupted as close as practicable to the point of entrance by an insulating joint or equivalent
device.
(1) The cable-sheath bonding conductor required by Clause 23.8.1 shall have an ampacity equal
to or greater than that of the outer conductive sheath of the exposed cable except that the
bonding conductor shall not be required to be larger than 10.0mm2 copper.
(1) Earthing conductor shall preferably be connected to a water-pipe earthing electrode as close
to the point of entrance as possible.
(2) Where waterpipe is not readily available and the earthing conductor of the power
consumer's service is connected to the water pipe at the building, the communication system
earthing conductor may be connected to the metal conduit, service equipment enclosures, or to
the earthing cond~ctor of the power consumer's service.
(3) In the absence of a waterpipe, the communication earthing conductor may be connected to
an effectively earthed metal structure or to"an earth rod or pipe driven into. permanently damp
earth; but:
a) steam, gas, or hot water pipes or lightning rod conductors shall not be used as earthing
electrodes; and
b) a driven rod or pipe used for earthing power circuits shall not be used as a
communication earthing electrode unless it is connected to the earthed conductor of a
multi-earthed power neutral.
(4) Where a driven earth rod or pipe is used as an earthing electrode for an electrical
communication system, it shall be separated by at least 2.0m from any other electrodes,
including those used for power circuits, radio, lightning rods, or for any other purpose and shall
be bonded only to that of the power circuits in accordance with applicable Clauses of Section 7.
(5) The normal length of driven earth rod used as the earthing electrode for a communication
system is 1.5m; but, where the normal rod would not reach moist soil when installed, a rod of
suitable additional length shall be used.
(1) The earthing conductor shall be attached to an earthing electrode by means of an approved
bolt clamp except that, in the case of an earth rod, a wire lead may be permanently connected
to the rod.
(2) Where a bolt clamp is used, the earthing conductor shall be soldered or otherwise acceptably
connected to the clamp in an effective manner.
(1) A copper conductor not smaller than 10.0mm2 shall be connected between communication
and power earthing electrodes when separate artificial earthing electrodes are required as
described per Clause 23.8.3.
24.1. SCOPE
(1) The following references contain provisions which, through reference in this text, constitute
provisions of the Ethiopian Building Code Standard on Electrical Installation of Buildings:
b) lEC 597 Aerials for the Reception of Sound and Television Broadcasting in
the Frequency Range 30.0MHZ to 1.0GHZ:
-.- -
SECTION 24: COMMUNITY ANTENNA INSTALLATION
c) IEC 728:1982 Cabled Distribution System Primarily Intended for Sound and
Television Signals Operating between 30.0MHz and 1.0GHz.
24.3.1 Mechanical
(1) A community antenna shall comply with' all mechanical properties or requirements outlined
in the IEC 597 and IEC 728.
24.3.2 Electrical
a) be desi.gned for the reception of signals within the permitted bandwidth for sound and
television broadcasting;
c) comply with all ether necessary electrical parameters that are required for the satisfactory
operation of the system (see IEC 597 and IEC 728).
24.4 EQUIPMENT
(1) Amplifiers and other devices which supply current to a community antenna distribution
circuit from an electric supply circuit shall be approved for the purpose.
(2) Where liIllplifiers and other power devices are connected to an electric supply circuit and
enclosed in a cabinet, the cabinet shall be so .located as to be readily accessible and shall be
adequately ventilated.
(3) The chassis and cabinets of the community antenna distribution amplifier or other power
sources, the outer conductive shield of the coaxial cables, and the metal conduit or the metal
cable sheath enclosing the electric supply conductors shall all be connected to the system earth
with a minimum of 16.0m2 copper conductor.
(4) Where a cabinet containing an amplifier or other power device is mounted accessible to the
public, it shall be provided with a lock or similar closing device.
(1) Exposed community antenna distribution equipment and/or associated terminations shall be
located in a suitable room or similar area, separate from electrical light or power installations,
except where necessary to place them in a joint-use room in which case a minimum separation
of 900.0mm from electrical equipment requiring adjustment and maintenance shall be provided
and maintained.
(1) Non-powered equipment and enclosures or equipment powered exclusively by the coaxial
cable shall be considered earthed when they are effectively connected to the earthed outer
conductive coaxial cable shield.
24.5.1 Conductor
(1) The conductors used in the distribution network shall consist of coaxial cable having inner
conductor and an outer conductive shield of circular cross-section .•
(2) Conductors placed within buildings shall be of the approved types as specified in Annex B,
Section 4, of this Code.
(3) Conductors placed outside of buildings shall be of the types that are acceptable for the
application.
(1) The coaxial cable shall be permitted to deliver low energy power to equipment directly
associated with the community antenna distribution circuits if the voltage is not over 60.0V and
if the current supply is from an approved amplifier, transformer, or other device having energy
limiting characteristics.
- - --
SECTION 24: COMMUNITY ANTENNA INSTALLATION
(1) Where the circuits or equipment within the scope of this Section are installed in hazardous
locations, they shall also comply with the applicable Clauses of Sections 12, 13 and 14.
24.5.4 Supports
(1) Where conductors are attached to or supported on buildings, the attachment or supporting
fixtures shall be acceptable for the purpose.
(1) Where coaxial cable is exposed to lightning or to accidental contact with lightning arrester
conductors or power conductors operating at voltage exceeding 380.0V-to-earth, the outer
conductive shield of the coaxial cable shall be earthed at the building as close to the point of
cable entry as possible.
(2) Where the outer conductive shield of a coaxial cable is earthed, no other protective device
shall be required.
(3) Earthing of a coaxial cable shield by means of a protective device shall be permitted -,
provided that the device does not interrupt the earthing system within the building.
(I) The earthing conductor for the outer conductive shield of a coaxial cable shall have rubber
insulation not less than O.8mm in thickness, and shall be covered by a substantial fibrous
covering except that conductors acceptable for the purpose, having less than O.8mm rubber
insulation, or having other kinds of insulation, may be used.
(4) The earthing conductor shall have an ampacity equal to or greater than that of the outer
conductive sheath of the exposed coaxial cable.
(5) Where two or more coaxial cables, which have outer conductive shields differing in size and
ampacity, join at a common connection to the earthing conductor, the ampacity of the earthing
conductor shall be equal to or exceed the ampacity of the largest coaxial outer conductive shield.
(6) The earthing conductor shall be run from the coaxial cable shield to the earthing electrode
in as straight a line as possible.
(7) The earthing conductor shall be protected in situations where it is or can be exposed to
mechanical damage.
(1) Earthing electrodes shall conform to the requirements of relevant Clauses of Section 7.
(2) Where artificial earthing electrodes are installed, they shall be in accordance with applicable
Clauses of Section 7 except that the minimum driven length of the rod electrode shall be 2.0m.
(3) Artificial earthing electrodes for community antenna distribution shall be spaced and bonded
with other electrodes in accordance with relevant Clause of Section 7.
(1) The earthing conductor shall be attached to an earthing electrode by means of.an approved
earth clamp except, in the case of an earth rod, a wire lead may be permanently connected to
the rod and the wire lead connected to the earthing conductor by means of pressure connector
or other acceptable means.
(2) Where an earth clamp is used, the earthing conductor shall be acceptably connected to the
clamp in an effective manner.
(1) Conductors of community antenna distribution circuits shall be separated at least 50.0mm
from insulated conductors of electric lighting, power, or Class 1 circuits operating at 380.0V or
less, and shall be separated at least 600.0mm from any insulated conductor of an electric
lighting, power, or Class 1 circuit operating at more than 380.0V unless effective separation is
afforded by use of:
a) earthing metal raceways for the community antenna distribution circuits, or for the
electric lighting, power and Class I circuits,
b) earthed metal sheathed or armoured cable for the electric lighting, power, and Class 1
conductors,
c) nonmetallic sheathed cable for the electric lighting, power, and Class 1 circuits operating
at 380.0V or less, or
(2) Where the electric lighting or power conductors are bare, all community antenna distribution
conductors in the same room or space shall be enclosed in an earthed metal raceway and no
opening, such as an outlet box, shall be located within 2.0m of bare conductors of up to and
including 15.0kV or within 3.0m of bare conductors above 15.0kV.
(3) The conductors of a community antenna: distribution circuit shall not be placed in any
raceway, compartment, outlet box, junction box, or similar fitting which contains conductors of
electric light, power, or Class I circuit unless:
a) the conductors of the community antenna distribution circuit are separated from the
electric light, power, or Class I circuit conductors by an acceptable barrier, or
b) the power or Class I conductors are placed solely for the purpose of supplying power
to the community antenna distribution circuit.
(1) Conductors of a community antenna distribution circuit extending through fire separation
shall be so installed as to limit fire spread.
(1) Community antenna distribution conductors shall not be placed in ducts or plenum chambers
except as permitted by relevant Clauses of Section 2 and Section 8 of this Code.
24.6.5 Raceways
(1) The installation of overhead community antenna distribution conductors in proximity with
power conductors on poles and in aerial spans between buildings, poles, and other structures
shall be established in conformity with rules and regulations of EELP A .
(1) Community antenna distribution conductors passing over buildings shall be kept at least
205m above any roof which may be readily walked upon.
(2) Community antenna distribution conductors shall not be attached to the upper surfaces of
roofs or be run within 205m, measured vertically, of a roof without special permission.
(1) Community antenna distribution conductors on buildings shall be separated from insulated
light or power conductors not in cable or conduit by at least 300.0mm unless, in addition to the
insulation on the conductors, they are permanently separated by a continuous and firmly fixed
non-metal type raceway as permitted in Section 8 0
(2) Community antenna distribution conductors subject to accidental contact with light or power
conductors operating at voltages exceeding 380.0V and attached exposed to buildings shall be
separated from combustible material by being supported on glass, porcelain, or other insulating
material acceptable for the purpose, except that such separation is not required where the outer
conductive sheath of the coaxial cable is earthed.
(3) Community antenna distribution conductors attached to buildings shall not conflict with
other communication conductors attached to the same building and sufficient clearance shall be
provided so that there will not be unnecessary interference to maintenance operations; and in no
case should the conductors, strand, or equipment of one system cause abrasion to the conductors,
strand, or equipment of the other system.
(1) The community antenna distribution conductors shall enter the building either thwugh a
noncombustible, non-absorptive insulating bushing or through a metal raceway except that the
insulating bushing or raceway may be omitted where the entering conductors pass through
masonry or are acceptable for the purpose.
(1) Where conductors are installed over or adjacent to swimming pools, they shall be placed in
accordance with the provisions of Clauses 25.4.2 and 25.4.3, Section25 of this Code.
(1) Where community antenna distribution conductors are direct buried, the sheath shall be
suitable for direct burial and the conductor shall be:
a) installed outside of the same vertical plane which contains differing underground
conductors other than communication conductors, except when installed in accordance
with (f) below;
d) placed with a layer of sand 75.0mm deep, both above and below the cable, if in rocky
or stony ground;
i) treated plank at least 38.0mm thick or other acceptable material which shall be placed
~ver the conductor or cable after first back-filling with 75.0mm of sand or earth
containing no rocks or stones; or
ii) a conduit suitable for earth burial placed to facilitate cable replacement and to
minimize traffic vibration damage; and
f) equipped with a metal shield when placed in a common trench involving random
separation with power supply cables or wiring operating at 750.0V or less, in which case
the community antenna distribution conductors shall not cross under the supply cables
(1) Where community antenna distribution conductors are placed in underground raceway
systems:
a) the raceway, including materials, shall be separated from those used for the electric
power system by not less than 50.0mm of concrete or 300.0mm of well-ta!T';,r..l -.alth;
b) the raceway shall be located to maintain a minimum depth of 600.0mm in areas subject
to vehicular traffic and 450.0mm in all other areas except that, where rock bottom it
encountered at shallower depth, the raceway shall be encased in concrete;
c) the raceway shall not terminate in the same manhole and the conductors or cable
assembly shall not be placed in the same manhole, used for electric power system,
d) the conductors shall not be placed in the same raceway containing electric lighting,
power or Class 1 circuit conductors; and
(1) Where the entire street circuit is run underground and the circuit is placed so. that it is not
liable to be in contact with electric lighting, power, or Class 1 circuits of more than 380.0V,
insulating bushings or raceways shall not be required where the circuit conductors enter a
building.
a) be provided for each lead-in conductor from an outdoor antenna to a receiving statio~
except where such lead-in conductor is protected by a continuous earthed metal shield
between the antenna and the point of entrance to the building;
b) be located outside the building or inside the building between the point of entrance or
the lead-in and the radio set or transformer, and as near as practicable to the entrance to
the conductors to the building; and
24.9.2.1 Material
(1) The earthing conductor shall be of copper, aluminium alloy, copper-clad steel, bronze, or
other corrosion-resistant material unless otherwise specified.
24.9.2.2 Insulation
24.9.2.3 Support
(1) The earthing conductor shall be securely fastened in place and may be directly attached to
the supporting surface without the use of insulating supports.
(1) The earthing conductor shall be protected where exposed to mechanical injury.
(1) The earthing conductor shall be run in as straight a line as is practicable from the lightning
arresters of antenna mast, or both, to the earthing electrode.
(1) The earthing conductor shall be connected to an earthing electrode as specified in Section 7.
(1) The earthing conductor may be run either inside or outside the building.
(1) The size of protective earthing conductor for receiving stations providing earth connection
for mast and lightning arresters shall be in accordance with the provisions of Section 7.
(1) A single earthing conductor may be used for both protective and operating purposes; but it
must be installed so that disconnection of the operating earth will not be after the protective
earth circuit.
_______
430 EBCS-10 1995 ETHIOPIAN BUILDING CODE STANDARD
ANNEX A (INFORMATIVE)
..
ANTENNA (AERIAL) SYSTEMSt
A.I GENERAL
A.I.1 Introduction
A.I.2 Terminology
individual antenna antenna installations that supply radio and television signals to
a single household. Modern household are provided with a
number of antenna sockets. To make an adequate signal level
available at each socket, amplifiers may also be required in
some individual antenna installations (see Figure A.I).
community antenna system antenna installations that supply radio and television signals to
households in one or more buildings. They consists of an
antenna assembly, a head station (amplifier unit) and the
distribution network including the cables, branch-in units,
antenna sockets and the associated receiver connection cables
(see Figure A.3).
private wide-band system a special fonn of the community antenna installation. The
signals to be received are fed to the private wide-band system
from a primary cable network (see Figure A.2).
Broadcast receiving antenna installations must comply with the requirements and regulations of
the Ethiopian Telecommunication Authority, if any, or shall meet the technical requirements
outlined in any applicable international standard.
A.2 PLANNING
Before the planning of a system ,is started, an accurate survey of the site should be carried out.
In the process, the followi~g data should be collected with the aid of the building plans 9r from
the direct observation:
Number and position of antenna sockets - Modem antenna system should be equipped with at
least two, and preferably three or four, antenna sockets per apartment. The number and position
of the sockets must be known for planning purposes.
Sound and television broadcast transmissions - The choice of transmission that are worth"
receiving depends on the reception conditions. If these are not known, measurement must be
undertaken with a suitable signal-strength meter.
Position of antenna - The antenna should be erected in the most satisfactory position for
reception and be as far positioned as possible from chimney and power cables.
A.3.1 General
The distribution system begins at the output of the head station and ends at the antenna socket
outlets. Its purpose is to provide reliable transmission of the signal from the head stations
through the sockets to the radio and television receivers.
Distribution boxes and branching boxes are generally referred to by the term "junction boxes".
Distribution boxes are advantageous where main feeders are run close together, e.g. in apartment
blocks and high-rise buildings, in which no long feeder lines are neGessary.
In long buildings or terrace houses, the use of branching boxes is more satisfactory.
Antenna socket outlets are distinguished according to their mode of application in the distribution
network and their transmission characteristics. Depending on the application, there are available
through-wired sockets, which are used in network arranged on the loop-through principle
(sockets fed in series, Figure AS) and spur sockets which are intended for main-feeder networks
arranged in the spur-line pattern (sockets fed in parallel, Figure A6).
In a combined distribution method, the sound radio and television signals are carried over the
same main reeders. The antenna socket outlets incorporate a socket for the sound radio and·
another for the television.
Figure A7 shows the combined distribution method applied to a community antenna system with
three television channels. Figure A8 provides a similar arrangement with six television channels.
Private wide-band cable-network systems supply subscribers on demand with radio and television
transmissions. These are comparable in terms of design to large community antenna systems.
The transmissions are obtained from a broadcast receiving station and relayed via cables and
amplifiers to system connection points on the perimeters of the private properties. Following
this, the received signals are amplified and fed to the antenna sockets (see Figure A.9).
A.4 PROTECTION
As a protection against accidental voltage transfer from the electrical installations, all inactive
conductive parts of the antenna system, such as the antenna post, housings, junction boxes and
amplifiers, outer conductors and metallic sheaths of the antenna cables should be connected
together and earthed, or included in the potential equalization system.
For potential equalization, a permanent connection must be made between the antenna system
and the main equipotential conductor (see Figure A.I 0).
A.5.l General
Reliable performance by radio and television receivers is dependent upon the careful planning
and competent construction of the aerial installation. Information relative to the length and
design of the antenna post is presented in Figure A.II and A.12.
The necessary length and strength of the post is determined by the number and separation of the
antennas. The upper end of the tubular post is usually closed by the LF/MFIHF and USW
antennas. The order of the other antennas is immaterial in itself. It is appropriate, however, to
mount the antennas that present a high wind load near the bottom so long as higher placing is
not called for on grounds of efficient reception.
Guidance values for the minimum separation "a" in centimeters, between the antennas on the
post are given in Table A.I. The separation should be increased for antennas with a larger
number of elements, particularly if they are aimed in the same direction.
The separation between the lowest antenna unit and the roof should be at least I.Om.
Table A.I Guidance values for the minimum separation "a" [em] between antennas on the spot
TV III 140 80 80 80 80
TVN 80 80 80 60 50
TVV 80 80 80 50 50
(AI)
A post should be chosen where permissible bending moment (from the manufacturer's data) is
at least equal to the calculated bending moment Mb in Equation (AI).
The capacity of the structural parts (buildings) to withstand the forces produced in the antenna
installation shall be verified.
The headstation is best mounted under the roof in the immediate vicinity of the antenna post
(Figure A13). It should be ensured that a loop is formed in the cable (a water trap) before it
enters the head station to prevent condensat.e from running out of the tabular post into the
amplifier (Figure A.14).
Such measurements should be carried out in commissioning as are necessary to prove the
technical performance of the aerial system.
Table A.3 shows a measurement schedule, representing a community antenna system in tabular
form, in which the test points and the required measurements are detailed and the results record.
To assess picture quality, the assessment symbols given in Table A.2 should be entered in the
measurement schedule.
For reflected
interference
(8) relative to picture
Not
Just
Not 5Assessment
one half
times
visible
visible
visible
Clearly SO
S2
S3 a12 G3
3S1R2
R1
R3
RO GO criteria
G2
G1 Forchannel
interference common
(G) Assessment grades
signal
interference
(R)
nce
In recording the amplifier output signal level in the headstation, the signal levels from the
individual band amplifiers (LF/MF/HF, USW, VHF, UHF) are measured using a calibrated
receiver and compared with the maximum permissible output signal levels of the amplifiers
according to the manufacturers' data. In this process, the manufacturer's instructions for the
measurements and for the proper adjustment of the amplifiers should be followed.
A.6.3 Maintenance
Trouble- free operation of the aerial system is assisted by regular checking of the mechanical and
electrical components.
a) Aerial structure:
- Orientation of aerials,
- Fixing clamps,
- Sealing of roof lead-in,
Seating of earthing clamps.
b) Headstation:
- Measurements as for commissioning at test points TPI and TP2.
- The checking and measurement results from each maintenance operation should be
recorded in a suitable schedule Table A.4 for comparison with other tests.
cable of
each
lead main
, receiver
FN5.W
cable
~2 spur
dB
Attenuati
LF/MF
'!"N
IV
MeasurementsOutput
Ouput ~hum,
xposition
LF/MF~94
ote of -6
Test-point
End of dB TV
TV)
Signal-level
of
(Values
of USW xxIVN~84
and
Observe
aerial'
TV IIII
xx commissioning
catalogue
relativehiss
~84
permissible
"lining-up"
level
Sound quality
in IVN ~S4
sound
mono
11~84
s80
~S2
stereo xreference
data
to~S7
measurement'
according
dBI!V)
x
carrier
~40
maximum (see
Picture
~SO
output
to signal
instructions)
quality
x
signal levels in
n
noise
--TPOon
Recommended
distortio
introduc
and
cracking,
--TP3
--TPI
~'TP2 FIMFI
"
additionalhead
ed
the
measurements
by
TV channels
between vision
connecting station
or
Difference
~
1) For sound broadcast transmissions, the selectively measured carriers: at least the Lm,s. values of the local and district
transmitters in the LF, MF, HF and USW bands should be measured,
For television transmissions, the channel signal levels (the r,m.s, level of the vision carrier at the point where the
synchronizing pulses occur) in the receiving or distribution channels
Ch .../. ..
G5TP1
TP2
Amplifier
R TP2R- f------
t-- TP2
[dB]
'.hum, Name:
Assessment
Date:
Picture
~ignalleve
nB,nt
dB"V aRof sound:
Name:
quality
chrackling,
Date:
TP1
Date:
noise, hiss) [dB]
Geometry,
I mechanical j-----
Name:
TP1 firmness lSignal leve
.../.
Aerial
Ch ...
.. / ....... structure:
./..
./...
.1...
Sealing
Seating of roofclamps
Equipotential
of earthing lead-in
bonding
DO DO Aerial sockel·
a) With one aerial socket b) With two aerial sockets and an amplifier
'CP 10 WC nolWolk
In basement' '
Apartment building
Aar\ill structure
Figure A.2 Private wide-band systems
MWl -4 I I • '
caol, I 2'WlY I ). .•••
ay.
: dlSUlDullOfl t Ol$UlbYllOt\ l14.'#j'V
d"lfibullOn
Sino"
blanf\lng
OtSlr1OUl!Of'it 00 ••0"
caDIt. I brHM:/\JnQ
"r-~-ll"
~ ~ f'J"r- '[1' r--u-ffr--.---""'l'----
--At:... DO' •••"n"b"_~:
l :: II II .:::: I
:I ::
II ~
: I::I II:I: I II :I
O'SU'10uhOn l;iol •• DlllllbuiiOt'l "1>1' OllUlbuuOl tlOll
Oi.lnbYlio-l , .
~~DULIOn
eaol.
ttlITMlling;ft$ISIOf (7$ OJ
II
Ch
~I ~'
Ch I
I I 6· Ch 21 USW
t
IIIII
'ft
C~2
Ch
th8
'ft
tlFI
I 12 eh 3~ Ch 8 II LF/MFI
Figure A.7 Community aerial system for LF MF, Figure A.8 Community aerial system for LF,
HF and USW reception and three MF, HF and USW reception and six
television transmission television transmissions
\
\
I
I
I
I
cuismm'l
III
1:1,L2: L1 - Phis.
I conductors
I N - neultill conductor
I
I
I
LF/MF/HF aenal
f
IV,
USWaerial
UHF aerial
1,-
I
I
L
a
a
J
VHF~al
Figure A.l1 Data relevant to the length of, an Figure A.12 Data relevant to the design of an
aerial post aerial post
I'
I
Ring section complelely
lemovl1d oV,era lenglh 015 mm
allhe Ipwesl point ollhe waler
Irap or,shealh
25.1 SCOPE
(1) This Section applies to electrical installations, electrical equipment in or adjacent to pools,
and non-electrical metal accessories in a pool or within 3.0m of the inside wall of a pool.
Note: The tenn "pool", as referred to in this Section, is deemed to include permanently installed and storable pools,
hydromassage bathtub, spas and hot tubs, wadding pools, baptismal pools,'and decorative pools.
(1) The following reference contains provisions which, through reference in this text, constitute
provisions of the Ethiopian Building Code Standard on Electrical Installation of Buildings:
a) C 22.1: 1990 Canadian Electrical Code, Part 1, Safety Standard Electrical Installation,
Sixteenth Edition.
25.3 DEFINITIONS
(1) In this Section, in additions to the terms defined in Section 1, the following definitions shall
apply:
permanently installed swimming pool a pool constructed in such a manner that it cannot be
disassembled for storage.
dry-niche Luminaire a luminaire intended for installation in the wall of a pool in a niche
which is sealed against the entry of pool water by a fixed lens.
spa or hot tub a pool or tub designed for the immersion of persons in heated water
circulated in closed system incorporating a filter, heater, pump, and
with or without a motor driven blower, but not intended to be filled
and drained with each use.
leakage current collector a section of corrosion resistant metal tubing. at least five times as
long as its diameter, provided with a brazed or welded copper lug
.placed in a run of nonmetallic pipe to provide a path to earth for
currerit leakage originating from device in contact with pool water.
decorative pool a pool that could be used as a wadding pool that is larger than
1.5m in any dimensions and that is readily accessible to the public.
25.4 GENERAL
(1) Equipment shall not be installed in the walls nor in the water of pools except as permitted
by this Section.
25.4.2.1 General
(1) There shall not be ~y overhead wiring above the pool, diving structures, observation stand,
tower or platform, or above the area extending 3.0m horizontally from the pool edge (see
Figure 25.1) except as permitted by 25.4.2.2 and 25.4.2.3.
(1) Conductors other than those covered by 25.4.2.2 and operating at not more than 50.0~Y
phase-to-phase shall be permitted to be located above a pool, diving structure, observation stand,
tower or plate, or above the area extending 3.0m horizontally from the pool edge provided there
is a clearance measured radially of at least 7.5m.
(1) The horizontal separation between the inside walls of pool and underground conductors,
except for bonding conductors or conductors supplying electrical equipment associated with the
pool and protected by an earth fault circuit breaker, shall be not less than that shown in
Table 25.1.
,
0.75
2.00
1.50
0.75
raceways 4.00
3.00
0.75in 1.5
Conductor underground
Conductor Minimum
buried directly in
separation [m]
0- 750.0V
25.4.4.1 General
(1) The metal parts ofthe pool and other non-electrical equipment associated with the pool such
as piping, pool reinforcing steel, ladders, diving board supports, and fences within 1.5m of the
pool, shall be bonded together and to' non-current carrying metal parts of electrical equipment
such as decorative type-pool luminaries and lighting equipment not located in a forming shells,
metal screens of shields for underwater speakers, conduit, junction boxes, and the like by a
copper bonding conductor.
Exemption: The metal parts of a pool need not be bonded to earth or to each other where the electrical equipment
associated with the pool is:
(1) Pool reinforcing steel shall be bonded with a minimum of four connections equally spaced
around the perimeter.
a) no smaller than 16.0mm2 for permanently installed pools and for all in-ground pools; or
b) as required by Table 7.1 of Section 7 for all other pools.
(1) Metal sheath and raceways shall not be relied upon as the bonding medium and separate
copper bonding conductor shall be used.
Exemptions: a) A metallic conductor between a forming shell and its associated junction box shall be permitted to
be used as the bonding medium provided the forming shell and junction box are installed in the same
structural section.
b) The bonding conductor shall be of copper and not smaller than that required by Table 7.1.
(1) The bonding conductor from the junction box referred to in Clause 25.4.5 shall be run to
the main distribution board, and, if it is smaller than 16.0mm2, it shall be installed and
mechanically protected in the same manner as the circuit conductor.
25.4.5.1 General
a) shall be permitted to be submerged in decorative pools provided the boxes are marked
for such· usage; and
b) conduits shall be water-tight and provided with a packing seal that will seal\around the
cord and effectively prevent water from entering the box through the conduit from the
forming shell.
(I) Junction "installed on the supply side of conduits extending to fonning shells, referred
hereinafter as "deck boxes", shall be specifically approved for the purpose and shall:
b) not contain the conductors of any circuits other than those used exclusively to s\lPply the
underwater equipment; and
c) be provided with electrical continuity between every connected metal conduit and the
bonding tenninals by means of copper, brass or other corrosion-resistant metal that is
integral with the box.
25.4.6.1 Location
(1) Transfonners shall not be located within 3.0m of the inside wall of the pool unless suitably
separated from the pool area by a fence, wall or other penn anent barrier which will make the
transfonner not accessible to persons using the pool area.
25.4.6.2 Bonding
(I) A metal shield, if provided between the primary and secondary windings of a transfonner,
shall be bonded to earth.
a) be connected between the audio output terminals of each amplifier and any loudspeaker
which is located within 3.0m of the pool wall; and
b) be located in or adjacent to the amplifier with which they are used; and
c) have an audio output voltage of not more than 75.0V r.m.s.
25.4.7.1 Location
(1) Socket outlets shall not be located within 1.5m of the inside walls of the pools.
25.4.7.2 Protection
(1) Sockcl Dutlets located between 1.5m and 3.0m of the inside wall of a pool shall be prote~ted
by an earth-fault circuit breaker.
Note: In maintaining the dimensions referred to in Clause 25.4.7, the distance to be measured is the shortest path
that the power supply cord of an appliance connected to the socket outlet would follow without piercing a
building floor, wall, or ceiling.
25.4.8.1.1 General
(1) Wet-niche luminaries shall, except for decorative pools, be mounted in forming shells which
shall have provision for suitable connection to the wiring method used.
(1) Wet-niche luminaries shall, unless specifically approved and marked for submersion at a
greater depth, not be submersed in the pool water at a depth of more than 600.0mm, such
distance being measured from the centre of the lense face of the luminaire to the normal water
level.
25.4.8.1.3 Voltage
(1) Wet-niche luminaire shall operate with neither the supply voltage to the luminaire nor the
associated ballast or transformer, if applicable, nor the secondary open-circuit voltage of the
ballast or transformer exceeding 230.0V during either starting or operating voltage.
25.4.8.2.1 Voltage
(1) Where dry-niche luminaries are installed so as to be accessible from a walkway or a service
tunnel outside the walls of the pool or from a closed drained recess in the wall of the pool,
neither the supply voltage to the fixture nor its associate ballast or transformer shall exceed
380.0V during either starting or operating conditions.
25.4.8.2.2 Accessib~lity
(1) Metal parts of lumnaires in contact with the pool water shall be of brass or other suitable
corrosion-resistant material
(1) Stands or supports for luminaries shall not be installed within 3.0m of the inside walls of
a swimming pool unless such luminaries are protected by earth-fault circuit breaker.
(1) Luminaries installed below or within 3.0m of the pool surface or walls, and not suitably
separated from the pool area by fence, wall or other permanent barrier shall be electrically
protected by an earth-fault circuit breaker.
(1) Forming shells for lamps supplied from an earthed circuit or a circuit operating at voltage
exceeding 30.0V shall be made from metal and have provision for a threaded connection to a
rigid metal conduit.
25.4.9.1 General
(1) Except as permitted in 25.4.9.2, earth-fault circuit breakers required per the provisions of
Clause 25.4.9 shall be of Class A typet.
(1) Where earth-fault circuit breakers of the Class A type are not available due to rating, the
equipment shall be protected by an earth-fault circuit breaker which will clear an earth fault
within the time specified for Class A type breaker.
25.4.9.3 Installation
a) permanently connected,
c) installed in a location which will facilitate testing required in 25.4.9.4, but not closer
within 3.0m of the pool water.
(1) A warning sign shall be located beside the switches controlling circuits, electrically protected
by earth-fault circuit breakers, advising that the circuits are protected and that the equipment
shall be tested regularly.
25.5.1 General
(1) The wiring between the wet-niche luminaries and the junction boxes referred to in
Clause 25.4.5 shall be of flexible cord suitable for use in wet locations and supplied as a part
of the luminaire.
(1) Rigid conduit of copper or other corrosion-resistant metal or rigid PVC conduit shall be
provided between the forming shell of luminaire installed below the pool surface and the
junction box referred to in Clause 25.4.5.
Exemption: Where Clauses 25.5.1 and 25.5.2 do not apply, any suitable wiring method specified in Section 8 of this
Standard shall be permitted.
(1) Conductors on the load side of each earth-fault circuit breakers shall be kept entirely
independent of all other wiring which is not so protected and shall not enter a luminaire
raceway, box, or cabinet occupied by other wiring except for panelboards which house the
breakers.
25.5.4 Drainage
(1) Conduits in the walls and deck of a swimming pool shall be installed so that suitable
drainage is provided.
25.6.2 Pumps
25.6.2.1 General
(1) Swimming pool pumps located within 3.0m ofthe pool walls shall be specifically approved
for the purpose.
25.6.2.2 Supply
(1) Swimming pool pumps shall be supplied from a pern'lanently installed receptacle located not
less than 1.5m nor more than 7.5m from the pool walls.
25.6.2.3 Protection
(1) Swimming pool pumps shall be protected by an earth fault-circuit breaker if located within
3.0m of the inside walls of the pool and not suitably separated from the pool area by a fence,
wall, or other permanent barrier.
25.7.1 Protection
(1) Electrical equipment forming an integral part of a hydromassage bathtub shall be protected
by an earth-fault circuit breaker of the Class A type.
25.7.2 Control
(1) A hydromassage bathtub shall be controlled by an automatic shut-off timer with an "on"
time of not more than 30.0min.
(1) Electrical controls associated with a hydromassage bathtub shall be located behind a barrier
or shall be located not less than 1.Om horizontally from a wall of the bathtub unless they form
an integral part of an approved factory-built hydromassage bathtub.
(1) Subject to 25.7.2.2 and notwithstanding the provisions of 25.4.9.3(1c), earth-fault circuit
breakers shall be permitted to be closer than 3.0m to the pool but not less than 1.5m from the
pool wall.
(1) Luminaries, switches, socket outlets, and other electrical equipment not directly associated
with a hydromassage bathtub shall be installed in accordance with relevant Clauses of this Code
covering the installation of equipment in bathrooms.
25.8.1.1 General
(1) Metal parts of spas and hot tubs shall be bonded together and to earth in accordance with
the provisions of Clause 25.4.4.
Exemption: Metal rings or bands used to secure staves or wooden hot tubs need not be bonded.
(1) A copper bonding conductor whose size is not less than that of the circuit conductors
supplying the equipment shall be connected between the control panel of a spa or hot tub and
the consumer's service or distribution panel.
25.8.2.1 Controls
(1) Controls for spa or hot tub shall be located behind a barrier or shall be located not within
1.5m horizontally from spa or hot tub unless they form an integral part of an approved factory
built spa or hot tub.
25.8.2.3 Luminaries
25.8.3.1 Installation
(1) Leakage current collectors shall be installed in all water inlets and in all water outlets of a
field-assembled spa or hot tub so that all water flows through leakage current collectors.
Exemption: Leakage water current collection shall not be required in a system in which the only component is a
pump marked as "insulated wet-end pump".
(1) Leakage current collecto~hall be electrically insulated from the spa or hot tub and shall
be bonded to the control panel or the main service earth with a copper bonding conductor.
(1) The bonding conductor for leakage current collectors shall be not smaller than that required
by Table 7.1, Section 7, where the bonding conductors are mechanically protected in the same
manner as the circuit conductor or a minimum 16.0mm2 copper conductor.
25.8.4.1 General
(1) Spas and hot tubs, field-assembled within divided components, shall be installed III
accordance with the provisions of Clauses 25.8.1 through 25.8.3, 25.8.4.2 and 25.8.4.3.
25.8.4.2 Component
(1) Individual components, such as pumps, heaters, and blowers, shall be specifically approved
for use with spas or hot tub.
(1) Air blower shall be installed above the tub rim, or other acceptable means shall be used to
prevent water from coming into contact with live parts of the blower.
Note: No conductors would be permitted under any circumstances in the area under line I. In the area above
Line I insulated communication conductors and neutral supported cables operating at 750.0V or less might
be permitted. Any other conductors operating at not more than 50.0kV might be permitted above the area
outlined by line 2.
a) have either the primary and secondary windings wound on separate bobbins 'On the
core legs or a grounded metal shield between the primary and secondary windings;
and
Microphones used in the vicinity of pools and baptismal fonts must have audio isolation
transformers and cables with ungrounded conductors installed between them and any mixer,
preamplifier, amplifier or similar equipment.
More specifically, a Class A earth-fault circuit interrupter is one which will interrupt the
circuit to the load when the earth-fault current is 6.0mA or more, but not when the earth
f~,ult current is 4.0mA or less in a time:
20
T (A.I)
I
I is the earth
fault current in La.ms milliamperes for fault current~ between
4.0mA and 260.0mA.
Note: when the ambient air temperature is less than -SoCor more than 40°C, the minimum tripping
current may be 3.5mA instead of 4.0mA.
The prime function of a Class A EFCI, therefore, is to provide protection against hazardous
electric shocks from leakage current flowing to earth from defective circuits or equipment.
It does not provided protection against shock should a person make contact with two of the
circuit conductors on the load side of the EFCI.
An EFCI must be applied to a circuit in accordance with the type and rating of the circuit
for which it is designed.
SECTION 26
GRAPHICAL SYMBOLS
26.1 SCOPE
(1) This Section of the Code sets provisions for graphical symbols to be used in electrical
installations and degree of protection provided by enclosures for electrical equipment.
(1) The following references contain provisions which, through reference in this text,
constitute provisions of the Ethiopian Building Code Standard on Electrical Installation of
Buildings:
26.3 DEFINITIONS
(1) For the purpose of this Section of the Code, the following definitions shall apply, in
addition to the terms defined in Section 1:
26.4 SYMBOLS
(1) Symbols for electrical installations and degree of protection provided by enclosures for
electrical equipment (lighting fittings) shall be as indicated in Tables 26.1 and 26.2,
respectively.
// / -----
SYMBOL Overhead
Radio
of line
Signal
Underground
Flexible
Junction line
line
Telephone
Protective
Surface lineConductor
line (PEl installation
line for flush
DESCRIPTION
conductor
conductors
In/Under surfaceline
-"-
• -
\J'--
... --
Identification Supply
Identification ofof Intended
Installation Method general
lines Application
Conductor,
Wiring
Wiring going
going
Wiring down
upward
passing through vertically
line Systems
SYMBOL DESCRIPTION
Earthing
Switchgear
Fuse, general
Fuse disconnector
Switch
Push-button
/ ,
mp -
®
/,.0\
Socket Outlets
)( I TelephoneSYMBOL
rh
'~ ~
,socket outlet Time
Dimmer
Empty
Twin
Florescent
Flood
Luminaires
Socket
switch
box
Antenna
Current--
socket
luminaire
Luminaire
Emergency
Wall mounted
Float with
switch
light
single-phase
Time
DESCRIPTION
switch
outlet
single
general
luminaire
switch
(Projector)
relay
outlet
Light-sensitive
Three-phase
Single-phas'e socket
pulse
socket
with lamp + PE
symbol
luminaire
outlet
switch
socket outlet
socketswitch
switch
outlet+ PE
outlet 7
purposes (conte'd)
I
xI
xSYMBOL
I I florescent luminaire
I of DESCRIPTION
-0.
Row Water
Florescent luminaire
Batteryheater
Inverter
Current
Rectifier
Voltage
Microwave
Exterior (Cell) double
transformer
transformer
Indicating lamp
instruments
cooker
luminaire (post top) symbol
Metre
Washing
Kitchen
Hotplate(ki
Electrical
Electric
Convertor
Baking ovenlowatthour-metre)
machine
appliance
range,
appliance,
General
general
Symbol
General
symbol
-Ir--
®
I0+-
f®l
~~
~
IKwhm [£J ®®®S
0 Luminaires(conte'd)
-CID- I [Z]
Indicating
Electrical
Instruments
Power Appliances
Supplyand (Power)
Transformers
Units
SYMBOL I
Non-automatic
Call indicator DESCRIPTION
fire alarm
panel deviceindicates
(Number (manual call
fire
Horn
U g
Motor Electric
fan
Generator
Master
Siren
Smoke
Dish
Intercom
AutomaticClock
Bell alarm
Freezer Clock
detector
washer
Telephone Telephone
exchange, exchange
general panel
symbol
Fire
Deep
Air freezer
control
conditioning & indicating
@®0
I~l
=:j)
®
II=:JI
CJ:=:=7
1**
[***
[Q]
E!J
~ I ~
Lf-o-Jlj1 Communication
~
Clothes dryer
call point)
stations, for example 9 stations)
appliances
Signalling Devices
Electrical Appliances(conte'd) I
J
SYMBOL
-
..
---- DESCRIPTION
lr
, Antenna
set
Flame -
detector (rate of rise)
TV
Loud
Radio
Heat ,.detector
speaker
set
detector
Amplifier
Optical (fixed temperature)
detector
EJ
em
oJ
=:::)
1ZSJ II I=::::
Radio, Television and accessories
Table 26.2 Graphical symbols for the degree of protection of electrical equipment
(symbols on light fittings)
••
SYMBOL
I Covered
covered
-----,
dust
11s1
Type of
IPproof
foreign 67substances
substance
foreign rain
IIII1.0mm
1.0mm
2.5mm
jet
substancesagainst
IP
IP
IP2260
54
IP 55
43
44
65
23 no
Digit - Protection against
protection
splash ~water
waterproof
nowaterproof
~water
inclined dripping water
protection
53 2nd Digit - Protection
50
Test marks
Lighting fittings for discharge lamps for direct mounting on fixtures and furnitures, which conform in their •
SYMBOL Lighting
Lighti ng fittings
fitti suitable
ngssuitable forformounti
mounting in fire-hazardous
DESCRIPTION locations andElektrotechiker"
premises (VDE 0100)
It certifies the of mounting
IPprocedure
50 (~Association
(dust
?t at 200°C, The
ImpactVDE-test
proof mark is the
lighting symbol
fittings are ofng on association
the
suitable materials
for with
gymnastic unknown
"Verein
and sportsinflammabi
Deutscher
prem ises. Iity.The
The tests are made accordi of
ng
Radio interference suppressionaccording to VDE 0875. All lighting fittings conform to the interference
W to DIifNthey
varnished,
German
C-specifications.
suppression
is 18032
specified.
behaviour
and and or
coated
Electrical
lighting
fordegree
remain VDE
fittings
G.
inflammation
stable By0711.
veneered.
Engineers.) for
using
to
and The
are notapproval
discharge
additional
hardly or
subjectlampsis deformation
based
with on
interference
normally
to this internationally
inflammable sign
suppression are specified
suitable
device
materials,
upto this ifNrules.
for direct
degree
although
temperature. mounting
will
these be on being
reached.
materials normal or easily
W
W
@VJ
PROTECTION CLASSES
The light fittings are classified in three categories against electrical shocks depending on the type of
protection.
1 INITIAL VERIFICATION
1.1 General
(1) Every installation shall, during erection and/or on completion but before being put into
service, be inspected and tested to verify,.so far as is reasonably practicable, that the
requirements of this Electrical Installation Code have been met.
(2) The method of test shall be. such that no danger to persons, livestock or property or
damage to equipment can occur even if the circuit tested is defective.
1.2 Inspection
(1) Detailed inspection shall precede testing and shall normally be carred out with that·
portion of the installation under inspection being disconnected from the supply.
(2) The detailed inspection shall be made to verify that the installed electrical equipment
IS:
(3) The detailed inspection shall include at least the checking of the following items, where
relevant to the installation, and, where necessary, during erection:
a) connection of conductors;
b) identification of conductors;
c) routing of cables in safe zones or mechanical protection;
d) selection of conductors for current carrying capacity and voltage drop in accordance
with the design;
e) connection of single pole devices for protection or switching in phase conductors
only;
t) correct connection socket-outlets and lampholders;
g) presence of fire barriers and protection against thermal effects;
h) methods of protection against direct contact (including measurement of distances,
where appropriate); i.e.,
, i) protection by insulation of live parts,
ii) protection by barrier or enclosure,
ill) protection by obstacles,
iv) protection by placing out of reach;
1.3 Testing
(1) The following tests, where relevant, shall be carried out in that sequence.
i) A test shall be made to verify the continuity of each conductor, including the
protective conductor, of every ring final circuit.
c) Insulation resistance
resistance between the exposed conductive parts and live parts of the
disconnected equipment shall be measured separately and shall be not less
than O.5mega Ohm.
Note: i) In the event of any test indicating failure to comply with the requirments of clause (lc) above, that
test and those preceding it (the results of which may have been influenced by the indicated fault)
3hall be repeated after the fault has been rectified.
ii) Reference methods of test are described in Guidance Notes on the Wiring Regulations published
by the Institution of Electrical Engineers (IEE); but the use of other methods giving no less
effective results is not precluded.
- when tested at 500.0V d.c. shall not be less than O.5mega ohm;
- shall be able to withstand a test voltage of at least 2.0kV r.m.s, a.c. and
- shall not pass a leakage 'current exceeding 1.0mA in normal conditions of
use.
(h) Polarity
(1) It shall be verified that every alteratian or additian complies with the requirements af
this Co.de and that it daes nat impair the safety af an existing installatian.
(1) Inspectian comprising careful scrutiny af an installatian shall be carned aut withaut
dismantling or with partial dismantling, as required, supplemented by testing to.provide far:
a) the safety af persans and livestack against the effects af electric shack and burns
even when the circuit is defective,
b) pratectian against damage to. praperty by fire and heat arising from an installatian
defect,
'"
APPENDIX 1: INSPECTION AND rESTING
(2) The frequency of periodic inspection and testing of an installation shall be determined
by the type of installation, its use and operation, the frequency of maintenance and the
external influences to which it is subjected.
4.1 General
(1) Following the initial verification required by Clause 1 or Clause 2 of this Appendix, a
Completion & Inspection Certificate in the form set out in Appendix 2 of this Code shall
be given to the person ordering the work.
(2) Following the periodic inspection and testing described in Clause 3 of this Appendix,
report on the findings and the extents of the periodic inspection and. testing of an
installation, or any part thereof, shall be recorded on a report and given by the person
carrying out the inspection, or by a person authorized to act on his behalf, to the person
ordering the work.
(3) Dangerous conditions arising from non-compliance with this Code, together with any
limitations of the inspection and testing in accordance with Clause 3(1) of this Appendix,
shall be recorded.
(1) The Inspection shall comply with the requirement of Clause 1 of this Appendix and any
defects or omissions revealed by the inspection shall be made good before a Completion
& Inspection· Certificate is issued.
(2) The Completion & Inspection Certificate shall be signed by a competent person or
persons stating that the installation has been designed, constructed and inspected and tested
in accordance with the provisions of this Code.
(1) The requirements of Clause 4.2 fdr the issuance of a Completion & Inspection
Certificate shall apply to all the work of the alterations or additions; any defects or
omissions revealed in that work shall be made good before a Completion Report is issued.
(2) The Contractor or other person responsible for the new work, or a person authorised
to act on his behalf, shall report in writing to the person ordering the work any defects
found in related parts of the existing installation.
APPENDIX 2
FORMS OF COMPLETION AND INSPECTION
CERTIFICATE
1. Installation
(1) The forms of completion, inspection and testing shall be made out and signed by
competent persons in respect of the design, construction, inspection and testing of work.
(2) Completed forms shall indicate a responsibility for design, construction, inspection
and testing, whether in relation to new work or further work on an existing installation.
Client:
Address:
DESIGN
"--
I/We, being the person(s) responsible (as indicated by my/our signatures below) for the Design of the electrical
installation, particulars of which are described on Page ... of this Form, CERTIFY that the said work for which I/we have
been responsible is to the best of my/our knowledge and belief in accordance with the Regulations for Electrical
, Installations published by except for the departures, if any, stated in this
Certificate.
The extent of liability of the signatory is limited to the work described above as the subject this Certificate.
For the DESIGN of the installation:
I/We, being the person(s) responsible (as indicated by my/our signature below) for the 'Construction of the electrical
installation, particulars of which are described on Page.... of this Form CERTIFY that the said wt>rkfor which I/we have
been responsible is to the best of my/our knowledge and felief in accordance with the Regulation for Electrical
Installations published by .......................•...................................................................................
except for the departures, if any,
stated in this Certificate.
The extent of liability of the signatory is limited to the work described above as the subject of this '.
Certificate.
For the CONSTRUCTION of the installation:
I/We, being the person(s) responsible (as indicated by my/our signatures below) for the Inspection and Test of the
electrical installation, particulars of which are described on Page ... of this Form, CERTIFY that the said work for which
l/we have been responsible is to the best of my/our knowledge and belief in accordance with the Regulations for
Electrical Installations published by except for departures,
if any, stated in this Certificate.
The extent of liability of the signatory is limited to the work described above as the subject this
~rtificate.
Address:
I RECOMMEND that this installation be further inspected and tested after an interval of not more than
.......... years.
!
APPENDIX 2: FORMS OF COMPLETION AND INSPECTION CERTIFICATE
NOTE:
1. This document is intended for the initial certification of a new installation or of an alteration or
addition to an existing installation and of an inspection.
2. The·signatures appended are those of the persons authorized by the companies executing the work
of design. construction and inspection and testing respectively. A signatory authorized to certify more
than one category of work shall sign in each of the appropriate places.
Method of Measurement
Frequency ............. Hz
Number of Phases .
oo No
oNo No the installation is correct
Polarity throughout DYes DYes DYes
stated below:
Each item of apparatus tested separately is in good serviceable condition, except as stated below.
parately is not less than 0.5 megao ]
llation is not less than 1 megohm
All
Thereflexible
is nocords, switches,
sign of fuses,ofplugs
overloading and socket-outlets
conductors are except
or accessories in goodas serviceable cop-dition, except as
stated below.
m.
Date: .
Signed
Address: ...................................................................................................
...................................................................................................
H
Mechanical and electrical requirements 188
Mechanical protection 430
Hazard 327 Metal car frame supported by cables 385
Heat barrier 354 Metal casing of a pump 169
Height consideration 351 Metal parts 453
Height of conductor 332 Meters instruments and relays 284
Highest voltag~ 358 Minimum height ofluminaries 322
Hoistway door interlocking wiring 378 Monitoring 350
Hydraulic lifts 383 Motor supply conductor insulation, temperature 257
Motors and generators 285,286,287 289, 2~1, 293
Motors and generators 285
I Motors and generators 286
Motors and generators 287
Motors and generators 289
Motors and generators 293
Illuminance 37
Multiple services 142
Illumination level 387
In hoistway, machine rooms and escalator wellways 379
N
Independent metal water pipes 168
Installation and bonding 458
Installation 357,375,400,454,458
Installation and type 148 Near or over combustible material 320
lnstanteneous trip circuit interrupters 262 Non - continuous duty 384
Insulation 429 Number and location of overload devices 263
Insulation rating 378 NUmber ·of circuit element 347
Insulation resistance 356
Internal metal 189 o
Interruption 361
J On cars 379
Open core - and soil type transformer 375
Origin of call indication 348
J~ints 189 Other wiring 378
Junction box bonding conductor 450 Other classes 454
Other factors 354
L Outlet boxes to be covered 322
Outlet distance 400
Over current protection 146,327,362375
Over load and over heating protection 362
Labelling 361 Overcurrent protection marked on equipment 260
Lamp holders 326, 332 Overheating protection required 265
Lantern lights 351,353 Overheating protection required for motors 265
Laying 170 Overload protection not required 264
Lengt11of cable from transformers 376 Overload protection required 262
Lighting 386
Lighting fixtures 292
Lighting fixtures 285,286, 288,290
p
Lighting switch 387
Linllts of spacing 352
Live parts 321 Pendant conductors 324
Location 145,451,452 Placement 349
Location oflighting equipment 320 Plate electrode 170
Location of the alarm contrast and indicating panel 346 Portable motors 257
Luminaire 387 Position relative to ceiling 351
Luminaire protection 453 Protection 452,456
Luminaire as a raceway 323 Protection device location 380
Luminaire construction 319 Protection ofuninsulated part 374
Luminaire exposed to flying objects 322 Provision for bonding of future equipment 189
Luminaire in damp or wet location 320 Protection 319
Luminaire support 453 Public water pipe 168
Luminaries 458
R
M
Rated duration of operation 38
Manual call in automatic alarm 349 Rating and ampacity 257
Marking 143,374 Rating or trip selection of overload devices 263
Material 318,429 Recessed luminaire 322
Material for bonding conductors 171 Recessed luminaire wiring 324
Material for system earthing 171 Reinforcing steel 449
Means of disconnect 146 Remote location 361
-~
INDEX