ZAKŁAD

ELEKTROBUDOWA

Gas-Insulated
Medium Voltage Switchgear
type
OPTIMA-24 CATALOGUE

energetyka energetyka energetyka przemysł przemysł przemysł przemysł przemysł przemysł trakcja
wytwarzanie przesył dystrybucja paliwowy chemiczny węglowy metalurgiczny mineralny papierniczy rail
power power power fuel chemical coal metallurgy mineral paper transport
generation transmission distribution industry industry industry industry industry industry
INTRUDUCTION
1. GENERAL _______________________________________________________1
1.1. Efficiency / compactness _____________________________________1
1.2. Safety for personel _________________________________________1
1.3. Safety of operation _________________________________________1
1.4. Application ________________________________________________1
1.5. Conformity to standards _____________________________________2
1.6. Environmental conditions ____________________________________2
1.7. General characteristics ______________________________________2
1.8. Features __________________________________________________2
2. TECHNOLOGY ____________________________________________________3
2.1. General___________________________________________________3
2.2. Interlocking _______________________________________________3
2.3. Modular design ____________________________________________3
2.4. Instrument transformers _____________________________________3
2.5. Vacuum circuit breakers______________________________________3
2.6. Secondary systems__________________________________________3
3. MONITORING SYSTEM _____________________________________________4
3.1. Insulating gas monitoring ____________________________________4
3.2. Voltage indicators __________________________________________4
4. SWITCHGEAR DESIGN _____________________________________________5
4.1. Switchgear construction _____________________________________5
4.2. Busbar system compartment__________________________________8
4.3. Auxiliary circuits compartment ________________________________9
4.4. Gas compartment _________________________________________10
4.5. Connection compartment ___________________________________11
4.6. Switch operating mechanisms compartment ____________________13
An award for an outstanding product
4.7. Three-position switch ______________________________________14
presented at “ENERGETAB 2015” fair
4.8. Two-position switch ________________________________________14
4.9. Busbar system earthing switch _______________________________14
4.10. Vacuum circuit breaker GMX-S _______________________________15
5. TECHNICAL DATA ________________________________________________16
6. MAIN CIRCUITS _________________________________________________17
6.1. Switchgear equipment______________________________________21
7. FOUNDATION ___________________________________________________23
8. INSTALLATION __________________________________________________25
9. DESIGNING_____________________________________________________27
10. TRANSPORT ___________________________________________________27
11. ORDERING ____________________________________________________27
12. NOTES _______________________________________________________28

An award for an outstanding product presented at ENERGETAB 2015 fair.


Responding to the needs of Polish and foreign users, ZARMEN Zakład
ELEKTROBUDOWA has developed and implemented the production of
compartmented, SF6-insulated switchgear with vacuum circuit breakers for the
parameters: up to 25 kV - 2500 A - 31,5 kA.
The design of the switchgear takes into account the latest trends in development
and experience of other users and manufacturers of switchgear of this class.
At the International Power Industry Fair ENERGETAB 2015 in Bielsko-Biala
OPTIMA-24 switchgear received an award for an outstanding product presented at
the Fair.
At the International Power Industry Fair ENERGETAB 2015 in Bielsko-Biala An award: MINISTRY OF ENERGY CUP
OPTIMA-24 switchgear was awarded the MINISTRY OF ENERGY CUP. “ENERGETAB 2017”

Catalogue edition No. 12/02/23K/2021


1. GENERAL
1.1. Efficiency / compactness
After installation OPTIMA-24 needs up to 25% less space in the switchgear room than air-insulated switchgear currently manufactured.
Application of OPTIMA-24 switchgear in the existing stations / switchgear rooms has many benefits:
n the switchgear rooms or stations may house twice as many SF6-insulated panels that of older-type switchgear,
n efficient use of the existing switchgear rooms and stations, with no need for their extension,
n economic use of the space in municipal areas.

Deciding to install OPTIMA-24 switchgear in newly designed rooms their size can be considerably minimized, in their length, width and
height, what brings substantial project savings.
Low maintenance costs owing to self-operating switchgear compartments filled with the SF6 gas and provided with vacuum circuit-
breakers characterized with high electrical endurance.

1.2. Safety for personel


For a manufacturer of electrical equipment ensuring safety for operators is of utmost importance, therefore our switchgear undergoes
comprehensive type tests in accredited, independent laboratories according to the requirements of the international standards and norms.
Safety is also ensured by consistent routine inspections and tests performed at all stages of production.
Safety of operation of OPTIMA-24 switchgear is provided through:
n encapsulating the primary part (a three-position switch, a two-position switch, a vacuum chamber of the circuit breaker) of the
switchgear in the solid-insulated sealed enclosure, preventing accidental contact with live parts,
n cable heads, busbars and voltage transformers protected by grounded coating,
n access to drives and auxiliary switches outside the gas tank of the switchgear,
n an interlocking system allowing operation only when the switchgear enclosure is closed,
n IP 67 degree of protection for all medium voltage elements of the gas compartment, IP 4X for the outer enclosure of the switchgear,
n high degree of protection against propagation of internal arcs, provided by logical mechanical interlocks and certified switchgear
enclosure,
n fast earthing by use of the circuit breaker,
n operator's panel mounted on the front of the switchgear,
n logical mechanical interlocks preventing maloperation,
n electromagnetic interlocks of manual operating mechanisms of the three-position switch.
All switchgear compartments have been successfully tested for arc protection.

1.3. Safety of operation


n Switching parts are enclosed in the hermetically sealed vessel filled with SF6 gas, so the operating conditions do not change during the
whole service life.
n High-voltage parts and the busbar system are outside the gas-filled compartment, are single-pole, enclosed and externally earthed.
n Reliable operating mechanisms of switching devices are accessible outside the switchgear enclosure.
n Metal-clad plug-in voltage transformers mounted outside the SF6 enclosure.
n Current transformers mounted outside the SF6 enclosure.
n Continuous protection against switching errors with logical interlocks.
n Welded enclosure ensuring tightness throughout the whole service life.
n Minimum fire hazard.
n Type-tested and routine-tested.

1.4. Application
Modern, indoor, SF6 gas-insulated medium voltage switchgear type OPTIMA-24 is designed for distribution of electrical Energy of the 3-
phase alternating current of frequency 50 Hz, at the rated voltage up to 25 kV both in the distribution network of power sector and in other
industries.
Modern design solutions ensure simple, safe operation and make the switchgear fit for use in self-operated stations. Areas of
application:
n power distribution companies,
n industrial plants,
n infrastructure,
n mining plants,
n railway traction supply systems,
n power stations.

1
1.5. Conformity to standards ISO 9001
ISO 14001
The SF6 gas-insulated switchgear type OPTIMA-24 fulfils the requirements of the standards:
n PN-EN 62271-200:2012, AQAP 2110
n PN-EN 62271-1:2009+A1:2011,
n PN-EN 62271-102:2005+A1:2011+A2:2013-10.
The switchgear has obtained a certificate after having been fully type-tested. It is designed, manufactured and installed according to the
certified quality management system conforming to ISO 9001, ISO 14001 and AQAP-2110.

1.6. Environmental conditions


The switchgear is designed for operation in rooms where the ambient conditions ensure normal service conditions acc. to PN-EN 62271-
200 and PN-EN 62271-1. Special service conditions must be agreed with the manufacturer.
Owing to hermetically tight, welded enclosure made of stainless steel, and single-pole solid insulation of the primary current circuit
outside the vessel, switchgear type OPTIMA-24:
n is insensitive to such aggressive environmental factors as:
§air humidity,
§dust,
§water steam condensation,
n primary circuits tight to ingress of foreign bodies such as:
§dust,
§dirt,
§small animals,
§humidity.

1.7. General characteristics


n Indoor, fixed-type, SF6-insulated switchgear.
n Wall-standing or free-standing.
n Compartmented.
n Single busbar system with solid insulation.
n Fit for computerized control and surveillance system.
n Mechanical interlocks of switching devices.
n Electromagnetic interlocks of manual operating mechanisms of a three-pole
switch.
n Stainless steel gas vessel.
n Voltage indicators.
n Gas pressure gauge.
n Safety pressure diaphragm.
n Satisfies the requirements of standards for protection against the effects of arcing
due to internal fault.
n Current and voltage transformers mounted outside the gas compartment.

1.8. Features
n High reliability.
n Efficiency.
n Long endurance.
n Maintenance-free.
n The interlocking system preventing switching errors.
n Safety for operators.
n Affordability.
n Operating parameters indicators.
n Easy access to equipment and cables.
n Environmentally safe production and operation.
n Professional manufacturer's service.
n Possibility to replace a panel during operation.
All medium voltage compartments are arc-proof. An OPTIMA-24 panel mounted in the MV/MV
Supply Station Trzebicko

2
2. TECHNOLOGY
2.1. General
n The 3-pole primary circuit with switches situated in the stainless-steel vessel.
n Insulating gas SF6.
n Three-position switch with the function of disconnector of busbars and outgoing earthing switch.
n Earthing process is executed by closing the vacuum circuit breaker after the three-position switch has been switched to EARTHED position.
n Compact size, owing to application of insulating gas SF6.
n Hermetically welded vessel made of stainless steel.
n Plug-in busbars in single-pole silicone insulation with earthed, conductive coating.
n Cable connection made in single-pole plug-in technology.
n Wall-standing or free-standing arrangement.
n Access to cable connections on the front of the panel.
n Installation and possibility of extension of the existing switchgear at both ends without gas work and without modification of the existing
panels.

2.2. Interlocking
The switchgear design solutions prevent accidental switching errors. The switchgear panel is provided with the following mechanical
interlocks:
n interlock against access to the operating mechanism of the three-position switch when the circuit breaker is in the “closed” position (this
refers to the circuit breaker panel),
n interlock against closing the circuit breaker during maneuvering the three-position switch (the circuit breaker can be closed only
when the interrogation lever has returned to its initial position),
n interlock against access to the socket of the manual operating mechanism of the circuit breaker when the earthing switch is in the “closed”
position,
n interlock against access to the socket of the manual operating mechanism of the earthing switch when the disconnector is in the “closed”
position,
n locking the “OFF” pushbutton on the circuit breaker with a padlock (earthed connection),
n locking with the padlock the operating mechanism of the two-position switch of voltage transformers in either of the positions:
“transformers earthed” or “transformers closed”,
n interlock of cable compartment cover preventing its removal when the earthing switch and the circuit breaker are open,
n bolt interlock of covers of the three-position switch and circuit breaker operating mechanism compartment and of the cable
compartment (option),
n control gate and locking device of selecting a switch depending on the position of the interrogation lever,
n interlock of interrogation lever operation when the circuit breaker is closed.

2.3. Modular design


n Panel replacement is possible without SF6 gas work.
n Each panel is independent of other panels in respect of construction and function.

2.4. Instrument transformers


n Current transformers without dielectric stress.
n Easy replacement of current transformers designed as ring-core transformers.
n Metal-coated voltage transformers, designed as plug-in and disconnectable.
n Ferranti transformers.

2.5. Vacuum circuit breakers


n Maintenance-free under normal ambient conditions according to IEC 62271-100
n No relubrication or readjustment needed.
n Stored energy spring mechanism for 10 000 / 30 000 operating cycles (series GMX-S circuit breaker).
n Stored energy spring mechanism for 10 000 operating cycles (series VEP circuit breaker).
n Vacuum tight for life.

2.6. Secondary systems


n Generally available protection, measuring and control equipment.
n Possibility of integrating in remote control systems.
n Standard dimensions of the auxiliary circuits compartment are presented in chapter 4.3., it is possible to change the height of the
compartment by 150 mm or 300 mm depending on the amount of mounted control devices.

3
3. MONITORING SYSTEM
3.1. Insulating gas monitoring
Pressure of the insulating gas in each vessel is measured with a pressure gauge [18] with auxiliary contacts, mounted inside the
compartment of switch operating mechanisms. The drawing below shows a method of mounting the gauge in the panel. Each panel is
provided with a pressure gauge. Indications of the gauge can be observed through the inspection window on the front cover of the
compartment. Operating personnel can locally identify a panel's readiness for service from colour indications on the gauge:
n green indicator – “ready”,
n yellow indicator – “warning”,
n red indicator – “alarm”.

Whenever a boundary between colours is exceeded, the auxiliary contacts are switched to signal relevant alarm states, which may be
used in the signaling circuits.
An allowable annual loss of SF6 gas < 0.1%.
1 2 3 4

A manometer mounted in the panel.


1. manometer
2. entry of cables of the gauge auxiliary contacts
Manometer [18] – pressure gauge
3. valve DN-8
State: “ready” State: “alarm”
4. construction of the gas vessel

3.2. Voltage indicators


Voltage indicators are fit for cooperation with a reactance or resistance insulator. The indicators are connected to bushings mounted
inside:
n on the busbars side: busbar system bushing [7],
n on the cable connections side: cable connection bushing [8].

Voltage indicators are used to check:


n voltage presence - they detect presence or lack of voltage,
n in cooperation with the PB relay possibility of use in electrical interlocking systems.

Voltage indicator type WN is fit for work with reactance insulators. An optical element which signals
voltage presence in each phase is based on three electroluminescent diodes on the front of the relay. The
front panel of the WN indicator houses test sockets to which an external portable voltage indicator can be
plugged (e.g. WNf indicator manufactured by ENERGOTEST sp. z o.o.), which can also be used for phase
comparison.
PB switching interlock relay cooperates with reactance insulators. Fitted for detecting voltage
presence; it is fitted for cooperation with the coil interlocking the earthing switch closing, preventing the
earthing switch from closing in the case of voltage presence on its contacts.
Use of other type voltage indicator is possible.

Main features of voltage indicators:


n the indicators cooperate with insulators of different manufacturers,
n voltage present indication is realized for each phase, Voltage indicator type WN
n the indicators are provided with test sockets for phase comparison,
n the detection system needs no separate power supply, it is energized from the connected
reactance insulators,
n the detection system is independent of the interlocking system (failure of the interlocking system
does not break the operation of the detection system) - refers to PB relay.

Stationary voltage indicators provide high degree of safety for switchgear operators. A stationary
voltage indicator included capacitance insulators connected to the voltage indicator socket mounted
on the front cover of the auxiliary circuits compartment.

PB switching interlock relay

4
4. SWITCHGEAR DESIGN
Following the current global trends, the switchgear has been so developed as to reduce the amount of SF6 gas to a minimum. The
switchgear type OPTIMA-24 is composed of prefabricated SF6-insulated panels and has been designed as a self-supporting construction
divided into functional compartments:
n auxiliary circuits compartment,
n busbar system compartment,
n connection compartment,
n switch operating mechanisms compartment,
n gas compartment (three-position switch, circuit breaker, optional two-position switch),
n pressure relief duct compartment.

The main part of the switchgear is a tight gas vessel made of welded 3 mm stainless-
steel sheet, mounted on the enclosure made from 2 mm steel sheet with corrosion-proof
aluzinc coating. There are removable covers on the front and side of end panels of the
section, facades and door of the auxiliary circuit compartment are made from steel sheet
coated with corrosion-proof paint.

- auxiliary circuits compartment

- busbar system compartment

- connection compartment

- switch operating mechanisms compartment

- gas compartment

- pressure relief duct compartment

4.1. Switchgear construction 25 11

n Vacuum circuit breaker type GMX-S is capable of up to 30 000 at a 1


rated current of 1250 A operating cycles and up to 10 000
24 26
operations with a rated current of 2500 A operating cycles.
n Vacuum circuit breaker type VEP can perform up to 10,000
operations with rated currents up to 2 500 A. 7 19
n The gas compartment filled with sulphur hexafluoride is fully tight
according to IEC 62271-1 and EN 62271-1 standards. 31 4
n The switchgear is maintenance-free and tight throughout its 5
18
service lifetime (hermetically sealed vessel).
n The gas compartment is made of stainless steel.
21
n During the whole service life of the switchgear no maintenance
2
work is needed on switching apparatus mounted in the gas 3 17
compartment.
n No replenishment of gas in the gas compartment is necessary 6 8
during the whole service life. 12
n No need for SF6 gas work during:
13
§installation,
§extension,
§removal of single panels (thanks to module design of the busbar 16
system) or the switchgear.
n The switchgear has a self-supporting, welded, riveted and
screwed steel construction.
n When a single panel is dismantled, the existing busbar system
must extended with suitable adapters of the relevant
manufacturer. 80

Przykładowy
Section przekrój
of a 2500 pola
A circuit wyłącznikowego
breaker 2500 A
panel (an example)
5
150
OPTIMA-24

25 11

1
26
23
7
19

5
4
0 0
20 31
1 1
21

18
B

8 17

D
23 6
12 14
13 9

10
15
16 29

A C

DISCONNECTOR PANEL
150

OPTIMA-24

25 11

1
26
23
24
7 19

5
4
0 0
20 31
1 1
21

22
2
B

3
17
D

0034

23 6 8

12
13
30
29
16

A C

CIRCUIT BREAKER PANEL

6
OPTIMA-24

150
25 11

1
26
23
7
19

5
4
0 0
20 31
1 1
21

27
28
B

17

D
23

15
16

A C

METERING PANEL

- auxiliary circuits compartment

- busbar system compartment

- connection compartment

- switch operating mechanisms compartment

- gas compartment

- pressure relief duct compartment

1. solid-insulated busbar system 17. safety membrane


2. vacuum circuit breaker operating mechanism 18. support insulators
3. circuit breaker vacuum chamber 19. gas guide
4. three-position switch 20. manometer
5. operating mechanism of the three-positions switch 21. copper busbars
6. current transformers 22. earthed connection interlock
7. bushings of the busbar system 23. bolt interlock
8. bushings of the cable connections 24. protection unit
9. bushings of the voltage transformers 25. busbar compartment cover
10. operating mechanism of the two-positions switch 26. transport lugs
11. safety flap 27. fuse enclosure
12. T connector head 28. cover of the fuse enclosure
13. coupling connector head 29. cable brackets
14. two-positions switch of voltage transformers 30. surge arresters
15. voltage transformer 31. DN-8 valve
16. earthing bus

Design of the switchgear is presented by describing its compartments. Numbers, as for example [1] refer to the drawing.

7
4.2. Busbar system compartment
The busbar system compartment is situated directly above the gas compartment – vessel of main circuits and is separated from other
compartments by metallic partitions. The bottom part of the compartment houses tight bushing insulators of busbars [7] on which the
insulated busbar system is mounted [1]. The busbar system is made of a round copper bar in silicone rubber insulation connected directly on
the busbar bushings [7] using special cross and end adapters. The busbar system enclosure has silicone rubber insulation. Surfaces of busbar
system enclosure are earthed to the designated earthing point in the upper part of the gas compartment. Upper cover of the busbar system
compartment [25] has standard ventillation openings which, appropriately arranged with a counter-cover, provide tightness of IP 4X.

Busbar features:
n 1-pole, plug-in and bolted design, fully insulated,
n consisting of round-bar copper, insulated by means of silicone rubber,
n busbar joints with cross and end adapters, insulated by means of silicone rubber,
n safe external lining, touchable as the external lining is earthed with switchgear enclosure,
n insensitive to water steam condensation and pollution,
n extension, installation or replacement of the panel is possible without interfering with the gas compartment,
n busbar system is mounted at the site of switchgear installation,
n busbar sections are divided by panels,
n the method of mounting the busbars is similar to the method of mounting the connector heads,
n busbar bushings comply with PN-EN 50181:2010 standard,
n metal enclosure of the system [25] provides protection against mechanical damage,
n easy modernization of the busbar system after dismantling a damaged panel,
n arc-proof, like other compartments of OPTIMA-24 switchgear.

2500 A busbar system


~365
~225 / 275*

1250 A
(2500 A*)

1250 A (2500 A) busbar


system
~245

Surge arrester mounted


on the busbar system

A view of a top box above the system with voltage


transformers

The busbar compartment may house:


n current transformers (option) [6],
n voltage transformers (option) [15],
n surge arresters (option).

If voltage transformers are mounted on the busbar system, the


switchgear is provided with additional top box 300 mm high. The
additional height must be taken into account in designing the
switchgear room.

Current transformers on the busbar system:


n toroidal core type, 1-pole,
n the transformers are mounted on the joint of two switchgear
panels.

In OPTIMA-24 switchgear current transformers of different A view of mounted current transformers


manufacturers may be mounted.

8
4.3. Auxiliary circuits compartment
The switchgear is provided with a separate compartment to house low voltage equipment and auxiliary circuits. It is situated on the front
of the switchgear, above the gas compartment, and has the dimensions:
n height - 510 mm,
n width - 600, 900 mm,
n depth - 360 mm.

The auxiliary circuits compartment houses terminal strips, auxiliary circuit equipment selected by the designer, and a luminaire (option).
Any protection / controller units of any manufacturer can be mounted.
Because of a big amount of control equipment, height of the auxiliary circuits compartment can be raised by 150 mm or 300 mm. The
dimension has to be taken into account at the stage of designing the switchgear room. The mounting plane for auxiliary circuits equipment is
on the rear wall of the compartment.
Auxiliary circuits cables can be entered to the channel situated above the auxiliary circuits compartment and running along the
switchear, or to the low voltage cable duct located in the floor of the operating gangway. Cables, which can be entered to the duct on the left
or right wall of the switchgear, are enclosed in the connection compartment in metallic enclosures which provide protection against the
effects of arcing.
The equipment of the auxiliary circuits compartment:
n control devices,
n monitoring devices,
n field protection,
n field controller,
n voltage indicator (facade of the compartment door),
n door opening limiter.

810 mm
Dimension Width Height Depth
Panel width mm
600 mm 600 Standard: 810
900 mm 900 Lowered : 360
510*
360 mm
660*

Mounting space in the auxiliary circuits compartment


* - optionally, the height can be lowered by 150, 300 mm

Dimensioned drawing of the auxiliary circuits


compartment

Open auxiliary circuits compartment with height raised by A view of an elevation auxiliary circuit compartment with
300 mm height raised by 300 mm

9
4.4. Gas compartment
The gas compartment is situated in the centre of switchgear construction, it houses switching equipment of the primary circuit. The
compartment enclosure is made of 3 mm stainless steel sheet, suitably reinforced from inside and outside provides stability and durability of
the construction. The sheet steel plates are joined by welding, providing tightness on the level of IP 67.
Standard gas compartment of an outgoing cubicle includes:
n circuit breaker vacuum chamber [3],
n three-position switch [4],
n copper bars [21],
n two-position switch of voltage transformers [14] (option– only when plug–in voltage transformers [15] are mounted inside the
connection compartment).

The compartment houses the vacuum circuit breaker poles, separated from the operating mechanism with a tight partition, three-
position switch [4], two-position switch of voltage transformers [14] and adequately shaped copper bars [21]. The switchgear construction is
fitted for installation of a vacuum circuit breaker type: GMX-S or VEP.
Tight bushings of the busbar system [7] are mounted on the connection between the gas compartment and the busbar compartment.
Similar bushings for voltage transformers [9] and for cable connection [8] are used on the entrance to the connection compartment.
Bushings of the cable connections [8] are of various length.
Switching devices built in inside the compartment depend on the rated current of the panel (630 ÷ 2500 A). Operating shaft of a three-
position switch [4] is entered into the gas compartment through special sealing which guarantees adequate tightness throughout the whole
service life of the switchgear.
In the rear of the compartment there is a safety membrane [17] which provides protection for the vessel against sudden pressure
increase due to arc-fault inside the gas compartment. Gases will be evacuated through the pressure relief duct to the top and outside the
switchgear.
On the front of the panel a manometer - pressure gauge [20] is built-in, it signals the level of gas pressure with the use of microswitches
(“ready”, “warning”, “alarm”).

Each gas compartment has an integrated valve for:


n connecting the gas monitoring system,
n gas recovery during decommissioning of the switchgear.

Main features of the gas compartment:


n self-operating,
n made of stainless steel,
n tight for life,
n maintenance-free,
n no replenishment of gas is necessary during the whole service life,
n no interference in the vessel during extension or dismantling of switchgear panels.

7 7
5
4 4

19
21 21
18
3

14 8

9
A gas compartment with switches: three-position A gas compartment with a three-position switch,
and two-position and with bushings vacuum chambers of the circuit breaker and
bushings

10
4.5. Connection compartment
The connection compartment is in the bottom part of the switchgear and is made of 2mm metal sheet with corrosion-proof aluzinc
coating. The compartment houses cable connections ended with silicone-insulated connector heads which, through the cable connection
bushings [8], are connected with primary circuits of the gas compartment.
Equipment of the connection compartment:
n connector cables connection [12, 13],
n current transformers [6], optionally, additional current transformers can be
mounted,
n voltage transformers [15] (option), optionally, additional voltage
transformers can be mounted,
n operating mechanism of a two-position switch of voltage transformers [10]
(option) - only when the switchgear is provided with plug-in voltage 29
transformers,
n if the panel is not provided with voltage transformers, bushing pins [9] are
protected with insulating plugs,
n cable brackets [29],
n surge arresters [30] (option), 16
n Ferranti transformer with a divided or non-divided core (option),
n earthing bus [16]. View of return wires and earthing conductors of
All elements in the connection compartment are covered with earthed cables connected to the earthing bus [16]
layers which protect users against direct touch.
The effects of arc-fault occurred in this compartment are evacuated
upwards outside the switchgear through an pressure relief duct.
Access to the connection compartment is possible thanks to a removable
cover provided with mechanical interlock against the three-position switch and
the circuit breaker.
All cable connections are of connector type conforming with PN-EN
13 6
50181:2010 standard, with the following features:
n outside cone end, 12
n single or double connection type C or single connection type F.

Cable connections depending on the panel type


n Circuit-breaker and disconnector panels 630 A:
§provided with a single connection type C,
2
15
§possibility of connecting up to 3 cable heads per phase 300 mm ,
§surge arrester (option).
n Circuit-breaker and disconnector panels 1250 A:
§provided with a single connection type C,
2
§possibility of connecting up to 3 cable heads per phase 300 mm , 29
§surge arrester (option).
n Circuit-breaker and disconnector panels 1600÷2500 A:
§provided with a double connection type C (2xC) or a single connection type F,
2
§possibility of connecting up to 8 cable heads 300 mm for the double
connection type C (2xC)*,
2
§up to 3 cable heads 500 mm for the connection type F,
§surge arrester (option). View of entered and terminated cables with T heads
* the same, even number of cable connections must be mounted on each [12] and coupling cables [13]
phase.

Cable test
n a cable tests performed at the front of the switchgear with the use of a special adapter,
n the test in a given cell can be performed when the other panels are energized.

A single connection type „C” in A double connection type C(2xC) in A single connection type „F” in
a 600 mm panel a 900 mm panel a 900 mm panel

11
Current transformers
Applied in switchgear type OPTIMA-24 single pole, toroidal current transformers are
mounted outside the gas compartment. Wires from the instrument transformers are entered
directly into the auxiliary circuits compartment, without any intermediate connections. The 6
transformers applied in the switchgear are listed in chapter 6.1.

Current transformers in the connection compartment


n As a standard, transformers are mounted on the extended cable connection.
n Easy replacement of transformers.
n Maximum length of a current transformer to be mounted on the interface type “C”: 214 mm.
6
n Maximum length of a current transformer to be mounted on the interface type “F”: 150 mm.
n In the case of transformer with a big number of secondary windings, which enclosure exceeds
the maximum allowable length, an additional transformer is mounted on the outgoing cable.

Voltage transformers
n Wires from the instrument transformers are entered directly into the auxiliary circuits
compartment, without any intermediate connections.
n 1-pole transformers.
n Transformers with earthed metal coating, plug-in, disconnectable type.
Current transformers [6]
Installation of voltage transformers in the connection compartment
n As a standard, voltage transformers are mounted in the connection compartment, on a pin of
a type A bushing [9].
n As a standard, voltage transformers in the primary circuit are switched on by a two-position
switch [14], mounted outside the gas compartment.
n Standard design enables measurements without removing the transformer from the
connection compartment. 10
n Voltage transformers are mounted outside the gas compartment.
n Possibility to replace a transformer when a fuse-link is damaged or blown.
n Possibility mounting of voltage transformers with unreplaceable fuse-links on the pin of
bushing type A [9].

Two-position switch of voltage transformers


n Operation of the two-position switch [14] with the use of operating mechanism of the two-
position switch [10]. Access to the operating mechanism is possible after removal of the
connection compartment cover.
n In its „earthed” position the primary side of the transformer is earthed.
n Possibility of padlocking the operating mechanism in two positions.
n A two-position switch of voltage transformers [14] in the gas compartment is always
mounted at the voltage transformer normally installed on bushings of voltage transformers Operating mechanism of a two-position switch [10]
[9].
n If the panel is not provided with voltage transformers, bushing pins [9] are protected with
insulating plugs.

Additional possibility of mounting voltage transformers in the connection compartment


n Installation of one voltage transformer (connected to the connector heads) for phase-to-
phase voltage testing. 15
n Installation of voltage transformers without fuse-links in the existing switchgear panels
subject to easy access to the connection compartment, i.e. a possibility to withdraw MV
cables from the compartment or access from the rear of the free-standing switchgear and
a possibility to connect a set of additional connector cable heads type T((K) 430 TB).
n Connecting voltage transformers located outside the switchgear if the number of cable
connections is not greater than the maximum allowable number of cables.
n Mounting of voltage transformers with unreplaceable fuse-links connected to connector
heads involves increasing the switchgear height by 125 mm.
Voltage transformers [15] of a metering panel
Voltage transformers in the metering panel
n Voltage transformers [15] mounted in the metering panel are protected with replaceable
fuse-links placed in special insulating enclosures [27].
n Replacement of a fuse-link after switching the three-position switch to “earthed” position.
n Earthing is made on both sides of the fuse-link enclosure, voltage transformer and the 28
internal busbars are earthed.

Fuse links
12
4.6. Switch operating mechanisms compartment
The operating mechanisms compartment is situated in the front part of the switchgear. The compartment is separated from the other
compartments by metallic partitions which provide suitable degree of protection. Wires of the switchgear control circuits run across the
compartment.
The operating mechanisms compartment can house various elements:
n napęd zasobnikowo sprężynowy wyłącznika próżniowego typu GMX-S, VEP,
n spring loaded operating mechanism of the three-position switch:
§manual actuating mechanisms, operating a disconnector and a circuit breaker with the use of a removable operating lever,,
n motor operating mechanism of a three-position switch (option):
§motor operating mechanism of a disconnector (in this design an earthing switch is manually operated),
§motor operating mechanisms of a disconnector and an earthing switch,
n electromagnetic interlocks of the socket of manual operating mechanism of a disconnector and/or earthing switch (option) of the three-
position switch,
n electromagnetic interlock of the socket of manual operating mechanism of busbar system earthing switch,,
n manometer for control of the insulation gas SF6,
n mechanical interlocks between switches which eliminate operator errors,
n a front cover with a synoptic diagram.
The equipment depends on the type of a panel.

0 0
7
1 1
1 8
Manual operating of a three-position switch with an operating lever
0 9

1. socket of manual operating mechanism of the three-position switch - earthing switch


13 2. socket of manual operating mechanism of the three-position switch - disconnector
3. switch position indicator - earthing switch
14
4. switch position indicator - disconnector
11
10 5. control gate of selecting a switch
6. interrogation lever
7. manometer
0034 12
8. “CLOSE” pushbutton of the circuit breaker
9. “OPEN” pushbutton of the circuit breaker
10. circuit breaker OPEN/CLOSE position indicator
11. spring charging position indicator
12. an opening for manual charging of the circuit breaker
13. locking of an earthed connection (e.g. the “open” pushbutton is locked
Operating panel of the circuit-breaker panel
with the use of a padlock)
with a busbar system earthing switch
14. operating cycles counter

5
6
0 0 0 0 0 0
7
1 1 1 1 1 1 1
8
2
9
3
4
13

14
11
10

0034 12

Operating panel of the Operating panel of the Operating panel of the


disconnector panel metering panel circuit breaker panel
13
4.7. Three-position switch
General characteristic
n Switching operations in the SF6-filled switchgear vessel.
n Maintenance-free.
n Torque transmission to the inside of the vessel and then to the 3P switch is made through a shaft sealed with O-rings to ensure tightness of
the vessel.
n Compact design thanks to short switching intervals in the SF6 gas.
n A three-position switch is the main switch in the switchgear.
Operating mechanisms
The three-position switch is operated on the front of the switchgear from the
operating panel, or from the facade of the auxiliary compartment door in the case
of design with motor driving mechanisms.
Options
n Motor driving mechanism type CTD-24/F-.. 4
§motor driving mechanism of the disconnector (in this design the earthing
switch is manually operated),
§motor driving mechanisms of the disconnector and the earthing switch.
n Spring-loaded operating mechanism (manual operating mechanisms of the
disconnector and the earthing switch).
n Electromagnetic interlocks of sockets of the operating mechanisms (Y80 of the
disconnector and/or Y81 of earthing switch of the panel).
Switching positions A view of the 3P switch mounted in
the gas compartment

closed open earthed

A view of operating panel of the three-position switch A view of operating mechanism A view of operating mechanism
type CTD-24/F-2M type CTD-24/F
4.8. Two-position switch
Operating mechanisms
A two-position switch is manually operated.
The operating mechanism is located inside the connection
compartment. 10
Options
n the operating mechanism is locked with the use of a padlock. 14
Switching positions 9

closed open and


earthed Two-position switch of a voltage Operating mechanism of the
transformer two-position switch

4.9. Busbar system earthing switch


General characteristics
n Switching operations in the SF6-filled switchgear vessel.
Operating mechanisms
The earthing switch is operated from the operating panel on the front of the switchgear.
Options
n Manual operating mechanism with a rotary lever.
n Electromagnetic interlock of the Y82 manual drive socket.
Switching positions

A view of operating panel of three-position switch and


busbar system earthing switch

Busbar system earthing Busbar system earthing 14


switch open switch closed
4.10. Vacuum circuit breaker GMX-S
General characteristics
n Maintenance-free.
n Interlocking system in the operating mechanism prevent maloperation.
n Reliable operating mechanism thanks to a small number of elements.
n Dedicated for OPTIMA-24 switchgear.
Operating mechanism
n Controlled on the front of the switchgear from the operating panel or from the facade of the auxiliary compartment door.
n Stored-energy motor operating mechanism for auto-reclosing.
n The operating mechanism located outside the gas compartment.
n Mechanical endurance for 30 000 operating cycles.
Functions of the operating mechanism
In the case of motor operating mechanism, the closing spring is charged by means of a motor and latched in the charged position (“spring
charged” indication is visible). Closing is effected either by means of an ON pushbutton or a closing solenoid. The closing spring is recharged
automatically (for auto-reclosing).

Equipment:
n Y1* - electromagnetic lock against closing with a rectifier - V4 (option)
n Y2 - opening voltage release with a rectifier - V3
n Y3 - closing voltage release with a rectifier - V2
n Y10* - 2nd opening voltage release with a rectifier - V5 (option)
n M0 - motor of the circuit breaker operating mechanism with a rectifier V1
n K0 - anti-pumping protection relay
n S1 - limit switch of operating mechanism charging
n S2 - limit switch on the locking electromagnet - Y1
n S3 - auxiliary switch on the operating mechanism shaft
n R0, R1 - series resistors
n XT - 50-terminal strip
n XB - 20-terminal strip

The basic design does not include


any optional elements. The S2 aux-
iliary switch must be bridged if Y1
electromagnetisnotrequired.
XT terminal strip of the circuit
breakercircuitsislocatedintheaux-
iliarycircuitscompartment.

Circuit breaker type GMX-S

Technical data GMX-S


Rated voltage kV up to 25
Power frequency withstand voltage kV 50
Lightning impulse withstand voltage kV 125
Rated current:
normal A up to 2500
short-time withstand current kA/s up to 31,5/3
peak withstand current kA up to 80
making current kA up to 31,5
breaking current kA up to 80
Rated operating sequence O - 0,3s - CO - 15s - CO
Rated frequency Hz 50
Opening time ms <30
Closin time ms <50
Rated control voltage V 110/220 DC
Electrical class E2
Mechanical class M2
Re-ignition class C2
Contact life 30 000 CO -- 1250 A / 10 000 CO -- 2500 A
Compilance with standards PN-EN 62271-1, PN-EN 62271-100

15
5. TECHNICAL DATA
Type of the switchgear OPTIMA-24
Rated voltage kV up to 25
Power frequency withstand voltage kV up to 50
Lightning impulse withstand voltage kV up to 125
Rated current
normal of main busbars A up to 2500
cubicle with circuit breaker A up to 2500
short-time withstand current kA/s up to 31,5/3
peak withstand current kA up to 80
Internal arc withstand current kA/s up to 31,5/1,2
Rated frequency Hz 50
Busbar system Single in solid insulation
Degree of enclosure protection IP 4X
Degree of reservoir protection IP 67
Rated filling pressure for pre insulation at 20°C kPa 130
Alarm level for pme insulation at 20°C kPa 120
Minimum operating pressure level for pme insulation at 20°C kPa 110
Weight of gas-insulated kg 2,850
Dimensions of panels
width [A] mm 600, 9001)
2)
height [B] mm 2150
depth [C] mm 1300, 14253)
Weight of:
disconnector panel 630 A kg 460
disconnector panel 1250 A kg 480
disconnector panel 2500 A kg 580
circuit breaker panel 630 A kg 580
circuit breaker panel 1250 A kg 600
circuit breaker panel 1600 ÷ 2500 A kg 740
metering panel kg 500
Internal Arc Classification AFLR
Loss of Service Continuity Classification LSC2B
PN-EN 62271-1, PN-EN 62271-102, PN-EN 62271-200
Compliance with standards
PN-EN 60529
1)
Width of a panel with rated current Ir > 1600 A.
2)
Other execution after consultation with the manufacturer.
3)
Depth of a panel with voltage transformers with fuse-links connected by cable connections with connector heads.

Examples of schematic diagrams

METERING PANEL CIRCUIT BREAKER PANEL CIRCUIT BREAKER PANEL DISCONNECTOR PANEL COUPLING PANEL COUPLING PANEL

16
6. MAIN CIRCUITS
- busbar system compartment - gas compartment - connection compartment

CIRCUIT BREAKER PANEL UP TO 1250 A

or and/or and/or

or or

and/or

2) 2)

or

1) 1)
or or
lub and/or or or

1)

BUS SECTIONALIZER UP TO 1250 A

or and/or and/or and/or or

or or or or

NOTE!
1) Voltage transformers and surge arresters use 1 connector connection.
2) Standard design.

17
DISCONNECTOR PANEL UP TO 1250 A

or and/or and/or

or or

and/or

2) 2)

or

1) 1)
or or
or and/or or or

1)

METERING PANEL UP TO 1250 A

or and/or and/or

1) 1)
or or
or

NOTE!
1) Voltage transformers and surge arresters use 1 connector connection.
2) Standard design.

18
CIRCUIT BREAKER PANEL UP TO 2500 A

or and/or and/or

or or

and-

2) 2)

or

1) 1)
or or
or and/or or or or

1)

or or or

BUS SECTIONALIZER UP TO 2500 A

or and/or and/or and/or or

or or or or or

or or or or or or

19
DISCONNECTOR PANEL UP TO 2500 A

or and/or and/or

or or

and/or

2) 2)

or

1) 1)
or or
or and/or or or or

1)

or or or

NOTE!
1) Voltage transformers and surge arresters use 1 connector connection.
2) Standard design.

SWITCHING POSITIONS
Two-position switch of
Three-position switch Three-position switch of metering panel a voltage transformer

transformers
earthed
closed closed

transformers
closed

open
open Busbar system earthing switch

busbar system
earthed earthing switch
closed
fuses,
transformers
earthed
busbar system
earthing switch
open
20
6.1. Switchgear equipment
Symbol Type of device Type; technical data Manufacturer
630 ÷ 2500 A
Three-position switch with
an operating mechanism
OU-3P-630 ZARMEN
type CTD-24/F
OU-3P-1250 Zakład ELEKTROBUDOWA
(manually operated)
OU-3P-2000

Manually operated busbar


US-2P ZARMEN
system earthing switch
Zakład ELEKTROBUDOWA

630 ÷ 2500 A
M M Three-position switch with
an operating mechanism
OU-3P-630 ZARMEN
type CTD-24/F-2M
OU-3P-1250 Zakład ELEKTROBUDOWA
(motor operated)
OU-3P-2000

Three-position switch with 630 ÷ 2500 A


M an operating mechanism
type CTD-24/F-M OU-3P-630 ZARMEN
(motor operated OU-3P-1250 Zakład ELEKTROBUDOWA
disconnetor) OU-3P-2000

Three-position switch with


an operating mechanism
OU-3P-P ZARMEN
type CTD-24/F
(manually operated) Zakład ELEKTROBUDOWA

Three-position switch with


an operating mechanism
OU-3P-P ZARMEN
type CTD-24/F-2M
M M Zakład ELEKTROBUDOWA
(motor operated)

Three-position switch with


an operating mechanism
type CTD-24/F-M OU-3P-P ZARMEN
M (motor operated Zakład ELEKTROBUDOWA
disconnetor)

GMX-S
630 ÷ 1250 A; 2500 A ZARMEN
Zakład ELEKTROBUDOWA
M Circuit breaker VEP-24T
630 ÷ 1250 A GELPAG
1600 ÷ 2500 A

Two-position switch
OU-2P ZARMEN
of a voltage transformer
Zakład ELEKTROBUDOWA

UEIN-24 ARTECHE
lub lub Plug-in and disconnectable
voltage transformer
GBEIC 12-24/0 SES 4)
RITZ
GBEIC 12-24/0 S 2) 5)

KSOH1911
KSOH 2710 RITZ

ICH-3 ARTECHE
Current transformer
ASG106 ASTAT

KATK-85/190-... ALCE

Voltage transformer
in Plug-in GBEAN 12-24/0 RITZ
at the busbar

Capacitive voltage WN
PB ENERGOTEST
detecting system
Wnd

21
Plug-in surge arrester CSA 15-10
NKT cables
on the busbar 3) CSA 17,5-10
CSA 24-10

ABB
Fuse - SIBA 2)
BUSCHMAN

CB24-630 (1250/2)
CB 24-630 (1250/2) + CC 24-630 (1250/2)
NKT cables
CB 42-2500/3
CB 42-2500/3 + CC 42-2500/3
Cable connection with
an outside cone plug K430TB
K430TB + K300PB
K434TB EUROMOLD NEXSANS
K484TB
K484TB + K804PB
CSA24-5(10)
NKT cables
screened

surge arrester 300PB-10SA-15N


to the 300PB-10SA-22N
1) 300PB-10SA-30N
connector head EUROMOLD NEXSANS
800PB-10SA-15N
800PB-10SA-22N
800PB-10SA-30N

Ferranti IO-13
IO-13d ENERGOTEST
transformer
IO-16

Plug-in voltage transformer,


mounted separately,
GBEIC 12-24/0 S RITZ
or connected through
a short cable

Plug-in voltage transformer


with fuses,
GBEI 12-24/0 SES RITZ
or mounted separately,
connected through
a short cable

1)
A surge arrester for cable heads as recommended by the manufacturer of the applied head
2)
Preferred solution
3)
A surge arrester for the busbar system as recommended by the manufacturer of the applied system
4)
With fuse-links
5)
Without fuse-links
! Switchgear equipment other than presented in the catalogue shall be agreed with the Construction Team in Konin.

22
7. FOUNDATION
The switchgear can be arranged in one row or in two rows. Panels in one raw must have the same depth and the with adjusted to
their equipment. The switchgear must be placed on a foundation frame fixed directly to the floor or on the raised floor.
The wall distance on the side and back of the switchgear shall be at least 50 mm. Fixing holes in the floor and the dimensions of
foundation frames are shown at the drawing below. Recommended height of the switchgear room: at least switchgear height
B + 600 mm. The manufacturer should be consulted in the case of lower rooms.

ΣA + 38
A
e
f

g5
Fixing holes
4x M10
g4

h
g
g3

B B

d A A

i
g2
g1

j
Design 1
ΣA + 38
A

f
g5

Fixing holes
4x M10

tube Ø160
g6

g9 g8 g8
g

B B
g7

d A A
g2

i
g1

j
Design 2
NOTE:
1. M 10 threaded holes for installation of the switchgear must be made in the channel bars of the foundation frame.
2. The foundation frame must be made of C50 steel channel bar and mounted on the concrete floor or on the construction of raised floor.
3. The frame of each panel must be fixed to the foundation floor with at least two M10 bolts, diagonally.
4. The following methods of arrangement shall be used in the concrete floors:
n Arrangement 1 - when the number of cables is greater than 3 per phase and in 900 mm panels with rated current > 1600 A.
n Arrangement 2 - when the number of cables is not greater than 2 per phase.

23
A g1
d e f h i j g g2 g3 g4 g5 g6 g7 g8 g9
Width
mm

600 30 512 360 44 29 120 75 200 455 540 22 715 170 190 110
1250
900 30 720 540 80 29 180 75 200 700 480 22 - - - -

B-B
cable ducts foundation frame
A-A

Anchor - shall be made of

3
38
4x70x30 sheet metal. Weld
min. 400

along the perimeter of the


frame in the distance not

50
greater than 1000 mm at the
angle approx. 60°.
cab
tube ø160 le nich
e foundation frame

B-B
Tube bushings
foundation frame

tube ø160

Preparation of the room for switchgear installation consists of:


n completion of civil works and painting, completion of ventilation, water and sewage works,
n installation of the lighting system,
n mounting and leveling the foundation frames,
n providing a suitable door opening (recommended dimensions: dimensions of a switchgear panel + 200 mm on the width and on the
height),
n ensuring that the entrance door can be locked or padlocked,
n for the free-standing switchgear - providing a required operating gangway with suitable width on the back.

24
8. INSTALLATION
The PN-EN 62271-200 standards specifies minimum admissible installation conditions for switchgear with classification of internal
arcing resistance IAC. It is forbidden to install the switchgear in rooms which do not meet the relevant requirements of the standard. A
drawing below shows the method of mounting OPTIMA-24 switchgear on the raised floor.

800 / 1100
Minimal dimensions of door in the switchgear
room
600

min. 50 min. 50
C

2650
B

min. 1500
820-1000

Preparation of the room for installing OPTIMA-24 switchgear consists in ensuring suitable door opening (recommended dimensions:
dimensions of a switchgear panel + 200 mm on the width and on the height). Please contact us if, for any reason, the dimension cannot be
assured.
Minimal dimensions of door [1] in the switchroom:
n width: 800; 1100 mm,
n height: 2650 mm (2350, 2500 - in the case of a lowered auxiliary circuit compartment).
It must be considered whether the switchgear is provided with higher auxiliary circuits compartment or additional voltage transformers
cabinet on the top, above the busbar compartment. Height of the auxiliary circuits compartment may be increased by 150 or 300 mm, while
an additional cabinet with voltage transformers is 300 mm high. These dimensions must be taken into account in designing the switchgear
room.

Minimal distance between the switchgear sections in the switchroom is 1500 mm (for a typical panel depth). Dimensions of a cable duct
[2] or cables space depending on the minimal bend radius of MV cables:
n depth of switchgear panel,
n width of the operating gangway.

25
Example of mounting and arrangement of a foundation frame
65

19

15
24
1250

19
19
35

66
600 900 600
4 x 600 = 2400 1800 4 x 600 =2400
ΣA + 38

800 / 1100
1500
1300

Example of switchgear arrangement


50
1300

35

50 600 600
4 x 600 = 2400 900 900 4 x 600 = 2400
800 / 1100
1500

50
1300
50

26
9. DESIGNING
ELEKTROBUDOWA SA offers designing of the switchgear.
It is advised to get acquainted with the following recommendations before starting to design OPTIMA-24 switchgear. Standard
diagrams are presented in the switchgear catalogue. The technical specification required for manufacture of the switchgear must
include:
n technical description of the switchgear;
n main circuits diagram indicating the selection of devices and connections (types, quantity, cross-section, load capacity; the
method of cable connections routing and phase sequence for each cell);
n development of auxiliary circuits:
§selection of devices,
§schematic diagrams and installation drawings,
§arrangement of equipment,
§the way of entering the auxiliary circuit cables (type, quantity, size),
n summary of equipment of the main and auxiliary circuits in electronic form;
n drawings of foundation and arrangement of panels in the room;
n a list of descriptions of switchgear panels application, numbering and process descriptions;
n colours of front covers (our standard colour is RAL 7032 grey);
n description of external inputs/outputs of the programmable controller;
n defining, either in descriptive or graphic form, logical – time relationships of the programmable controller, accounting for
relations with external signals and internal (logic) signals of the controller.

In the standard design, ELEKTROBUDOWA SA makes connections between devices with the use of single-core conductors (stranded
copper wire) following the rule:
2
n 0,75 mm control and signalling circuits,
2
n 1,5 mm auxiliary circuits of voltage transformers,
2
n 2,5 mm auxiliary circuits of current transformers.
On request, it is possible to use a conductor of different size or type.
External installations and foundation frames are subject to separate agreement. Other than offered in the catalogue equipment of
switchgear panels must be agreed with the Construction Department (TR) in Konin.

10. TRANSPORT
The switchgear is adjusted to road transport. Another means of transport, such as a container or ship, shall be specified together
with the order. A transport set includes one switchgear panel (functional unit). Weight of one transport set as in the table, chapter 5.
Devices which are not shock-resistant, busbar system and additional equipment (levers, keys, etc.) are shipped in separate packages.
Loading and unloading with the use of a hoisting or travelling crane. The switchgear should be transported directly to a suitable
prepared switchroom.

11. ORDERING
An order should include technical data of the switchgear and a technical specification prepared according to the guidelines in
chapter 9 “DESIGNING”.
Warranty terms granted for the switchgear are specified in “Certificate of Warranty”.
Validity of the warranty is subject to the user's conforming to the manufacturer's requirements and the requirements set in the
switchgear operating and maintenance manual.
The switchgear warranty does not cover equipment supplied by the Client.

ZARMEN Zakład ELEKTROBUDOWA offers:


n professional manufacture and mounting of the foundation frame in the prepared room,
n transport of switchgear to the indicated address,
n installation of switchgear together with connections in the prepared room according to chapter 8,
n professional supervision of the installation works performed by a third party,
n tests after erection.

27
12. NOTES

28
29
Designing, manufacture and installation of:
n gas-insulated high voltage switchgear,
OPTIMA 145
n gas-insulated medium voltage switchgear,
OPTIMA-24
n medium voltage switchgear,
n drawout of D series of types,
D-12P(L), D-17P(L), D-24P(L), D-40P, D-12PT, D-17PT and double-level D-12-2P
n drawout, double-system of D series of types,
D-12-2S, D-17-2S, D-24-2S, D-36-2S
n drawout,
PREM-14S, PREM-14SM
n mining, for application in underground mines, with approval of Chairman of WUG,
PREM-G1dM, D-12-2S, PREM-12G SMART (D-12P - in progress )
n fixed-type,
J-7, J-17, J-24, J-36, D-17G
n secondary distribution,
UNIPANEL
n low voltage switchgear,
NGW R I RNM-2
n traction DC switchgear,
RT-1, RT-3
n rectifier units,
PD 1700/3,3 EB
n medium voltage vacuum circuit breakers,
EV1, GMX-S
n indoor medium voltage earthing switches,
UM i UMR
n mobile containerized power substations provided with switchgear for rated voltages up to 40 kV,
SKP
n operator cabin,
KO-1, KO-2
n transformer chambers,
NGW K
n low voltage busducts,
NGW M-1, PONTIS
n medium voltage busducts
ELPO, ELPE, PELPO

Specialist services:
n overhauls of power equipment,
n control and instrumentation work,
n after-sales service,
n powder paint coating,
n processing of sheet metal on numerically-controlled machines.

Zakład Produkcji Rozdzielnic / Switchgear Production Plant


ul. Przemysłowa 156, 62-510 Konin ZAKŁAD
zaklad.konin@zarmen-elektrobudowa.pl ELEKTROBUDOWA

Biuro Północ / Office north Biuro Południe / Office South Biuro Zachód / Office West Rynek Eksportu/ Export Market
ul. Przemysłowa 156, 62-510 Konin ul. Porcelanowa 12, 40-246 Katowice Aleja Karkonoska 59B, 53-015 Wrocław ul. Przemysłowa 156, 62-510 Konin
tel. +48 691 780 451 tel. +48 695 759 394 tel. +48 721 060 614 tel. +48 603 338 672
marketing.polnoc@zarmen-elektrobudowa.pl marketing.poludnie@zarmen-elektrobudowa.pl marketing.zachod@zarmen-elektrobudowa.pl products@zarmen-elektrobudowa.pl

© Copyright by ZARMEN Zakład ELEKTROBUDOWA Wszelkie prawa zastrzeżone / All rights reserved Wydanie / Edition 02-2021
® Rozwiązania konstrukcyjne są chronione prawem autorskim / The design solutions are protected by copyright 23/K/2020

ZARMEN Sp. z o.o.


ul. Chłodna 51, 00-867 Warszawa,
zarmen@zarmen.pl, www.zarmen.pl

You might also like