DB

LP
REFERENCE
LOCATION VERIFY ACTUAL
VOLTS 230 VOLTS, 1PHASE
CIRCUIT BREAKER RATING VA CKT LOAD
CKT NO: POL VOLT CURRENT WIRE
AT HZ LOAD DESCRIPTION WIRE SIZE AND CONDUITS
E S (AMPERE) SIZE
1 20 60HZ 2 230 ICE CREAM MACHINE 2,700 11.73 3.5 mm² 2-3.5 mm² THHN WIRE +1-3.5 mm² THHN WIRE GROUND in 15mm PVC Ø
2 20 60H 2 230 FRIED CE CREAM 1000 4.34 3.5 mm² 2-3.5 mm² THHN WIRE +1-3.5 mm² THHN WIRE GROUND in 15mm PVC Ø
3 Z
20 60H 2 230 LED TV 32" FOR MENU 6PCS 250 0.97 3.5 mm² 2-3.5 mm² THHN WIRE +1-3.5 mm² THHN WIRE GROUND in 15mm PVC Ø
4 Z
20 60H 2 230 PENDANT LIGHT 4PCS 20 1.08
0.08 3.5 mm² 2-3.5 mm² THHN WIRE +1-3.5 mm² THHN WIRE GROUND in 15mm PVC Ø
5 Z
20 60H 2 230 ACU 1.5HP 1046 4.54 3.5 mm² 2-3.5 mm² THHN WIRE +1-3.5 mm² THHN WIRE GROUND in 15mm PVC Ø
6 Z
20 60H 2 230 ACU l.5HP 1046 4.54 3.5 mm² 2-3.5 mm² THHN WIRE +1-3.5 mm² THHN WIRE GROUND in 15mm PVC Ø
7 Z
20 60H 2 230 PIN LIGHTS LIGHT (29PCS) 87 0.37 3.5 mm² 2-3.5 mm² THHN WIRE +1-3.5 mm² THHN WIRE GROUND in 15mm PVC Ø
Z COUNTER AREA PIN LIGHTS 54 0.14
60H LIGHT (18PCS) 2-3.5 mm² THHN WIRE +1-3.5 mm² THHN WIRE GROUND in 15mm PVC Ø
8 20 2 230 CEILING LIGHTS LIGHT (llPCS) 33 0.14 3.5 mm²
Z 2-3.5 mm² THHN WIRE +1-3.5 mm² THHN WIRE GROUND in 15mm PVC Ø
WALL LIGHTS LIGHT (5PCS) 165 0.71 2-3.5 mm² THHN WIRE +1-3.5 mm² THHN WIRE GROUND in 15mm PVC Ø
9 20 60H 2 230 CONVINIENCE OUTLET 1000 4.34 3.5 mm² 2-3.5 mm² THHN WIRE +1-3.5 mm² THHN WIRE GROUND in 15mm PVC Ø
Z

TOTAL LOAD= 32.98(0.8) DF + 0.25 (4.54)= 27.52 AMPERE TOTAL TOTAL=


WATTAGE = 32.98
MAIN FEEDER 8.0 mm² THHN TWN COPPER WIRE
7,401 AMPERE
MAIN CIRCUIT BREAKER 40 AT, 2POLE, 230V

GENERAL NOTES
1. All electrical works shall comply in accordance with these plans and specifications.
The applicable provisions of the latest edition of the Philippine Electrical Code (PEC).
The rules and regulation of the local enforcing authority and the requirements of the local power company. The electrical works shall be done under the immediate supervision of a duly registered electrical engineer.
2. Wiring method shall be as follows
A. Feeders and risers - intermediate metallic conduit
B. Lighting, power receptacle - polyvinyl chloride conduit sch. 40 branch ckt. & auxiliar
3. All wires shall be copper and thermoplastic insulated type "thwn" unless otherwise indicated in the plan. The minimum size of wire for power and lighting circuit homerun shall be 3.5mm2 and
insulated for 600 volts. The smallest raceway shall be 15mm nominal size.
4. All outlet boxes shall be galvanized gage no. 16 deep types with factory knockouts.
5. All materials to be used shall be brand new and approved type for the particular location and purpose of usage.
6. Grounding system shall be provided to all lighting and power circuit as per Philippine Electrical Code requirement.
7. Mounting height of wiring devices shall be as follows :
a. Light switch - 1.20 m above finish floor
b. Convenience outlet - 0.30 m above finish floor
c. Panel board - 1.50 m above finish floor.
d. Fire alarm station outlet - 1.50 m. above finish floor.
e. push button outlet - 1.20 m above finish floor
f. fire aIarm & vibrating bell - 0.30 m below ceiling line
Project: Owner: PEE Signature

Proposed load downgrade of Miguelito's Ice Cream House Michella A. Aman PRC: TIN:
1514 National Road P. Guevarra St. Sta. Cruz Laguna PTR: DATE: