Typical Limiting Valuesof Sub Station Electrical Equipment
Typical Limiting Valuesof Sub Station Electrical Equipment
1. Transformer / Reactor:
Sr.
Equipment / test data
No. Permissible limits Reference
Transformer oil
a) BDV
600 kV (Gap – 2.5 mm) –
-At the time of first charging
Minimum IS – 1866
50 kV (Gap – 2.5 mm) –
-During O&M
Minimum IS – 1867
b) Moisture content IS – 1868
A) -At the time of first charging 15 PPM (Max.) IS – 1869
-During O&M 25 PPM (Max.) IS – 1870
c) Resistivity at 90 degree C 0.1-1012 Ohm-CM (Min.) IS – 1871
d) Acidity 0.2 mg KOH/gm (Max.) IS – 1872
e) IFT at 27 degree C 0.018 N/M (Min.) IS – 1873
f) Tan delta at 90 degree C 0.20 (Max.) IS – 1874
g) Flash point 126 Deg. C (Min.) IS – 1875
Vibration level for reactors 200 Microns (Peak to Peak) IS – 1876
B)
60 Microns (Average) IS – 1877
Tan delta for bushing at 20 0.007* IEC – 137
C)
Deg. C
D) Capacitance for bushing + 5% variation IEC – 138
1000 M-Ohm By 5.0/10.0 kV IEC – 139
E) IR value for winding
Megger
Tan delta for windings at 20 0.007* IEEE/C57.12.90.1980
F)
Deg. C
Contact resistance of 10 M. Ohm / Connector
G)
bushing terminal connectors NGC.UK Recommendations
H) Turret Neutral CT ratio errors 39 IS – 2705
2. Circuit Breakers
Sr.
Equipment / test data
No. Permissible limits Reference
Manufacturers
ABB make
8-12 MS Recommendations
D) Manufacturers
NGEF make
8-12 MS Recommendations
Manufacturers
M&G make
8-12 MS Recommendations
Manufacturers
TELK make
8-12 MS Recommendations
Manufacturers
ABB make (HVDC)
8-12 MS Recommendations
PIR opening time prior to
opening of main contacts
E)
(ABB, CGL, NGEF make Manufacturers
CBs) 5 MS (Min.) at rated pressure Recommendations
Pir and main contacts
F) overlap time [BHEL, M&G, Manufacturers
ABB (imported) make CBs] 6 MS (Min.) at rated pressure Recommendations
Tan delta of grading
G)
capacitors 0.007 at 20 Deg. C
Capacitance of grading Within + 10% / -5% of the rated
H)
capacitors value IEC 359
I) Contact resistance of CB 150 M. Ohm
Contact resistance of CB NGC, UK
J)
terminal connector 10 M. Ohm per connector recommendations
IR value:
1000 M Ohm (Min.) by 5.0 /
1. Phase – earth
10.0 kV Megger
K) 1000 M Ohm (Min.) by 5.0/10.0
2. Across open contacts
kV Megger
50 M Ohm (Min.) by 0.5 kV
3. Control cables
Megger
Pressure switch settings
-SF6 gas pressure switches Within + 0.1 Bar of set value
L)
-Operating air pr. Switches Within + 0.1 Bar of set value
-Operating oil pr. Switches Within + 0.1 Bar of set value
BDV of oil used for MOCB
M) -At the time of filling 40 kV at 2.5 mm Gap (Min.) Mfgs. Recommendation
-During O&M 20 kV at 2.5 mm Gap. (Min.) Mfgs. Recommendation
3. Current Transformer
Sr.
Equipment / test data
No. Permissible limits Reference
IR value
1000 M – Ohm (Min.) by
1. Primary – earth
5.0/10.0 kV Megger
A) 50 M – Ohm (Min.) by 0.5 kV
2. Secondary – earth
Megger
50 M-Ohm (Min.) by 0.5 kV
3. Control cables
Megger
B) Tan delta value 0.007* at 20 Deg. C
NGC, UK
C) Terminal Connector
10 M-Ohm per connector Recommendations
D) CT ratio errors + 3% -Protection cores IS – 2705
D) CT ratio errors + 1% -Metering cores IS – 2706
4. Capacitive Voltage
Sr.
Equipment / test data
No. Permissible limits Reference
5. Isolators
Sr.
Equipment / test data
No. Permissible limits Reference
6. Surge Arrester
Sr.
Equipment / test data
No. Permissible limits Reference
7. Miscellaneous
Sr.
Equipment / test data
No. Permissible limits Reference
8. Batteries
Sr.
Equipment / test data
No. Permissible limits Reference
1 10 0.8
2 15 0.9
3 20 1.0
4 25 1.12
5 30 1.25
6 35 1.40
7 40 1.55
8 45 1.75
9 50 1.95
10 55 2.18
11 60 2.42
12 65 2.70
13 70 3.00
If Tan Delta of bushing/winding/CVT/CT is measured at oil temperature T Deg. C. Then Tan Delta at 20 Deg. C shall
be as given below:
Tan Delta at 20 Deg. C = Tan Delta at Temp T Deg. C / Factor K.
Dew Point Limits for SF6 Gas in EHV Circuit Breakers
Sr. Make of Dew point at Corresponding dew
rated Pr. Deg. point at Atmospheric
No C.B C .Pr. Remarks