N-267 Oct.

2000
Data Sheet for Medium Voltage Metal-Clad Switchgear
from 2.4 kV to 34.5 kV

Client       Engineering Org.       Spec. No.      


Project title       Location       Date      
Project location       Contract No.       Equip. No.      
Project No       Specifier Name       Tele. No      
P.O. No.      
Refer to PIP ELSSG02 for General Requirements
Applicable State and Local Codes:      

Data Provided By:  Buyer  Seller With Proposal  Seller After Order

Service Conditions (4): Power Circuit Breakers (8): (cont’d)


Altitude       m Seismic Zone       Ground & Test Switch Required
Ambient Temperature: Max.       C Min.       C Description:      
Other            
Rating & System Parameters (5): Main Bus Ratings (9.1):
Volts      Phase       Hertz             Amperes Silver-Plated Tin-Plated
Wye Delta Other:       Barriers (9.3.3)
Fault Current       (RMS SYM) X/R Ratio       No Yes
One-Line Dwg. No.       Remote Control (10.2)
System Grounding: Required (Description Attached) Not Required
High Resistance Low Resistance Ungrounded CT Wire Color (10.3.2)
Ground Fault Current       Amperes Black Gray
Feeder Breaker Configuration (6.1.5): Differential CT Wire Color (10.3.10)
Red/Blue/Yellow Gray
One-High Two-High
Indicating Lights (10.7.1):
Enclosure (6.1):
Amber       Purpose      
Indoor Outdoor per ELSSG12
Other       Purpose      
Cable (6.2):
Heat Output Data:
Power Cable Entry: Top Bottom
_________________ BTU/HR For Entire Swgr. Line Up
Cable Lugs: By Buyer By Seller
Metering (10.7):
Control Cable Entry: Top Bottom
Microprocessor-Based Other:      
Bus Duct (6.3)
Communication Req’d. Communication Not Req’d.
By Switchgear Seller By Others Not Required
RS 485  Other:      
Bus Duct Entrance (6.3) :
Partial Discharge Sensors (10.7):
Top Bottom Back Per Layout
Sketch Required Not Required
Arc - Resistant Construction (7): IR Termography (10.7):
No Yes Type B Other:       Required Not Required
Power Circuit Breakers (8): Protective Relaying (10.8):
Operating Voltage, 125 VDC Other:       Relay Description Shown on One-Line      
Capacitive Trips for AC Operating Voltage Flexitest Switches per PIP ELSSG02, Section 10.8.2
For Failure of Capacitive Trip Device: Relay Description Shown on Attachment      
 Auto Trip Alarm Contacts Automatic Trip Device or Trip Circuit Monitoring
Relay
Dual Trip Coils Not Required for Motor & Generator
Breakers Double Output Contacts
Operating Voltage Source: Space Heaters (10.9):
 By Buyer By Seller (per attachments) Thermostat Switch Not Required
 Interrupting Rating:       kA @       kV  Space Heater Load       Watts @       Volts
 Close and Latch:       kA Other:      
Remote Racking Device Required Not Required Space Heater Current Monitoring (10.9.4 e)
Accessories in PIP ELSSG02, Section 8.13 Not Required Not Required Required

Process Industry Practices Page 1 of 2


N-267 Oct. 2000
Data Sheet for Medium Voltage Metal-Clad Switchgear
from 2.4 kV to 34.5 kV

Data Provided By:  Buyer  Seller With Proposal  Seller After Order
DC Power Supply (10.10): Documentation:
Required Per Attached Electronic Document Format: .DXF Other:      
Spec.:       Manufacturer To Provide:
Not Required
Interior Finish (11):      Reproducible Plus
Mfg. Std. White      Number of Copies of All Documentation Plus
Shop Inspection & Tests (12.4):      Copies of the Operating Manuals
 Mfr./ANSI Standard Tests Other Tests as Described
Witnessed Not Witnessed Other Requirements:
Preshipment Shop Inspection      
Certified Test Reports      
Other:      
     
     

     

Process Industry Practices Page 2 of 2