F.F Room DB: 4x95mm cu/XLPE/PVC+50mm

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

MDB1

MCCB
250Af

2
4x95mm
2
cu/XLPE/PVC+50mm

F.F ROOM DB

MCCB
250af

400V, 250A 3PH+N+E CU. BUS

MCCB MCcB McCB MCB MCB


150af 63a 100a 40a 40a

2 2 2
4x35mm 4x16mm 4x16mm
cu/XLPE/ cu/XLPE/ cu/XLPE/
2 2 2
PVC+16mm PVC+16mm PVC+16mm

fire fighting water outdoor pumps SPARE SPARE


control panel treatment db
60kw plant
37kw
FF ROOM DB

MCCB
63A

2
4x16mm
2
cu/XLPE/PVC+16mm

OUTDOOR PUMPS DB

MCCB
63a

400V, 100A 3PH+N+E CU. BUS

MCB MCB MCB MCB MCB


16a 16a 32a 40a 40a

2 2 2
4x6mm 4x6mm 4x6mm
cu/XLPE/ cu/XLPE/ cu/XLPE/
2 2 2
PVC+6mm PVC+6mm PVC+6mm

CITY WATER WELL FUTURE FUEL SPARE SPARE


PUMP C.P. WATER PUMP C.P
PUMP C.P.
- All DBs boxes must be weather proof
- The distance from the main cable entry to the main
CB and the distances between other CBs must be
suitable for maintenance or if there will be any
change of CBs to other size rather than the
installed.
- Cable entry from the bottom.
- Cables' entry plate must be removable, and
contains a rubber seal and leave the openings to be
made on site.

You might also like