Download as pdf or txt
Download as pdf or txt
You are on page 1of 38

HITACHI AIR-COOLED WATER CHILLERS

– SCREW TYPE –
HITACHI
Nominal Capacity Range
R22: 116kW to 1,146kW Technical Catalog I
99,760kcal/h to 985,560kcal/h Design Information
33RT to 326 RT
R407C: 110kW to 1,089kW
94,600kcal/h to 936,540kcal/h Model: R22 R407C
31RT to 310 RT
RCU40AHYZ1 RCUG40AHYZ1
RCU50AHYZ1 RCUG50AHYZ1
RCU60AHYZ1 RCUG60AHYZ1
RCU75AHYZ1 RCUG75AHYZ1
RCU100AHYZ1 RCUG100AHYZ1
RCU120AHYZ1 RCUG120AHYZ1
RCU150AHYZ1 RCUG150AHYZ1
RCU180AHYZ1 RCUG180AHYZ1
RCU200AHYZ1 RCUG200AHYZ1
RCU240AHYZ1 RCUG240AHYZ1
RCU270AHYZ1 RCUG270AHYZ1
RCU300AHYZ1 RCUG300AHYZ1
RCU330AHYZ1 RCUG330AHYZ1
RCU350AHYZ1 RCUG350AHYZ1
RCU360AHYZ1 RCUG360AHYZ1
RCU380AHYZ1 RCUG380AHYZ1
RCU400AHYZ1 RCUG400AHYZ1

New Series! This series of HITACHI air-cooled water chillers up to 400HP has been developed for various
requirements of air-conditioning systems and industrial chilled water systems, where these equipment are operated under high
ambient temperatures of 43 ℃,Therefore, the units can be utilized under a wide temperature range.
These water chillers are equipped with newly model-changed semi-hermetic HITACHI A-type screw compressors,
featuring high reliability, low noise and low vibration, and highly efficient air-cooled condenser, resulting in compact design.
The unit is composed of compressors, air-cooled condensers, shell-tube type water coolers, and other auxiliary and control
devices, compactly packaged in a weather-proof cabinet which is constructed of galvanized steel plates processed with
specially baked resin paint.
FEATURE

NEW HITACHI AIR-COOLED WATER CHILLERS…


THAT’S THE ACHIEVEMENT OF TOTAL HITACHI TECHNOLOGE…
● The most reliable semi-hermetic screw type compressor
Adopting new profile screw rotors, HITACHI have developed the higher performance screw type compressor
to obtain a higher reliability and durability of the unit operation.

In this new century when people pay more attention to the change of the environment,
HITACHI semi-hermetic screw type compressors ,which use the R407C refrigerant directly,
and reduce the refrigerant leak greatly, have been sold 140,000 in the world !

Discharge Outlet 1. Efficiency is improved by using the highly precision rotors.


2. Separation efficiency is enhanced greatly by changing the oil separation mode.
Motor for Compressor

Slide Valve

Suction Inlet

Bearing
●Highly Efficiency Operation
The appropriate combination of the air side heat exchangers with high performance SLIT fins, highly efficient
screw compressors and water side heat exchangers has achieved this high efficiency of operation.

Heat-Exchanger(AHYZ1)

Air side heat-exchanger using the converse

M-type distributing resulting in an equality

distribution of the air velocity, achieves highly


heat exchange efficiency.

1.Improve the air heat exchanger configuration. 2.Adopt high heat exchange efficiency inner thread tube 3.Improve air velocity
distribution to enhance efficiency .

●Smaller Vibration and Lower Operation Sound


Due to the combination of the HITACHI semi-hermetic screw compressors and smooth-air-flow propeller fans for
air side heat exchangers, smaller vibration and lower sound operation has been achieved, therefore, in most
cases, special vibration absorbing curbs are not required by utilizing factory-supplied rubber mats.

1
FEATURE

Capacity Control

Continuous Capacity Control


z Chilled water outlet temperature can be controlled precisely within ±0.5℃ of the setting
temperature. This control is performed by applying a micro-computer to the continuous
capacity control type screw compressor.
z This precise temperature control is not only suitable for air conditioning, but also for industrial
use. Load-up signal When there is a big
difference between
set temperature and
12sec.
60sec. actual temperature

Load-up signal
Start
Inlet water
Inlet water 2sec. temperature
temperature 60sec.
Outlet water

Outlet water temperature
temperature


Neutral zone
6 standard
(Set temperature:5℃)
4 Stop temperature
Stop standard
Lapsed time
Load-down signal The inlet water temperature
A given load status is is detected at a stop, and it
maintained. is restarted by a raise in
2sec.
60sec. inlet water temperature

-Principle of Continuous Capacity Control-


Continuous capacity control is performed by adjusting the slide valve position as shown below.
The slide position can be changed freely between 100% and 15% in accordance with cooling load.
Load-up Load-down Hold

Pd: Discharge Pressure, Ps: Suction Pressure S1,2,3 :Solenoid Valve

Micro-Processor Control for Various Functions Other Option


z Alarm Indication for each cycle by 7-Segment The following specifications are available on
z Rotating control of compressor starting order order basis. Please contact local Hitachi’s
z Current limitation control distributors if required.
z Automatic start after instantaneous power failure z RS485 physics connector
Complete Standard Accessory z High static pressure fan (Max. outside
z Water connection companion flange static pressure:150Pa)
z Vibration-proof Mat z Remote control box
z Foundation Bolt, Nut, Washer and Bushing z Liquid crystal touch panel with big
z Spreader bar for rigging screen(Independent Box)
z Acoustic panel for compressor z HITACHI water chillers group control system
z Protection net for condenser

2
GENERAL DATA

General Data(R22 and R407C)

RCU100AHYZ RCU120AHYZ RCU150AHYZ RCU180AHYZ RCU200AHYZ


R22 RCU40AHYZ1 RCU50AHYZ1 RCU60AHYZ1 RCU75AHYZ1
1 1 1 1 1
Model
RCUG40AHY RCUG50AHY RCUG60AHY RCUG75AHY RCUG100AHY RCUG120AHY RCUG150AHY RCUG180AHY RCUG200AHY
R407C
Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1 Z1
kW 116 143 179 191 286 358 382 537 573
Nominal Cooling Capacity*1 R22 kcal/h 99,760 122,980 153,940 164,260 245,960 307,880 328,520 461,820 492,780
RT 33 41 51 54 81 102 109 153 163
kW 110 136 170 181 272 340 363 510 544
Nominal Cooling Capacity*1 R407C kcal/h 94,600 116,960 146,200 155,660 233,920 292,400 312,180 438,600 467,840
RT 31 39 48 51 77 97 103 145 155
─ Continuous Capacity Control
Capacity Control
% 100~15,0 100~15(7.5)*2,0 100~15(5)*2,0
Depth mm 2,390 4,490 6,590
Outer
Width mm 1,940 1,940 1,940
Dimension
Height mm 2,170 2,170 2,170
Net Weight kg 1,790 1,830 1,870 1,890 3,210 3,280 3,320 4,865 4,900
Standard — R22
R407C — R407C
Refrigerant
Flow Control — Thermal Expansion Valve
Number of Circuit — 1 2 3
Type ─ Semi-Hermetic Screw Type
Compressor Model ─ 40ASCC-Z 50ASCC-Z 60ASCC-Z 60ASCC-Z 50ASCC-Z 60ASCC-Z 60ASCC-Z 60ASCC-Z 60ASCC-Z
Quantity ─ 1 2 3
Condenser ─ Cross Fin Type
Condenser Fan ─ Direct drive Propeller Fan
Power Input kW 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1
Heat-Exchanger Fan Motor
Quantity ─ 4 4 4 4 8 8 8 12 12
Air Discharge m3/min 930 930 930 930 1,860 1,860 1,860 2,790 2,790
Evaporator ─ Shell and Tube Type

Overcurrent Relay for Compressor , Internal Thermostat for Compressor, Reverse Phase Protection Device for Compressor,Thermal
Safety Devices ─ Overcurrent Relay for Fan Motor,High Pressure Switch, Low Pressure Control, Suction Gas Temperature Control,Freeze Protection
Thermistor control,Oil Heater, Discharge Gas Thermistor, Fusible Plug, Fuse for Control Circuit and Pressure Relief Valve

Piping Connections for Water-Side Heat


─ With φ90 Inner Diameter Companion Flange With φ142 Inner Diameter Companion Flange
Exchanger(Inlet/Outlet)
Main Power
mm 233×140
(square orifice)
Connection Hole
Circuit mm 3×φ48;2×φ75 3×φ48;φ64;φ52;2×φ75

Shipping Weight*3 kg 2,000 2,040 2,080 2,100 3,610 3,680 3,720 5,500 5,535
Depth mm 2,600 2,600 2,600 2,600 4,700 4,700 4,700 6,800 6,800
Shipping
Width mm 2,190 2,190 2,190 2,190 2,190 2,190 2,190 2,190 2,190
Dimension
Height mm 2,510 2,510 2,510 2,510 2,510 2,510 2,510 2,510 2,510

NOTE:
1. The nominal cooling capacities are based on GB/T 4. Water Flow
18430.1-2007(*1) 1) RCU(G)240,300,360,400AHYZ1
Chilled Water Inlet/Outlet Temperature:12/7℃ It is necessary to control the common water flow volume to
Condenser Air Inlet Temperature:35℃(DB) each cooler.
2. Applicable Power Supply 2) RCU(G)270,330,350,380AHYZ1
Main Power Source Control Power Source Because the chilled water flow rate is different between No.1
(AC3φ) (AC1φ) and No.2 units. It is necessary to control the water flow
380V,50HZ 220V,50HZ volume of each unit with adjusting valves (Filed-Supplied).
415V,50HZ 240V,50HZ 5. It is required to connect electrical control wires between No.1
3. The units greater than 240AHYZ1 including 240AHYZ1 and No.2 units for the unit greater than 240AHYZ1including
consist of two modules and are separately shipped. (*3). 240AHYZ1.
The common chilled water piping (Filed-Supplied) 6. ( ) marked with *2 is available by selection switch.
between each water cooler shall be directly connected
at site.
Working Range
Item Standard
Chilled Water Outlet Temperature 5~15℃
Condenser Air Inlet Temperature(DB) 5~43℃

3
GENERAL DATA
General Data(R22 and R407C)
R22 RCU240AHYZ1 RCU270AHYZ1 RCU300AHYZ1 RCU330AHYZ1 RCU350AHYZ1 RCU360AHYZ1 RCU380AHYZ1 RCU400AHYZ1
Model
R407C RCUG240AHYZ1 RCUG270AHYZ1 RCUG300AHYZ1 RCUG330AHYZ1 RCUG350AHYZ1 RCUG360AHYZ1 RCUG380AHYZ1 RCUG400AHYZ1

kW 716 740 764 919 955 1,074 1,110 1,146


Nominal Cooling
R22 kcal/h 615,760 636,400 657,040 790,340 821,300 923,640 954,600 985,560
Capacity*1
RT 204 210 217 261 272 305 316 326

kW 680 703 726 873 907 1,020 1,055 1,089


Nominal Cooling
R407C kcal/h 584,800 604,580 624,360 750,780 780,020 877,200 907,300 936,540
Capacity*1
RT 193 200 206 248 258 290 300 310

─ Continuous Capacity Control


Capacity Control
% 100~15(7.5)*2,0 100~15(6)*2,0 100~15(7.5)*2,0

Depth mm 9,080(Minimum) 11,180(Minimum) 13,280(Minimum)


Outer
Width mm 1,940 1,940 1,940
Dimension
Height mm 2,170 2,170 2,170

Net Weight kg 2×3,280 3,320+3,280 2×3,320 4,865+3,320 4,900+3,320 2×4,865 4,900+4,865 2×4,900
Standard — R22

R407C — R407C
Refrigerant
Flow Control — Thermal Expansion Valve

Number of Circuit — 4 5 6

Type ─ Semi-Hermetic Screw Type

Compressor Model ─ 60ASCC-Z 60ASCC-Z 60ASCC-Z 60ASCC-Z 60ASCC-Z 60ASCC-Z 60ASCC-Z 60ASCC-Z
Quantity ─ 4 5 6

Condenser ─ Cross Fin Type

Condenser Fan ─ Direct Drive Propeller Fan

Heat- Fan Power Input kW 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1
Exchanger Motor
Quantity ─ 2×8 8+8 2×8 12+8 12+8 2×12 12+12 2×12

Air Discharge m3/min 3,720 3,720 3,720 4,650 4,650 5,580 5,580 5,580
Evaporator ─ Shell and Tube Type

Overcurrent Relay for Compressor , Internal Thermostat for Compressor, Reverse Phase Protection Device for Compressor,Thermal Overcurrent Relay for Fan Motor,High
Safety Devices ─ Pressure Switch, Low Pressure Control, Suction Gas Temperature Control,Freeze Protection Thermistor control,Oil Heater, Discharge Gas Thermistor, Fusible Plug, Fuse for
Control Circuit and Pressure Relief Valve

Piping Connections for Water-Side Heat


─ With φ142 Inner Diameter Companion Flange
Exchanger(Inlet/Outlet)

Main Power
mm 2×233×140
Connection Hole (square orifice)

Circuit mm 6×φ48;2×φ64;2×φ52;4×φ75

Shipping Weight*3 kg 2×3,680 3,720+3,680 2×3,720 5,500+3,720 5,535+3,720 2×5,500 5,535+5,500 2×5,535

Depth mm 2×4,700 2×4,700 2×4,700 6,800+4,700 6,800+4,700 2×6,800 2×6,800 2×6,800


Shipping
Dimension Width mm 2,190 2,190 2,190 2,190 2,190 2,190 2,190 2190
Height mm 2,510 2,510 2,510 2,510 2,510 2,510 2,510 2,510

NOTE:
1. The nominal cooling capacities are based on GB/T 4. Water Flow
18430.1-2007(*1) 1) RCU(G)240,300,360,400AHYZ1
Chilled Water Inlet/Outlet Temperature:12/7℃ It is necessary to control the common water flow volume to
Condenser Air Inlet Temperature:35℃(DB) each cooler.
2. Applicable Power Supply 2) RCU(G)270,330,350,380AHYZ1
Main Power Source Control Power Source Because the chilled water flow rate is different between No.1
(AC3φ) (AC1φ) and No.2 units. It is necessary to control the water flow
380V,50HZ 220V,50HZ volume of each unit with adjusting valves (Filed-Supplied).
415V,50HZ 240V,50HZ 5. It is required to connect electrical control wires between No.1
3. The units greater than 240AHYZ1 including 240AHYZ1 and No.2 units for the unit greater than 240AHYZ1including
consist of two modules and are separately shipped. (*3). 240AHYZ1.
The common chilled water piping (Filed-Supplied) 6. ( ) marked with *2 is available by selection switch.
between each water cooler shall be directly connected
at site.

Working Range

Item Standard
Chilled Water Outlet Temperature 5~15℃
Condenser Air Inlet Temperature(DB) 5~43℃

4
DIMENSION DATA

Unit Dimensions

RCU(G)40AHYZ1, RCU(G)50AHYZ1, RCU(G)60AHYZ1,RCU(G)75AHYZ1


Air Discharge
Air Side Heat-Exchanger

Air Inlet Air Inlet

Rigging holes(4-φ50)

Mounting Holes(4-φ26)
Earth Connection Terminal Screw Type Compressor

NOTES:
Fan 1.Surpport the water pipes with stay not to give the weight of water pipes directly to the unit.
Wiring Hole
for Power Supply 2.Water connection flanges( 90mm inner diameter )are supplied by factory with the unit.

RCU(G)100AHYZ1, RCU(G)120AHYZ1 and RCU(G)150AHYZ1

Air Discharge
Air Side Heat-Exchanger

Air Inlet Air Inlet

Rigging Holes(4-φ50)

Screw Type Compressor Mounting Holes(6- φ26)


Earth Connection Terminal

Wiring Hole Fan NOTES:


for Power Supply

1.Surpport the water pipes with stay not to give the weight of water pipes directly to the unit .

2.Water connection flanges( 142mm inner diameter)are supplied by factory with the unit.

5
DIMENSION DATA

Unit Dimensions

RCU(G)180AHYZ1and RCU(G)200AHYZ1

Air Discharge
Air Side Heat-Exchanger

Air Inlet Air Inlet

Rigging Holes
(4-φ50)
Mounting Holes
Earth Connection Terminal Screw Type Compressor (8-φ26)

Fan
NOTES:
Wiring Hole 1.Surpport the water pipes with stay not to give the
for Power Supply
give the weight of water pipes directly to the unit.
2.Water connection flanges( 142mm inner diameter )
are supplied by factory with the unit.

RCU(G)240AHYZ1,RCU(G)270AHYZ1 and RCU(G)300AHYZ1

Air Discharge
Air Side Heat-Exchanger
Minimum) Air Side Heat-Exchanger

Air Inlet Air Inlet

Rigging Holes(8-φ50)

Screw Type Compressor Screw Type Compressor Screw Type Compressor Screw Type Compressor Mounting Holes(12-φ26)
Earth Connection Terminal Earth Connection Terminal

No.1 Water Outlet No.1 Water Inlet No.2 Water Outlet


No.2 Water Inlet
NOTES:
1.This chiller consists of unit No.1 and No.2 and should be
Fan
separately shipped.
2.Support the water pipes with stay not to give
Wiring Hole for the weight of water pipes directly to the unit.
Power Supply 3.Provide a field-supplied common water piping
at the water coolers to connect unit No.1 and No.2.
Furthermore,for RCU240,300AHYZ1:as the No.1 unit and No.2 unit
have a same water flow rate, it just needs to control the common water volume
to the chiller; for RCU270AHYZ1:because the chilled water flow rate
Wiring Hole for between No.1and No.2 unit is different, It is necessary to
Power Supply control the water volume of each unit with adjusting valves.
4.It needs to field-connect the control wiring between the
No.1 unit and No. 2 unit.

6
DIMENSION DATA

Unit Dimensions

RCU(G)330AHYZ1 and RCU(G)350AHYZ1

(Minimum) Air Discharge


Air Side Heat-Exchanger Air Side Heat-Exchanger

Air Inlet Air Inlet

Rigging Holes
(8-φ50)
P
Mounting Holes
Earth Connection Terminal Screw Type Compressor Earth Connection Terminal Screw Type Compressor Screw Type Compressor (14-φ26)

No.1Water Outlet No.1WaterInlet No.2Water Outlet No.2WaterInlet


NOTES:
1.This chiller consists of unit No.1 and No.2 and should be
separately shipped.
Fan 2.Support the water pipes with stay not to give
Wiring Hole for the weight of water pipes directly to the unit.
Power Supply 3.Provide a field-supplied common water piping
at the water coolers to connect unit No.1 and No.2.
Furthermore,for RCU330,350AHYZ1,because the chilled water
flow rate between No.1and No.2 unit is different, it needs to
control the water volume of each unit with adjusting valves.
Wiring Hole for 4.It needs to field-connect the control wiring between the
Power Supply No.1 unit and No. 2 unit.
5.The dimension of No.2 unit marked with P is 300mm.

RCU(G)360AHYZ1, RCU(G)380AHYZ1 and RCU(G)400AHYZ1

(Minimum)
Air Discharge
Air Side Heat-Exchanger Air Side Heat-Exchanger

Air Inlet Air Inlet

起吊孔(8-φ50)

安装孔(16-φ26)
Earth Connection Terminal Screw Type Compressor Earth Connection Terminal Screw Type Compressor

No.1 Water Outlet No.1 Water Inlet No.2 Water Outlet No.2 Water Inlet NOTES:
1.This chiller consists of unit No.1 and No.2 and should be
separately shipped.
Fan 2.Support the water pipes with stay not to give
the weight of water pipes directly to the unit.
3.Provide a field-supplied common water piping
Wiring Hole for at the water coolers to connect unit No.1 and No.2.
Power Supply Furthermore,for RCU360,400AHYZ1:as the No.1 unit and No.2 unit
have a same water flow rate, it just needs to control the common water volume
to the chiller; for RCU380AHYZ1:because the chilled water flow rate
between No.1and No.2 unit is different, It is necessary to
Wiring Hole for control the water volume of each unit with adjusting valves.
Power Supply 4.It needs to field-connect the control wiring between the
No.1 unit and No. 2 unit.

7
PREPARATION

Operation Space

h1≤h2

h1≤h2

For Models: RCU(G)40AHYZ1, RCU(G)50AHYZ1, For Models: RCU(G)240AHYZ1,RCU(G)270AHYZ1,


RCU(G)60AHYZ1,RCU(G)75AHYZ1, RCU(G)300AHYZ1, RCU(G)330AHYZ1,
RCU(G)100AHYZ1,RCU(G)120AHYZ1, RCU(G)350AHYZ1, RCU(G)360AHYZ1,
RCU(G)380AHYZ1,RCU(G)400AHYZ1
RCU(G)150AHYZ1,RCU(G)180AHYZ1,
RCU(G)200AHYZ1.
Maximum Foundation Gradient

Refer to C,D
Refer to C,D
E F
30mmm

Refer to C,D
15mm
G

Model Maintain Space (mm) Air Inlet Space (mm)


A B C D E F G
RCU(G)40AHYZ1 2,390 1,200 100 900 1,200 2,000 1,200
RCU(G)50AHYZ1 2,390 1,200 100 900 1,200 2,000 1,200
RCU(G)60AHYZ1 2,390 1,200 100 900 1,200 2,000 1,200
RCU(G)75AHYZ1 2,390 1,200 100 900 1,200 2,000 1,200
RCU(G)100AHYZ1 4,490 1,200 100 900 1,200 2,000 1,200
RCU(G)120AHYZ1 4,490 1,200 100 900 1,200 2,000 1,200
RCU(G)150AHYZ1 4,490 1,200 100 900 1,200 2,000 1,200
RCU(G)180AHYZ1 6,590 1,200 100 900 1,200 2,000 1,200
RCU(G)200AHYZ1 6,590 1,200 100 900 1,200 2,000 1,200
RCU(G)240AHYZ1 9,080(Minimum) 1,200 900 900 1,200 2,000 1,200
RCU(G)270AHYZ1 9,080(Minimum) 1,200 900 900 1,200 2,000 1,200
RCU(G)300AHYZ1 9,080(Minimum) 1,200 900 900 1,200 2,000 1,200
RCU(G)330AHYZ1 11,800(Minimum) 1,200 900 900 1,200 2,000 1,200
RCU(G)350AHYZ1 11,800 (Minimum) 1,200 900 900 1,200 2,000 1,200
RCU(G)360AHYZ1 13,280(Minimum) 1,200 900 900 1,200 2,000 1,200
RCU(G)380AHYZ1 13,280 (Minimum) 1,200 900 900 1,200 2,000 1,200
RCU(G)400AHYZ1 13,280 (Minimum) 1,200 900 900 1,200 2,000 1,200

8
PREPARATION

Center of Gravity

Center of Center of
Gravity Operation Gravity Operation
Model Model
Weight(kg) Weight(kg)
X Y X Y
RCU(G)40AHYZ1 1050 970 1870 RCU(G)270AHYZ1-2 2240 870 3420
RCU(G)50AHYZ1 1050 970 1900 RCU(G)300AHYZ1-1 2050 870 3460
RCU(G)60AHYZ1 1050 970 1940 RCU(G)300AHYZ1-2 2240 870 3460
RCU(G)75AHYZ1 1050 970 1960 RCU(G)330AHYZ1-1 3240 857 5075
RCU(G)100AHYZ1 2050 870 3350 RCU(G)330AHYZ1-2 2240 870 3460
RCU(G)120AHYZ1 2050 870 3420 RCU(G)350AHYZ1-1 3240 857 5110
RCU(G)150AHYZ1 2050 870 3460 RCU(G)350AHYZ1-2 2240 870 3460
RCU(G)180AHYZ1 3240 857 5075 RCU(G)360AHYZ1-1 3240 857 5075
RCU(G)200AHYZ1 3240 857 5110 RCU(G)360AHYZ1-2 3440 857 5075
RCU(G)240AHYZ1-1 2050 870 3420 RCU(G)380AHYZ1-1 3240 857 5110
RCU(G)240AHYZ1-2 2240 870 3420 RCU(G)380AHYZ1-2 3440 857 5075
RCU(G)400AHYZ1-1 3240 857 5110
RCU(G)270AHYZ1-1 2050 870 3460
RCU(G)400AHYZ1-2 3440 857 5110

Weight Balance
Weight Destribution (kg)
Model
1 2 3 4
RCU(G)40AHYZ1 380 360 615 515
RCU(G)50AHYZ1 385 365 625 525
RCU(G)60AHYZ1 395 375 635 535
RCU(G)75AHYZ1 400 380 640 540

Weight Destribution (kg)


Model
1 2 3 4 5 6
RCU(G)100AHYZ1 550 502 485 610 600 603
RCU(G)120AHYZ1 560 520 495 620 610 615
RCU(G)150AHYZ1 570 535 510 620 610 615
RCU(G)240AHYZ1-1 560 520 495 620 610 615
RCU(G)240AHYZ1-2 495 520 560 615 610 620
RCU(G)270AHYZ1-1 570 535 510 620 610 615
RCU(G)270AHYZ1-2 495 520 560 615 610 620
RCU(G)300AHYZ1-1 570 535 510 620 610 615
RCU(G)300AHYZ1-2 510 535 570 615 610 620

Weight Destribution (kg)


Model
1 2 3 4 5 6 7 8
RCU(G)180AHYZ1 538 556 557 553 708 720 728 715
RCU(G)200AHYZ1 538 564 565 553 708 730 737 715
RCU(G)330AHYZ1-1 538 556 557 553 708 720 728 715
RCU(G)330AHYZ1-2 510 535 570 615 610 620
RCU(G)350AHYZ1-1 538 564 565 553 708 730 737 715
RCU(G)350AHYZ1-2 510 535 570 615 610 620
RCU(G)360AHYZ1-1 538 556 557 553 708 720 728 715
RCU(G)360AHYZ1-2 553 556 557 538 715 720 728 708
RCU(G)380AHYZ1-1 538 564 565 553 708 730 737 715
RCU(G)380AHYZ1-2 553 556 557 538 715 720 728 708
RCU(G)400AHYZ1-1 538 564 565 553 708 730 737 715
RCU(G)400AHYZ1-2 553 564 565 538 715 730 737 708

9
SELECTION DATA

Selection Example Cooling Capacity and Compressor Input


Determination the System Requirements: When the fouling factor is different from
Condenser Air Inlet Temperature: 40℃ 2
0.018m .℃/kW, the cooling capacity or the
Chilled Water Outlet Temperature 7℃
compressor input will be corrected utilizing follow
Chilled Water Inlet Temperature 12℃
formulas:
Cooling Load 453kW
Power Source Frequency: 50Hz
Corrected Correction Cooling Capacity
= ×
From the cooling capacity table, model Cooling Capacity Factor Indicated in Table
RCU180AHYZ1 can be selected with the following
performance: and
Cooling Capacity: 507.5kW
Chilled Water Flow Rate: 87.3m3/h
Water Cooler Pressure Drop: 69.7kPa Corrected Correction Compressor Input
Compressor Input Power: 173.2kW
Compressor = Factor ×
indicated in Table
The water flow rate in the cooling capacity table is Input
based on the 5 ℃ temperature difference between
Correction Factor for Cooling Capacity and
the chilled water inlet and outlet temperature, if the
Compressor Input Regarding Fouling Factor
temperature difference is not 5 ℃ , correct the
water flow rater of the water cooler utilizing follow
Fouling Cooling Compressor
formulas.
Factor Capacity Input
Flow Rate
2
m . ℃/kW
Corrected Flow = 5℃ × From the Table (CFR)
Water 0.000 1.01 1.00
Rate
Given Temperature
Cooler 0.018 1.00 1.00
Difference (℃)

The corrected chilled water flow rate must be


confirmed to be within the working range described
on pages 20

1、RCU(G)40AHYZ1
2、RCU(G)50AHYZ1
3、RCU(G)60AHYZ1
RCU(G)75AHYZ1
Water Cooler Pressure Drop(kPa)

4、RCU(G)100AHYZ1
5、RCU(G)120AHYZ1
RCU(G)150AHYZ1
RCU(G)240AHYZ1-1
RCU(G)240AHYZ1-2
RCU(G)270AHYZ1-1
RCU(G)270AHYZ1-2
RCU(G)300AHYZ1-1
RCU(G)300AHYZ1-2
RCU(G)330AHYZ1-2
RCU(G)350AHYZ1-2
6、RCU(G)180AHYZ1
RCU(G)200AHYZ1
RCU(G)330AHYZ1-1
RCU(G)350AHYZ1-1
RCU(G)360AHYZ1-1
RCU(G)360AHYZ1-2
RCU(G)380AHYZ1-1
RCU(G)380AHYZ1-2
RCU(G)400AHYZ1-1
RCU(G)400AHYZ1-2
3
Chilled Water Flow Rate of Each Water Cooler(m /h)
(Total Flow Rate /Number of Cooler)

NOTE: The flow rate of each model is not different; please refer to the chilled water flow rate on the pages 11 to 16.
10
SELECTION DATA
Cooling Capacities(R22)
Conversion Multiplier:1kW=860kcal/h
=3412Btu/h
-50Hz- 1kPa=0.102mAq

RCU40AHYZ1 RCU50AHYZ1 RCU60AHYZ1 RCU75AHYZ1 RCU100AHYZ1


ABT CLOT
CCAP CFR CPD IPT CCAP CFR CPD IPT CCAP CFR CPD IPT CCAP CFR CPD IPT CCAP CFR CPD IPT
5 120.5 20.7 38.2 27.2 148.7 25.6 41.3 33.1 186.1 32.0 44.8 41.3 198.5 34.1 50.8 44.0 297.3 51.1 55.7 66.3
6 124.6 21.4 40.7 27.5 153.7 26.4 43.9 33.4 192.4 33.1 47.8 41.7 205.3 35.3 54.1 44.4 307.3 52.9 59.3 66.9
7 128.7 22.1 43.2 27.7 158.7 27.3 46.6 33.7 198.7 34.2 50.9 42.0 212.0 36.5 57.6 44.8 317.5 54.6 62.9 67.4
25
8 132.7 22.8 45.7 27.9 163.7 28.2 49.3 34.0 204.9 35.2 54.0 42.4 218.7 37.6 61.1 45.1 327.5 56.3 66.6 68.0
9 136.7 23.5 48.3 28.2 168.7 29.0 52.1 34.4 211.1 36.3 57.1 42.8 225.3 38.7 64.7 45.5 337.4 58.0 70.4 68.7
10 140.7 24.2 50.9 28.4 173.5 29.8 54.9 34.6 217.2 37.3 60.3 43.2 231.8 39.9 68.3 46.0 347.1 59.7 74.1 69.3
5 114.4 19.7 34.7 30.6 141.1 24.3 37.5 37.3 176.7 30.4 40.6 46.5 188.5 32.4 46.0 49.4 282.2 48.5 50.6 74.7
6 118.4 20.4 37.0 30.9 146.0 25.1 39.9 37.7 182.7 31.4 43.3 46.9 195.0 33.5 49.1 49.9 292.0 50.2 53.9 75.3
7 122.3 21.0 39.3 31.1 150.9 25.9 42.4 38.0 188.9 32.5 46.1 47.3 201.5 34.7 52.2 50.3 301.7 51.9 57.3 76.0
30
8 126.2 21.7 41.7 31.4 155.7 26.8 44.9 38.4 194.9 33.5 49.0 47.7 208.0 35.8 55.5 50.8 311.4 53.6 60.7 76.7
9 130.1 22.4 44.0 31.7 160.5 27.6 47.5 38.7 200.9 34.5 51.9 48.1 214.3 36.9 58.8 51.1 320.9 55.2 64.2 77.4
10 133.9 23.0 46.4 31.9 165.2 28.4 50.1 39.0 206.7 35.5 54.9 48.5 220.6 37.9 62.1 51.6 330.3 56.8 67.7 78.1
5 108.3 18.6 31.4 34.0 133.6 23.0 33.9 41.6 167.2 28.8 36.5 51.6 178.4 30.7 41.4 54.8 267.2 46.0 45.8 83.1
6 112.1 19.3 33.5 34.3 138.3 23.8 36.1 42.0 173.1 29.8 39.0 52.1 184.7 31.8 44.2 55.3 276.6 47.6 48.8 83.9
7 115.9 19.9 35.6 34.6 143.0 24.6 38.4 42.3 179.0 30.8 41.6 52.5 191.0 32.8 47.1 55.8 286.0 49.2 51.9 84.6
35
8 119.7 20.6 37.8 34.9 147.7 25.4 40.8 42.6 184.9 31.8 44.3 52.9 197.2 33.9 50.1 56.3 295.4 50.8 55.1 85.3
9 123.5 21.2 40.0 35.1 152.3 26.2 43.1 43.0 190.6 32.8 47.0 53.4 203.4 35.0 53.2 56.8 304.6 52.4 58.3 86.1
10 127.1 21.9 42.2 35.4 156.8 27.0 45.5 43.4 196.3 33.8 49.7 53.8 209.4 36.0 56.2 57.1 313.6 53.9 61.5 86.7
5 102.2 17.6 28.2 37.4 126.0 21.7 30.4 45.8 157.8 27.1 32.7 56.8 168.4 29.0 37.0 60.4 252.1 43.4 41.1 91.6
6 105.9 18.2 30.1 37.7 130.6 22.5 32.5 46.2 163.5 28.1 35.0 57.2 174.4 30.0 39.6 60.8 261.2 44.9 43.9 92.4
7 109.5 18.8 32.1 38.0 135.1 23.2 34.6 46.6 169.2 29.1 37.4 57.7 180.5 31.0 42.3 61.3 270.3 46.5 46.8 93.2
40
8 113.2 19.5 34.1 38.3 139.6 24.0 36.8 47.0 174.8 30.1 39.8 58.2 186.5 32.1 45.0 61.8 279.3 48.0 49.7 94.0
9 116.8 20.1 36.1 38.6 144.1 24.8 38.9 47.4 180.4 31.0 42.2 58.7 192.5 33.1 47.9 62.3 288.1 49.6 52.6 94.7
10 120.3 20.7 38.1 38.9 148.5 25.5 41.2 47.8 185.8 32.0 44.7 59.1 198.3 34.1 50.7 62.8 296.9 51.1 55.6 95.5

RCU120AHYZ1 RCU150AHYZ1 RCU180AHYZ1 RCU200AHYZ1


ABT CLOT
CCAP CFR CPD IPT CCAP CFR CPD IPT CCAP CFR CPD IPT CCAP CFR CPD IPT
5 372.1 64.0 66.2 82.6 397.0 68.3 75.6 88.0 558.2 96.0 83.6 123.9 595.5 102.4 94.7 132.0
6 384.8 66.2 70.9 83.4 410.6 70.6 81.0 88.7 577.2 99.3 89.2 125.1 615.9 105.9 101.1 133.1
7 397.4 68.3 75.7 84.1 424.0 72.9 86.5 89.5 596.1 102.5 94.9 126.1 636.0 109.4 107.5 134.3
25
8 409.9 70.5 80.7 84.9 437.4 75.2 92.2 90.3 614.8 105.7 100.7 127.3 656.1 112.8 114.1 135.4
9 422.2 72.6 85.8 85.6 450.6 77.5 98.1 91.0 633.3 108.9 106.6 128.4 675.9 116.2 120.8 136.5
10 434.4 74.7 90.9 86.4 463.6 79.7 104.0 92.0 651.6 112.0 112.6 129.6 695.4 119.6 127.6 138.0
5 353.3 60.8 59.5 93.0 377.0 64.8 68.0 98.8 530.0 91.1 75.7 139.5 565.5 97.2 85.8 148.3
6 365.5 62.9 63.8 93.8 390.0 67.1 72.9 99.8 548.2 94.3 80.8 140.6 585.0 100.6 91.5 149.7
7 377.7 65.0 68.2 94.5 403.0 69.3 77.9 100.6 566.6 97.4 86.1 141.8 604.5 104.0 97.5 150.8
30
8 389.8 67.0 72.8 95.4 416.0 71.5 83.2 101.5 584.7 100.5 91.4 143.1 624.0 107.3 103.6 152.3
9 401.7 69.1 77.4 96.2 428.6 73.7 88.5 102.3 602.6 103.6 96.9 144.3 642.9 110.6 109.8 153.4
10 413.4 71.1 82.2 97.0 441.2 75.9 93.9 103.2 620.2 106.6 102.4 145.4 661.8 113.8 116.0 154.8
5 334.5 57.5 53.1 103.3 356.8 61.4 60.7 109.7 501.7 86.3 68.1 154.9 535.2 92.0 77.1 164.5
6 346.2 59.5 57.0 104.1 369.4 63.5 65.2 110.6 519.3 89.3 72.8 156.2 554.1 95.3 82.5 166.0
7 358.0 61.6 61.1 105.0 382.0 65.7 69.8 111.6 537.0 92.3 77.6 157.5 573.0 98.5 88.0 167.4
35
8 369.7 63.6 65.3 105.9 394.4 67.8 74.6 112.6 554.6 95.4 82.6 158.8 591.6 101.7 93.5 168.8
9 381.2 65.6 69.5 106.7 406.8 70.0 79.5 113.5 571.8 98.3 87.6 160.1 610.2 104.9 99.3 170.3
10 392.6 67.5 73.9 107.6 418.8 72.0 84.4 114.3 588.9 101.3 92.7 161.4 628.2 108.0 105.0 171.4
5 315.6 54.3 47.1 113.6 336.8 57.9 53.9 120.7 473.4 81.4 60.9 170.4 505.2 86.9 69.0 181.1
6 327.0 56.2 50.7 114.5 348.8 60.0 57.9 121.7 490.5 84.3 65.2 171.7 523.2 90.0 73.9 182.5
7 338.4 58.2 54.4 115.5 361.0 62.1 62.2 122.6 507.5 87.3 69.7 173.2 541.5 93.1 78.9 184.0
40
8 349.6 60.1 58.2 116.3 373.0 64.1 66.5 123.6 524.5 90.2 74.2 174.5 559.5 96.2 84.0 185.4
9 360.7 62.0 62.1 117.3 385.0 66.2 71.0 124.6 541.1 93.0 78.8 176.0 577.5 99.3 89.3 186.8
10 371.7 63.9 66.0 118.3 396.6 68.2 75.4 125.5 557.5 95.9 83.4 177.4 594.9 102.3 94.5 188.3

ABT:Condensate Air Inlet Temperature(℃) CLOT:Chilled Water Outlet Temperature(℃)


CCAP:Cooling Capacity(kW) CFR:Chilled Water Flow Rate at 5℃ Difference Between Inlet and Outlet Temperature(m3/h)
CPD:Water Cooler Pressure Drop(kPa) IPT:Input Power for Compressor(kW)

11
SELECTION DATA
Cooling Capacities(R22)
Conversion Multiplier:1kW=860kcal/h
=3412Btu/h
-50Hz- 1kPa=0.102mAq
RCU240AHYZ1 RCU270AHYZ1
ABT CLOT
CCAP CFR1 CFR2 CPD1 CPD2 IPT CCAP CFR1 CFR2 CPD1 CPD2 IPT
5 744.2 64.0 64.0 66.2 66.2 165.2 769.1 68.3 64.0 75.6 66.2 170.6
6 769.6 66.2 66.2 70.9 70.9 166.8 795.4 70.6 66.2 81.0 70.9 172.1
7 794.8 68.3 68.3 75.7 75.7 168.2 821.4 72.9 68.3 86.5 75.7 173.6
25
8 819.7 70.5 70.5 80.7 80.7 169.7 847.3 75.2 70.5 92.2 80.7 175.1
9 844.4 72.6 72.6 85.8 85.8 171.3 872.8 77.5 72.6 98.1 85.8 176.7
10 868.7 74.7 74.7 90.9 90.9 172.8 898.0 79.7 74.7 104.0 90.9 178.4
5 706.7 60.8 60.8 59.5 59.5 186.0 730.3 64.8 60.8 68.0 59.5 191.8
6 731.0 62.9 62.9 63.8 63.8 187.5 755.5 67.1 62.9 72.9 63.8 193.6
7 755.5 65.0 65.0 68.2 68.2 189.1 780.7 69.3 65.0 77.9 68.2 195.1
30
8 779.6 67.0 67.0 72.8 72.8 190.8 805.8 71.5 67.0 83.2 72.8 196.9
9 803.4 69.1 69.1 77.4 77.4 192.4 830.3 73.7 69.1 88.5 77.4 198.5
10 826.9 71.1 71.1 82.2 82.2 193.9 854.6 75.9 71.1 93.9 82.2 200.2
5 668.9 57.5 57.5 53.1 53.1 206.5 691.3 61.4 57.5 60.7 53.1 213.0
6 692.4 59.5 59.5 57.0 57.0 208.3 715.6 63.5 59.5 65.2 57.0 214.8
7 716.0 61.6 61.6 61.1 61.1 210.0 740.0 65.7 61.6 69.8 61.1 216.6
35
8 739.4 63.6 63.6 65.3 65.3 211.7 764.1 67.8 63.6 74.6 65.3 218.4
9 762.4 65.6 65.6 69.5 69.5 213.5 788.0 70.0 65.6 79.5 69.5 220.2
10 785.2 67.5 67.5 73.9 73.9 215.2 811.4 72.0 67.5 84.4 73.9 221.9
5 631.2 54.3 54.3 47.1 47.1 227.2 652.4 57.9 54.3 53.9 47.1 234.4
6 653.9 56.2 56.2 50.7 50.7 229.0 675.8 60.0 56.2 57.9 50.7 236.2
7 676.7 58.2 58.2 54.4 54.4 230.9 699.4 62.1 58.2 62.2 54.4 238.1
40
8 699.3 60.1 60.1 58.2 58.2 232.7 722.6 64.1 60.1 66.5 58.2 239.9
9 721.4 62.0 62.0 62.1 62.1 234.6 745.7 66.2 62.0 71.0 62.1 241.9
10 743.3 63.9 63.9 66.0 66.0 236.5 768.3 68.2 63.9 75.4 66.0 243.8

RCU300AHYZ1 RCU330AHYZ1
ABT CLOT
CCAP CFR1 CFR2 CPD1 CPD2 IPT CCAP CFR1 CFR2 CPD1 CPD2 IPT
5 794.0 68.3 68.3 75.6 75.6 176.0 955.2 96.0 68.3 83.6 75.6 211.9
6 821.2 70.6 70.6 81.0 81.0 177.5 987.8 99.3 70.6 89.2 81.0 213.8
7 848.0 72.9 72.9 86.5 86.5 179.0 1020.1 102.5 72.9 94.9 86.5 215.6
25
8 874.8 75.2 75.2 92.2 92.2 180.5 1052.2 105.7 75.2 100.7 92.2 217.5
9 901.2 77.5 77.5 98.1 98.1 182.1 1083.9 108.9 77.5 106.6 98.1 219.5
10 927.2 79.7 79.7 104.0 104.0 184.0 1115.2 112.0 79.7 112.6 104.0 221.6
5 754.0 64.8 64.8 68.0 68.0 197.7 907.0 91.1 64.8 75.7 68.0 238.3
6 780.0 67.1 67.1 72.9 72.9 199.6 938.2 94.3 67.1 80.8 72.9 240.4
7 806.0 69.3 69.3 77.9 77.9 201.1 969.6 97.4 69.3 86.1 77.9 242.4
30
8 832.0 71.5 71.5 83.2 83.2 203.0 1000.7 100.5 71.5 91.4 83.2 244.6
9 857.2 73.7 73.7 88.5 88.5 204.5 1031.2 103.6 73.7 96.9 88.5 246.5
10 882.4 75.9 75.9 93.9 93.9 206.4 1061.4 106.6 75.9 102.4 93.9 248.7
5 713.6 61.4 61.4 60.7 60.7 219.4 858.5 86.3 61.4 68.1 60.7 264.6
6 738.8 63.5 63.5 65.2 65.2 221.3 888.7 89.3 63.5 72.8 65.2 266.8
7 764.0 65.7 65.7 69.8 69.8 223.2 919.0 92.3 65.7 77.6 69.8 269.1
35
8 788.8 67.8 67.8 74.6 74.6 225.1 949.0 95.4 67.8 82.6 74.6 271.4
9 813.6 70.0 70.0 79.5 79.5 227.0 978.6 98.3 70.0 87.6 79.5 273.6
10 837.6 72.0 72.0 84.4 84.4 228.5 1007.7 101.3 72.0 92.7 84.4 275.7
5 673.6 57.9 57.9 53.9 53.9 241.5 810.2 81.4 57.9 60.9 53.9 291.2
6 697.6 60.0 60.0 57.9 57.9 243.4 839.3 84.3 60.0 65.2 57.9 293.4
7 722.0 62.1 62.1 62.2 62.2 245.3 868.5 87.3 62.1 69.7 62.2 295.8
40
8 746.0 64.1 64.1 66.5 66.5 247.2 897.5 90.2 64.1 74.2 66.5 298.1
9 770.0 66.2 66.2 71.0 71.0 249.1 926.1 93.0 66.2 78.8 71.0 300.5
10 793.2 68.2 68.2 75.4 75.4 251.0 954.1 95.9 68.2 83.4 75.4 302.9

ABT:Condensate Air Inlet Temperature(℃) CLOT:Chilled Water Outlet Temperature(℃)


CCAP:Cooling Capacity(kW)
CFR1,CFR2:Chilled Water Flow Rate of No.1 Unit and No.2 Unit at 5℃ Difference Between Inlet and Outlet Temperature(m3/h).
CPD1,CPD2:Water Cooler Pressure Drop of No.1 Unit and No.2 Unit(kPa) IPT:Input Power for Compressor(kW)

12
SELECTION DATA
Cooling Capacities(R22)
Conversion Multiplier:1kW=860kcal/h
=3412Btu/h
-50Hz- 1kPa=0.102mAq
RCU350AHYZ1 RCU360AHYZ1
ABT CLOT
CCAP CFR1 CFR2 CPD1 CPD2 IPT CCAP CFR1 CFR2 CPD1 CPD2 IPT
5 992.5 102.4 68.3 94.7 75.6 220.0 1116.3 96.0 96.0 83.6 83.6 247.9
6 1026.5 105.9 70.6 101.1 81.0 221.9 1154.4 99.3 99.3 89.2 89.2 250.2
7 1060.0 109.4 72.9 107.5 86.5 223.8 1192.1 102.5 102.5 94.9 94.9 252.2
25
8 1093.5 112.8 75.2 114.1 92.2 225.7 1229.6 105.7 105.7 100.7 100.7 254.6
9 1126.5 116.2 77.5 120.8 98.1 227.6 1266.7 108.9 108.9 106.6 106.6 256.9
10 1159.0 119.6 79.7 127.6 104.0 230.0 1303.1 112.0 112.0 112.6 112.6 259.2
5 942.5 97.2 64.8 85.8 68.0 247.1 1060.0 91.1 91.1 75.7 75.7 279.0
6 975.0 100.6 67.1 91.5 72.9 249.5 1096.5 94.3 94.3 80.8 80.8 281.3
7 1007.5 104.0 69.3 97.5 77.9 251.4 1133.2 97.4 97.4 86.1 86.1 283.6
30
8 1040.0 107.3 71.5 103.6 83.2 253.8 1169.4 100.5 100.5 91.4 91.4 286.2
9 1071.5 110.6 73.7 109.8 88.5 255.7 1205.2 103.6 103.6 96.9 96.9 288.6
10 1103.0 113.8 75.9 116.0 93.9 258.1 1240.3 106.6 106.6 102.4 102.4 290.9
5 892.0 92.0 61.4 77.1 60.7 274.2 1003.4 86.3 86.3 68.1 68.1 309.8
6 923.5 95.3 63.5 82.5 65.2 276.6 1038.5 89.3 89.3 72.8 72.8 312.4
7 955.0 98.5 65.7 88.0 69.8 279.0 1074.0 92.3 92.3 77.6 77.6 315.0
35
8 986.0 101.7 67.8 93.5 74.6 281.4 1109.1 95.4 95.4 82.6 82.6 317.6
9 1017.0 104.9 70.0 99.3 79.5 283.8 1143.6 98.3 98.3 87.6 87.6 320.2
10 1047.0 108.0 72.0 105.0 84.4 285.7 1177.8 101.3 101.3 92.7 92.7 322.8
5 842.0 86.9 57.9 69.0 53.9 301.9 946.7 81.4 81.4 60.9 60.9 340.9
6 872.0 90.0 60.0 73.9 57.9 304.2 980.9 84.3 84.3 65.2 65.2 343.5
7 902.5 93.1 62.1 78.9 62.2 306.6 1015.1 87.3 87.3 69.7 69.7 346.4
40
8 932.5 96.2 64.1 84.0 66.5 309.0 1048.9 90.2 90.2 74.2 74.2 349.0
9 962.5 99.3 66.2 89.3 71.0 311.4 1082.1 93.0 93.0 78.8 78.8 351.9
10 991.5 102.3 68.2 94.5 75.4 313.8 1115.0 95.9 95.9 83.4 83.4 354.8

RCU380AHYZ1 RCU400AHYZ1
ABT CLOT
CCAP CFR1 CFR2 CPD1 CPD2 IPT CCAP CFR1 CFR2 CPD1 CPD2 IPT
5 1153.7 102.4 96.0 94.7 83.6 255.9 1191.0 102.4 102.4 94.7 94.7 264.0
6 1193.1 105.9 99.3 101.1 89.2 258.2 1231.8 105.9 105.9 101.1 101.1 266.2
7 1232.1 109.4 102.5 107.5 94.9 260.4 1272.0 109.4 109.4 107.5 107.5 268.5
25
8 1270.9 112.8 105.7 114.1 100.7 262.7 1312.2 112.8 112.8 114.1 114.1 270.8
9 1309.2 116.2 108.9 120.8 106.6 265.0 1351.8 116.2 116.2 120.8 120.8 273.1
10 1347.0 119.6 112.0 127.6 112.6 267.6 1390.8 119.6 119.6 127.6 127.6 276.0
5 1095.5 97.2 91.1 85.8 75.7 287.7 1131.0 97.2 97.2 85.8 85.8 296.5
6 1133.2 100.6 94.3 91.5 80.8 290.3 1170.0 100.6 100.6 91.5 91.5 299.4
7 1171.1 104.0 97.4 97.5 86.1 292.6 1209.0 104.0 104.0 97.5 97.5 301.7
30
8 1208.7 107.3 100.5 103.6 91.4 295.4 1248.0 107.3 107.3 103.6 103.6 304.5
9 1245.5 110.6 103.6 109.8 96.9 297.7 1285.8 110.6 110.6 109.8 109.8 306.8
10 1282.0 113.8 106.6 116.0 102.4 300.3 1323.6 113.8 113.8 116.0 116.0 309.7
5 1036.9 92.0 86.3 77.1 68.1 319.4 1070.4 92.0 92.0 77.1 77.1 329.1
6 1073.4 95.3 89.3 82.5 72.8 322.2 1108.2 95.3 95.3 82.5 82.5 331.9
7 1110.0 98.5 92.3 88.0 77.6 324.9 1146.0 98.5 98.5 88.0 88.0 334.8
35
8 1146.2 101.7 95.4 93.5 82.6 327.6 1183.2 101.7 101.7 93.5 93.5 337.7
9 1182.0 104.9 98.3 99.3 87.6 330.4 1220.4 104.9 104.9 99.3 99.3 340.5
10 1217.1 108.0 101.3 105.0 92.7 332.8 1256.4 108.0 108.0 105.0 105.0 342.8
5 978.6 86.9 81.4 69.0 60.9 351.5 1010.4 86.9 86.9 69.0 69.0 362.2
6 1013.7 90.0 84.3 73.9 65.2 354.3 1046.4 90.0 90.0 73.9 73.9 365.1
7 1049.0 93.1 87.3 78.9 69.7 357.2 1083.0 93.1 93.1 78.9 78.9 367.9
40
8 1084.0 96.2 90.2 84.0 74.2 359.9 1119.0 96.2 96.2 84.0 84.0 370.8
9 1118.6 99.3 93.0 89.3 78.8 362.8 1155.0 99.3 99.3 89.3 89.3 373.7
10 1152.4 102.3 95.9 94.5 83.4 365.7 1189.8 102.3 102.3 94.5 94.5 376.5

ABT:Condensate Air Inlet Temperature(℃) CLOT:Chilled Water Outlet Temperature(℃)


CCAP:Cooling Capacity(kW)
CFR1,CFR2:Chilled Water Flow Rate of No.1 Unit and No.2 Unit at 5℃ Difference Between Inlet and Outlet Temperature(m3/h).
CPD1,CPD2:Water Cooler Pressure Drop of No.1 Unit and No.2 Unit(kPa) IPT:Input Power for Compressor(kW)

13
SELECTION DATA

Cooling Capacities (R407C)


Conversion Multiplier:1kW=860kcal/h
=3412Btu/h
-50Hz- 1kPa=0.102mAq
RCUG40AHYZ1 RCUG50AHYZ1 RCUG60AHYZ1 RCUG75AHYZ1 RCUG100AHYZ1
ABT CLOT
CCAP CFR CPD IPT CCAP CFR CPD IPT CCAP CFR CPD IPT CCAP CFR CPD IPT CCAP CFR CPD IPT
5 114.5 19.7 34.8 29.1 141.2 24.3 37.5 35.5 176.7 30.4 40.6 44.2 188.6 32.4 46.0 47.1 282.5 48.6 50.7 70.9
6 118.3 20.4 37.0 29.4 146.0 25.1 39.9 35.8 182.7 31.4 43.3 44.6 195.0 33.5 49.1 47.5 292.0 50.2 53.9 71.5
7 122.2 21.0 39.3 29.6 150.8 25.9 42.4 36.1 188.7 32.5 46.1 45.0 201.4 34.6 52.2 47.9 301.6 51.9 57.2 72.2
25
8 126.1 21.7 41.6 29.9 155.5 26.7 44.9 36.4 194.6 33.5 48.9 45.4 207.8 35.7 55.4 48.3 311.1 53.5 60.6 72.8
9 129.9 22.3 43.9 30.2 160.3 27.6 47.4 36.8 200.5 34.5 51.7 45.8 214.0 36.8 58.6 48.7 320.5 55.1 64.0 73.5
10 133.6 23.0 46.3 30.4 164.9 28.4 49.9 37.1 206.3 35.5 54.6 46.2 220.2 37.9 61.9 49.2 329.7 56.7 67.4 74.1
5 108.7 18.7 31.6 32.8 134.1 23.1 34.1 39.9 167.8 28.9 36.8 49.7 179.1 30.8 41.7 52.9 268.1 46.1 46.1 79.9
6 112.4 19.3 33.6 33.0 138.7 23.9 36.3 40.3 173.6 29.8 39.2 50.2 185.3 31.9 44.5 53.4 277.4 47.7 49.1 80.6
7 116.2 20.0 35.7 33.3 143.3 24.6 38.6 40.7 179.4 30.8 41.8 50.6 191.4 32.9 47.4 53.8 286.6 49.3 52.1 81.3
30
8 119.9 20.6 37.9 33.6 147.9 25.4 40.9 41.0 185.1 31.8 44.4 51.0 197.6 34.0 50.3 54.3 295.9 50.9 55.2 82.1
9 123.6 21.3 40.1 33.9 152.4 26.2 43.2 41.4 190.8 32.8 47.0 51.5 203.6 35.0 53.3 54.7 304.9 52.4 58.4 82.8
10 127.2 21.9 42.2 34.2 156.9 27.0 45.6 41.8 196.3 33.8 49.7 51.9 209.6 36.0 56.3 55.2 313.8 54.0 61.6 83.5
5 102.9 17.7 28.6 36.4 126.9 21.8 30.8 44.5 158.8 27.3 33.1 55.2 169.5 29.1 37.5 58.7 253.8 43.7 41.7 89.0
6 106.5 18.3 30.4 36.7 131.4 22.6 32.8 44.9 164.4 28.3 35.4 55.7 175.5 30.2 40.1 59.2 262.8 45.2 44.4 89.8
7 110.1 18.9 32.4 37.0 135.9 23.4 34.9 45.3 170.0 29.2 37.7 56.2 181.5 31.2 42.7 59.7 271.7 46.7 47.2 90.5
35
8 113.7 19.6 34.4 37.3 140.3 24.1 37.1 45.6 175.6 30.2 40.1 56.6 187.3 32.2 45.4 60.2 280.6 48.3 50.1 91.3
9 117.3 20.2 36.4 37.6 144.7 24.9 39.2 46.0 181.0 31.1 42.5 57.1 193.2 33.2 48.2 60.7 289.4 49.8 53.0 92.1
10 120.7 20.8 38.4 37.9 148.9 25.6 41.4 46.4 186.4 32.1 45.0 57.6 198.9 34.2 51.0 61.1 297.9 51.2 55.9 92.8
5 97.1 16.7 25.6 40.0 119.7 20.6 27.7 49.0 149.9 25.8 29.6 60.8 160.0 27.5 33.6 64.6 239.5 41.2 37.4 98.0
6 100.6 17.3 27.4 40.3 124.1 21.3 29.5 49.4 155.3 26.7 31.7 61.3 165.7 28.5 35.9 65.1 248.1 42.7 39.9 98.9
7 104.1 17.9 29.2 40.7 128.4 22.1 31.5 49.8 160.7 27.6 33.9 61.8 171.5 29.5 38.3 65.6 256.8 44.2 42.5 99.7
40
8 107.5 18.5 31.0 41.0 132.6 22.8 33.4 50.3 166.0 28.6 36.1 62.2 177.2 30.5 40.8 66.1 265.3 45.6 45.2 100.5
9 110.9 19.1 32.8 41.3 136.9 23.5 35.4 50.7 171.3 29.5 38.3 62.8 182.9 31.4 43.4 66.6 273.7 47.1 47.9 101.4
10 114.3 19.7 34.7 41.7 141.0 24.3 37.4 51.1 176.5 30.4 40.5 63.3 188.4 32.4 45.9 67.1 282.1 48.5 50.6 102.2

RCUG120AHYZ1 RCUG150AHYZ1 RCUG180AHYZ1 RCUG200AHYZ1


ABT CLOT
CCAP CFR CPD IPT CCAP CFR CPD IPT CCAP CFR CPD IPT CCAP CFR CPD IPT
5 353.4 60.8 59.5 88.4 377.2 64.9 68.0 94.1 530.1 91.2 75.7 132.6 565.7 97.3 85.8 141.2
6 365.4 62.8 63.7 89.2 390.1 67.1 72.9 95.0 548.2 94.3 80.8 133.9 585.1 100.6 91.6 142.4
7 377.4 64.9 68.1 90.0 402.8 69.3 77.9 95.8 566.1 97.4 85.9 134.9 604.2 103.9 97.4 143.7
25
8 389.2 66.9 72.6 90.8 415.5 71.5 83.0 96.6 583.9 100.4 91.2 136.2 623.3 107.2 103.4 144.9
9 401.0 69.0 77.2 91.6 428.1 73.6 88.2 97.4 601.5 103.4 96.6 137.4 642.1 110.4 109.5 146.1
10 412.5 70.9 81.8 92.5 440.4 75.7 93.6 98.4 618.8 106.4 102.0 138.7 660.6 113.6 115.6 147.6
5 335.6 57.7 53.5 99.5 358.2 61.6 61.2 105.8 503.4 86.6 68.6 149.2 537.2 92.4 77.7 158.6
6 347.1 59.7 57.3 100.3 370.5 63.7 65.6 106.8 520.7 89.5 73.2 150.5 555.8 95.6 82.9 160.2
7 358.8 61.7 61.4 101.2 382.9 65.8 70.1 107.6 538.1 92.5 78.0 151.7 574.3 98.8 88.3 161.4
30
8 370.2 63.7 65.5 102.1 395.2 68.0 74.9 108.6 555.3 95.5 82.8 153.1 592.8 101.9 93.9 162.9
9 381.5 65.6 69.6 102.9 407.2 70.0 79.6 109.4 572.3 98.4 87.7 154.4 610.8 105.0 99.4 164.1
10 392.6 67.5 73.9 103.7 419.1 72.1 84.5 110.4 589.0 101.3 92.7 155.6 628.7 108.1 105.1 165.7
5 317.6 54.6 47.8 110.5 339.0 58.3 54.6 117.4 476.5 81.9 61.7 165.7 508.4 87.4 69.9 176.1
6 328.8 56.5 51.3 111.4 350.9 60.3 58.7 118.4 493.2 84.8 65.9 167.1 526.4 90.5 74.7 177.6
7 340.0 58.5 55.0 112.4 362.9 62.4 62.8 119.4 510.0 87.7 70.3 168.5 544.4 93.6 79.7 179.1
35
8 351.1 60.4 58.7 113.3 374.7 64.4 67.1 120.4 526.7 90.6 74.8 169.9 562.0 96.7 84.7 180.6
9 362.0 62.3 62.5 114.2 386.5 66.5 71.5 121.4 543.1 93.4 79.3 171.3 579.7 99.7 89.9 182.2
10 372.9 64.1 66.4 115.1 397.9 68.4 75.9 122.3 559.3 96.2 84.0 172.7 596.8 102.6 95.1 183.4
5 299.7 51.5 42.4 121.6 320.0 55.0 48.5 129.2 449.6 77.3 55.2 182.4 479.9 82.5 62.6 193.8
6 310.5 53.4 45.6 122.5 331.4 57.0 52.1 130.2 465.8 80.1 59.1 183.8 497.0 85.5 66.9 195.3
7 321.4 55.3 48.9 123.5 343.0 59.0 55.9 131.2 482.0 82.9 63.1 185.3 514.4 88.5 71.5 196.8
40
8 332.1 57.1 52.4 124.5 354.4 60.9 59.8 132.2 498.1 85.7 67.2 186.7 531.5 91.4 76.1 198.4
9 342.6 58.9 55.8 125.5 365.8 62.9 63.9 133.3 513.9 88.4 71.3 188.3 548.6 94.3 80.9 199.9
10 353.0 60.7 59.4 126.5 376.8 64.8 67.9 134.3 529.5 91.1 75.6 189.8 565.2 97.2 85.7 201.4

ABT:Condensate Air Inlet Temperature(℃) CLOT:Chilled Water Outlet Temperature(℃)


CCAP:Cooling Capacity(kW) CFR:Chilled Water Flow Rate at 5℃ Difference Between Inlet and Outlet Temperature(m3/h)
CPD:Water Cooler Pressure Drop(kPa) IPT:Input Power for Compressor(kW)

14
SELECTION DATA

Cooling Capacities (R407C)


Conversion Multiplier:1kW=860kcal/h
=3412Btu/h
-50Hz- 1kPa=0.102mAq
RCUG240AHYZ1 RCUG270AHYZ1
ABT CLOT
CCAP CFR1 CFR2 CPD1 CPD2 IPT CCAP CFR1 CFR2 CPD1 CPD2 IPT
5 706.8 60.8 60.8 59.5 59.5 176.8 730.5 64.9 60.8 68.0 59.5 182.6
6 730.9 62.8 62.8 63.7 63.7 178.5 755.5 67.1 62.8 72.9 63.7 184.2
7 754.8 64.9 64.9 68.1 68.1 179.9 780.2 69.3 64.9 77.9 68.1 185.7
25
8 778.5 66.9 66.9 72.6 72.6 181.6 804.8 71.5 66.9 83.0 72.6 187.4
9 802.0 69.0 69.0 77.2 77.2 183.2 829.1 73.6 69.0 88.2 77.2 189.0
10 825.1 70.9 70.9 81.8 81.8 184.9 853.0 75.7 70.9 93.6 81.8 190.9
5 671.1 57.7 57.7 53.5 53.5 199.0 693.7 61.6 57.7 61.2 53.5 205.3
6 694.2 59.7 59.7 57.3 57.3 200.7 717.6 63.7 59.7 65.6 57.3 207.1
7 717.5 61.7 61.7 61.4 61.4 202.3 741.6 65.8 61.7 70.1 61.4 208.7
30
8 740.4 63.7 63.7 65.5 65.5 204.2 765.4 68.0 63.7 74.9 65.5 210.7
9 763.0 65.6 65.6 69.6 69.6 205.8 788.7 70.0 65.6 79.6 69.6 212.3
10 785.3 67.5 67.5 73.9 73.9 207.5 811.8 72.1 67.5 84.5 73.9 214.2
5 635.3 54.6 54.6 47.8 47.8 221.0 656.6 58.3 54.6 54.6 47.8 227.9
6 657.5 56.5 56.5 51.3 51.3 222.8 679.7 60.3 56.5 58.7 51.3 229.8
7 680.0 58.5 58.5 55.0 55.0 224.7 702.9 62.4 58.5 62.8 55.0 231.8
35
8 702.3 60.4 60.4 58.7 58.7 226.6 725.8 64.4 60.4 67.1 58.7 233.7
9 724.1 62.3 62.3 62.5 62.5 228.4 748.5 66.5 62.3 71.5 62.5 235.7
10 745.7 64.1 64.1 66.4 66.4 230.3 770.7 68.4 64.1 75.9 66.4 237.4
5 599.4 51.5 51.5 42.4 42.4 243.1 619.7 55.0 51.5 48.5 42.4 250.8
6 621.1 53.4 53.4 45.6 45.6 245.0 641.9 57.0 53.4 52.1 45.6 252.7
7 642.7 55.3 55.3 48.9 48.9 247.1 664.3 59.0 55.3 55.9 48.9 254.8
40
8 664.1 57.1 57.1 52.4 52.4 249.0 686.4 60.9 57.1 59.8 52.4 256.7
9 685.2 58.9 58.9 55.8 55.8 251.0 708.3 62.9 58.9 63.9 55.8 258.8
10 706.0 60.7 60.7 59.4 59.4 253.1 729.8 64.8 60.7 67.9 59.4 260.8

RCUG300AHYZ1 RCUG330AHYZ1
ABT CLOT
CCAP CFR1 CFR2 CPD1 CPD2 IPT CCAP CFR1 CFR2 CPD1 CPD2 IPT
5 754.3 64.9 64.9 68.0 68.0 188.3 907.2 91.2 64.9 75.7 68.0 226.8
6 780.1 67.1 67.1 72.9 72.9 189.9 938.2 94.3 67.1 80.8 72.9 228.8
7 805.6 69.3 69.3 77.9 77.9 191.5 968.9 97.4 69.3 85.9 77.9 230.7
25
8 831.1 71.5 71.5 83.0 83.0 193.2 999.4 100.4 71.5 91.2 83.0 232.8
9 856.1 73.6 73.6 88.2 88.2 194.8 1029.6 103.4 73.6 96.6 88.2 234.8
10 880.8 75.7 75.7 93.6 93.6 196.8 1059.2 106.4 75.7 102.0 93.6 237.1
5 716.3 61.6 61.6 61.2 61.2 211.5 861.5 86.6 61.6 68.6 61.2 255.0
6 741.0 63.7 63.7 65.6 65.6 213.6 891.2 89.5 63.7 73.2 65.6 257.3
7 765.7 65.8 65.8 70.1 70.1 215.2 921.0 92.5 65.8 78.0 70.1 259.3
30
8 790.4 68.0 68.0 74.9 74.9 217.2 950.5 95.5 68.0 82.8 74.9 261.7
9 814.3 70.0 70.0 79.6 79.6 218.9 979.5 98.4 70.0 87.7 79.6 263.8
10 838.3 72.1 72.1 84.5 84.5 220.9 1008.1 101.3 72.1 92.7 84.5 266.1
5 677.9 58.3 58.3 54.6 54.6 234.7 815.4 81.9 58.3 61.7 54.6 283.1
6 701.9 60.3 60.3 58.7 58.7 236.8 844.1 84.8 60.3 65.9 58.7 285.5
7 725.8 62.4 62.4 62.8 62.8 238.8 872.9 87.7 62.4 70.3 62.8 287.9
35
8 749.4 64.4 64.4 67.1 67.1 240.9 901.4 90.6 64.4 74.8 67.1 290.4
9 772.9 66.5 66.5 71.5 71.5 242.9 929.5 93.4 66.5 79.3 71.5 292.8
10 795.7 68.4 68.4 75.9 75.9 244.5 957.2 96.2 68.4 84.0 75.9 295.0
5 639.9 55.0 55.0 48.5 48.5 258.4 769.5 77.3 55.0 55.2 48.5 311.6
6 662.7 57.0 57.0 52.1 52.1 260.4 797.2 80.1 57.0 59.1 52.1 314.0
7 685.9 59.0 59.0 55.9 55.9 262.5 825.0 82.9 59.0 63.1 55.9 316.5
40
8 708.7 60.9 60.9 59.8 59.8 264.5 852.5 85.7 60.9 67.2 59.8 319.0
9 731.5 62.9 62.9 63.9 63.9 266.5 879.6 88.4 62.9 71.3 63.9 321.5
10 753.5 64.8 64.8 67.9 67.9 268.6 906.2 91.1 64.8 75.6 67.9 324.1

ABT:Condensate Air Inlet Temperature(℃) CLOT:Chilled Water Outlet Temperature(℃)


CCAP:Cooling Capacity(kW)
CFR1,CFR2:Chilled Water Flow Rate of No.1 Unit and No.2 Unit at 5℃ Difference Between Inlet and Outlet Temperature(m3/h).
CPD1,CPD2:Water Cooler Pressure Drop of No.1 Unit and No.2 Unit(kPa) IPT:Input Power for Compressor(kW)

15
SELECTION DATA
Cooling Capacities (R407C)
Conversion Multiplier:1kW=860kcal/h
=3412Btu/h
-50Hz- 1kPa=0.102mAq

RCUG350AHYZ1 RCUG360AHYZ1
ABT CLOT
CCAP CFR1 CFR2 CPD1 CPD2 IPT CCAP CFR1 CFR2 CPD1 CPD2 IPT
5 942.9 97.3 64.9 85.8 68.0 235.4 1060.2 91.2 91.2 75.7 75.7 265.2
6 975.2 100.6 67.1 91.6 72.9 237.4 1096.3 94.3 94.3 80.8 80.8 267.7
7 1007.0 103.9 69.3 97.4 77.9 239.4 1132.2 97.4 97.4 85.9 85.9 269.9
25
8 1038.8 107.2 71.5 103.4 83.0 241.5 1167.7 100.4 100.4 91.2 91.2 272.4
9 1070.2 110.4 73.6 109.5 88.2 243.5 1203.0 103.4 103.4 96.6 96.6 274.9
10 1101.1 113.6 75.7 115.6 93.6 246.1 1237.6 106.4 106.4 102.0 102.0 277.4
5 895.4 92.4 61.6 77.7 61.2 264.4 1006.7 86.6 86.6 68.6 68.6 298.5
6 926.3 95.6 63.7 82.9 65.6 266.9 1041.3 89.5 89.5 73.2 73.2 301.0
7 957.1 98.8 65.8 88.3 70.1 269.0 1076.3 92.5 92.5 78.0 78.0 303.5
30
8 988.0 101.9 68.0 93.9 74.9 271.5 1110.6 95.5 95.5 82.8 82.8 306.3
9 1017.9 105.0 70.0 99.4 79.6 273.6 1144.6 98.4 98.4 87.7 87.7 308.8
10 1047.9 108.1 72.1 105.1 84.5 276.1 1177.9 101.3 101.3 92.7 92.7 311.2
5 847.4 87.4 58.3 69.9 54.6 293.4 952.9 81.9 81.9 61.7 61.7 331.5
6 877.3 90.5 60.3 74.7 58.7 296.0 986.3 84.8 84.8 65.9 65.9 334.3
7 907.3 93.6 62.4 79.7 62.8 298.5 1020.0 87.7 87.7 70.3 70.3 337.1
35
8 936.7 96.7 64.4 84.7 67.1 301.1 1053.4 90.6 90.6 74.8 74.8 339.8
9 966.2 99.7 66.5 89.9 71.5 303.6 1086.1 93.4 93.4 79.3 79.3 342.6
10 994.7 102.6 68.4 95.1 75.9 305.7 1118.6 96.2 96.2 84.0 84.0 345.4
5 799.9 82.5 55.0 62.6 48.5 323.0 899.1 77.3 77.3 55.2 55.2 364.7
6 828.4 85.5 57.0 66.9 52.1 325.5 931.6 80.1 80.1 59.1 59.1 367.5
7 857.4 88.5 59.0 71.5 55.9 328.1 964.1 82.9 82.9 63.1 63.1 370.6
40
8 885.9 91.4 60.9 76.1 59.8 330.6 996.2 85.7 85.7 67.2 67.2 373.4
9 914.4 94.3 62.9 80.9 63.9 333.2 1027.7 88.4 88.4 71.3 71.3 376.5
10 941.9 97.2 64.8 85.7 67.9 335.7 1058.9 91.1 91.1 75.6 75.6 379.6

RCUG380AHYZ1 RCUG400AHYZ1
ABT CLOT
CCAP CFR1 CFR2 CPD1 CPD2 IPT CCAP CFR1 CFR2 CPD1 CPD2 IPT
5 1095.8 97.3 91.2 85.8 75.7 273.8 1131.5 97.3 97.3 85.8 85.8 282.4
6 1133.3 100.6 94.3 91.6 80.8 276.3 1170.2 100.6 100.6 91.6 91.6 284.9
7 1170.3 103.9 97.4 97.4 85.9 278.6 1208.4 103.9 103.9 97.4 97.4 287.3
25
8 1207.2 107.2 100.4 103.4 91.2 281.1 1246.6 107.2 107.2 103.4 103.4 289.8
9 1243.6 110.4 103.4 109.5 96.6 283.5 1284.2 110.4 110.4 109.5 109.5 292.2
10 1279.4 113.6 106.4 115.6 102.0 286.3 1321.3 113.6 113.6 115.6 115.6 295.3
5 1040.6 92.4 86.6 77.7 68.6 307.9 1074.5 92.4 92.4 77.7 77.7 317.3
6 1076.4 95.6 89.5 82.9 73.2 310.7 1111.5 95.6 95.6 82.9 82.9 320.3
7 1112.4 98.8 92.5 88.3 78.0 313.1 1148.6 98.8 98.8 88.3 88.3 322.8
30
8 1148.1 101.9 95.5 93.9 82.8 316.1 1185.6 101.9 101.9 93.9 93.9 325.8
9 1183.0 105.0 98.4 99.4 87.7 318.5 1221.5 105.0 105.0 99.4 99.4 328.3
10 1217.7 108.1 101.3 105.1 92.7 321.3 1257.4 108.1 108.1 105.1 105.1 331.3
5 984.9 87.4 81.9 69.9 61.7 341.8 1016.9 87.4 87.4 69.9 69.9 352.1
6 1019.5 90.5 84.8 74.7 65.9 344.7 1052.8 90.5 90.5 74.7 74.7 355.2
7 1054.4 93.6 87.7 79.7 70.3 347.6 1088.7 93.6 93.6 79.7 79.7 358.2
35
8 1088.7 96.7 90.6 84.7 74.8 350.6 1124.0 96.7 96.7 84.7 84.7 361.3
9 1122.8 99.7 93.4 89.9 79.3 353.5 1159.4 99.7 99.7 89.9 89.9 364.3
10 1156.1 102.6 96.2 95.1 84.0 356.1 1193.6 102.6 102.6 95.1 95.1 366.8
5 929.5 82.5 77.3 62.6 55.2 376.2 959.9 82.5 82.5 62.6 62.6 387.6
6 962.8 85.5 80.1 66.9 59.1 379.1 994.1 85.5 85.5 66.9 66.9 390.6
7 996.5 88.5 82.9 71.5 63.1 382.2 1028.9 88.5 88.5 71.5 71.5 393.7
40
8 1029.6 91.4 85.7 76.1 67.2 385.1 1063.1 91.4 91.4 76.1 76.1 396.7
9 1062.5 94.3 88.4 80.9 71.3 388.2 1097.3 94.3 94.3 80.9 80.9 399.8
10 1094.6 97.2 91.1 85.7 75.6 391.3 1130.3 97.2 97.2 85.7 85.7 402.9

ABT:Condensate Air Inlet Temperature(℃) CLOT:Chilled Water Outlet Temperature(℃)


CCAP:Cooling Capacity(kW)
CFR1,CFR2:Chilled Water Flow Rate of No.1 Unit and No.2 Unit at 5℃ Difference Between Inlet and Outlet Temperature(m3/h).
CPD1,CPD2:Water Cooler Pressure Drop of No.1 Unit and No.2 Unit(kPa) IPT:Input Power for Compressor(kW)

16
SELECTION DATA
Electric Data (Voltage:380V)
Application Compressor(Three Phases) Motor for Condenser
Unit Main Power Maximum Unit
Model Voltage(V) Fan
STC(A) RNC(A) IPT (kW) Current(A)
Voltage Hz Max. Min. RNC(A) IPT (kW)
RCU40AHYZ1 114 58 34.6 4×2.7 4×1.1 96
RCU50AHYZ1 148 75 42.3 4×2.7 4×1.1 129
RCU60AHYZ1 178 95 52.5 4×2.7 4×1.1 162
RCU75AHYZ1 178 100 55.8 4×2.7 4×1.1 173
RCU100AHYZ1 148 2×75 2×42.3 8×2.7 8×1.1 258
RCU120AHYZ1 178 2×95 2×52.5 8×2.7 8×1.1 324
RCU150AHYZ1 178 2×100 2×55.8 8×2.7 8×1.1 346
RCU180AHYZ1 178 3×95 3×52.5 12×2.7 12×1.1 486
RCU200AHYZ1 178 3×100 3×55.8 12×2.7 12×1.1 519
RCU240AHYZ1 178 4×95 4×52.5 16×2.7 16×1.1 648
RCU270AHYZ1 178 2×100+2×95 2×55.8+2×52.5 16×2.7 16×1.1 670
RCU300AHYZ1 178 4×100 4×55.8 16×2.7 16×1.1 692
RCU330AHYZ1 178 3×95+2×100 3×52.5+2×55.8 20×2.7 20×1.1 832
RCU350AHYZ1 178 5×100 5×55.8 20×2.7 20×1.1 865
RCU360AHYZ1 178 6×95 6×52.5 24×2.7 24×1.1 972
RCU380AHYZ1 178 3×100+3×95 3×55.8+3×52.5 24×2.7 24×1.1 1005
RCU400AHYZ1 178 6×100 6×55.8 24×2.7 24×1.1 1038
380 50 418 342
RCUG40AHYZ1 114 64 36.6 4×2.7 4×1.1 114
RCUG50AHYZ1 148 81 45.3 4×2.7 4×1.1 138
RCUG60AHYZ1 178 102 56.2 4×2.7 4×1.1 171
RCUG75AHYZ1 178 107 59.7 4×2.7 4×1.1 181
RCUG100AHYZ1 148 2×81 2×45.3 8×2.7 8×1.1 276
RCUG120AHYZ1 178 2×102 2×56.2 8×2.7 8×1.1 342
RCUG150AHYZ1 178 2×107 2×59.7 8×2.7 8×1.1 362
RCUG180AHYZ1 178 3×102 3×56.2 12×2.7 12×1.1 513
RCUG200AHYZ1 178 3×107 3×59.7 12×2.7 12×1.1 543
RCUG240AHYZ1 178 4×102 4×56.2 16×2.7 16×1.1 684
RCUG270AHYZ1 178 2×107+2×102 2×59.7+2×56.2 16×2.7 16×1.1 704
RCUG300AHYZ1 178 4×107 4×59.7 16×2.7 16×1.1 724
RCUG330AHYZ1 178 3×102+2×107 3×56.2+2×59.7 20×2.7 20×1.1 875
RCUG350AHYZ1 178 5×107 5×59.7 20×2.7 20×1.1 905
RCUG360AHYZ1 178 6×102 6×56.2 24×2.7 24×1.1 1026
RCUG380AHYZ1 178 3×107+3×102 3×59.7+3×56.2 24×2.7 24×1.1 1056
RCUG400AHYZ1 178 6×107 6×59.7 24×2.7 24×1.1 1086

RNC: Running Current IPT: Power Input

1. These data are based on the same conditions as those for the cooling capacity; please refer to the notes for the Unit
General Data.
2. The starting current is indicated for each compressor.
3. The “Maximum Unit Current” is the total running current of the unit under the following conditions, which consume the
maximum current within the unit working range.
Supplied Voltage: Rated Voltage×0.9
Condenser Air Inlet Temperature: 43 ℃
Chilled Water Outlet Temperature: 15℃
Capacity Control: 100%
Therefore, the size of wiring and fuses must be determined according to applicable national and local codes.
4. In addition to the conditions mentioned in the item 3, the compressor currents can be estimated as shown below.

One-Compressor

Maximum

Instantaneous STC

Current
5. The unit power input can be estimated from that of the compressor in the Cooling Capacity Table and that of the condenser fan
motor above.

17
SELECTION DATA

Electric Data (Voltage:415V)


Application Compressor(Three Phases)
Unit Main Power Motor for Condenser Fan Maximum Unit
Model Voltage(V)
STC(A) RNC(A) IPT (kW) Current(A)
Voltage Hz Max. Min. RNC(A) IPT (kW)
RCU40AHYZ1 125 53 34.6 4×2.7 4×1.1 88
RCU50AHYZ1 161 69 42.3 4×2.7 4×1.1 118
RCU60AHYZ1 195 87 52.5 4×2.7 4×1.1 148
RCU75AHYZ1 195 92 55.8 4×2.7 4×1.1 158
RCU100AHYZ1 161 2×69 2×42.3 8×2.7 8×1.1 236
RCU120AHYZ1 195 2×87 2×52.5 8×2.7 8×1.1 297
RCU150AHYZ1 195 2×92 2×55.8 8×2.7 8×1.1 317
RCU180AHYZ1 195 3×87 3×52.5 12×2.7 12×1.1 445
RCU200AHYZ1 195 3×92 3×55.8 12×2.7 12×1.1 475
RCU240AHYZ1 195 4×87 4×52.5 16×2.7 16×1.1 593
RCU270AHYZ1 195 2×92+2×87 2×55.8+2×52.5 16×2.7 16×1.1 613
RCU300AHYZ1 195 4×92 4×55.8 16×2.7 16×1.1 634
RCU330AHYZ1 195 3×87+2×92 3×52.5+2×55.8 20×2.7 20×1.1 762
RCU350AHYZ1 195 5×92 5×55.8 20×2.7 20×1.1 792
RCU360AHYZ1 195 6×87 6×52.5 24×2.7 24×1.1 890
RCU380AHYZ1 195 3×92+3×87 3×55.8+3×52.5 24×2.7 24×1.1 920
RCU400AHYZ1 195 6×92 6×55.8 24×2.7 24×1.1 950
415 50 456 374
RCUG40AHYZ1 125 59 36.6 4×2.7 4×1.1 104
RCUG50AHYZ1 161 74 45.3 4×2.7 4×1.1 126
RCUG60AHYZ1 195 93 56.2 4×2.7 4×1.1 157
RCUG75AHYZ1 195 98 59.7 4×2.7 4×1.1 166
RCUG100AHYZ1 161 2×74 2×45.3 8×2.7 8×1.1 253
RCUG120AHYZ1 195 2×93 2×56.2 8×2.7 8×1.1 313
RCUG150AHYZ1 195 2×98 2×59.7 8×2.7 8×1.1 331
RCUG180AHYZ1 195 3×93 3×56.2 12×2.7 12×1.1 470
RCUG200AHYZ1 195 3×98 3×59.7 12×2.7 12×1.1 497
RCUG240AHYZ1 195 4×93 4×56.2 16×2.7 16×1.1 626
RCUG270AHYZ1 195 2×98+2×93 2×59.7+2×56.2 16×2.7 16×1.1 645
RCUG300AHYZ1 195 4×98 4×59.7 16×2.7 16×1.1 663
RCUG330AHYZ1 195 3×93+2×98 3×56.2+2×59.7 20×2.7 20×1.1 801
RCUG350AHYZ1 195 5×98 5×59.7 20×2.7 20×1.1 829
RCUG360AHYZ1 195 6×93 6×56.2 24×2.7 24×1.1 939
RCUG380AHYZ1 195 3×98+3×93 3×59.7+3×56.2 24×2.7 24×1.1 967
RCUG400AHYZ1 195 6×98 6×59.7 24×2.7 24×1.1 994

RNC: Running Current IPT: Power Input


1. These data are based on the same conditions as those for the cooling capacity; please refer to the notes for the Unit
General Data.
2. The starting current is indicated for each compressor.
3. The “Maximum Unit Current” is the total running current of the unit under the following conditions, which consume the
maximum current within the unit working range.
Supplied Voltage: Rated Voltage×0.9
Condenser Air Inlet Temperature: 43℃
Chilled Water Outlet Temperature: 15℃
Capacity Control: 100%
Therefore, the size of wiring and fuses must be determined according to applicable national and local codes.
4. In addition to the conditions mentioned in the item 3, the compressor currents can be estimated as shown below.

One-Compressor

Maximum

Instantaneous STC

Current
5. The unit power input can be estimated from that of the compressor in the Cooling Capacity Table and that of the condenser fan
motor above.

18
SOUND DATA

Sound Data
Unit Power Frequency :50Hz
Model Frequency Band(Hz)
45~90 90~180 180~355 355~710 710~1400 1400~2800 2800~5600 5600~11200 Overall

RCU40AHYZ1
49.6 54.4 62.4 65.2 66.5 60.9 44.3 38.9 69.0
RCUG40AHYZ1
RCU50AHYZ1
49.9 54.8 63.0 65.8 67.0 61.2 44.7 39.1 69.5
RCUG50AHYZ1
RCU60AHYZ1
51.1 55.2 63.4 66.4 67.2 61.5 44.9 39.3 69.8
RCUG60AHYZ1
RCU75AHYZ1
51.5 55.8 63.8 66.7 67.4 61.8 45.3 39.8 70.1
RCUG75AHYZ1
RCU100AHYZ1
52.4 56.5 64.7 66.3 67.4 66.5 46.2 41.5 71.4
RCUG100AHYZ1
RCU120AHYZ1
52.8 57.2 65.4 66.5 67.8 66.9 46.7 42.2 71.8
RCUG120AHYZ1
RCU150AHYZ1
52.8 57.3 65.5 66.8 68.1 66.9 46.8 42.3 72.0
RCUG150AHYZ1
RCU180AHYZ1
53.1 57.5 66.4 67.3 68.7 67.2 47.2 42.6 72.5
RCUG180AHYZ1
RCU200AHYZ1
53.1 57.7 66.7 67.6 68.8 67.5 47.2 42.6 72.7
RCUG200AHYZ1
RCU240AHYZ1
53.3 57.9 66.8 68.1 69.3 67.8 47.3 43.1 73.1
RCUG240AHYZ1
RCU270AHYZ1
53.3 57.9 66.8 68.3 69.4 67.9 47.3 43.1 73.2
RCUG270AHYZ1
RCU300AHYZ1
53.3 57.9 66.8 68.4 69.5 67.9 47.3 43.1 73.3
RCUG300AHYZ1
RCU330AHYZ1
53.5 58.1 67.3 68.8 70.1 68.2 47.6 43.4 73.7
RCUG330AHYZ1
RCU350AHYZ1
53.5 58.1 67.3 69.1 70.3 68.4 47.6 43.4 73.9
RCUG350AHYZ1
RCU360AHYZ1
54.7 58.6 67.9 69.5 70.9 69.2 49.4 44.5 74.6
RCUG360AHYZ1
RCU380AHYZ1
54.7 58.6 67.9 69.7 71.1 69.4 49.4 44.5 74.8
RCUG380AHYZ1
RCU400AHYZ1
55.2 58.5 68.1 69.9 71.4 69.7 49.6 44.9 75.0
RCUG400AHYZ1

SPL-A: A Scale Sound Pressure Level (dB)


Notes:
1. The measuring point is 1.0 meter from the center of the unit surface and 1.5 meter from the floor level.
2. The units are operating under the standard working condition for cooling operation.
3. The above data was measured on a flat ground, Therefore, reflected sounds should be taken into consideration when the unit is
surrounded by walls, etc.

19
WOKING RANGE

Working Range
Power Supply:
Working Voltage :90%-100% Rating Voltage
Unbalanced Voltage :Within ±3% Deviation from Each Voltage at Compressor Terminals
Start Voltage:Higher than 85% of the Rated Voltage

Maximum Water Flow Rate and Minimum Water Flow Rate (m3/h)
Max.Flow Rate Min.Flow Rate Max.Flow Rate Min.Flow Rate
Model Model
(No.1) (No.1) (No.1/No.2) (No.1/No.2)
RCU40AHYZ1, RCUG40AHYZ1 41.0 12.8 RCU200AHYZ1, RCUG200AHYZ1 159.4 57.1
RCU50AHYZ1, RCUG50AHYZ1 50.5 15.7 RCU240AHYZ1, RCUG240AHYZ1 98.3/98.3 35.2/35.2
RCU60AHYZ1, RCUG60AHYZ1 63.3 19.7 RCU270AHYZ1, RCUG270AHYZ1 135/98.3 42/35.2
RCU75AHYZ1, RCUG75AHYZ1 67.5 21.0 RCU300AHYZ1, RCUG300AHYZ1 135/135 42/42
RCU100AHYZ1, RCUG100AHYZ1 76.4 28.6 RCU330AHYZ1, RCUG330AHYZ1 152.2/135 53.4/42
RCU120AHYZ1, RCUG120AHYZ1 98.3 35.2 RCU350AHYZ1, RCUG350AHYZ1 159.4/135 57.1/42
RCU150AHYZ1, RCUG150AHYZ1 135.0 42.0 RCU360AHYZ1, RCUG360AHYZ1 152.2/152.2 53.4/53.4
RCU380AHYZ1, RCUG380AHYZ1 159.4/152.2 57.1/53.4
RCU180AHYZ1, RCUG180AHYZ1 152.2 53.4
RCU400AHYZ1, RCUG400AHYZ1 159.4/159.4 57.1/57.1
3
Internal Water Volume in Water Cooler (m )
Model Volume(No.1) Model Volume(No.1/No.2)
RCU40AHYZ1, RCUG40AHYZ1 0.08 RCU200AHYZ1, RCUG200AHYZ1 0.21
RCU50AHYZ1, RCUG50AHYZ1 0.07 RCU240AHYZ1, RCUG240AHYZ1 0.14/0.14
RCU60AHYZ1, RCUG60AHYZ1 0.07 RCU270AHYZ1, RCUG270AHYZ1 0.14/0.14
RCU75AHYZ1, RCUG75AHYZ1 0.07 RCU300AHYZ1, RCUG300AHYZ1 0.14/0.14
RCU100AHYZ1, RCUG100AHYZ1 0.14 RCU330AHYZ1, RCUG330AHYZ1 0.21/0.14
RCU120AHYZ1, RCUG120AHYZ1 0.14 RCU350AHYZ1, RCUG350AHYZ1 0.21/0.14
RCU150AHYZ1, RCUG150AHYZ1 0.14 RCU360AHYZ1, RCUG360AHYZ1 0.21/0.21
RCU380AHYZ1, RCUG380AHYZ1 0.21/0.21
RCU180AHYZ1, RCUG180AHYZ1 0.21
RCU400AHYZ1, RCUG400AHYZ1 0.21/0.21

Minimum Internal System Water Volume


RCU40AHYZ1 RCU50AHYZ1 RCU60AHYZ1 RCU75AHYZ1 RCU100AHYZ1 RCU120AHYZ1 RCU150AHYZ1 RCU180AHYZ1 RCU200AHYZ1
Model
RCUG40AHYZ1 RCUG50AHYZ1 RCUG60AHYZ1 RCUG75AHYZ1 RCUG100AHYZ1 RCUG120AHYZ1 RCUG150AHYZ1 RCUG180AHYZ1 RCUG200AHYZ1

Volume
0.42 0.51 0.64 0.68 1.02 1.28 1.37 1.92 2.05
(m3)
RCU240AHYZ1 RCU270AHYZ1 RCU300AHYZ1 RCU330AHYZ1 RCU350AHYZ1 RCU360AHYZ1 RCU380AHYZ1 RCU400AHYZ1
Model
RCUG240AHYZ1 RCUG270AHYZ1 RCUG300AHYZ1 RCUG330AHYZ1 RCUG350AHYZ1 RCUG360AHYZ1 RCUG380AHYZ1 RCUG400AHYZ1

Volume
2.57 2.65 2.74 3.29 3.42 3.85 3.98 4.11
(m3)

Note: Minimum internal system water volume in the above table is setting according to the standard neutral zone temperature.
In case of changing the setting, minimum internal system water volume shall be increased as follows.

Water Neutral Zone Temperature Minimum Water Volume in System

2℃(Standard) 100%
1.5℃ 130%
1℃ 200%

Temperature Range
The temperature range is given in the following table.
Item Standard
Chilled Water Outlet Temperature 5~15℃
Condenser Air Inlet Temperature(DB) 5~43℃

20
COMPONENT DATA

Component Detailed Data(R22 and R407C)


Compressor
Model — 40ASCC-Z 50ASCC-Z 60ASCC-Z

Compressor Type — Semi-Hermetic


Revolution 50Hz r/min 2,880
Displacement 50Hz m3/h 137.4 169.5 208.7
Continuous Control
Capacity Control % 100~15, 0
Type
Air Tight
Discharge MPa 3.0
Pressure
Suction MPa 2.0
Type — Special Squirrel Cage, Three-Phase Motor
Starting Method — Star-Delta Starting
Motor
Poles — 2
Insulation — F
Name — ICEMATIC UX300
Oil
Charge Liters 6

Condenser and Condenser Fan


RCU40AHYZ RCU50AHYZ RCU60AHYZ RCU75AHYZ RCU100AHYZ RCU120AHYZ RCU150AHYZ RCU180AHYZ
R22 1 1 1 1 1 1 1 1
Model
RCUG40AH RCUG50AH RCUG60AH RCUG75AH RCUG100AHY RCUG120AHY RCUG150AHY RCUG180AHY
R407C
YZ1 YZ1 YZ1 YZ1 Z1 Z1 Z1 Z1
Condenser Type — Multi-Pass Cross Finned Tube

Material — Copper Tube


Condenser
Piping Outer Diameter mm 9.53 9.53 9.53 9.53 9.53 9.53 9.53 9.53
Tube Thickness(mean) mm 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4

Fin Material — Aluminum

Maximum Operation Pressure MPa 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
Number of Condenser/unit(s) — 4 4 4 4 8 8 8 12
Type — Direct-Drive Propeller Fan

Condeser Fan Number/Unit — 4 4 4 4 8 8 8 12


Outer Diameter mm 710 710 710 710 710 710 710 710
Revolution r/min 960 960 960 960 960 960 960 960
Type — Drip-Proof Enclosure

Starting Method — Direct-On-Line Starting


Condenser Fan
Motor Nominal Output kW 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9
Quantity — 4 4 4 4 8 8 8 12
Insulation Class — E E E E E E E E
Poles — 6 6 6 6 6 6 6 6
RCU200AHY RCU240AHY RCU270AHY RCU300AHY RCU330AHYZ RCU350AHYZ RCU360AHYZ RCU380AHYZ RCU400AHYZ
R22 Z1 Z1 Z1 Z1 1 1 1 1 1
Model
RCUG200A RCUG240A RCUG270A RCUG300A RCUG330AHY RCUG350AHY RCUG360AHY RCUG380AHY RCUG400AHY
R407C
HYZ1 HYZ1 HYZ1 HYZ1 Z1 Z1 Z1 Z1 Z1
Condenser Type — Multi-Pass Cross Finned Tube
Material — Copper Tube
Condenser
Outer Diameter mm 9.53 9.53 9.53 9.53 9.53 9.53 9.53 9.53 9.53
Piping
Tube Thickness(mean) mm 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4
Fin Material — Aluminum
Maximum Operation Pressure MPa 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
Number of Condenser/unit(s) — 12 2×8 2×8 2×8 20 20 2×12 2×12 2×12
Type — Direct-Drive Propeller Fan

Condeser Fan Number/Unit — 12 2×8 2×8 2×8 20 20 2×12 2×12 2×12


Outer Diameter mm 710 710 710 710 710 710 710 710 710
Revolution r/min 960 960 960 960 960 960 960 960 960
Type — Drip-Proof Enclosure
Starting Method — Direct-On-Line Starting
Condenser Fan Nominal Output kW 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9
Motor
Quantity — 12 2×8 2×8 2×8 20 20 2×12 2×12 2×12
Insulation Class — E E E E E E E E E
Poles — 6 6 6 6 6 6 6 6 6

21
COMPONENT DATA

Water Cooler

RCU(G)40 RCU(G)50 RCU(G)60 RCU(G)75A RCU(G)100 RCU(G)120 RCU(G)150 RCU(G)180


Model
AHYZ1 AHYZ1 AHYZ1 HYZ1 AHYZ1 AHYZ1 AHYZ1 AHYZ1

Shell Material Steel


Water Side Outer Diameter 356.2 356.2 356.2 356.2 356.2 356.2 356.2 431.8
Length 1,276 1,276 1,276 1,276 2,296 2,296 2,296 2,400
Shell Shell Material Steel

Refrigerant Outer Diameter 420 420 420 420 420 420 420 500
Side
Length 101 101 101 101 101 101 101 101
Thickness 10 10 10 10 10 10 10 12
Material Copper
Tube Outer Diameter 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7
Quantity 220 272 310 310 272 310 310 437
Number of Pass 4 4 4 4 2 2 2 2
Maximum Refrigerant R22 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
Pemissable Side R407C 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
Pressure Water Side 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05

Insulation Polyethylene(25mm)

RCU(G)200 RCU(G)24 RCU(G)270 RCU(G)300 RCU(G)330 RCU(G)350 RCU(G)360 RCU(G)380 RCU(G)400


Model
AHYZ1 0AHYZ1 AHYZ1 AHYZ1 AHYZ1 AHYZ1 AHYZ1 AHYZ1 AHYZ1

Shell Material Steel


Water Side Outer Diameter 431.8 356.2 356.2 356.2 431.8+356.2 431.8+356.2 431.8 431.8 431.8
Length 2,400 2,296 2,296 2,296 2,400+2,296 2,400+2,296 2,400 2,400 2,400
Shell
Shell Material Steel
Refrigerant Outer Diameter 500 420 420 420 500+420 500+420 500 500 500
Side Length 101 101 101 101 101 101 101 101 101
Thickness 12 10 10 10 12+10 12+10 12 12 12
Material Copper
Tube Outer Diameter 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7
Quantity 437 310 310 310 437+310 437+310 437 437 437
Number of Pass 2 2 2 2 2 2 2 2 2
Maximum Refrigerant R22 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
Pemissable Side R407C 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
Pressure Water Side 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05

Insulation Polyethylene(25mm)

Note: the data above is indicated for each water cooler, as these units greater than 240AHYZ1 including
240AHYZ1 consist of two water coolers for two modules, in the case the data for the two water coolers are different,
it is showed as no.1water cooler data + no.2 water cooler data.

22
CONTROL SYSTEM

Refrigerant System
In addition to the basic air-cooled water chiller components (compressor, condenser, thermal expansion
valves and water cooler), the following components are equipped in each refrigerant cycle:
Stop Valve for Compressor Discharge Line and Liquid Line:
These stop valves are equipped at the liquid line, and facilitate easy compressor service without appreciable
leakage of refrigerant.

Capacity Control
All models are equipped with an unloading system for each compressor, in order to adjust the cooling
capacity and provide precise temperature control for the chilled water, coupled with electric thermostat.

Electric Operation Control


Electrical Operation Control advanced HITACHI Water Chillers are as follows.

Control Panel
ON switch, OFF switch, Power Supply Lamp, Operation Lamp, Alarm Lamp, Operation/Alarm Indicator for
each refrigerant cycle and check switch are mounted in the Control Panel. The Control Panel is located at a
position where easy access is available. Operation/Alarm indicator can display individual alarm codes such
as High-Cut, Low-Cut etc. This function is very useful for detecting what alarm has occurred. Check
switches are for checking chilled water temperature and alarm occurrence data. Chilled water temperature
setting switches, ON/OFF Differential Setting Switches, Remote-Local Switch and so on are located at the
rear side of Control Panel, in order not to access during operation.

Operation Hour Meter


This hour-meter indicates the sum of the compressor operation.

Screw Compressor Cycling Protection Circuit


The electric timer of the screw compressor cycling protection (CCP ) connected in the compressor control
circuit delays the screw compressor restarting period for approximately three (3) minutes for No.1 compressor,
four (4) minutes for No.2 compressor,
five (5) minutes for No.3 compressor and six (6) minutes for No.4 compressor after the electronic thermostat
calls for the cooling operation or automatic resetting of the protection devices, thereby preventing harmful
screw compressor cycling operation.

Electronic Thermostat Circuit


The electronic thermostat senses chilled water temperatures at the water cooler outlet, and operates solenoid
valves for HITACHI screw compressor capacity control.

Screw Compressor Reversing Protection Circuit


This circuit is composed of a reverse-phase protection devices, preventing reverse operation of the screw
compressor, because the screw compressor definitely cannot be operated in the wrong direction as the
misconnection of the main power phases.

Rotation of Compressor Operation


Rotation of compressor operation order is available in order to balance operation hours of compressors.
This function extends machine life.

Restart after Short Period Power-Failure


In the case that a power failure shorter than 2 seconds occurred, compressors can be restarted automatically
within 3 minutes after power supply.

23
CONTROL SYSTEM

Refrigerant Charge
R22
Model RCU40A RCU50A RCU60AHYZ RCU75AH RCU100A RCU120AHY RCU150A RCU180AHY
HYZ1 HYZ1 1 YZ1 HYZ1 Z1 HYZ1 Z1
Charge(kg) 38 44 48 50 2×42 2×43 2×47 3×43
Model RCU200 RCU240 RCU270AHY RCU300A RCU330A RCU350AHY RCU360A RCU380AHY RCU400
AHYZ1 AHYZ1 Z1 HYZ1 HYZ1 Z1 HYZ1 Z1 AHYZ1
Charge(kg) 3×48 4×43 2×47+ 2×43 4×47 3×43+2x47 3×48+2×47 6×43 3×48+3×43 6×48

R407C
Model RCUG40 RCUG50 RCUG60A RCUG75A RCUG100 RCUG120A RCUG150A RCUG180A
AHYZ1 AHYZ1 HYZ1 HYZ1 AHYZ1 HYZ1 HYZ1 HYZ1
Charge(kg) 38 48 2×35 2×38 2×40 3×44
Model RCUG200 RCUG240 RCUG270 RCUG300 RCUG330 RCUG350A RCUG360A RCUG380A RCUG400
AHYZ1 AHYZ1 AHYZ1 AHYZ1 AHYZ1 HYZ1 HYZ1 HYZ1 AHYZ1
Charge(kg) 3×46 4×38 2×40+ 4×40 3×44+2×40 3×46+2×40 6×44 3×46+3×44 6×46
2×38
Note: for the details of the blank places, please contact HITACHI or Hitachi’s distributors.

Protection and Safety Control

The safety and protective devices are equipped in the unit to ensure dependable and long life operation.
Their functions should be carefully noted, and field adjustment is not recommended, if the setting is
maintained at the point listed in the table.

Compressor Protection

1、The high pressure switch and the low pressure control protect against excessive discharge pressure and
exceedingly low suction pressure. The switch and control cut out compressor operation when the
discharge pressure exceeds the setting or when the suction pressure decrease below the setting.
2、Overcurrent relays equipped in the magnetic switch box cut out each compressor operation when the
current to the compressor exceeds the setting.
3、The internal thermostat embedded in the compressor motor winding cuts out each operations, when the
temperature of the motor winding exceeds the setting.
4、An oil heater in the compressor prevents from oil foaming during cold starting. Energize this heater to
warm the oil, while the compressor is stopped.

Fan Motor Protection

The thermal overcurrent relays for the condenser fan motors cut out fan operation and compressor operation,
when the current to the fan motor exceeds the setting.

Refrigerant Cycle

1、The fusible plug is equipped on the liquid line. When refrigerant temperature exceeds the melting point,
and the plug melts and purges the refrigerant gas, in order to avoid explosion of the condenser.
2、The freeze protection control, for which the sensor is located in the water outlet near the water cooler, cuts
out the compressor operation, when the water outlet temperature decreases below the setting.

24
CONTROL SYSTEM

Safety and Control Device Setting (R22)


RCU40AHY RCU50AHY RCU60AHYZ RCU75AHY RCU100AHY RCU120AHY RCU150AHY RCU180AHY
Model
Z1 Z1 1 Z1 Z1 Z1 Z1 Z1
High Pressure Control Manual Reset, Adjustable(One Switch for Each Compressor Motor)
Cut-Out MPa 2.98 2.98 2.98 2.98 2.98 2.98 2.98 2.98
Low Pressure Control Control by Micro-Processor
Cut-Out MPa 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05
Internal Thermostat Automatic Reset, Non-Adjustable(One Switch for Each Compressor Motor)
Cut-Out ℃ 115 115 115 115 115 115 115 115
Cut-In ℃ 93 93 93 93 93 93 93 93
Overcurrent Relay *1  Manual Reset Adjustable (One Switch for Each Compressor Motor)
For 380V/415V 50Hz A 58 72 90 100 72 90 100 90
Compressor Oil Heater One Oil Heater for Each Compressor Motor
Capacity W 150 150 150 150 150 150 150 150
Discharge Gas Thermistor (One for Each Circuit)
Cut-Out ℃ 70 70 70 70 70 70 70 70
Cut-In ℃ 100 100 100 100 100 100 100 100
CCP Timer Non-Adjustable (One Timer for Each Compressor Motor)
Setting Time s 180 180 180 180 180 180 180 180
Star-Delta Starting s 5 5 5 5 5 5 5 5
From Start to Load-up s 30 30 30 30 30 30 30 30
For Control Fuse
A 6 6 6 6 6 6 6 6
Circuit Capacity(220V/240V)
Fusible Plug (One for Each Circuit)
Melting Temperature ℃ 72 72 72 72 72 72 72 72
For
Freeze Protection Control
Refrigerant
Circuit Cut-Out ℃ 2 2 2 2 2 2 2 2
Discharge Temperature Control
Cut-Out ℃ 140 140 140 140 140 140 140 140
Overcurrent Relay for Motor of Fan Manual Reset, Adjustable(One Three-Phase Set for Each Fan Motor)
380V/415V 50Hz A 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
Pressure Relief Valve (One for Each Compressor)
Starting to Open MPa 3.13 3.13 3.13 3.13 3.13 3.13 3.13 3.13
RCU200AH RCU240AH RCU270AHY RCU300AH RCU330AHY RCU350AHY RCU360AHY RCU380AHY RCU400AHY
Model
YZ1 YZ1 Z1 YZ1 Z1 Z1 Z1 Z1 Z1
High Pressure Control Manual Reset, Adjustable(One Switch for Each Compressor Motor)
Cut-Out MPa 2.98 2.98 2.98 2.98 2.98 2.98 2.98 2.98 2.98
Low Pressure Control Control by Micro-Processor
Cut-Out MPa 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05
Internal Thermostat Automatic Reset, Non-Adjustable(One Switch for Each Compressor Motor)
Cut-Out ℃ 115 115 115 115 115 115 115 115 115
Cut-In ℃ 93 93 93 93 93 93 93 93 93
Overcurrent Relay*1  Manual Reset Adjustable (One Switch for Each Compressor Motor)
For 380V /415V 50Hz A 100 90 100/90 100 90/100 100 90 100/90 100
Compressor Oil Heater One Oil Heater for Each Compressor Motor
Capacity W 150 150 150 150 150 150 150 150 150
Discharge Gas Thermistor (One for Each Circuit)
Cut-Out ℃ 70 70 70 70 70 70 70 70 70
Cut-In ℃ 100 100 100 100 100 100 100 100 100
CCP Timer Non-Adjustable (One Timer for Each Compressor Motor)
Setting Time s 180 180 180 180 180 180 180 180 180
Star-Delta Starting s 5 5 5 5 5 5 5 5 5
From Start to Load-up s 30 30 30 30 30 30 30 30 30
For Control Fuse
A 6 6 6 6 6 6 6 6 6
Circuit Capacity(220V/240V)
Fusible Plug (One for Each Circuit)
Melting Temperature ℃ 72 72 72 72 72 72 72 72 72
For
Freeze Protection Control
Refrigerant
Circuit Cut-Out ℃ 2 2 2 2 2 2 2 2 2
Discharge Temperature Control
Cut-Out ℃ 140 140 140 140 140 140 140 140 140
Overcurrent Relay for Motor of Fan Manual Reset, Adjustable(One Three-Phase Set for Each Fan Motor)
380V /415V 50Hz A 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
Pressure Relief Valve (One for Each Compressor)
Starting to Open MPa 3.13 3.13 3.13 3.13 3.13 3.13 3.13 3.13 3.13

Note: The data marked with *1 is indicated for each compressor, as in a module the same compressors are used,
for these chillers greater than 240AHYZ1 including 240AHYZ1 which consist of two modules, when the data for the
compressor in the two modules are different, it is showed as data for one of the compressor in the no.1 module /
data for one of the compressor in the no.2 module.

25
CONTROL SYSTEM

Safety and Control Device Setting (R407C)


RCUG40A RCUG50A RCUG60A RCUG75A RCUG100A RCUG120A RCUG150A RCUG180A
Model
HYZ1 HYZ1 HYZ1 HYZ1 HYZ1 HYZ1 HYZ1 HYZ1
High Pressure Control Manual Reset, Adjustable(One Switch for Each Compressor Motor)
Cut-Out MPa 2.98 2.98 2.98 2.98 2.98 2.98 2.98 2.98
Low Pressure Control Control by Micro-Processor
Cut-Out MPa 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05
Internal Thermostat Automatic Reset, Non-Adjustable(One Switch for Each Compressor Motor)
Cut-Out ℃ 115 115 115 115 115 115 115 115
Cut-In ℃ 93 93 93 93 93 93 93 93
Overcurrent Relay *1  Manual Reset Adjustable (One Switch for Each Compressor Motor)
For 380V/415V 50Hz A 64 80 100 100 80 100 100 100
Compressor Oil Heater One Oil Heater for Each Compressor Motor
Capacity W 150 150 150 150 150 150 150 150
Discharge Gas Thermistor (One for Each Circuit)
Cut-Out ℃ 70 70 70 70 70 70 70 70
Cut-In ℃ 100 100 100 100 100 100 100 100
CCP Timer Non-Adjustable (One Timer for Each Compressor Motor)
Setting Time s 180 180 180 180 180 180 180 180
Star-Delta Starting s 5 5 5 5 5 5 5 5
From Start to Load-up s 30 30 30 30 30 30 30 30
For Control Fuse
A 6 6 6 6 6 6 6 6
Circuit Capacity(220V/240V)
Fusible Plug (One for Each Circuit)
Melting Temperature ℃ 72 72 72 72 72 72 72 72
For Freeze Protection Control
Refrigerant Cut-Out ℃ 2 2 2 2 2 2 2 2
Circuit
Discharge Temperature Control

Cut-Out ℃ 140 140 140 140 140 140 140 140


Overcurrent Relay for Motor of Fan Manual Reset, Adjustable(One Three-Phase Set for Each Fan Motor)
380V/415V 50Hz A 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
Pressure Relief Valve (One for Each Compressor)
Starting to Open MPa 3.13 3.13 3.13 3.13 3.13 3.13 3.13 3.13
RCUG200 RCUG240 RCUG270A RCUG300 RCUG330A RCUG350A RCUG360A RCUG380A RCUG400A
Model
AHYZ1 AHYZ1 HYZ1 AHYZ1 HYZ1 HYZ1 HYZ1 HYZ1 HYZ1
High Pressure Control Manual Reset, Adjustable(One Switch for Each Compressor Motor)
Cut-Out MPa 2.98 2.98 2.98 2.98 2.98 2.98 2.98 2.98 2.98
Low Pressure Control Control by Micro-Processor
Cut-Out MPa 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05
Internal Thermostat Automatic Reset, Non-Adjustable(One Switch for Each Compressor Motor)
Cut-Out ℃ 115 115 115 115 115 115 115 115 115
Cut-In ℃ 93 93 93 93 93 93 93 93 93
Overcurrent Relay*1  Manual Reset Adjustable (One Switch for Each Compressor Motor)
For 380V/415V 50Hz A 100 100 100 100 100 100 100 100 100
Compressor Oil Heater One Oil Heater for Each Compressor Motor
Capacity W 150 150 150 150 150 150 150 150 150
Discharge Gas Thermistor (One for Each Circuit)
Cut-Out ℃ 70 70 70 70 70 70 70 70 70
Cut-In ℃ 100 100 100 100 100 100 100 100 100
CCP Timer Non-Adjustable (One Timer for Each Compressor Motor)
Setting Time s 180 180 180 180 180 180 180 180 180
Star-Delta Starting s 5 5 5 5 5 5 5 5 5
From Start to Load-up s 30 30 30 30 30 30 30 30 30
For Control Fuse
A 6 6 6 6 6 6 6 6 6
Circuit Capacity(220V/240V)
Fusible Plug (One for Each Circuit)
Melting Temperature ℃ 72 72 72 72 72 72 72 72 72
For
Freeze Protection Control
Refrigerant
Circuit Cut-Out ℃ 2 2 2 2 2 2 2 2 2
Discharge Temperature Control
Cut-Out ℃ 140 140 140 140 140 140 140 140 140
Overcurrent Relay for Motor of Fan Manual Reset, Adjustable(One Three-Phase Set for Each Fan Motor)
380V/415V 50Hz A 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
Pressure Relief Valve (One for Each Compressor)
Starting to Open MPa 3.13 3.13 3.13 3.13 3.13 3.13 3.13 3.13 3.13

Note: The data marked with *1 is indicated for each compressor, as in a module the same compressors are used,
for these chillers greater than 240AHYZ1 including 240AHYZ1 which consist of two modules, when the data for the
compressor in the two modules are different, it is showed as data for one of the compressor in the no.1 module /
data for one of the compressor in the no.2 module.

26
INSTALLATION DATA

Recommended Concrete Curbs


RCU(G)40、50、60、75AHYZ1

Drain Ditch
6-Vibration Proof Rubber Mat [Tubing Side]

Foundation Bolt
(4-M20×300)

☆Foundation Bolt
☆Nut
3

☆Washer
☆Bushing

☆Vibration Proof Rubber Mat


Steel Plate(1mm)

[Compressor Side]
☆:Supplied by Factory
Steel Plate(1mm): Field Supply

Concrete Mortar Cement


Drain Ditch

RCU(G)100AHYZ1、RCU(G)120AHYZ1 and RCU(G)150AHYZ1

Drain Ditch 10-Vibration Proof Rubber Mat

Foundation Bolt
(6-M20×300)

☆Foundation Bolt
☆Nut
☆Washer
☆Bushing

☆Vibration Proof Rubber Mat


Steel Plate(1mm)

☆:Supplied by Factory
Steel Plate(1mm) : Field Supply

Drain Ditch Concrete Mortar Cement

27
INSTALLATION DATA

Recommended Concrete Curbs


RCU(G)180AHYZ1 and RCU(G)200AHYZ1

14-Vibration
Drain Ditch Proof Rubber Mat [Tubing Side]

Foundation Bolt

☆Foundation Bolt
☆Nut
☆Washer
☆Bushing
☆Vibration Proof Rubber Mat
Steel Plate(1mm)

☆:Supplied by Factory

Compressor Side Steel Plate(1mm) : Field Supply

Drain Ditch Concrete Mortar Cement

RCU(G)240AHYZ1,RCU(G)270AHYZ1 and RCU(G)300AHYZ1

10-Vibration Proof 10-Vibration Proof


Drain Ditch Rubber Mat [Tubing Side] Rubber Mat [Tubing Side]

Foundation Bolt Foundation Bolt


(6-M20×300) (6-M20×300)

[Compressor Side] [Compressor Side ]

Drain Ditch Concrete Mortar Cement

☆Foundation Bolt
☆Nut
☆Washer
☆Bushing

☆Vibration Proof Rubber Mat


Steel Plate(1mm)

☆:Supplied by Factory
Steel Plate(1mm) : Field Supply

28
INSTALLATION DATA
Recommended Concrete Curbs
RCU(G)330AHYZ1 and RCU(G)350AHYZ1
14-Vibration Proof 10-Vibration Proof
Drain Ditch
Rubber Mat [Tubing Side] Rubber Mat [Tubing Side]

Foundation Bolt Foundation Bolt


(6-M20×300)

[Compressor Side] [Compressor Side]

Drain Ditch Concrete Mortar Cement

☆Foundation Bolt
☆Nut
☆Washer
☆Bushing
☆Vibration Proof Rubber Mat
Steel Plate(1mm)

☆:Supplied by Factory
Steel Plate(1mm): Field Supply

RCU(G)360AHYZ1,RCU(G)380AHYZ1 and RCU(G)400AHYZ1

14-Vibration Proof 14-Vibration Proof


Drain Ditch Rubber Mat [Tubing Side] Rubber Mat [Tubing Side]

Foundation Bolt Foundation Bolt

Compressor Side Compressor Side

Drain Ditch Concrete Mortar Cement

☆Foundation Bolt
☆Nut
☆Washer
☆Bushing

☆Vibration Proof Rubber Mat


Steel Plate(1mm)

☆:Supplied by Factory
Steel Plate(1mm) : Field Supply

29
CONTROL SYSTEM
Electrical Wiring Diagram
MODELS: RCU(G)40、50、60、75AHYZ1

30
CONTROL SYSTEM

Electrical Wiring Diagram


MODELS: RCU(G)100、120、150AHYZ1,RCU(G)240、270、300AHYZ1-No.1

Motor for Compressor

1,2,4

31
CONTROL SYSTEM

Electrical Wiring Diagram


MODELS: RCU(G)180、200AHYZ1,RCU(G)330、350、360、380、400AHYZ1-No.1

32
CONTROL SYSTEM

Electrical Wiring Diagram


MODELS: RCU(G)240、270、300、330、350AHYZ1-No.2

Motor for Compressor

1,2,4

33
CONTROL SYSTEM

Electrical Wiring Diagram


MODELS: RCU(G)360、380、400AHYZ1-No.2

34
CONTROL SYSTEM

DIP SWITCH SETTING


MODELS: RCU(G)40AHYZ1~RCU(G)400AHYZ1

35
SPECIFICATIONS
Standard Specifications

Unit − The unit shall be an air-cooled screw type Compressor − The compressor shall be a
water chiller with R22 or R407C refrigerant, and semi-hermetic compressor from the same
shall be factory-completed with screw-type manufacturer. The compressor shall be
compressors, refrigeration cycle(s), air-cooled serviceable type. The compressor protection
condensers, shell-and-tube water coolers, system shall include an overcurrent relay, a
condenser fan motors, a star-delta starter, protective pressure switch, a timer relays and an internal
and safety devices, thermal expansion valves and thermostat embedded in the motor winding.
compressor discharge stop valves, and shall be
factory-assembled, piped, internal wired and Water-Cooler-the water cooler shall be the dry
charged with R22 or R407C refrigerant. The unit expansion type with a horizontal welded steel
shall be completely weather-proofed for outdoor construction shell, containing inside tubes. The
installation. The unit shall comply with Chinese refrigerant side of the water cooler shall be cleaned,
Industrial Standards and other Chinese Industrial dehydrated and tested for leakage at the maximum
Standardization statutes, including safety codes. permissible working pressure of _ MPa.The water
side of the water cooler shall be cleaned and
Capacity − The cooling capacity of the unit shall performed water pressure test at_ MPa.
be kW or greater under the following
conditions: Air-Side Heat Exchanger Fan and Fan Motor −
m3/h chilled water flow rate, The fan shall be the propeller type directly driven by
℃chilled water inlet temperature, a kW motor. The motor shall be thermally
℃chilled water outlet temperature, protected from overloaded conditions with a thermal
m2.℃/W fouling factor for the water-side overcurrent relay and shall be permanently
heat exchanger or greater. lubricated, The winding and bearing of the
The water-side heat exchanger pressure decrease condenser fan motor shall be weather-proof
shall not exceed kPa. construction.
The compressor power input shall not exceed
kW under the prescribed conditions. Condenser-The condenser shall be the multi-pass,
cross-finned tube type, equipped with aluminum slit
Power Supply − The unit shall operate on V, fins, mechanically bonded to seamless, oxygen-free
___Hz, three-phase current, and shall be capable to copper tubes. The condenser shall be cleaned,
operate within maximum V and minimum dehydrated and tested for leakage at the maximum
V. permissible working pressure of MPa.

Dimensions and Weight − The height of the unit Accessories-Standard accessories shall include
shall be mm, the width shall be mm, and vibration-proof mats, foundation bolts
the depth shall be mm. The weight of the
unit shall not exceed kg.

Cabinet − The cabinet shall be constructed of


galvanized steel, baked with synthetic resin paint.
The service panels shall be easily removable for
service access to the electrical components such as
magnetic switches and electrical devices.

36
Hitachi Appliances , Inc.

Distributed By:
Air Conditioning Division
URL: http://www.hitachiacs.co.jp
Specifications in this catalogue are subject to change without notice in order that HITACHI may bring the latest innovations to
their customers.

Printed in china No:Z0011121-IX-B

36

You might also like