INTERNATIONAL CERTIFICATION SERVICES PVT. LTD.

INSPECTION REPORT (IR)

STATION ICS REGISTRATION REPORT NO. DATE:


MUMBAI HO NO.:RINSP/2021/8753 IR/INSP/91/Inspection/Survey/6141894/20230406 07/04/2023
CUSTOMER NAME : ONGC-TPI-HAZIRA-CABLE TRAY-2021-24
END USER / EPC / LSTK / : Mayur Electric Works
CONSTRUCTION CONTRACTOR NAME
MANUFACTURER / SUPPLIER NAME : EFFRA INDUSTRIES LLP
PROJECT / VENDOR P.O. NO. : MEW/MS/PO-02/2022-23 dated 28/01/2023
ITEM / MATERIALS / EQUIPMENTS : Cable Tray Duct With Cover Hot Dip 1200 X 375
HEAT / BATCH / SR. / MODEL NO.. : HEAT NO. 22102621
QUANTITY : 180 Meters
QAP / ITP / DRAWING / SPECIFICATION : QAP No. QAP/EFRA/MEW Rev.00
REF NO
CODES / STANDARDS : IS 1079, IS 2629, IS 4759, IS 6745, IS 2633
DATE(S) OF INSPECTION : 06/04/2023 INSPECTION TYPE : Final
The undersigned Surveyor working under general terms and conditions of International Certification Services, did visit at
Effra Industries LLP for Inspection of the above.
FINDINGS / OBSERVATIONS:
A) Visual & Marking / Identification Examination:
(1) As Per QAP Sr.No:3.1: Surface Finish: 10% Randomly Witnessed And Found No Any Defects Like Ash Marks,
Lumps, Runs, Black Spot. But Weavins Found In Acceptable.
(2) As Per QAP Sr.No:4.1: Visual Inspection: Witnessed And Found No Any Defects Like, Crack, Etc.
(3) Note: The Cable Tray Size Was Very Large According To The Customization, And The Galvanizing Pond Was Small.
As A Result Of The Cable Tray Multiple Deepening In The Pond, A Black Spot And A Bare Spot Were Discovered On The
Surface, Which Is Acceptable In This Special Condition.

B) Dimensional Examination:
(1) As Per QAP Sr.No:4.2: Dimension Inspection: Witnessed As Per Approved Drawings And Found Within Limits No Any
Deviatation Found.

C) Calibration Status of Instruments / Equipment used (Name,Sr./ID No,Range,Date of calibration,Date of


Expiry,Traceability & Suitability) :
(1) Vernier Caliper:
Make: INSIZE
Id. No. : 2010221445
Range: 0-150 Micron
Calibration Date: 14-03-2023
Calibration Due Date: 13-03-2024 Annexure C_1
(2) Digital Coating Thickness Gauge: Make- Kusam-Meco / KM 117A
Id No. : 200574
Range: 0-2000 m
Calibration Date: 14.03.2023, Calibration Due Date: 13.03.2024
(3) Measuring Tape
Make: Freemans
Id. No. : EIL/5 MT/01
Range : 0-5000 Mm
Calibration Date: 14.03.2023
Calibration Due Date:- 13.03.2024

D) Reports Reviewed :
(1) As Per QAP Sr.No:1.3 & 1.4: Reviewed Chemical & Mechanical Properties MTC And Found In Order. Annexure
D_1
(2) PO And Approved Drawing Reviewed Found Ok.

E)Tests Witnessed:
(1) As Per QAP Sr.No:3.1: Surface Finish: 10% Randomly Witnessed And Found No Any Defects Like Ash Marks,

Page 1 / 2 FI/01/Issue 2/Rev.1/07.07.2022


INTERNATIONAL CERTIFICATION SERVICES PVT. LTD.
INSPECTION REPORT (IR)

Lumps, Runs, Black Spot, Etc. Found Acceptable. Annexure E_1


(2) As Per QAP Sr.No:3.2: Thickness Of Zinc Coating: 10% Randomly Witnessed And Found Greater Than 86 Microns
Found Satisfactory.
(3) As Per QAP Sr.No:3.3: Weight Of Zinc Coating: Witnessed, As Per Standards/Codes And Found Satisfactory.

F) Safety & Environment Condition at work place / Any Other observation :


(1) NIL

G) Non Conformities / Deviations (if any) :


(1) NIL

H) Inspection Results / Conclusion :


(1) As Per QAP Sr. No. 3.0 Galvanizing Testing Found Satisfactory.
(2) As Per QAP Sr. No.4.0
Final Inspection Of Cable Tray And With Associates Hardware Checked And Found Satisfactory, Ready For Dispatched
And Accepted.
(3) I Visited Efra Industries,
Block No.521, Nr. Magicrete;
Village- Arak-Sisodara; Ta.:Jalalpore;
Dist.-Navsari-396475 Not Any Observation Was Found During The Inspection, And Offer Items Release For Dispatch.
I) ICS Stamp / Identification provided on accepted Items / Materials / Equipments :
Soft Stamped ICS/1664 On Approved Documents.
J) Photographs of inspected Items / Materials / Equipments :
(1) Witnessed Photograph Annexure J_1
ANNEXURES :01. Visit Slip, 02 Vendor Contact detail :Mr. Gaurang Jogi Contact No. 7405767098
M.T.C., 03 Calibration Certificates.
Order Completed Yes Comp. Date Continued on separate attachment Yes
Sign and Stamp:
Surveyor : Chintan Chotaliya

Contact No. : 9372742685

Email : chintan.chotaliya@icsasian.com
Place :
Date : 06/04/2023
Original : ONGC-TPI-HAZIRA-CABLE TRAY-2021-24 Copy : ICS Copy :
Corporate Office: 22/23, Goodwill Premises, Swastik Estate, 178 CST Road, Kalina, Santacruz (E), Mumbai-400098,
Maharashtra, India.
Tel.:+91-22-26507777-82, 42200900, 30608900-4 Fax:+91-22-42200933
E-mail.:info@icspl.org, ics_tpi@icsasian.com , insp_cell@icsasian.com Web.:www.icspl.org
ICS shall not be liable for any loss or damage sustained by any person due to any act omission or error whatsoever or however ceased during the performance of its survey audit,
assessment, certification, inspection of other services except in the ease of deliberate neglect on part of ICS and its employees, servants, sub-contractor and agents. Then only the
International Certifications Services shall pay compensation to such person for his proved direct loss or damage and such a compensation/liabilities will be limited to an amount not
exceeding the maximum fee (if any) charged by ICS for the particular service in respect of which neglect arise.

Page 2 / 2 FI/01/Issue 2/Rev.1/07.07.2022

You might also like