A. SPRINKLER SYSTEM
Hazard Classification :
From NFPA-13, sec. A-1-4.7.1, p 13-72
Storage = Light Hazard Occupancies
Protection Area/Sprinkler :
From NFPA-13, Table 4-2.2, p 13-52
Ap = Protection Area/ Sprinkler
Ap = 225 ft2
Density/Area :
From NFPA-13, Figure 5-2.3 and Ordinary Hazard Occupancy Group 2
Density = 0.074 gpm/ft2
P10 = (Q10/k)2
P10 = (17/5.6)2
P10 = 9.2 psi
Saudconsult
Job No.: Sheet 1 of
Project : GES For Community Package - MEN'S CLUBHOUSE Date : April 03,2003
Subject : FIRE PROTECTION CALCULATION By : RTB
Ch'k. by :
Pa = 77 - 8 + 65 =134 psi
Conclusion :
For Fire Protection With Combined Sprinklers & Hose Cabinets, Approximate
Minimum Pressure Required At Sprinkler Riser Shall Be 134 psi .