AVERAGE ILLUMINANCE CALCULATION SHEET

PROJECT IDENTIFICATION : CHILDRENS ROOM


REQUIRED LUX : 150

LAMP DATA:
LIGHT SOURCE : 20W T8 FLUORESCENNT
NO.OF LAMP/FIXTURE :2
LUMENS/LAMP : (20)(80) = 1600
LENGTH OF THE ROOM :6m
WIDTH OF THE ROOM : 4.75 m
AREA : (6m)(4.75m) = 28.5㎡
CEILING HEIGHT :3m
MOUNTING HEIGHT : 3m - .85m = 2.15 m
AREA ATMOSPHERE : MEDIUM CLEAN

SELECTION OF COEFFICENT UTILIZATION

FIXTURE DESCRIPTION COEFFICIENT UTILIZATION SELECTION


Efficient fixture, large unit colored room 0.45
Average fixture, medium size room 0.35
Inefficient fixture, small or dark room 0.25

SELECTION OF MAINTENANCE FACTOR

FIXTURE DESCRIPTION MAINTENANCE FACTOR SELECTION


Enclosed fixture, clean room 0.80
Average condition 0.70
Open fixture or dirty room 0.60

UNIFORMITY OF LIGHTING

SYSTEM S/M = RATIO SELECTION


Direct Concentrating 0.40
Direct Spreading 1.20
Direct Indirect Diffusing 1.30
Semi – Direct - Indirect 1.50
CALCULATION

TOTAL NO. OF FIXTURES


N
( R EQUIRED LUX ) ( AREA )
¿
( LIGHT / FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTENACE FACTOR)
150(6 × 4.75)
N¿
2(1600)( 0.35)( 0.70)
4275
N¿
784
N ¿ 5.45
N≅6

SPACING OF FIXTURE

SWIDTH = MOUNTING HEIGHT × RATIO


SWIDTH ¿ 2.15 ×1. 20
SWIDTH ¿ 2.58m

S WIDTH
SBOTHENDS ¿
2
2.58
SBOTHENDS ¿
2
SBOTHENDS ¿ 1.29m

W
No. OF ROWS OF LAMPS ¿
S WIDTH
4.75
No. OF ROWS OF LAMPS ¿
2.58
No. OF ROWS OF LAMPS ¿ 1.84
No. OF ROWS OF LAMPS ≅ 2

TOTAL NO .OF FIXTURE


No. OF LAMPS PER ROW ¿
No. OF ROW
6
No. OF LAMPS PER ROW ¿
2
No. OF LAMPS PER ROW ¿ 3

L
SLENGTH ¿
No . OF LAMP/ROW
6
SLENGTH ¿
3
SLENGTH¿ 2m

SLENGTH
SBOTHENDS ¿
2
2
SBOTHENDS ¿
2
SBOTHENDS¿ 1m

ACTUAL ILLUMINANCE
ILLUMINANCE
( No .OF LAMP/ FIXTURE) ( No .OF FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTEN
¿
AREA
2(6)(1600)( 0.35)(0.70)
ILLUMINANCE ¿
6 × 4.75
4844
ILLUMINANCE ¿
28.5
ILLUMINANCE ¿ 169.98 lux
AVERAGE ILLUMINANCE CALCULATION SHEET

PROJECT IDENTIFICATION : NURSING AREA


REQUIRED LUX : 150

LAMP DATA:
LIGHT SOURCE : 20W T8 FLUORESCENNT
NO.OF LAMP/FIXTURE :2
LUMENS/LAMP : (20)(80) = 1600
LENGTH OF THE ROOM :6m
WIDTH OF THE ROOM : 3.75 m
AREA : (6m)(3.75m) = 22.5㎡
CEILING HEIGHT :3m
MOUNTING HEIGHT : 3m - .85m = 2.15 m
AREA ATMOSPHERE : MEDIUM CLEAN

SELECTION OF COEFFICENT UTILIZATION

FIXTURE DESCRIPTION COEFFICIENT UTILIZATION SELECTION


Efficient fixture, large unit colored room 0.45
Average fixture, medium size room 0.35
Inefficient fixture, small or dark room 0.25

SELECTION OF MAINTENANCE FACTOR

FIXTURE DESCRIPTION MAINTENANCE FACTOR SELECTION


Enclosed fixture, clean room 0.80
Average condition 0.70
Open fixture or dirty room 0.60

UNIFORMITY OF LIGHTING

SYSTEM S/M = RATIO SELECTION


Direct Concentrating 0.40
Direct Spreading 1.20
Direct Indirect Diffusing 1.30
Semi – Direct - Indirect 1.50
CALCULATION

TOTAL NO. OF FIXTURES

N
( R EQUIRED LUX ) ( AREA )
¿
( LIGHT / FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTENACE FACTOR)
150( 6 ×3.75)
N¿
2(1600)( 0.25)( 0.70)
3375
N¿
560
N ¿ 6.02
N≅6

SPACING OF FIXTURE

SWIDTH = MOUNTING HEIGHT × RATIO


SWIDTH ¿ 2.15 ×1. 20
SWIDTH ¿ 2.58m

S WIDTH
SBOTHENDS ¿
2
2.58
SBOTHENDS ¿
2
SBOTHENDS ¿ 1.29m

W
No. OF ROWS OF LAMPS ¿
S WIDTH
3.75
No. OF ROWS OF LAMPS ¿
2.58
No. OF ROWS OF LAMPS ¿ 1.45
No. OF ROWS OF LAMPS ≅ 2

TOTAL NO .OF FIXTURE


No. OF LAMPS PER ROW ¿
No. OF ROW
6
No. OF LAMPS PER ROW ¿
2
No. OF LAMPS PER ROW ¿ 3

L
SLENGTH ¿
No . OF LAMP/ROW
6
SLENGTH ¿
3
SLENGTH ¿ 2m

SLENGTH
SBOTHENDS ¿
2
2
SBOTHENDS ¿
2
¿
SBOTHENDS 1m

ACTUAL ILLUMINANCE
ILLUMINANCE
( No .OF LAMP/ FIXTURE) ( No .OF FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTEN
¿
AREA
2(6)(1600)(0.25)( 0.70)
ILLUMENANCE ¿
6 × 3.75
3360
ILLUMENANCE ¿
22.5
ILLUMINANCE ¿ 149.33 lux
AVERAGE ILLUMINANCE CALCULATION SHEET

PROJECT IDENTIFICATION : ADJUSTING ROOM 1


REQUIRED LUX : 250

LAMP DATA:
LIGHT SOURCE : 20W T8 FLUORESCENNT
NO.OF LAMP/FIXTURE :2
LUMENS/LAMP : (20)(80) = 1600
LENGTH OF THE ROOM : 8.25 m
WIDTH OF THE ROOM : 7.25 m
AREA : (8.25m)(7.25m) = 59.81㎡
CEILING HEIGHT :3m
MOUNTING HEIGHT : 3m - .85 = 2.15 m
AREA ATMOSPHERE : MEDIUM CLEAN

SELECTION OF COEFFICENT UTILIZATION

FIXTURE DESCRIPTION COEFFICIENT UTILIZATION SELECTION


Efficient fixture, large unit colored room 0.45
Average fixture, medium size room 0.35
Inefficient fixture, small or dark room 0.25

SELECTION OF MAINTENANCE FACTOR

FIXTURE DESCRIPTION MAINTENANCE FACTOR SELECTION


Enclosed fixture, clean room 0.80
Average condition 0.70
Open fixture or dirty room 0.60

UNIFORMITY OF LIGHTING

SYSTEM S/M = RATIO SELECTION


Direct Concentrating 0.40
Direct Spreading 1.20
Direct Indirect Diffusing 1.30
Semi – Direct - Indirect 1.50
CALCULATION

TOTAL NO. OF FIXTURES

N
( R EQUIRED LUX ) ( AREA )
¿
( LIGHT / FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTENACE FACTOR)
250 (8.25 ×7.25)
N¿
2(1600)( 0.35)( 0.70)
14953
N¿
784
N ¿ 19.07
N ≅ 18

SPACING OF FIXTURE

SWIDTH = MOUNTING HEIGHT × RATIO


SWIDTH ¿ 2.15 ×1. 20
SWIDTH ¿ 2.58m

S WIDTH
SBOTHENDS ¿
2
2.58
SBOTHENDS ¿
2
SBOTHENDS ¿ 1.29m

W
No. OF ROWS OF LAMPS ¿
S WIDTH
7.25
No. OF ROWS OF LAMPS ¿
2.58
No. OF ROWS OF LAMPS ¿ 2.81
No. OF ROWS OF LAMPS ≅ 3

TOTAL NO .OF FIXTURE


No. OF LAMPS PER ROW ¿
No. OF ROW
18
No. OF LAMPS PER ROW ¿
3
No. OF LAMPS PER ROW ¿ 6

L
SLENGTH ¿
No . OF LAMP/ROW
8.25
SLENGTH ¿
6
SLENGTH ¿ 1.3 7m

SLENGTH
SBOTHENDS ¿
2
1.37
SBOTHENDS ¿
2
¿
SBOTHEND 0.7m

ACTUAL ILLUMINANCE
ILLUMINANCE
( No .OF LAMP/ FIXTURE) ( No .OF FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTEN
¿
AREA

2(18)(1600)(0.35)(0.70)
ILLUMINANCE ¿
8.25 ×7.25
14122
ILLUMINANCE ¿
59.81
ILLUINANCE ¿ 235.95 lux
AVERAGE ILLUMINANCE CALCULATION SHEET

PROJECT IDENTIFICATION : ADJUSTING ROOM 2


REQUIRED LUX : 250

LAMP DATA:
LIGHT SOURCE : 20W T8 FLUORESCENNT
NO.OF LAMP/FIXTURE :2
LUMENS/LAMP : (20)(80) = 1600
LENGTH OF THE ROOM : 8.25 m
WIDTH OF THE ROOM : 7.25 m
AREA : (8.25m)(7.25m) = 59.81㎡
CEILING HEIGHT :3m
MOUNTING HEIGHT : 3m - .85 = 2.15 m
AREA ATMOSPHERE : MEDIUM CLEAN

SELECTION OF COEFFICENT UTILIZATION

FIXTURE DESCRIPTION COEFFICIENT UTILIZATION SELECTION


Efficient fixture, large unit colored room 0.45
Average fixture, medium size room 0.35
Inefficient fixture, small or dark room 0.25

SELECTION OF MAINTENANCE FACTOR

FIXTURE DESCRIPTION MAINTENANCE FACTOR SELECTION


Enclosed fixture, clean room 0.80
Average condition 0.70
Open fixture or dirty room 0.60

UNIFORMITY OF LIGHTING

SYSTEM S/M = RATIO SELECTION


Direct Concentrating 0.40
Direct Spreading 1.20
Direct Indirect Diffusing 1.30
Semi – Direct - Indirect 1.50
CALCULATION

TOTAL NO. OF FIXTURES


N
( R EQUIRED LUX ) ( AREA )
¿
( LIGHT / FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTENACE FACTOR)
250 (8.25 ×7.25)
N¿
2(1600)( 0.35)( 0.70)
14953
N¿
784
N ¿ 19.07
N ≅ 18

SPACING OF FIXTURE

SWIDTH = MOUNTING HEIGHT × RATIO


SWIDTH ¿ 2.15 ×1. 20
SWIDTH ¿ 2.58m

S WIDTH
SBOTHENDS ¿
2
2.58
SBOTHENDS ¿
2
SBOTHENDS ¿ 1.29m

W
No. OF ROWS OF LAMPS ¿
S WIDTH
7.25
No. OF ROWS OF LAMPS ¿
2.58
No. OF ROWS OF LAMPS ¿ 2.81
No. OF ROWS OF LAMPS ¿ 3

TOTAL NO .OF FIXTURE


No. OF LAMPS PER ROW ¿
No. OF ROW
18
No. OF LAMPS PER ROW ¿
3
No. OF LAMPS PER ROW ¿ 6

L
SLENGTH ¿
No . OF LAMP/ROW
8.25
SLENGTH ¿
6
SLENGTH ¿ 1.3 7m

SLENGTH
SBOTHENDS ¿
2
1.37
SBOTHENDS ¿
2
SBOTHENDS ¿ 0.7m

ACTUAL ILLUMINANCE
ILLUMINANCE
( No .OF LAMP/ FIXTURE) ( No .OF FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTEN
¿
AREA
2(18)(1600)(0.35)(0.70)
ILLUMINANCE ¿
8.25 ×7.25
14122
ILLUMINANCE ¿
59.81
ILLUINANCE ¿ 235.95 lux

AVERAGE ILLUMINANCE CALCULATION SHEET

PROJECT IDENTIFICATION : THERAPY ROOM


REQUIRED LUX : 250

LAMP DATA:
LIGHT SOURCE : 20W T8 FLUORESCENNT
NO.OF LAMP/FIXTURE :2
LUMENS/LAMP : (20)(80) = 1600
LENGTH OF THE ROOM : 21 m
WIDTH OF THE ROOM :8m
AREA : (21m)(8m) = 168㎡
CEILING HEIGHT :3m
MOUNTING HEIGHT : 3m - .85m = 2.15 m
AREA ATMOSPHERE : MEDIUM CLEAN

SELECTION OF COEFFICENT UTILIZATION

FIXTURE DESCRIPTION COEFFICIENT UTILIZATION SELECTION


Efficient fixture, large unit colored room 0.45
Average fixture, medium size room 0.35
Inefficient fixture, small or dark room 0.25

SELECTION OF MAINTENANCE FACTOR

FIXTURE DESCRIPTION MAINTENANCE FACTOR SELECTION


Enclosed fixture, clean room 0.80
Average condition 0.70
Open fixture or dirty room 0.60

UNIFORMITY OF LIGHTING

SYSTEM S/M = RATIO SELECTION


Direct Concentrating 0.40
Direct Spreading 1.20
Direct Indirect Diffusing 1.30
Semi – Direct - Indirect 1.50
CALCULATION

TOTAL NO. OF FIXTURES


N
( R EQUIRED LUX ) ( AREA )
¿
( LIGHT / FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTENACE FACTOR)
250 (21× 8)
N¿
2(1600)( 0.45)( 0.70)
42000
N¿
1008
N ¿ 41.66
N ≅ 42

SPACING OF FIXTURE

SWIDTH = MOUNTING HEIGHT × RATIO


SWIDTH ¿ 2.15 ×1. 20
SWIDTH ¿ 2.58

S WIDTH
SBOTHENDS ¿
2
2.58
SBOTHENDS ¿
2
SBOTHENDS ¿ 1.29

W
No. OF ROWS OF LAMPS ¿
S WIDTH
8
No. OF ROWS OF LAMPS ¿
2.58
No. OF ROWS OF LAMPS ¿ 3.10
No. OF ROWS OF LAMPS ≅ 3

TOTAL NO .OF FIXTURE


No. OF LAMPS PER ROW ¿
No. OF ROW
42
No. OF LAMPS PER ROW ¿
3
No. OF LAMPS PER ROW ¿ 14

L
SLENGTH ¿
No . OF LAMP/ROW
21
SLENGTH ¿
14
SLENGTH 1.5
¿
SLENGTH
SBOTHENDS ¿
2
1.5
SBOTHENDS ¿
2
SBOTHENDS .75
¿ 0

ACTUAL ILLUMINANCE

ILLUMINANCE
( No .OF LAMP/ FIXTURE) ( No .OF FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTEN
¿
AREA
2(42)(1600)(0.45)( 0.70)
ILLUMINANCE ¿
21 ×8
42336
ILLUMINANCE ¿
168
ILLUMINANCE ¿ 252 lux

AVERAGE ILLUMINANCE CALCULATION SHEET

PROJECT IDENTIFICATION : MECHANICAL/ELECTRICAL STORAGE


REQUIRED LUX : 250

LAMP DATA:
LIGHT SOURCE : 20W T8 FLUORESCENNT
NO.OF LAMP/FIXTURE :2
LUMENS/LAMP : (20)(80) = 1600
LENGTH OF THE ROOM : 10 m
WIDTH OF THE ROOM : 7.25 m
AREA : (10m)(7.25m) = 72.5㎡
CEILING HEIGHT :3m
MOUNTING HEIGHT : 2.15 m
AREA ATMOSPHERE : MEDIUM CLEAN

SELECTION OF COEFFICENT UTILIZATION

FIXTURE DESCRIPTION COEFFICIENT UTILIZATION SELECTION


Efficient fixture, large unit colored room 0.45
Average fixture, medium size room 0.35
Inefficient fixture, small or dark room 0.25

SELECTION OF MAINTENANCE FACTOR

FIXTURE DESCRIPTION MAINTENANCE FACTOR SELECTION


Enclosed fixture, clean room 0.80
Average condition 0.70
Open fixture or dirty room 0.60
UNIFORMITY OF LIGHTING

SYSTEM S/M = RATIO SELECTION


Direct Concentrating 0.40
Direct Spreading 1.20
Direct Indirect Diffusing 1.30
Semi – Direct - Indirect 1.50

CALCULATION

TOTAL NO. OF FIXTURES


N
( R EQUIRED LUX ) ( AREA )
¿
( LIGHT / FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTENACE FACTOR)
250 (10× 7.25)
N¿
2(1600)( 0.45)( 0.70)
18125
N¿
1008
N ¿ 17.98
N ≅ 18

SPACING OF FIXTURE

SWIDTH = MOUNTING HEIGHT × RATIO


SWIDTH ¿ 2.15 ×1. 20
SWIDTH ¿ 2.58m

S WIDTH
SBOTHENDS ¿
2
2.58
SBOTHENDS ¿
2
SBOTHENDS ¿ 1.29m

W
No. OF ROWS OF LAMPS ¿
S WIDTH
7.25
No. OF ROWS OF LAMPS ¿
2.58
No. OF ROWS OF LAMPS ¿ 2.81
No. OF ROWS OF LAMPS ≅ 3

TOTAL NO .OF FIXTURE


No. OF LAMPS PER ROW ¿
No. OF ROW
18
No. OF LAMPS PER ROW ¿
3
No. OF LAMPS PER ROW ¿ 6

L
SLENGTH ¿
No . OF LAMP/ROW
10
SLENGTH ¿
6
SLENGTH ¿ 1.6 6m

SLENGTH
SBOTHENDS ¿
2
1.67
SBOTHENDS ¿
2
SBOTHENDS¿0.83m

ACTUAL ILLUMINANCE

ILLUMINANCE
( No .OF LAMP/ FIXTURE) ( No .OF FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTEN
¿
AREA
2(18)( 1600)(0.45)(0.70)
ILLUMENANCE ¿
10 ×7.25
1844
ILLUMENANCE ¿
72.5
ILLUMINANCE ¿ 250.26 lux
AVERAGE ILLUMINANCE CALCULATION SHEET

PROJECT IDENTIFICATION : KITCHEN/EATERY


REQUIRED LUX : 250

LAMP DATA:
LIGHT SOURCE : 20W T8 FLUORESCENNT
NO.OF LAMP/FIXTURE :2
LUMENS/LAMP : (20)(80) = 1600
LENGTH OF THE ROOM : 10 m
WIDTH OF THE ROOM : 9.50 m
AREA : (10m)(9.50) = 95㎡
CEILING HEIGHT :3m
MOUNTING HEIGHT : 3m - .85m = 2.15 m
AREA ATMOSPHERE : MEDIUM CLEAN

SELECTION OF COEFFICENT UTILIZATION

FIXTURE DESCRIPTION COEFFICIENT UTILIZATION SELECTION


Efficient fixture, large unit colored room 0.45
Average fixture, medium size room 0.35
Inefficient fixture, small or dark room 0.25

SELECTION OF MAINTENANCE FACTOR

FIXTURE DESCRIPTION MAINTENANCE FACTOR SELECTION


Enclosed fixture, clean room 0.80
Average condition 0.70
Open fixture or dirty room 0.60

UNIFORMITY OF LIGHTING

SYSTEM S/M = RATIO SELECTION


Direct Concentrating 0.40
Direct Spreading 1.20
Direct Indirect Diffusing 1.30
Semi – Direct - Indirect 1.50
CALCULATION

TOTAL NO. OF FIXTURES


N
( R EQUIRED LUX ) ( AREA )
¿
( LIGHT / FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTENACE FACTOR)
250( 10× 9.50)
N¿
2(1600)( 0.45)( 0.70)
23750
N¿
1008
N ¿ 23.56
N ≅ 24

SPACING OF FIXTURE

SWIDTH = MOUNTING HEIGHT × RATIO


SWIDTH ¿ 2.15 ×1. 20
SWIDTH ¿ 2.58m

S WIDTH
SBOTHENDS ¿
2
2.58
SBOTHENDS ¿
2
SBOTHENDS ¿ 1.29m

W
No. OF ROWS OF LAMPS ¿
S WIDTH
9.50
No. OF ROWS OF LAMPS ¿
2.58
No. OF ROWS OF LAMPS ¿ 3.68
No. OF ROWS OF LAMPS ≅ 4

TOTAL NO .OF FIXTURE


No. OF LAMPS PER ROW ¿
No. OF ROW
24
No. OF LAMPS PER ROW ¿
4
No. OF LAMPS PER ROW ¿ 6

L
SLENGTH ¿
No . OF LAMP/ROW
10
SLENGTH ¿
6
SLENGTH ¿ 1.6 6m

SLENGTH
SBOTHENDS ¿
2
1.66
SBOTHENDS ¿
2
SBOTHENDS ¿ 0.8 3 m

ACTUAL ILLUMINANCE
ILLUMINANCE
( No .OF LAMP/ FIXTURE) ( No .OF FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTEN
¿
AREA
2(24)(1600)(0.45)(0.70)
ILLUMINANCE ¿
10 × 9.5
24916
ILLUMINANCE ¿
95
ILLUMINANCE ¿ 254.65 lux
AVERAGE ILLUMINANCE CALCULATION SHEET

PROJECT IDENTIFICATION : CORRIDOR


REQUIRED LUX : 150
LAMP DATA:
LIGHT SOURCE : 20W T8 FLUORESCENNT
NO.OF LAMP/FIXTURE :2
LUMENS/LAMP : (20)(80) = 1600
LENGTH OF THE ROOM : 10 m
WIDTH OF THE ROOM : 4.25 m
AREA : (10m)(4.25) = 42.5㎡
CEILING HEIGHT :3m
MOUNTING HEIGHT : 3m - .85m = 2.15 m
AREA ATMOSPHERE : MEDIUM CLEAN

SELECTION OF COEFFICENT UTILIZATION

FIXTURE DESCRIPTION COEFFICIENT UTILIZATION SELECTION


Efficient fixture, large unit colored room 0.45
Average fixture, medium size room 0.35
Inefficient fixture, small or dark room 0.25

SELECTION OF MAINTENANCE FACTOR

FIXTURE DESCRIPTION MAINTENANCE FACTOR SELECTION


Enclosed fixture, clean room 0.80
Average condition 0.70
Open fixture or dirty room 0.60

UNIFORMITY OF LIGHTING

SYSTEM S/M = RATIO SELECTION


Direct Concentrating 0.40
Direct Spreading 1.20
Direct Indirect Diffusing 1.30
Semi – Direct - Indirect 1.50
CALCULATION

TOTAL NO. OF FIXTURES


N
( R EQUIRED LUX ) ( AREA )
¿
( LIGHT / FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTENACE FACTOR)
150(10 × 4.25)
N¿
2(1600)( 0.35)( 0.70)
6375
N¿
784
N ¿ 8.13
N≅8

SPACING OF FIXTURE

SWIDTH = MOUNTING HEIGHT × RATIO


SWIDTH ¿ 2.15 ×1. 20
SWIDTH ¿ 2.58m

S WIDTH
SBOTHENDS ¿
2
2.58
SBOTHENDS ¿
2
SBOTHENDS ¿ 1.29m

W
No. OF ROWS OF LAMPS ¿
S WIDTH
4.25
No. OF ROWS OF LAMPS ¿
2.58
No. OF ROWS OF LAMPS ¿ 1.65
No. OF ROWS OF LAMPS ≅ 2

TOTAL NO .OF FIXTURE


No. OF LAMPS PER ROW ¿
No. OF ROW
21
No. OF LAMPS PER ROW ¿
3
No. OF LAMPS PER ROW ¿ 7

L
SLENGTH ¿
No . OF LAMP/ROW
8.25
SLENGTH ¿
7
SLENGTH ¿ 1.1 8m

SLENGTH
SBOTHENDS ¿
2
1.18
SBOTHENDS ¿
2
SBOTHENDS¿ 0.58m

ACTUAL ILLUMINANCE
ILLUMINANCE
( No .OF LAMP/ FIXTURE) ( No .OF FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTEN
¿
AREA
2(21)(1600)(0.35)(0.70)
ILLUMINANCE ¿
10 × 4.25
16464
ILLUMINANCE ¿
42.5
ILLUMINANCE ¿ 387.39 lux
AVERAGE ILLUMINANCE CALCULATION SHEET

PROJECT IDENTIFICATION : COMFORT ROOM 1


REQUIRED LUX : 150

LAMP DATA:
LIGHT SOURCE : 20W T8 FLUORESCENNT
NO.OF LAMP/FIXTURE :2
LUMENS/LAMP : (20)(80) = 1600
LENGTH OF THE ROOM : 6.5 m
WIDTH OF THE ROOM :5m
AREA : (6.5m)(5m) = 32.5㎡
CEILING HEIGHT :3m
MOUNTING HEIGHT : 3m - .85m = 2.15 m
AREA ATMOSPHERE : MEDIUM CLEAN

SELECTION OF COEFFICENT UTILIZATION

FIXTURE DESCRIPTION COEFFICIENT UTILIZATION SELECTION


Efficient fixture, large unit colored room 0.45
Average fixture, medium size room 0.35
Inefficient fixture, small or dark room 0.25

SELECTION OF MAINTENANCE FACTOR

FIXTURE DESCRIPTION MAINTENANCE FACTOR SELECTION


Enclosed fixture, clean room 0.80
Average condition 0.70
Open fixture or dirty room 0.60

UNIFORMITY OF LIGHTING

SYSTEM S/M = RATIO SELECTION


Direct Concentrating 0.40
Direct Spreading 1.20
Direct Indirect Diffusing 1.30
Semi – Direct - Indirect 1.50
CALCULATION

TOTAL NO. OF FIXTURES


N
( R EQUIRED LUX ) ( AREA )
¿
( LIGHT / FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTENACE FACTOR)
150( 6.5× 5)
N¿
2(1600)( 0.35)( 0.70)
4875
N¿
784
N ¿ 6.22
N≅6

SPACING OF FIXTURE

SWIDTH = MOUNTING HEIGHT × RATIO


SWIDTH ¿ 2.15 ×1. 20
SWIDTH ¿ 2.58m

S WIDTH
SBOTHENDS ¿
2
2.58
SBOTHENDS ¿
2
SBOTHENDS ¿ 1.29m

W
No. OF ROWS OF LAMPS ¿
S WIDTH
5
No. OF ROWS OF LAMPS ¿
2.58
No. OF ROWS OF LAMPS ¿1.94
No. OF ROWS OF LAMPS ≅ 2

TOTAL NO .OF FIXTURE


No. OF LAMPS PER ROW ¿
No. OF ROW
6
No. OF LAMPS PER ROW ¿
2
No. OF LAMPS PER ROW ¿ 3

L
SLENGTH ¿
No . OF LAMP/ROW
6.5
SLENGTH ¿
3
SLENGTH ¿ 2.17 m

SLENGTH
SBOTHENDS ¿
2
2.17
SBOTHENDS ¿
2
SBOTHENDS¿ 1.08m

ACTUAL ILLUMINANCE
ILLUMINANCE
( No .OF LAMP/ FIXTURE) ( No .OF FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTEN
¿
AREA
2(6)(1600)( 0.35)(0.70)
ILLUMINANCE ¿
6.5 ×5
4704
ILLUMINANCE ¿
32.5
ILLUMINANCE ¿ 144.74 lux
AVERAGE ILLUMINANCE CALCULATION SHEET

PROJECT IDENTIFICATION : COMFORT ROOM 2


REQUIRED LUX : 150

LAMP DATA:
LIGHT SOURCE : 20W T8 FLUORESCENNT
NO.OF LAMP/FIXTURE :2
LUMENS/LAMP : (20)(80) = 1600
LENGTH OF THE ROOM : 6.5 m
WIDTH OF THE ROOM :5m
AREA : (6.5m)(5m) = 32.5㎡
CEILING HEIGHT :3m
MOUNTING HEIGHT : 3m - .85m = 2.15 m
AREA ATMOSPHERE : MEDIUM CLEAN

SELECTION OF COEFFICENT UTILIZATION

FIXTURE DESCRIPTION COEFFICIENT UTILIZATION SELECTION


Efficient fixture, large unit colored room 0.45
Average fixture, medium size room 0.35
Inefficient fixture, small or dark room 0.25

SELECTION OF MAINTENANCE FACTOR

FIXTURE DESCRIPTION MAINTENANCE FACTOR SELECTION


Enclosed fixture, clean room 0.80
Average condition 0.70
Open fixture or dirty room 0.60

UNIFORMITY OF LIGHTING

SYSTEM S/M = RATIO SELECTION


Direct Concentrating 0.40
Direct Spreading 1.20
Direct Indirect Diffusing 1.30
Semi – Direct - Indirect 1.50
CALCULATION

TOTAL NO. OF FIXTURES


N
( R EQUIRED LUX ) ( AREA )
¿
( LIGHT / FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTENACE FACTOR)
150( 6.5× 5)
N¿
2(1600)( 0.35)( 0.70)
4875
N¿
784
N ¿ 6.22
N≅6

SPACING OF FIXTURE

SWIDTH = MOUNTING HEIGHT × RATIO


SWIDTH ¿ 2.15 ×1. 20
SWIDTH ¿ 2.58m

S WIDTH
SBOTHENDS ¿
2
2.58
SBOTHENDS ¿
2
SBOTHENDS ¿ 1.29m

W
No. OF ROWS OF LAMPS ¿
S WIDTH
5
No. OF ROWS OF LAMPS ¿
2.58
No. OF ROWS OF LAMPS ¿ 1.94
No. OF ROWS OF LAMPS ≅ 2

TOTAL NO .OF FIXTURE


No. OF LAMPS PER ROW ¿
No. OF ROW
6
No. OF LAMPS PER ROW ¿
2
No. OF LAMPS PER ROW ¿ 3

L
SLENGTH ¿
No . OF LAMP/ROW
6.5
SLENGTH ¿
3
SLENGTH ¿ 2.17 m

SLENGTH
SBOTHENDS ¿
2
2.17
SBOTHENDS ¿
2
SBOTHENDS¿1.08m

ACTUAL ILLUMINANCE
ILLUMINANCE
( No .OF LAMP/ FIXTURE) ( No .OF FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTEN
¿
AREA
2(6)(1600)( 0.35)(0.70)
ILLUMINANCE ¿
6.5 ×5
4704
ILLUMINANCE ¿
32.5
ILLUMINANCE ¿ 144.74 lux
AVERAGE ILLUMINANCE CALCULATION SHEET

PROJECT IDENTIFICATION : XRAY ROOM


REQUIRED LUX : 250

LAMP DATA:
LIGHT SOURCE : 20W T8 FLUORESCENNT
NO.OF LAMP/FIXTURE :2
LUMENS/LAMP : (20)(80) = 1600
LENGTH OF THE ROOM : 9.5 m
WIDTH OF THE ROOM : 6.5 m
AREA : (9.5m)(6.5m) = 61.75㎡
CEILING HEIGHT :3m
MOUNTING HEIGHT : 3m - .85 = 2.15 m
AREA ATMOSPHERE : MEDIUM CLEAN

SELECTION OF COEFFICENT UTILIZATION

FIXTURE DESCRIPTION COEFFICIENT UTILIZATION SELECTION


Efficient fixture, large unit colored room 0.45
Average fixture, medium size room 0.35
Inefficient fixture, small or dark room 0.25

SELECTION OF MAINTENANCE FACTOR

FIXTURE DESCRIPTION MAINTENANCE FACTOR SELECTION


Enclosed fixture, clean room 0.80
Average condition 0.70
Open fixture or dirty room 0.60

UNIFORMITY OF LIGHTING

SYSTEM S/M = RATIO SELECTION


Direct Concentrating 0.40
Direct Spreading 1.20
Direct Indirect Diffusing 1.30
Semi – Direct - Indirect 1.50
CALCULATION

TOTAL NO. OF FIXTURES


N
( R EQUIRED LUX ) ( AREA )
¿
( LIGHT / FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTENACE FACTOR)
250( 9.5× 6.5)
N¿
2(1600)( 0.35)( 0.70)
15437.5
N¿
784
N ¿ 19.69
N ≅ 18

SPACING OF FIXTURE

SWIDTH = MOUNTING HEIGHT × RATIO


SWIDTH ¿ 2.15 ×1. 20
SWIDTH ¿ 2.58m

S WIDTH
SBOTHENDS ¿
2
2.58
SBOTHENDS ¿
2
SBOTHENDS ¿ 1.29m

W
No. OF ROWS OF LAMPS ¿
S WIDTH
6.5
No. OF ROWS OF LAMPS ¿
2.58
No. OF ROWS OF LAMPS ¿2.51
No. OF ROWS OF LAMPS ≅ 3

TOTAL NO .OF FIXTURE


No. OF LAMPS PER ROW ¿
No. OF ROW
18
No. OF LAMPS PER ROW ¿
3
No. OF LAMPS PER ROW ¿ 6

L
SLENGTH ¿
No . OF LAMP/ROW
9.5
SLENGTH ¿
6
¿ 1.
SLENGTH 58m

SLENGTH
SBOTHENDS ¿
2
1.58
SBOTHENDS ¿
2
SBOTHENDS ¿ 0.79m

ACTUAL ILLUMINANCE
ILLUMINANCE
( No .OF LAMP/ FIXTURE) ( No .OF FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTEN
¿
AREA
2(18)(1600)(0.35)(0.70)
ILLUMINANCE ¿
9.5 ×6.5
14112
ILLUMINANCE ¿
61.75
ILLUMINANCE ¿ 228.53 lux
AVERAGE ILLUMINANCE CALCULATION SHEET

PROJECT IDENTIFICATION : DOCTOR OFFICE 1


REQUIRED LUX : 150

LAMP DATA:
LIGHT SOURCE : 20W T8 FLUORESCENNT
NO.OF LAMP/FIXTURE :2
LUMENS/LAMP : (20)(80) = 1600
LENGTH OF THE ROOM : 8.25 m
WIDTH OF THE ROOM : 6.5 m
AREA : (8.25m)(6.5m) = 53.62㎡
CEILING HEIGHT :3m
MOUNTING HEIGHT : 3m - .85m = 2.15 m
AREA ATMOSPHERE : MEDIUM CLEAN

SELECTION OF COEFFICENT UTILIZATION

FIXTURE DESCRIPTION COEFFICIENT UTILIZATION SELECTION


Efficient fixture, large unit colored room 0.45
Average fixture, medium size room 0.35
Inefficient fixture, small or dark room 0.25

SELECTION OF MAINTENANCE FACTOR

FIXTURE DESCRIPTION MAINTENANCE FACTOR SELECTION


Enclosed fixture, clean room 0.80
Average condition 0.70
Open fixture or dirty room 0.60

UNIFORMITY OF LIGHTING

SYSTEM S/M = RATIO SELECTION


Direct Concentrating 0.40
Direct Spreading 1.20
Direct Indirect Diffusing 1.30
Semi – Direct - Indirect 1.50
CALCULATION

TOTAL NO. OF FIXTURES


N
( R EQUIRED LUX ) ( AREA )
¿
( LIGHT / FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTENACE FACTOR)
150( 8.25× 6.5)
N¿
2(1600)( 0.35)( 0.70)
8043.75
N¿
784
N ¿ 10.25
N ≅ 10

SPACING OF FIXTURE

SWIDTH = MOUNTING HEIGHT × RATIO


SWIDTH ¿ 2.15 ×1. 20
SWIDTH ¿ 2.58m

S WIDTH
SBOTHENDS ¿
2
2.58
SBOTHENDS ¿
2
SBOTHENDS ¿ 1.29m

W
No. OF ROWS OF LAMPS ¿
S WIDTH
6.5
No. OF ROWS OF LAMPS ¿
2.58
No. OF ROWS OF LAMPS ¿ 2.52
No. OF ROWS OF LAMPS ≅ 2

TOTAL NO .OF FIXTURE


No. OF LAMPS PER ROW ¿
No. OF ROW
10
No. OF LAMPS PER ROW ¿
2
No. OF LAMPS PER ROW ¿ 5

L
SLENGTH ¿
No . OF LAMP/ROW
8.25
SLENGTH ¿
5
SLENGTH ¿1.65 m

SLENGTH
SBOTHENDS ¿
2
1.65
SBOTHENDS ¿
2
SBOTHENDS ¿0.82m

ACTUAL ILLUMINANCE
ILLUMINANCE
( No .OF LAMP/ FIXTURE) ( No .OF FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTEN
¿
AREA
2(10)(1600)(0.35)(0.70)
ILLUMINANCE ¿
8.25 ×6.5
7840
ILLUMINANCE ¿
53.62
ILLUMINANCE ¿ 146.21 lux
AVERAGE ILLUMINANCE CALCULATION SHEET

PROJECT IDENTIFICATION : DOCTOR OFFICE 2


REQUIRED LUX : 150

LAMP DATA:
LIGHT SOURCE : 20W T8 FLUORESCENNT
NO.OF LAMP/FIXTURE :2
LUMENS/LAMP : (20)(80) = 1600
LENGTH OF THE ROOM : 8.25 m
WIDTH OF THE ROOM : 6.5 m
AREA : (8.25m)(6.5m) = 53.62㎡
CEILING HEIGHT :3m
MOUNTING HEIGHT : 3m - .85m = 2.15 m
AREA ATMOSPHERE : MEDIUM CLEAN

SELECTION OF COEFFICENT UTILIZATION

FIXTURE DESCRIPTION COEFFICIENT UTILIZATION SELECTION


Efficient fixture, large unit colored room 0.45
Average fixture, medium size room 0.35
Inefficient fixture, small or dark room 0.25

SELECTION OF MAINTENANCE FACTOR

FIXTURE DESCRIPTION MAINTENANCE FACTOR SELECTION


Enclosed fixture, clean room 0.80
Average condition 0.70
Open fixture or dirty room 0.60

UNIFORMITY OF LIGHTING

SYSTEM S/M = RATIO SELECTION


Direct Concentrating 0.40
Direct Spreading 1.20
Direct Indirect Diffusing 1.30
Semi – Direct - Indirect 1.50
CALCULATION

TOTAL NO. OF FIXTURES


N
( R EQUIRED LUX ) ( AREA )
¿
( LIGHT / FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTENACE FACTOR)
150( 8.25× 6.5)
N¿
2(1600)( 0.35)( 0.70)
8043.75
N¿
784
N ¿ 10.25
N ≅ 10

SPACING OF FIXTURE

SWIDTH = MOUNTING HEIGHT × RATIO


SWIDTH ¿ 2.15 ×1. 20
SWIDTH ¿ 2.58m

S WIDTH
SBOTHENDS ¿
2
2.58
SBOTHENDS ¿
2
SBOTHENDS ¿ 1.29m

W
No. OF ROWS OF LAMPS ¿
S WIDTH
6.55
No. OF ROWS OF LAMPS ¿
2.58
No. OF ROWS OF LAMPS ¿ 2.52
No. OF ROWS OF LAMPS ≅ 2

TOTAL NO .OF FIXTURE


No. OF LAMPS PER ROW ¿
No. OF ROW
10
No. OF LAMPS PER ROW ¿
2
No. OF LAMPS PER ROW ¿ 5

L
SLENGTH ¿
No . OF LAMP/ROW
8.25
SLENGTH ¿
5
SLENGTH ¿ 1.65 m

SLENGTH
SBOTHENDS ¿
2
1.65
SBOTHENDS ¿
2
SBOTHENDS¿ 0.82m

ACTUAL ILLUMINANCE
ILLUMINANCE
( No .OF LAMP/ FIXTURE) ( No .OF FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTEN
¿
AREA
2(10)(1600)(0.35)(0.70)
ILLUMINANCE ¿
8.25 ×6.5
7840
ILLUMINANCE ¿
53.62
ILLUMINANCE ¿ 146.21 lux

AVERAGE ILLUMINANCE CALCULATION SHEET

PROJECT IDENTIFICATION : MANAGER ROOM


REQUIRED LUX : 150

LAMP DATA:
LIGHT SOURCE : 20W T8 FLUORESCENNT
NO.OF LAMP/FIXTURE :2
LUMENS/LAMP : (20)(80) = 1600
LENGTH OF THE ROOM :7m
WIDTH OF THE ROOM : 6.5 m
AREA : (7m)(6.5m) = 45.5㎡
CEILING HEIGHT :3m
MOUNTING HEIGHT : 3m - .85m = 2.15 m
AREA ATMOSPHERE : MEDIUM CLEAN

SELECTION OF COEFFICENT UTILIZATION

FIXTURE DESCRIPTION COEFFICIENT UTILIZATION SELECTION


Efficient fixture, large unit colored room 0.45
Average fixture, medium size room 0.35
Inefficient fixture, small or dark room 0.25

SELECTION OF MAINTENANCE FACTOR

FIXTURE DESCRIPTION MAINTENANCE FACTOR SELECTION


Enclosed fixture, clean room 0.80
Average condition 0.70
Open fixture or dirty room 0.60

UNIFORMITY OF LIGHTING

SYSTEM S/M = RATIO SELECTION


Direct Concentrating 0.40
Direct Spreading 1.20
Direct Indirect Diffusing 1.30
Semi – Direct - Indirect 1.50

CALCULATION

TOTAL NO. OF FIXTURES


N
( R EQUIRED LUX ) ( AREA )
¿
( LIGHT / FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTENACE FACTOR)
150( 7× 6.5)
N¿
2(1600)( 0.35)( 0.70)
6825
N¿
784
N ¿ 8.70
N≅8

SPACING OF FIXTURE

SWIDTH = MOUNTING HEIGHT × RATIO


SWIDTH ¿ 2.15 ×1. 20
SWIDTH ¿ 2.58m

S WIDTH
SBOTHENDS ¿
2
2.58
SBOTHENDS ¿
2
SBOTHENDS ¿ 1.29m

W
No. OF ROWS OF LAMPS ¿
S WIDTH
6.5
No. OF ROWS OF LAMPS ¿
2.58
No. OF ROWS OF LAMPS ¿ 2.52
No. OF ROWS OF LAMPS ≅ 2

TOTAL NO .OF FIXTURE


No. OF LAMPS PER ROW ¿
No. OF ROW
8
No. OF LAMPS PER ROW ¿
2
No. OF LAMPS PER ROW ¿ 4

L
SLENGTH ¿
No . OF LAMP/ROW
7
SLENGTH ¿
4
SLENGTH 1.75 m
¿
SLENGTH
SBOTHENDS ¿
2
1.75
SBOTHENDS ¿
2
SBOTHENDS ¿0.87m

ACTUAL ILLUMINANCE

ILLUMINANCE
( No .OF LAMP/ FIXTURE) ( No .OF FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTEN
¿
AREA
2(8)(1600)(0.35)( 0.70)
ILLUMINANCE ¿
7 × 6.5
6272
ILLUMINANCE ¿
45.5
ILLUMINANCE ¿ 144.18 lux
AVERAGE ILLUMINANCE CALCULATION SHEET

PROJECT IDENTIFICATION : WAITING AREA


REQUIRED LUX : 150

LAMP DATA:
LIGHT SOURCE : 20W T8 FLUORESCENNT
NO.OF LAMP/FIXTURE :2
LUMENS/LAMP : (20)(80) = 1600
LENGTH OF THE ROOM : 13.75 m
WIDTH OF THE ROOM : 12.5 m
AREA : (13.75m)(12.5m) = 171.87 ㎡
CEILING HEIGHT :3m
MOUNTING HEIGHT : 3m - .85 = 2.15 m
AREA ATMOSPHERE : MEDIUM CLEAN

SELECTION OF COEFFICENT UTILIZATION

FIXTURE DESCRIPTION COEFFICIENT UTILIZATION SELECTION


Efficient fixture, large unit colored room 0.45
Average fixture, medium size room 0.35
Inefficient fixture, small or dark room 0.25

SELECTION OF MAINTENANCE FACTOR

FIXTURE DESCRIPTION MAINTENANCE FACTOR SELECTION


Enclosed fixture, clean room 0.80
Average condition 0.70
Open fixture or dirty room 0.60

UNIFORMITY OF LIGHTING

SYSTEM S/M = RATIO SELECTION


Direct Concentrating 0.40
Direct Spreading 1.20
Direct Indirect Diffusing 1.30
Semi – Direct - Indirect 1.50
CALCULATION

TOTAL NO. OF FIXTURES


N
( R EQUIRED LUX ) ( AREA )
¿
( LIGHT / FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTENACE FACTOR)
150 (13.75× 12.5)
N¿
2(1600)( 0.45)( 0.70)
25782.25
N¿
1008
N ¿25.58
N ≅ 25

SPACING OF FIXTURE

SWIDTH = MOUNTING HEIGHT × RATIO


SWIDTH ¿ 2.15 ×1. 20
SWIDTH ¿ 2.58m

S WIDTH
SBOTHENDS ¿
2
2.58
SBOTHENDS ¿
2
SBOTHENDS ¿ 1.29m

W
No. OF ROWS OF LAMPS ¿
S WIDTH
12.5
No. OF ROWS OF LAMPS ¿
2.58
No. OF ROWS OF LAMPS ¿ 4.84
No. OF ROWS OF LAMPS ≅ 5

TOTAL NO .OF FIXTURE


No. OF LAMPS PER ROW ¿
No. OF ROW
25
No. OF LAMPS PER ROW ¿
5
No. OF LAMPS PER ROW ¿ 5

L
SLENGTH ¿
No . OF LAMP/ROW
13.75
SLENGTH ¿
5
SLENGTH ¿ 2. 75 m

SLENGTH
SBOTHENDS ¿
2
2.75
SBOTHENDS¿
2
SBOTHENDS ¿1.37m

ACTUAL ILLUMINANCE
ILLUMINANCE
( No .OF LAMP/ FIXTURE) ( No .OF FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTEN
¿
AREA
2(25)(1600)(0.45)( 0.70)
ILLUMINANCE ¿
13.75 ×12.5
25200
ILLUMINANCE ¿
171.87
ILLUMINANCE ¿ 146.62 lux
AVERAGE ILLUMINANCE CALCULATION SHEET

PROJECT IDENTIFICATION : FRONT DESK


REQUIRED LUX : 150

LAMP DATA:
LIGHT SOURCE : 20W T8 FLUORESCENNT
NO.OF LAMP/FIXTURE :2
LUMENS/LAMP : (20)(80) = 1600
LENGTH OF THE ROOM : 15 m
WIDTH OF THE ROOM : 12.5 m
AREA : (15m)(12.5m) = 187.5㎡
CEILING HEIGHT :3m
MOUNTING HEIGHT : 3m - .85m = 2.15 m
AREA ATMOSPHERE : MEDIUM CLEAN

SELECTION OF COEFFICENT UTILIZATION

FIXTURE DESCRIPTION COEFFICIENT UTILIZATION SELECTION


Efficient fixture, large unit colored room 0.45
Average fixture, medium size room 0.35
Inefficient fixture, small or dark room 0.25

SELECTION OF MAINTENANCE FACTOR

FIXTURE DESCRIPTION MAINTENANCE FACTOR SELECTION


Enclosed fixture, clean room 0.80
Average condition 0.70
Open fixture or dirty room 0.60

UNIFORMITY OF LIGHTING

SYSTEM S/M = RATIO SELECTION


Direct Concentrating 0.40
Direct Spreading 1.20
Direct Indirect Diffusing 1.30
Semi – Direct - Indirect 1.50
CALCULATION

TOTAL NO. OF FIXTURES


N
( R EQUIRED LUX ) ( AREA )
¿
( LIGHT / FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTENACE FACTOR)
150 (15× 12.5)
N¿
2(1600)( 0.45)( 0.70)
28125
N¿
1008
N ¿ 27.99
N ≅ 28

SPACING OF FIXTURE

SWIDTH = MOUNTING HEIGHT × RATIO


SWIDTH ¿ 2.15 ×1. 20
SWIDTH ¿ 2.58m

S WIDTH
SBOTHENDS ¿
2
2.58
SBOTHENDS ¿
2
SBOTHENDS ¿ 1.29m

W
No. OF ROWS OF LAMPS ¿
S WIDTH
12.5
No. OF ROWS OF LAMPS ¿
2.58
No. OF ROWS OF LAMPS ¿ 4.84
No. OF ROWS OF LAMPS ≅ 4

TOTAL NO .OF FIXTURE


No. OF LAMPS PER ROW ¿
No. OF ROW
28
No. OF LAMPS PER ROW ¿
4
No. OF LAMPS PER ROW ¿ 7

L
SLENGTH ¿
No . OF LAMP/ROW
15
SLENGTH ¿
7
SLENGTH ¿ 2. 14 m

SLENGTH
SBOTHENDS ¿
2
2.14
SBOTHENDS ¿
2
SBOTHENDS ¿1.08m

ACTUAL ILLUMINANCE
ILLUMINANCE
( No .OF LAMP/ FIXTURE) ( No .OF FIXTURE ) ( LUMENS /LAMP ) ( C OEFICIENT UTILIZATION ) ( M AINTEN
¿
AREA
2(28)(1600)(0.45)( 0.70)
ILLUMINANCE ¿
15 ×12.5
28224
ILLUMINANCE ¿
187.5
ILLUMINANCE ¿ 150.53 lux