THE BUREAU ASKS PERMISSION FROM THE CONGRESS TO MAKE ANY EDITORIAL CHANGES
SUCH AS RENUMBERING OF RULES WHEN PUBLISHING THE NEW FINA HANDBOOK.
Page 2 of 110
APPLICATIONS AND PROPOSALS FOR ALTERATION OF OR ADDITION TO THE
Annex 7 - Swimming
Page 3 of 110
FINA FACILITIES RULES – TABLE OF CONTENTS
(2020-11-09)
1
Page 4 of 110
FINA FACILITIES RULES – TABLE OF CONTENTS
FR 5.3 Equipment for Water Polo
FR 6 Artistic Swimming
FR 6.1 Artistic Swimming Facilities
FR 6.1 Artistic Swimming Facilities for Olympic Games and World Championships
FR 6.3 Automatic Officiating Equipment for Artistic Swimming
FR 6.4 Sound Equipment and Presentation Standards for Artistic Swimming
2
Page 5 of 110
SWIMMING FACILITIES RULES
(2020-11-09)
NOTE: The numbering of the new table of contents does not match with the current FINA FACILITIES RULES
FR 1 Swimming
FR 1.1 Swimming Facilities
FR 1.1.1 Length
FR 1.1.2 Dimensional Tolerances
FR 1.1.3 Width
FR 1.1.4 Depth
FR 1.1.5 Walls
FR 1.1.6 Lanes
FR 1.1.7 Lane Ropes
FR 1.1.8 Starting Platforms
FR 1.1.9 Numbering
FR 1.1.10 Backstroke Turn Indicators
FR 1.1.11 Backstroke Ledge
FR 1.1.12 False Start Rope
FR 1.1.13 Water Conditions
FR 1.1.14 Lighting
FR 1.1.15 Lane Markings
FR 1.1.16 Bulkheads
1
Page 6 of 110
SWIMMING FACILITIES RULES
FR 1.2.3 Width
FR 1.2.4 Depth
FR 1.2.5 Walls
FR 1.2.6 Lanes
FR 1.2.7 Lane Ropes
FR 1.2.8 Starting Platforms
FR 1.2.9 Numbering
FR 1.2.10 Backstroke Turn Indicators
FR 1.2.11 Backstroke Ledge
FR 1.2.12 False Start Rope
FR 1.2.13 Water Conditions
FR 1.2.14 Lighting
FR 1.2.15 Lane Markings
FR 1.2.16 Bulkheads
FR 1.2.17 Minimum distance separating the pools
2
Page 7 of 110
SWIMMING FACILITIES RULES
NOTE: The numbering of the below rules matches with the current FINA FACILITIES RULES 2017-2021
FR 2 SWIMMING POOLS
FR 2.1 Length
FR 2.1.1 FINA Facilities 50.000 metres. When touch panels of Automatic Officiating Equipment are used on the starting end, or additionally on the
Committee /
turning end, the pool must be of such length that ensures the required distance of 50.000 metres between the two panels.
FINA TSC
See Swimming Diagrams, Annex SW 1, SW 2, SW 3 and SW 4
FR 2.1.2 FINA Facilities 25.000 metres. When touch panels of Automatic Officiating Equipment are used on the starting end, or additionally on the
Committee /
turning end, the pool must be of such length that ensures the required distance of 25.000 metres between the two panels.
FINA TSC
See Swimming Diagrams, Annex SW 5, SW 6, SW 7, SW 8 and SW 9
For swimming pools with touch panels of Automatic Officiating Equipment on both ends the Wall to Wall
distance shall be: Minimum 50.020 metre / Maximum 50.030 metre.
Tolerances have to be consistent 0.300 metre above to 0.800 metre bellow the water surface.
These measurements should be certified by a surveyor or other qualified official, appointed or approved by the Member
in the country in which the pool is situated.
3
Page 8 of 110
SWIMMING FACILITIES RULES
The admissible tolerance in 25.00 m swimming pools will be +0.010, -0.000 metre when touch panels are installed.
For swimming pools with touch panels of Automatic Officiating Equipment on both ends the Wall to Wall distance
shall be: Minimum 25.020 metre / Maximum 25.030 metre.
For swimming pools with a touch panel of Automatic Officiating Equipment on one end the Wall to Wall distance
shall be: Minimum 25.010 metre / Maximum 25.020 metre.
Tolerances have to be consistent 0.300 metre above to 0.800 metre bellow the water surface.
These measurements should be certified by a surveyor or other qualified official, appointed or approved by the Member in
the country in which the pool is situated.
FR 2.4 Walls
FINA Facilities
FR 2.4.1 Committee / End walls shall be vertical, parallel and form 90 degree right angles to the swimming course and to the surface of the
FINA TSC water. They shall be constructed of solid material, with a non-slipslip-resistant surface extending 0.8 metre below the
water surface, so as to enable the competitor to touch and push off in turning without hazard.
FINA Facilities
FR 2.5 Committee / Lanes
FINA TSC
Lanes shall be at least 2.5 metres wide, with two spaces of at least 0.2 metre outside of the first and last lanes.
There is no minimum number of lanes. Lanes shall be at least 2.5 metres wide, first and last lane may be 2.4 metres wide
with 2 spaces of at least 0.1 metres wide outside of the first and the last lanes.
4
Page 9 of 110
SWIMMING FACILITIES RULES
FINA Facilities
FR 2.6.1 Committee / FR 2.6.1 The main function of a lane rope is not only to separate swimming lanes, but to reduce the pool waves. A lane
FINA TSC rope should have the properties to reduce the waves going through to the other side of rope or bouncing back into the
swimming lane.
In an 8 lane pool, lane Lane ropes shall extend the full length of the course and components not contributing to its wave
reduction function, such as tension spring and take‐up reel, shall measure less than 200mm each end of rope.
Lane rope should be secured at each end wall to anchor brackets recessed into the end walls. If anchor placement is on
pool deck, an extender, firm and non‐elastic, should be in place. The installed lane rope should stay in the pool water. The
anchor, including extender, shall not extend more than 10mm into the pool. The anchor shall not influence the length of
the lane rope by more than ±+‐ 10mm each end of rope.
The anchor shall be positioned so that the wave reducing components at each end wall of the pool shall be 50% below the
surface of the water. Anchors should be installed to withstand 20kN. Each lane rope will consist of wave reducing
components placed end‐to‐end having a minimum diameter of 0,150,10 metre. The design of discs and floats should be
so that the floats, by themselves, do not influence the length of the lane rope. A float should be an integral part in between
two discs. The lane rope length of the course shall have a negative buoyancy in such a way that at least one half to
maximum two thirds of the height of the wave reducing components should be beneath the water surface.
The take‐up reel of the lane rope should require a tool to lock tensioning into position and to prevent non‐authorized
tampering. The lane rope shall be equipped with a tension spring, absorbing sudden high point loads and a wire
withstanding a tensile force of 12kN.
In an 8 lane swimming pool, the colour of the lane ropes should be as follows:
• Two (2) GREEN ropes for lanes 1 and 8
• Four (4) BLUE ropes for lanes 2, 3, 6 and 7
• Three (3) YELLOW ropes for lanes 4 and 5
The components extending for a distance of 5.0 metres from each end of the pool shall be of RED colour.
There shall not be more than one lane rope between each lane. The lane ropes shall be firmly stretched and the tensions
should be 1‐1,2kN.
5
Page 10 of 110
SWIMMING FACILITIES RULES
FINA Facilities Moved to
FR 2.6.5 Committee / Lane marking measurements, please read in conjunction with FR 2.6.6.
FR2.14
FINA TSC See Swimming Diagram SW 1, SW 6, SW 7
FINA Facilities
FR 2.7 Committee / Starting Platforms
FINA TSC
Starting Platforms shall be firm and give no springing effect. The height of the platform above the water surface shall be
from 0.5 metre to 0.75 metre. The surface area shall be at least 0.5 metre x 0.5 metre and covered with a non-slipslip-
resistant material.
Maximum slope shall not be more than 10 degrees. The starting platform may have an adjustable setting back plate. The
platform shall be constructed so as to permit the gripping of the platform by the swimmer in the forward start at the front
and the sides; it is recommended that, if the thickness of the starting platform exceeds 0.04 metre, grips of at least 0.1
metre width on each side and 0.4 metre width in the front be cut out to 0.03 metre from the surface of the platform.
Handgrips for the forward start may be installed on the sides of the starting platforms. Handgrips for backstroke starts
shall be placed within 0.3 mete to 0.6 metre above the water surface both horizontally and vertically. They shall be parallel
to the surface of the end wall and must not protrude beyond the end wall.
A minimum depth of 1.35 metres, extending from 1.0 metre to at least 6.0 metres from the end wall is required for pools
with starting blocks. Electronic read‐out boards may be installed under the blocks. Flashing is not allowed. Figures must
not move during a backstroke start.
FINA Facilities
FR 2.11 Committee / False Start Rope
FINA TSC
False Start Rope may be suspended across the pool not less than 1.2 metres above the water level from fixed standards
placed 15.0 metres in front of the starting end. It shall be attached to the standards by a quick release mechanism. The
rope must effectively cover all lanes when activated.
6
Page 11 of 110
SWIMMING FACILITIES RULES
FINA Facilities
FR 2.12.2 Committee / Water Movement
FINA TSC
During competition, the water in the pool must be at a constant level, with no appreciable movement.
In order to keep the water level, preserve the transparency of water and take into consideration the health regulations in
force in most countries, inflow and outflow has to be regulated as follows:
In daily use, inflow and outflow has to follow the health regulation of each country.
At these turnover rates, the water distribution has to be such that no appreciable current or turbulence is created.
“Appreciable current” is defined as water movement that can move a floating basketball (filled with 6 literslitres of water to
obtain the right buoyancy) in one direction for more than 1,25m in 60 seconds.
The practical way to test this is to install two floating lines crosswise in a swim lane (to obtain a square with 2,5m size, ref.
Image 1) and then to leave the basketball in the central point of the square. If the ball does not touch any of the four lane
ropes within 60 seconds, the turbulence test is successful.
Test should be repeated in lanes 1,3,6,8 on two sides, at 5m from each headwall.
FINA Facilities
FR 2.12.3 Committee / Salinity of the water
FINA TSC
Worlds Records and World Junior Records can be established only in water with less than 3 gr/litre of salt.
7
Page 12 of 110
SWIMMING FACILITIES RULES
FINA Facilities
FR 2.14 Committee / Lane Markings
FINA TSC
Lane Markings shall be of a dark contrasting colour, placed on the floor of the pool in the centre of each lane.
Each lane line shall end 2.0* metres from the end wall of the pool with a distinctive cross line 1.0 metre long and of
the same width as the lane line. The distance between the centre points of each lane shall be 2.5 metres. *Pool
length tolerances must be considered.
Target lines shall be placed on the end walls or on the touch panels, in the centre of each lane, of the same width
as the lane lines. *Pool length tolerances must be considered.
They shall extend without interruption from the deck edge (curb), to the floor of the pool to a maximum of 3 metres.
A cross line 0.5 metre long shall be placed 0.3 metre below the water surface, measured to the centre point of the
cross line.
For 50m and 25m pools constructed after 1st January 2006, cross lines 0.5 metre long shall be placed at the 15
metre mark from each end of the pool. After October 2013 this shall be measured from the end wall to the centre
point of the cross line.
For swimming pools with bulkheads, lane markings shall be as shown on Swimming Diagrams, Annex SW 8 SW
4, SW 5.
8
Page 13 of 110
SWIMMING FACILITIES RULES
FINA Facilities NEW World Records Application
FR 2.(*) Committee /
FINA TSC For the Homologation of the Swimming World Records, the pools must have a valid Certificate (*) and fulfil the
requirements established in the following FR:
- FR 2.1 Length
- FR 2.2 Dimensional Tolerances
- FR 2.3 Depth
- FR 2.7 Starting Platforms
- FR 2.12.2 Water Movement
- FR 2.12.3 Salinity of water
- FR 2.14 Marking lanes
9
Page 14 of 110
SWIMMING FACILITIES RULES
SUBMITTED STATUS
RULE N° RULE
BY:
FINA Facilities
FR 3.(*) Committee / Length
FINA TSC
Length: 50.0 metres between the Automatic Officiating Equipment touch panels, except for the World Swimming
Championships (25m), which shall be 25.0 metres between the Automatic Officiating Equipment touch panels at the
starting end and the wall or touch panels at the turning end.
The admissible tolerance in 50.00 m swimming pools will be +0.010, -0.000 metre when touch panels are installed.
For swimming pools with touch panels of Automatic Officiating Equipment on both ends the Wall to Wall
distance shall be: Minimum 50.020 metre / Maximum 50.030 metre.
Tolerances have to be consistent 0.300 metre above to 0.800 metre bellow the water surface.
These measurements should be certified by a surveyor or other qualified official, appointed or approved by FINA.
The admissible tolerance in 25.00 m swimming pools will be +0.010, -0.000 metre when touch panels are installed.
10
Page 15 of 110
SWIMMING FACILITIES RULES
For swimming pools with touch panels of Automatic Officiating Equipment on both ends the Wall to Wall
distance shall be: Minimum 25.020 metre / Maximum 25.030 metre.
Tolerances have to be consistent 0.300 metre above to 0.800 metre bellow the water surface.
These measurements should be certified by a surveyor or other qualified official, appointed or approved by FINA.
FINA Facilities
FR 3.4 Committee / Walls: as in FR 2.4.1.
FINA TSC
11
Page 16 of 110
SWIMMING FACILITIES RULES
FR 3.7 Lanes
FINA Facilities
FR 3.(*).(*) Committee / Number of lanes:
FINA TSC
• 8 lanes for OLYMPIC GAMES
FINA Facilities
FR 3.7.2 Committee / World Championships. For permanent swimming pools, lanes from 1 to 8 shall be 2.5 metres wide and lanes 0 and 9
FINA TSC shall be 2.4 metres wide with 2 spaces 0.1 metres wide outside of lanes 0 and 9. There must be a lane rope separating
these spaces from lanes 0 and 9 for World Championships. See Diagrams: Annex SW 2, SW 4and SW8.
For temporary swimming pools, lanes shall be 2.5 metres wide with 2 spaces 0.5 metres wide outside of lanes 0 and 9.
There must be a lane rope a separating these spaces from lanes 0 and 9. See Diagrams: Annex SW 3, SW 5SW 3 and
SW 9
FR 3.(*).(*) The main function of a lane rope is not only to separate swimming lanes, but to reduce the pool waves. A lane rope
should have the properties to reduce the waves going through to the other side of rope or bouncing back into the
swimming lane.
In an 8 lane pool, lane Lane ropes shall extend the full length of the course and components not contributing to its wave
reduction function, such as tension spring and take‐up reel, shall measure less than 200mm each end of rope.
Lane rope should be secured at each end wall to anchor brackets recessed into the end walls. If anchor placement is on
pool deck, an extender, firm and non‐elastic, should be in place. The installed lane rope should stay in the pool water. The
anchor, including extender, shall not extend more than 10mm into the pool. The anchor shall not influence the length of
the lane rope by more than +‐ 10mm each end of rope.
The anchor shall be positioned so that the wave reducing components at each end wall of the pool shall be 50% below
the surface of the water. Anchors should be installed to withstand 20kN. Each lane rope will consist of wave reducing
components placed end‐to‐end having a minimum diameter of 0, 15 metre. The design of discs and floats should be so
that the floats, by themselves, do not influence the length of the lane rope. A float should be an integral part in between
12
Page 17 of 110
SWIMMING FACILITIES RULES
two discs. The lane rope length of the course shall have a negative buoyancy in such a way that at least one half to
maximum two thirds of the height of the wave reducing components should be beneath the water surface.
The take‐up reel of the lane rope should require a tool to lock tensioning into position and to prevent non‐ authorized
tampering. The lane rope shall be equipped with a tension spring, absorbing sudden high point loads and a wire
withstanding a tensile force of 12kN.
The components extending for a distance of 5.0 metres from each end of the pool shall be of RED colour.
There shall not be more than one lane rope between each lane. The lane ropes shall be firmly stretched and the tensions
should be 1‐1,2kN. See Swimming Diagram SW 1, SW 2, SW 3, SW8
OLYMPIC GAMES
In an 8 (eight) lanes swimming pool the colour of the lane ropes should be as follows:
• Two (2) GREEN ropes for lanes 1 and 8
• Four (4) BLUE ropes for lanes 2, 3, 6 and 7
• Three (3) YELLOW ropes for lanes 4 and 5
See Swimming Diagram, Annex SW 1
13
Page 18 of 110
SWIMMING FACILITIES RULES
WORLD CHAMPIONSHIPS
In a 10 (ten) lanes swimming pool the colour of the lane ropes should be as follows:
• Two (2) GREEN ropes for lanes 0 and 9
• Six (6) BLUE ropes for lanes 1, 2, 3, 6, 7 and 8
• Three (3) YELLOW ropes for lanes 4, 5
See Swimming Diagrams, Annex SW 2, SW 3, SW8, SW9
14
Page 19 of 110
SWIMMING FACILITIES RULES
FINA Facilities AS IN FR2
FR 3.9 Committee / Starting Platforms: as in FR 2.7.
FINA TSC
Except the surface area shall be at least 0.5 metres wide X 0.6 metres in length and covered with non-slip material. False
start control equipment must be installed.
Starting Platforms shall be firm and give no springing effect. The height of the platform above the water surface shall be
from 0.5 metre to 0.75 metre. The surface area shall be at least 0.5 metre x 0.6 metre and covered with a slip-resistant
material.
Maximum slope shall not be more than 10 degrees. The starting platform may have an adjustable setting back plate. The
platform shall be constructed so as to permit the gripping of the platform by the swimmer in the forward start at the front
and the sides; it is recommended that, if the thickness of the starting platform exceeds 0.04 metre, grips of at least 0.1
metre width on each side and 0.4 metre width in the front be cut out to 0.03 metre from the surface of the platform.
Handgrips for the forward start may be installed on the sides of the starting platforms. Handgrips for backstroke starts
shall be placed within 0.3 mete to 0.6 metre above the water surface both horizontally and vertically. They shall be parallel
to the surface of the end wall and must not protrude beyond the end wall.
A minimum depth of 1.35 metres, extending from 1.0 metre to at least 6.0 metres from the end wall is required for pools
with starting blocks. Electronic read‐out boards may be installed under the blocks. Flashing is not allowed. Figures must
not move during a backstroke start.
15
Page 20 of 110
SWIMMING FACILITIES RULES
Flagged ropes must be 1.8 metres above the water surface. Flags must be fixed to the ropes having the following
dimensions: 0.20m metres on the rope forming a triangle measuring 0.40 metres on the sides. The distance between each
flag must be 0.25metres. If the flags are printed with or support / carry any signage this must be approved in advance by
FINA
See Diagram
16
Page 21 of 110
SWIMMING FACILITIES RULES
FINA Facilities AS IN FR2
FR 3.13 Committee / False Start Rope: as in FR 2.11
FINA TSC
False Start Rope may be suspended across the pool not less than 1.2 metres above the water level from fixed standards
placed 15.0 metres in front of the starting end. It shall be attached to the standards by a quick release mechanism. The
rope must effectively cover all lanes when activated.
In order to keep the water level, preserve the transparency of water and take into consideration the health regulations in
force in most countries, inflow and outflow has to be regulated as follows:
In daily use, inflow and outflow has to follow the health regulation of each country.
At these turnover rates, the water distribution has to be such that no appreciable current or turbulence is created.
“Appreciable current” is defined as water movement that can move a floating basketball (filled with 6 litres of water to
obtain the right buoyancy) in one direction for more than 1,25m in 60 seconds.
The practical way to test this is to install two floating lines crosswise in a swim lane (to obtain a square with 2,5m size, ref.
Image 1) and then to leave the basketball in the central point of the square. If the ball does not touch any of the four lane
ropes within 60 seconds, the turbulence test is successful.
Test should be repeated in lanes 1,3,6,8 on two sides, at 5m from each headwall.
17
Page 22 of 110
SWIMMING FACILITIES RULES
FINA Facilities
FR 3.16 Committee / Lane Markings: as in FR 2.14. The distance between the centre points of each lane shall be 2.5 metres
FINA TSC
Lane Markings shall be of a dark contrasting colour, placed on the floor of the pool in the centre of each lane.
Target lines shall be placed on the end walls or on the touch panels, in the centre of each lane, of the same width as the
lane lines. They shall extend without interruption from the deck edge (curb), to the floor of the pool to a maximum of 3
metres. A cross line 0.5 metre long shall be placed 0.3 metre below the water surface, measured to the centre point of the
cross line.
For 50m and 25m pools constructed after 1 January 2006, cross lines 0.5 metre long shall be placed at the 15 metre mark
from each end of the pool. After October 2013 this shall be measured from the end wall to the centre point of the cross
line.
For swimming pools with bulkheads, lane markings shall be as shown on Swimming Diagrams, Annex SW 4 and SW 5.
18
Page 23 of 110
SWIMMING FACILITIES RULES
FINA Facilities AS IN FR2
FR 3.(*) Committee / Bulkheads
FINA TSC When a bulkhead serves as an end wall, it must extend the full width of the course and present a solid smooth, non-
slippery stable vertical surface on which touch pads may be mounted extending not less than 0.8m below and 0.3m above
the surface of the water, and must be free of hazardous openings above or below the waterline which may be penetrated
by a swimmer s hands, feet, toes or fingers. A bulkhead must be of a design that provides for the free movement of
officials along its length without such movement creating any appreciable current or water turbulence.
FINA Facilities
FR 3.17 Committee / Minimum distance separating the pools
FINA TSC
If the swimming pool and the diving well are in the same area the minimum distance separating the pools shall be 5.0
metres. For pools constructed from 1 January 2014 the minimum distance separating the pool shall be a minimum of 8
metres however 10 metres is preferred
19
Page 24 of 110
SWIMMING FACILITIES RULES
SUBMITTED STATUS
RULE N° RULE
BY:
FINA Facilities
FR 4.4.1 Committee / The minimum measurement of the touch panels shall be 2.4 metres wide and 0.9 metre high, and the thickness shall be
FINA TSC 0.01m when the contact is closed (and the time is stopped).
They shall extend 0.3 metre above and 0.6 metre below the surface of the water. The equipment in each lane shall be
electronically connected independently, so it may be controlled and maintained individually. The surface of the panels
shall be of a bright colour and shall bear the line markings approved for the end walls.
20
Page 25 of 110
SWIMMING FACILITIES RULES
FINA Facilities MOVED
FR 4.5.1 Committee / Semi-Automatic Equipment may be used as a backup to the Automatic Officiating Equipment at FINA or other major
FROM
FINA TSC events if there are three buttons per lane, each operated by a separate official (in which case other finish judges shall not
FR4.8
be required). An inspector of turns may operate one of the buttons
See diagram
21
Page 26 of 110
SWIMMING FACILITIES RULES
22
Page 27 of 110
APPLICATIONS AND PROPOSALS FOR ALTERATION OF OR ADDITION TO THE
Page 28 of 110
FACILITIES RULES 2021-2025
Lane Ropes
In a 8 (eight) lanes swimming pool the
colour of the lane ropes should be as
follows:
• Two (2) GREEN ropes for lanes 1
and 8.
• Four (4) BLUE ropes for lanes 2,
3, 6 and 7.
• Three (3) YELLOW ropes for lanes
4, 5.
Page 29 of 110
FACILITIES RULES 2021-2025
Lane Ropes
In a 10 (ten) lanes swimming pool the
colour of the lane ropes should be as
follows:
• Two (2) GREEN ropes for lanes 0
and 9.
• Six (6) BLUE ropes for lanes 1, 2,
3, 6, 7 and 8.
• Three (3) YELLOW ropes for lanes
4, 5.
Page 30 of 110
FACILITIES RULES 2021-2025
Lane Ropes
In a 10 (ten) lanes swimming pool the
colour of the lane ropes should be as
follows:
• Two (2) GREEN ropes for lanes 0
and 9.
• Six (6) BLUE ropes for lanes 1, 2,
3, 6, 7 and 8.
• Three (3) YELLOW ropes for lanes
4, 5.
Page 31 of 110
FACILITIES RULES 2021-2025
Lane Ropes
In a 10 (ten) lanes swimming pool the
colour of the lane ropes should be as
follows:
• Two (2) GREEN ropes for lanes 0
and 9.
• Six (6) BLUE ropes for lanes 1, 2,
3, 6, 7 and 8.
• Three (3) YELLOW ropes for lanes
4, 5.
Annex SW4 - Diagram Swimming Pool 50x25m with one Bulkhead - Bulkhead in lateral position
Page 32 of 110
FACILITIES RULES 2021-2025
Annex SW5 - Diagram Swimming Pool 50x25m with one Bulkhead - Bulkhead in central position
Page 33 of 110
FACILITIES RULES 2021-2025
Lane Ropes
In a 8 (eight) lanes swimming pool the
colour of the lane ropes should be as
follows:
• Two (2) GREEN ropes for lanes 1
and 8.
• Four (4) BLUE ropes for lanes 2,
3, 6 and 7.
• Three (3) YELLOW ropes for lanes
4, 5.
Page 34 of 110
FACILITIES RULES 2021-2025
Lane Ropes
In a 8 (eight) lanes swimming pool the
colour of the lane ropes should be as
follows:
• Two (2) GREEN ropes for lanes 1
and 8.
• Four (4) BLUE ropes for lanes 2,
3, 6 and 7.
• Three (3) YELLOW ropes for lanes
4, 5.
Page 35 of 110
FACILITIES RULES 2021-2025
Lane Ropes
In a 10 (ten) lanes swimming pool the
colour of the lane ropes should be as
follows:
• Two (2) GREEN ropes for lanes 0
and 9.
• Six (6) BLUE ropes for lanes 1, 2,
3, 6, 7 and 8.
• Three (3) YELLOW ropes for lanes
4, 5.
Page 36 of 110
FACILITIES RULES 2021-2025
Lane Ropes
In a 10 (ten) lanes swimming pool the
colour of the lane ropes should be as
follows:
• Two (2) GREEN ropes for lanes 0
and 9.
• Six (6) BLUE ropes for lanes 1, 2,
3, 6, 7 and 8.
• Three (3) YELLOW ropes for lanes
4, 5.
Page 37 of 110
FACILITIES RULES 2021-2025
Lane Markings
Page 38 of 110
FACILITIES RULES 2021-2025
Lane Markings
Page 39 of 110
APPLICATIONS AND PROPOSALS FOR ALTERATION OF OR ADDITION TO THE
Page 40 of 110
OPEN WATER SWIMMING FACILITIES RULES
(2021-02-09)
NOTE: The numbering of the new table of contents does not match with the current FINA FACILITIES RULES
1
Page 41 of 110
OPEN WATER SWIMMING FACILITIES RULES
NOTE: The numbering of the below rules matches with the current FINA FACILITIES RULES 2017-2021
FR XX.1.2 Finish
FR XX.1.2.1 FINA FC/ FINA Copied from The final approach to the finish shall be clearly defined with markers of a distinctive colour, and shall comprise the
TOWSC OWS 5.9
boundary of the course.
FR XX.1.2.2 FINA FC/ FINA Copied from The area leading to the finish apparatus should be clearly marked by rows of buoys which narrow as they get closer to the
TOWSC OWS 7.1
finish wall.
FR XX.1.2.3 FINA FC/ FINA Copied from The finish shall be clearly defined and marked by a vertical face.
TOWSC OWS 5.10
FR XX.1.2.4 FINA FC/ FINA Copied from The finish apparatus should, where possible, be a vertical wall at least 5 metres wide fixed if necessary to floatation
TOWSC OWS 7.2
devices, securely fastened in place so as not to be moved by wind, tide or the force of a swimmer striking the wall. The
finish should be filmed and recorded from each side and above by a video system with slow motion and recall facilities
including timing equipment.
FR XX.1.3.1 FINA FC/ FINA Copied from All turns/alterations of the course shall be clearly indicated. Directional Buoys which are alterations of the course shall be
TOWSC OWS 5.6
of a different colour to guidance buoys.
FR XX.1.3.2 FINA FC/ FINA Copied from A clearly marked craft or platform, containing a Turn Judge, shall be positioned at all alterations of course in such a
TOWSC OWS 5.7
manner as not to obstruct a swimmer's visibility of the turn.
2
Page 42 of 110
OPEN WATER SWIMMING FACILITIES RULES
FR XX.1.6.1 FINA FC/ FINA Copied from The course shall be in water that is subject to only minor currents or tide and may be salt or fresh water.
TOWSC OWS 5.2
FR XX.1.6.2 FINA FC/ FINA Copied from A certificate of suitability for use of the venue shall be issued by the appropriate local health and safety authorities. In
TOWSC OWS 5.3
general terms the certification must relate to water purity and to physical safety from other considerations.
FR XX.1.6.3 FINA FC/ FINA Copied from The minimum depth of water at any point on the course shall be 1.40 meter.
TOWSC OWS 5.4
FR XX.1.6.4 FINA FC/ FINA Copied from The water temperature should be a minimum of 16°C and a maximum of 31°C. It should be checked the day of the race, 2
TOWSC OWS 5.1
hours before the start, in the middle of the course at a depth of 40 cm. This control should be done in the presence of a
Commission made up of the following persons present: a Referee, a member of the Organising Committee and one coach
from the teams present designated during the Technical Meeting.
FR XX.3.1 FINA FC/ FINA Copied from When automatic Officiating Equipment is used for timing of competitions in accordance with rule SW 11, microchip
TOWSC OWS 7.2.1
transponder technology capable of providing split times is mandatory and should be added to the Equipment. Use of
microchip transponder technology is mandatory for competitions at the World Championships and Olympic Games.
Microchip transponder timing technology will be recorded officially in tenths of seconds.
3
Page 43 of 110
APPLICATIONS AND PROPOSALS FOR ALTERATION OF OR ADDITION TO THE
Page 44 of 110
FACILITIES RULES 2021-2025
5
2 6
1 5
4 Directional Buoy
8
6 4
5 Guidance Buoy
3
6 Turn Judge platform or craft
Water Conditions
1
• The course shall be in water that is subject to only minor
currents or tide and may be salt or fresh water.
• The minimum depth of water at any point on the course
shall be 1.40 meter
6 4 • The water temperature should be a minimum of 16°C and
a maximum of 31°C. It should be checked the day of the
race, 2 hours before the start, in the middle of the course
at a depth of 40 cm. This control should be done in the
presence of a Commission.
Page 45 of 110
FACILITIES RULES 2021-2025
4 9
16
14
17
10
12 13 17
11
1 5 16
6
7
15
3 8
1 Kayak - Left side of the pontoon 12 Boat - Swim Course Manager / Tracking Manager
2 Kayak - Right side of the pontoon 13 Boat - Medical 1 + 1 Driver + 1 Lifeguard + 1 NTO
3 Kayak - Right side of Turn 1 14 Boat - Swim Course Coordinator + 1 Driver + 1 Lifeguard
Page 46 of 110
FACILITIES RULES 2021-2025
Starting Platform
Entry
to the
Platform
Feeding Platform
Annex OWS3 - Diagram Open Water Swimming Facilities - Platforms and Buoys
Page 47 of 110
FACILITIES RULES 2021-2025
Finish Gate
Ladder
Stable pontoon
Ladder
Finish Line
Intermediate Gate
Intermediate Line
Page 48 of 110
FACILITIES RULES 2021-2025
Timing Room
11
1 2 3 4 5 6 7
8 9 10 10
Page 49 of 110
APPLICATIONS AND PROPOSALS FOR ALTERATION OF OR ADDITION TO THE
Annex 11 - Diving
Page 50 of 110
DIVING FACILITIES RULES
(2020-11-09)
NOTE: The numbering of the new table of contents does not match with the current FINA FACILITIES RULES
FR 3 Diving
FR 3.1 Diving Facilities
FR 3.1.1 Springboard Diving
FR 3.1.2 Platform Diving
FR 3.1.3 General Requirements
FR 3.1.4 Lighting
FR 3.1.5 Water Temperature
FR 3.1.6 Lane Markings
FR 3.1.7 Placement and seating of diving judges
FR 3.1.8 Dry Land Facilities
FR 3.2 Diving Facilities for Olympic Games and World Championships
FR 3.2.1 Springboard Diving
FR 3.2.2 Platform Diving
FR 3.2.3 General Requirements
FR 3.2.4 Lighting
FR 3.2.5 Water Temperature
FR 3.2.6 Lane Markings
FR 3.2.7 Placement and seating of diving judges
FR 3.2.8 Dry Land Facilities
FR 3.2.9 Field of Play
1
Page 51 of 110
DIVING FACILITIES RULES
FR 3.3 Automatic Officiating Equipment for Diving
FR 3.3.1 General Description
FR 3.3.2 Equipment requirements
2
Page 52 of 110
DIVING FACILITIES RULES
NOTE: The numbering of the below rules matches with the current FINA FACILITIES RULES 2017-2021
FR 5 DIVING FACILITIES
FR 5.1.6 FINA FC / The springboards should be placed on either one or both sides of the platform. For Synchronised Diving, it is
FINA TDC required that at least two springboards at the same height shall be placed side by side and no objects should
obstruct the visibility in any part of the dive between the divers.
See Diving Diagrams, Annex 2.1 & Annex 2.2 DV 1 and DV 2.
FR 5.1.7 FINA FC / The back and sides of 3m springboards shall be surrounded by handrails with a minimum clearance of 1.0
FINA TDC metres between vertical pairs. The minimum height shall be 1.0 metre, measured from the level of the
springboard, and they shall be with at least two horizontal crossbars placed outside the platform. A solid
transparent barrier is also permitted instead of a crossbar.
See Diagram: Annex DV 1
FR 5.2.3 FINA FC / The preferred thickness of the front edge of the platform shall be 0.2 metre but not exceeding 0.3 metre, and can be
FINA TDC vertical or inclined at an angle not greater than 10º to the vertical inside the plummet line. The front edge is to be
applied first and then the top surface.
FR 5.2.4 FINA FC / The surface and the front edge of the platform shall be covered throughout with a resilient slip-resistant
FINA TDC surfacematerial. The two surfaces shall be covered separately in order to achieve a clean 90° angle or as described
in FR 5.2.3. The front surface is to be applied first and then the top surface.
The platforms shall be covered in a slip-resistant material that shall have a tread pattern that provides sufficient
traction in wet and dry conditions such that the divers are prevented from slipping when performing dives in all
directions. The minimum thickness must be 6mm and the colour should give a contrast to the surrounding décor.
The material shall be easily cleaned to maintain the slip-resistant feature of the product.
3
Page 53 of 110
DIVING FACILITIES RULES
FR 5.2.5 FINA FC / Moved to The platforms shall be covered in a slip-resistant material that shall have a tread pattern that provides sufficient
FINA TDC FR5.2.4 traction in wet and dry conditions such that the divers are prevented from slipping when performing dives in all
directions. The minimum thickness must be 6mm (- 0 / + 1mm) and the colour should give a contrast to the
surrounding décor. The material shall be easily cleaned to maintain the antislip feature of the product. The
installation of the slip-resistant platform covering shall respect FINA Rule FR 5.2.4.
FR 5.2.10 FINA FC / It is preferable that a platform is not constructed directly under any other platform however in circumstance where
FINA TDC this cannot be avoided then you must refer to Diving Diagrams, Annex 1.1, 1.2, 2.1&2.2DV 1 and DV 2.
FR 5.3.1 FINA FC / For pools designed and constructed after 26th September 2013 the minimum dimensions in metres for diving
FINA TDC facilities as detailed on the Diving Facilities Diagram (Anne 1.2) Diving Diagram, Annex DV 1 and DV 2 shall
prevail, using, as a basic measuring point of reference, the plummet line, which is a vertical line extending through
the centre of the front edge of the springboard or platform. It is recommended that the preferred dimensions be used
for projects considered to have an important status.
FR 5.3.2 FINA FC / The dimensions C from plummet to adjacent plummet in the FINA Dimensions for Diving , Annex 1.2 Diving
FINA TDC Diagram, Annex DV 1 and DV 2 table apply to platforms with widths as detailed in FR 5.2.2. If platform widths
are increased then the dimensions B and C shall be increased by half the additional widths.
FR 5.3.(*) FINA FC / New With regard to dimensions for diving facilities a combination of preferred and minimum measurements found in the
FINA TDC Diving Diagram, DV 1 and DV 2 shall be used. However, measurements less than minimum are not acceptable.
FR 5.3.(*) FINA FC / New The vertical height from the plummet of the diving board and or springboard at rest to the water surface at rest and
FINA TDC before water sprays or bubbles are set in motion shall be specified in the Diving Facilities Dimensions table. These
measurements should be certified by a surveyor or other qualified officials, appointed or approved by or the member
of the country in which the pool is situated.
FR 5.3.7 FINA FC / Moved to The minimum illumination at a level of 1 metre above the water surface shall not be less than 600 lux.
FINA TDC Lighting
FR 5.3.8 FINA FC / Moved to Sources of natural and artificial illumination shall be provided with controls to prevent glare.
FINA TDC Lighting
4
Page 54 of 110
DIVING FACILITIES RULES
FR 5.3.9 FINA FC / Moved to The water temperature shall be not less than 26º Celsius.
FINA TDC Water
Temperature
FR 5.3.10 FINA FC / Pool walls shall be vertical and form 90 degree right angles to the surface of the water. They shall be constructed
FINA TDC of solid material, with a non‐slip slip-resistant surface.
The admissible tolerance in walls verticality will be ±0.3 degrees.
Rest ledges along the pool walls are permitted; they must be not less than 1.2 metres below the water surface, and
may be 0.1 metre to 0.15 metre wide. Only internal rest ledges are permitted
FR 5.3.12 FINA FC / Moved to For Diving Pools that will also be used for swimming.
FINA TDC Lane
Lane markings for Diving pools shall be of a dark contrasting colour, placed on the floor of the pool in the centre of
markings
each lane.
Width: minimum 0.2 metre, maximum 0.3 metre.
Length: 21.0 metres for 25 metre long pools.
Each lane line shall end 2.0 metres from the end wall of the pool with a distinctive cross line 1.0 metre long and of
the same width as the lane line.
Target line shall be placed on the end of the walls or on the touch panels, in the centre of each lane, of the same
width as the lane lines. A cross line 0.5 metre long shall be placed 0.3 metre below the water surface, measured to
the centre point of the cross line. They shall extend without interruption from the deck edge (curb) to the floor or to a
maximum of 3 metres.
FR.5.(*).1 FINA FC / NEW The minimum illumination at a level of 1 metre above the water surface shall not be less than 600 lux
FINA TDC
FR.5.(*).2 FINA FC / NEW Sources of natural and artificial illumination shall be provided with controls to prevent glare.
FINA TDC
5
Page 55 of 110
DIVING FACILITIES RULES
For Diving pools that will also be used for swimming, lane markings for Diving pools shall be of a dark
contrasting colour, placed on the floor of the pool in the centre of each lane. Width: minimum 0.2 metre,
maximum 0.3 metre.
Length: 21.0 metres for 25 metre long pools.
Each lane line shall end 2.0 metres from the end wall of the pool with a distinctive cross line 1.0 metre long and of
the same width as the lane line.
Target line shall be placed on the end of the walls or on the touch panels, in the centre of each lane, of the same
width as the lane lines. A cross line 0.5 metre long shall be placed 0.3 metre below the water surface, measured to
the centre point of the cross line. They shall extend without interruption from the deck edge (curb) to the floor or to
a maximum of 3 metres.
FR 5.3.13.1 FINA FC / The judges will be placed side by side in a in a straight line on each both sides of the springboard / platform diving
5.(*).1.1 FINA TDC pool by the Referee
FR 5.3.13.2 FINA FC / When seven (7) judges are officiating, four (4) will be on the side of the pool closest to where the springboard or
5.(*).1.2 FINA TDC platform event is being contested. When five (5) judges are officiating, (3) will be on the side of the pool closest
to where the springboard or platform event is being contested. seven (7) / five (5) judges are used, four (4) /
three (3) judges will be on the side closest to the competition.
Note: The Referee may decide to place the majority of judges (i.e. four (4) / three (3) as outlined above)
judgeson the side of the pool farthest from the competition springboard or platform event being contested if
reasonable to do so for logistical or situational purposes. depending of the local situation in the pool.
FR 5.3.13.3 FINA FC / No judge shall be seated behind inside or behind the direct line of the the front edge of the springboards or platforms.
5.(*).1.3 FINA TDC
FR 5.3.13.4 FINA FC / The numbering of the judge chairschairs used by judges will be numbered clockwise in consecutive order
5.(*).1.4 FINA TDC when facing the springboards / platforms.
FR 5.3.13.5 FINA FC / In the 1 metre springboard competitions, chairs suitable for use placed directly on poolside shall be used.
5.(*).1.5 FINA TDC
6
Page 56 of 110
DIVING FACILITIES RULES
FR5.3.13.6 FINA FC / In the 3 metre springboard competitions, the judges shall be seated at a height of not lower than two (2) metres
5.(*).1.6 FINA TDC above the water level.
FR 5.3.13.7 FINA FC / In the 10 metre platform competitions, the chairs from the 3m springboard competitions can may be used but if at
5.(*).1.7 FINA TDC all possible, the judges shall be seated at an even a higher level than two (2) metres.
FR 5.3.13.8 FINA FC / To assist the judges in the 3 metre springboard and 10 metre platform competitions, the judges chairs must be
5.(*).1.8 FINA TDC positioned as far back from the edge of the pool as is practical.
5.(*).1.9 FINA FC / The above recommendations are shown in Diving Diagram, Annex DV 3
FINA TDC
FR 5.3.14.1 FINA FC / Three (3) or/ two (2) execution judges will be placed on either both sides of the springboard / platform diving pool by
5.(*).2.1 FINA TDC the Referee.
FR 5.3.14.2 FINA FC / The chairs used by execution judges in a synchronised event will be numbered numbering of the execution judge
5.(*).2.2 FINA TDC chairs will be clockwise in consecutive order when facing the springboard / platform, namely for example E 1, E 2
and E 3 (or E 1, E 2) on the left side and E 4, E 5 and E 6 (or E 3, E 4) on the right side.
FR 5.3.14.3 FINA FC / In between the execution judges on either side of the pool, the The synchronised judges will be placed in a
5.(*).2.3 FINA TDC straight line in between the execution judges on both sides of the pool. All synchronised judges on both sides of
the pool must be placed at the same horizontal distance from the springboards or platforms (not side-to-side) but
will be positioned at different heights to ensure that no judge s view is obstructed.
FR 5.3.14.4 FINA FC / Three (3) synchronised judges will be on the side of the pool closest to where the springboard or/ platform
5.(*).2.4 FINA TDC competitionevent is being contested, and the other two (2) synchronised judges on the opposite side.
FR 5.3.14.5 FINA FC / The chairs used by synchronised judges in a synchronised event will be numbered clockwise in consecutive order
5.(*).2.5 FINA TDC when facing the springboard or platform. Numbering will start at S1 with lowest chair on the left side of the pool,
through to S5 for the highest chair on the right side of the pool. numbering of the synchronised judge chairs will start
on the left-hand side on the pool with the lowest chair being S 1, and the highest chair on the right-hand side of the
pool being S 5.
FR 5.3.14.6 FINA FC / In the synchronised competitions, the synchronised judges closest to the pool edge, shall ideally be seated at a
5.(*).2.6 FINA TDC height of not lower than 2.0 (two) metres above the water level.
7
Page 57 of 110
DIVING FACILITIES RULES
FR 5.3.14.7 FINA FC / The subsequent chair heights for the remaining synchronised judges (or additional execution judge) must increase
5.(*).2.7 FINA TDC no less than by at least 0.5 metre 50 cm per seat.
FR 5.3.14.8 FINA FC / There shall be no interference or movement by any person in front of the judge chairs during a competition event
5.(*).2.8 FINA TDC
FR 5.3.14.9 The above recommendations are shown in Diving Diagram, Annex DV 3 and DV 4
5.(*).2.9
8
Page 58 of 110
DIVING FACILITIES RULES
FR 6.1 FINA FC / MOVED General requirements: Dimensions in Metres for Diving Facilities as detailed in Diving Diagram, Annex 1.1 &
FINA TDC Annex 1.2 and Field of Pla for Ol mpic Games and World Championships: Diving Diagram, Annex 2.1 & Annex
2.2.
FR 6.1.1 FINA FC / MOVED For Olympic Games and World Championships FR 5 in total shall apply; however, the light intensity at the level of 1 metre
FINA TDC above the water surface shall not be less than 1500 lux
FR 6.2 FINA FC / MOVED With regard to dimensions for diving facilities a combination of preferred and minimum measurements found in the
FINA TDC FINA Dimensions for Diving Facilities, Annex 1.1 & Annex 1.2 table may be used. However, measurements less than
minimum are not acceptable and may not be used. If the swimming pool and diving well are in the same area, the
minimum distance separating the pools shall be of 8 metres, however 10 metres is preferred (see FR 3.16).
FR 6.2.1 FINA FC / MOVED The vertical height from the plummet of the diving board and or springboard at rest to the water surface at rest and before
FINA TDC water sprays or bubbles are set in motion shall be specified in the Diving Facilities Dimensions table. These
measurements should be certified by a surveyor or other qualified officials, appointed or approved by the member of the
country in which the pool is situated.
FR 6.3 FINA FC / MOVED Line markings for the diving well will consist of 3 lines running the width of the diving well 90 degree angle to the diver
FINA TDC facing forward on the springboard or platform. These lines shall be as follows:
Width: minimum 0.2 metre, maximum 0.3 metres
Length: 21.0 metre for 25 metre wide diving well
The distance between the centre points of each lane shall be 2.5 metres.
The centre of the first line shall be directly under the plummet of the 3 metre springboard. See Diving Diagram,
Annex 2.1 & Annex 2.2.
FR 6.4 FINA FC / MOVED The host facility must provide a trampoline with spotting equipment and a hot tub. It is preferred that there be two
FINA TDC trampolines and a dry land area with a springboard and a platform take-off into foam landing pits as detailed in Annex 3.1.
9
Page 59 of 110
DIVING FACILITIES RULES
FR 6.2 FINA FC / NEW Platform Diving
FINA TDC
For Olympic Games and World Championships FR 5.2 in total shall apply
10
Page 60 of 110
DIVING FACILITIES RULES
If the swimming pool and diving well are in the same area, the minimum distance separating the pools shall be of 8
metres, however 10 metres is preferred (see FR 3.17).
FR 7.2.1 FINA FC / NEW 7.2.1 Record judges awards by whole and half points
FINA TDC (MOVED)
FR 7.2.2 FINA FC / NEW 7.2.2 Be able to display all recorded and calculated information for each diver both before and after each dive.
FINA TDC (MOVED)
FR 7.2.3 FINA FC / NEW 7.2.3 Be able to display the scores for all divers before and after each dive
FINA TDC (MOVED)
FR 7.2.4 FINA FC / NEW 7.2.4 Be able to display the rank order and scores for all divers after each round of dives.
FINA TDC (MOVED)
FR 7.2.5 FINA FC / NEW 7.2.5 The equipment must provide each judge with an electronic judging device that will permit each judge to enter their
FINA TDC (MOVED) award and to see their award on a window on the device. After the referee has accepted the judges awards, all awards
shall be displayed on each electronic judging device.
FR 7.2.6 FINA FC / NEW 7.2.6Judges analysis is to be provided at the conclusion of each event or series
FINA TDC (MOVED)
FR 7.2.7 FINA FC / NEW 7.2.7The referee must be provided with a monitor on which he/ she will be able to view the awards of all the judges prior
FINA TDC (MOVED) to the awards then being displayed on the score board.
11
Page 61 of 110
DIVING FACILITIES RULES
FR 7.2.8 FINA FC / NEW 7.2.8There is a requirement for a print out of the following information;
FINA TDC (MOVED)
1. The draw for the diving order
2. A start list for each session or event
3. A ranking of dives at the end of each round
4. A ranking of dives at the end of each event
Judges awards and scores for each diver at the end of each session and event
12
Page 62 of 110
APPLICATIONS AND PROPOSALS FOR ALTERATION OF OR ADDITION TO THE
Page 63 of 110
FACILITIES RULES 2021-2025
F F F G
P10
P7.5 A D
J
P5
S3 S3 S3 P3
A/A
B C C C C C C C B A
P1 S1 S1
S3 S3 S3 S1 S1
A P1
A P3 A
A/A P7.5 P5
P10
B C C C C C C C B
D D D
Page 64 of 110
FACILITIES RULES 2021-2025
From plummet back to Designation A-1 A-3 A-1P A-3P A-5 A-7.5 A-10
pool wall platform edge for Minimum 2.22 2.22 0.75 1.25 1.25 1.25 1.50
Concrete Platform Preferred 2.22 2.22 0.75 1.25 1.25 1.25 1.50
A
From plummet back to pool Minimum 1.50 1.50
wall for Pedestals and
Preferred 1.83 1.83
Metal Stands
Clear Overhead Designation F-1 E-1 F-3 E-3 F-1P E-1P F-3P E-3P F-5 E-5 F-7.5 E-7.5 F-10 E-10
F behind and each Minimum 2.50 5.00 2.50 5.00 2.75 3.25 2.75 3.25 2.75 3.25 2.75 3.25 2.75 4.00
side of plummet Preferred 2.50 5.00 2.50 5.00 2.75 3.50 2.75 3.50 2.75 3.50 2.75 3.50 2.75 5.00
Designation G-1 E-1 G-3 E-3 G-1P E-1P G-3P E-3P G-5 E-5 G-7.5 E-7.5 G-10 E-10
Clear Overhead
G Minimum 5.00 5.00 5.00 5.00 5.00 3.25 5.00 3.25 5.00 3.25 5.00 3.25 6.00 4.00
ahead of plummet
Preferred 5.00 5.00 5.00 5.00 5.00 3.50 5.00 3.50 5.00 3.50 5.00 3.50 6.00 5.00
Designation H-1 H-3 H-1P H-3P H-5 H-7.5 H-10
Depth of Water
H Minimum 3.40 3.70 3.20 3.50 3.70 4.10 4.50
at plummet
Preferred 3.50 3.80 3.30 3.60 3.80 4.50 5.00
Distance and Depth Designation J-1 K-1 J-3 K-3 J-1P K-1P J-3P K-3P J-5 K-5 J-7.5 K-7.5 J-10 K-10
J
ahead of plummet Minimum 5.00 3.30 6.00 3.60 4.50 3.10 5.50 3.40 6.00 3.60 8.00 4.00 11.00 4.25
K
for all stands Preferred 5.00 3.40 6.00 3.70 4.50 3.20 5.50 3.50 6.00 3.70 8.00 4.40 11.00 4.75
Designation L-1 M-1 L-3 M-3 L-1P M-1P L-3P M-3P L-5 M-5 L-7.5 M-7.5 M-10 L-10
L Distance and Depth
Minimum 1.50 3.30 2.00 3.60 1.40 3.10 1.80 3.40 3.00 3.60 3.75 4.00 4.50 4.25
M each side of plummet
Preferred 2.00 3.40 2.50 3.70 1.90 3.20 2.30 3.50 3.50 3.70 4.50 4.40 5.25 4.75
N Maximum slope to reduce dimensions beyond full requirements for pool depth and ceiling height = 30 Degrees
Notes
• The minimum distance between adjacent platforms must be at least 0.25 metres.
• Dimensions B (plummet to pool wall at side) and C (plummet to adjacent plummet) apply to Platforms with widths as detailed in FR.5.2.2. If Platform
widths are increased then B and C shall be increased by half the additional width(s).
• The 10 Metre Platform must project 0.25 metres beyond any adjacent platform.
• All platforms must project 0.75 metres beyond any platform directly below.
• The leading edge of the concrete platforms for springboards must be at least constructed to be directly above the pool wall or beyond.
• FR 5.3.4 The end of 5, 3 and 1m platforms must not project beyond the ends of the 3 and 1m springboards when they are adjacent to each other.
Page 65 of 110
FACILITIES RULES 2021-2025
Showers
Hot Tub
S3 S3 S3 S1 S1
Coaches Area
Coaches Area
P1
P3
A P5 A
Plummet Line P7.5 P10 Plummet Line
2.50 2.50
Area - 1
Area - 2
Judges
Judges
Min
20.00
2.50 2.50
Secretary Table
Athletes Stand
Min 25.00
Photo Photo
Area Area
1m 1m
Individual diving Individual diving
Annex DV3 - Diagram Diving Field of Play for Olympic Games and World Championships
Page 66 of 110
FACILITIES RULES 2021-2025
K K
E
L
C D
D D C
1.20 0.70 0.60 Cross Section - C1
F E
01 05
Longitudinal Section - L1
E G
A M 02
07 07
03 Longitudinal Section - L2
C1
A B
C
Platform 01
D 05
L1 O P
Springboard
N
O P
C1
Page 67 of 110
FACILITIES RULES 2021-2025
E
E
A B A B
O O P
P
Section - S1 Section - S2
A B
C
S1
Platform
D O P
A B S2
Springboard M
N O P
A B
0.60 A B
1.24
0.60 0.60 0.60
Min 0.60
Section - S3 Floor recess
Springboard Landing
H
Pad
Page 68 of 110
FACILITIES RULES 2021-2025
Springboard Platform
Length 4.88 Varies
Diving Dry Land Facilities
Width 0.50 Varies
Design Guidelines
Height 1.24 Varies
Horizontal Vertical Horizontal Vertical
Designation A-1 A-PL
Use and installation guidelines for dry land
From plummet facilities with in ground and above ground
A Minimum 4.88 Varies
Back to Building Wall trampolines
Preferred 6.10
Designation B-1 B-PL Installation and use instructions for trampolines
From plummet to and related equipment, such as frame pads,
B Minimum 3.66 3.66
Building Wall at Ahead mats, end decks, and spotting systems, shall
Preferred be provided by the manufacturer and shall
Designation C-1 C-PL specify the minimum safe area dimensions
From plummet to required for each trampoline type and relating
C Minimum 1.83 1.83
Building Wall at Side their products to centre or edge of the
Preferred
trampoline.
Designation D-1 D-PL
From plummet to
D Minimum 2.00 2.00 Clearance (trampolines): users should refer
Adjacent Plummet
Preferred 2.40 2.40
clearance, which may vary depending upon
Designation E-1 E-PL the manufacturer, the size of the trampoline,
On plummet from
E Minimum 5.00 2.70 the type of bed in place, the type of spotting
Board to Ceiling
Preferred 6.40 6.40 system in place, if any, and other variables. In
any event, adequate space should be provided
Clear Overhead Designation F-1 F-1 F-PL F-PL
so that intended users and equipment* will not
F behind and each Minimum 2.50 4.50 1.50 2.70 come into contact with any obstacles during
side of plummet Preferred Varies 6.40 Varies 6.40 their anticipated use of the equipment.
Designation G-1 G-1 G-PL G-PL *i.e., bottoming out a trampoline or dry land
Clear Overhead diving board.
G Minimum 5.00 4.50 1.50 2.70
ahead of plummet
Preferred Varies 6.40 Varies 6.40 Clearance (platforms):
Designation H-1 H-PL apply to facilities used by FINA level
Width of Landing Pit
H Minimum 1.83 1.50
in front of plummet may be appropriate for junior or development
Preferred Varies Varies programs, so long as adequate space is
Designation J-1 J-PL provided so that intended users and equipment
Length of Landing Pit will not come into contact with any obstacle
J Minimum 3.66 1.50
in front of plummet during their anticipated use of the equipment.
Preferred Varies Varies
Designation K-1 K-PL
Angle of Spotting
K Minimum 30º 30º
Rig Ropes
Preferred 30º ± 30º ±
Page 69 of 110
FACILITIES RULES 2021-2025
Diving Board Landing Foam landing pads for Dry land diving boards are located in Minimum 2 Floor Width Length
2
Pads front of the diving boards Preferred 4 120 cm 1.50 m min. 1.50 m min.
Minimum 1
3 Trampolines
Preferred 3
7 Large Mirrors Should be placed on walls so divers can observer body movements while training on equipment.
9 Weight Lifting Equipment Combination of free weights and weight lifting machines.
Cardio Conditioning
10 Treadmills and stationary bicycles.
Equipment
* Please note: Foam crash mats may be stacked to a height of 120 cm for the foam landing pads, or Foam pits maybe used instead of landing pads.
Page 70 of 110
APPLICATIONS AND PROPOSALS FOR ALTERATION OF OR ADDITION TO THE
Page 71 of 110
WATER POLO FACILITIES RULES
(2020-11-09)
NOTE: The numbering of the new table of contents does not match with the current FINA FACILITIES RULES
1
Page 72 of 110
WATER POLO FACILITIES RULES
FR 5.3 Equipment for Water Polo
FR 5.3.1 Markings
FR 5.3.2 Referee platforms
FR 5.3.3 Goals
FR 5.3.4 Re-entry area
FR 5.3.5 Nets
FR 5.3.6 Secretariat table
FR 5.3.7 Automatic Officiating Equipment for Water Polo
FR 5.3.8 Requirements for VAR
2
Page 73 of 110
WATER POLO FACILITIES RULES
NOTE: The numbering of the below rules matches with the current FINA FACILITIES RULES 2017-2021
FR 7.1 FINA General requirements: Water Polo Dimensions and Equipment as detailed in Field of Play diagram. for Olympic
Facilities Games and World Championships.
Committee /
See Water Polo Diagram, Annex 5 WP 1
FINA TWPC
3
Page 74 of 110
WATER POLO FACILITIES RULES
FR 7.5 FINA FC / Moved Exception from FR 7.2 may be allowed on the discretion of the federation controlling the match.
FINA TWPC
FR 7.6 FINA FC / Moved The game secretariat shall be placed at a table behind the referees and at the same height
FINA TWPC
4
Page 75 of 110
WATER POLO FACILITIES RULES
5
Page 76 of 110
WATER POLO FACILITIES RULES
Lane rope should be secured at each wall to anchor brackets recessed into the walls. If anchor placement is on pool deck,
an extender, firm and non‐elastic, should be in place. The installed lane rope should stay in the pool water. The anchor,
including extender, shall not extend more than 10mm into the pool. The anchor shall not influence the length of the lane
rope by more than ± 10mm each end of rope.
Anchors should be installed to withstand 20kN. The lane rope shall be equipped with a tension spring, absorbing sudden
high point loads and a wire withstanding a tensile force of 12kN.
6
Page 77 of 110
WATER POLO FACILITIES RULES
7
Page 78 of 110
WATER POLO FACILITIES RULES
The inner sides of the goal posts must be 3.0 metre apart. The underside of the cross bar must be 0.9 metre above the
water surface.
FR 9.4 FINA FC / MOVED The inner sides of the goal posts must be 3.0 metre apart. The underside of the cross bar must be 0.9 metre above the
FINA TWPC water surface.
FR 9.5 FINA FC / REMOVED The underside of the crossbar must be 0.9 metre above the water surface when the water is 1.5 metre or more in depth,
FINA TWPC and 2.4 metre above the bottom of the pool when the depth of the water is less than 1.5 metre.
8
Page 79 of 110
WATER POLO FACILITIES RULES
FR 9.(*).2 FINA FC / NEW Server & Monitors
FINA TWPC
All cameras shall be connected to the server. Capacity of the server shall be that to keep in memory all games played for
the last 24 hours in HD quality, preferably with a memory of 4 TB.
Two high resolution monitors shall be connected to the server. One monitor should be available for support of the
technician and another one for the VAR official.
A jo stick or mo se m st be a ailable for se b the VAR official.
9
Page 80 of 110
APPLICATIONS AND PROPOSALS FOR ALTERATION OF OR ADDITION TO THE
Page 81 of 110
FACILITIES RULES 2021-2025
Official table
2.00 3.00 Min 8.00m - Max 18.00m (Men) 13.00m (Women) 3.00 2.00
0.30 1.00 1.00 0.30
1.08 1.08
2.00 2.00
Page 82 of 110
FACILITIES RULES 2021-2025
Min 1.00
1.08 1.08
2.00 2.00
Page 83 of 110
FACILITIES RULES 2021-2025
Cameras
1. Four cameras on the goal lines, two per goal. The location of the cameras should be at the edge of the pool or under referee’s catwalk
at about 1 m above the water level
2.
3.
Page 84 of 110
APPLICATIONS AND PROPOSALS FOR ALTERATION OF OR ADDITION TO THE
Page 85 of 110
ARTISTIC SWIMMING FACILITIES RULES
(2020-11-09)
NOTE: The numbering of the new table of contents does not match with the current FINA FACILITIES RULES
1
Page 86 of 110
ARTISTIC SWIMMING FACILITIES RULES
FR 6.3 Automatic Officiating Equipment for Artistic Swimming
FR 6.4 Sound Equipment and Presentation Standards for Artistic Swimming
2
Page 87 of 110
ARTISTIC SWIMMING FACILITIES RULES
NOTE: The numbering of the below rules matches with the current FINA FACILITIES RULES 2017-2021
FR 10.1 FINA Removed General requirements: Field of Play for Artistic Swimming in Olympic Games and World Championships as detailed
Facilities in: Artistic Swimming Diagram, Annex 6
Committee
(FC)/ FINA
TASC
FR 10.2.1 FINA FC/ Removed Delimit in width and length the field of play in the Solo and the Duet with two lanes (maximum width 16m length
FINA TASC 25m).
For the Solo and Duet competition, the field of play may be delimited in width and length
3
Page 88 of 110
ARTISTIC SWIMMING FACILITIES RULES
FR 10.4 FINA FC/ Moved to FR The areas for figure competition in FR 10.1 can occupy the same area of the pool as that used for routine
FINA TASC 10.1 competition.
FR 10.6 The water must be of sufficient clarity for the bottom of the pool to be visible.
FR 10.6.1
FR 10.7 FINA FC/ The water temperature shall not be less than 27° plus 1º minus 1º Centigrade.
FINA TASC
FR 10.6.2
4
Page 89 of 110
ARTISTIC SWIMMING FACILITIES RULES
FR 11.3 FINA FC/ Moved to The light intensity shall not be less than 1500 lux
FINA TASC FR 11.6
FR 11.5.1 FINA FC/ The water must be of sufficient clarity for the bottom of the pool to be visible.
FINA TASC
5
Page 90 of 110
ARTISTIC SWIMMING FACILITIES RULES
FR 11.5.2 FINA FC/ The water temperature shall not be less than 27° Centigrade.
FINA TASC
6
Page 91 of 110
ARTISTIC SWIMMING FACILITIES RULES
FR 12.5 A dge e a a e ba ed e ec ded e (FR 13.2). The FINA TASC approved evaluation programme
is required.
7
Page 92 of 110
APPLICATIONS AND PROPOSALS FOR ALTERATION OF OR ADDITION TO THE
Page 93 of 110
FACILITIES RULES 2021-2025
2.50
2.50
2.50
2.50
2.50
2.50
Min 4.00 Min 30.00
Max 2.00
Annex AS1 - Diagram Artistic Swimming Field of Play for Olympic Games and World Championships
Page 94 of 110
FACILITIES RULES 2021-2025
Annex AS2 - Diagram Artistic Swimming Field of Play for Olympic Games and World Championships
Page 95 of 110
APPLICATIONS AND PROPOSALS FOR ALTERATION OF OR ADDITION TO THE
Page 96 of 110
HIGH DIVING FACILITIES RULES
(2020_11_09)
NOTE: The numbering of the new table of contents does not match with the current FINA FACILITIES RULES
1
Page 97 of 110
HIGH DIVING FACILITIES RULES
NOTE: The numbering of the below rules matches with the current FINA FACILITIES RULES 2017-2021
FR 14 HIGH DIVING
General FINA FINA High Diving can be is preferably performed in controlled environments with customised from fabricated
requirements Facilities diving towers in conjunction with fabricated pools. , platforms on existing buildings or platforms on natural rocks
and Committee / (cliffs) into open water (sea, lake, river) or in Rectangular dimensions are the preferred option for or permanent
definitions: FINA THDC artificial pools. Temporary round pools can be used in special circumstances.
Permanent artificial pools are preferable square, temporary artificial pools are normally round.
High Diving can also be performed from fabricated platforms on existing buildings or natural cliff faces into open
water (sea, lakes or rivers etc). Special permission and guidance is required from FINA under these
circumstances.
Dimensions in metres for all high diving facilities as detailed in High Diving Facilities Table Diagram, HD 1 2 and HD 2 4,
shall be observed. The HD 1, HD 2, HD 3, and HD 4 and HD 5 are established by the FINA Facilities Committee in
cooperation with the FINA Technical High Diving Committee and approved by the FINA Bureau.
In special surroundings the dimensions and requirements can be adjusted to the local situation upon recommendation by
the FINA Facilities Committee and the FINA THDC and approved by the FINA Bureau.
Security: The dimensions of these facilities are only for the use of expert athletes and they are not suitable for public use.
It is required by the local organising committees and local authorities to provide security guards and / or lockable
structures or gates to prevent any unauthorised persons to climb the diving towers.
2
Page 98 of 110
HIGH DIVING FACILITIES RULES
15 m (11 m – 19 m) 2.00 m (1.50 m *) 5.00 m (2.0 m *)
20 m 2.00 m 5.00 m
27 m 2.00 m 5.00 m
* Accepted for events other than FINA World Championships and World Cups
FR 14.1.2 3 FINA FC / The preferred thickness of the front edge of the platform shall not exceeding 0.16 0.20 metre and can be vertical or
FINA THDC inclined at an angle not greater than 10° to the vertical inside the plummet line.
FR 14.1.3 4 FINA FC / The entire surface of all platforms shall be covered with slip-resistant material that shall have a tread pattern that
FINA THDC provides sufficient traction in wet and dry conditions such that the divers are prevented from slipping when performing
dives in all directions.
FR 14.1.4.1 FINA FC / NEW If an unknown surface material is proposed, a physical sample must be sent to the FINA THDC for testing and
FINA THDC approval before it can be used.
FR 14.1.4.2 FINA FC / NEW Terracotta is the preferred colour of the platform surface material. Black, white and blue coloured surface
FINA THDC material is not permitted.
FR 14.1.4.3 FINA FC / NEW The colour of the carpet on the pool deck must not be blue. Grey is the preferred option.
FINA THDC
FR 14.1.4 5 FINA FC / The back and sides of each platform shall be surrounded by handrails up to 1m from the edge of the platform with a
FINA THDC minimum clearance of 1.8 metres between vertical pairs. The minimum height shall be 1.0 metre and they shall be with at
least two horizontal crossbars placed outside the platform beginning 1.00 metre from the front edge of the platform.
FR 14.1.5 6 FINA FC / Each platform shall be accessible by suitable slip- e i a ai ( ladde ) a e i ed b he c b ildi g
FINA THDC regulations and or health and safety standards that are applicable.
FR 14.1.6 7 FINA FC / It is preferable that a platform is not constructed directly under any other platform however in circumstances where this
FINA THDC cannot be avoided (example: artificial pools) then the dimensions in High Diving Table Diagram, HD 2 must be observed.
FR 14.1.7 8 FINA FC / The platform shall be a concrete, steel or other rigid material construction as approved by FINA. The longitude and
FINA THDC latitude movement/oscillation allowance for the entire 27 metres high tower structure shall be 2.7 cm (1/1000 from 27m).
The maximum wind speed for the tower oscillation stability is 54km/hour (banners will affect the stability). The downward
flex at the diving end of the platform shall not exceed 2-3mm and approved by the local authority of the area.
3
Page 99 of 110
HIGH DIVING FACILITIES RULES
FR 14.2 General Requirements
FR 14.2.1 FINA FC / For High Diving platforms designed and constructed after 31st t December 2017 the minimum dimensions in metres for
FINA THDC high di i g facili ie a de ailed he High Di i g Facili ie Table Diagram (HD 1 2 and HD 2 4) shall prevail, using, as
a basic measuring point of reference, the plummet line, which is a vertical line extending through the centre of the front
edge of the platforms.
FR 14.2.6 FINA FC / If the average wind speed exceeds 40kphm per hour then the Referee shall decide if the competition can continue or
FINA THDC must be interrupted until the average wind speed is below 40kphm. A transportable air speed indicator must be available
for use on the 20m and 27m platforms.
If lightning strikes are within 3km of the dive site then the training or the competition must be suspended until the storm
distance is greater than 3km. If lighting is within 3km of the site then the competition is to be postponed until the lighting
subsides or moves away from the venue.
FR 14.4.1 FINA FC / The judges shall be placed side by side in two lines on one side of the platform with the sunlight in the back or above the
FINA THDC judges. In indoor facilities and special circumstances the Referee may decide that the judges are placed on both
sides of the platforms.
FR 14.4.3 FINA FC / The judges shall be seated at a distance of not less than 30 approximately 35 meters and not more than 40 meters
FINA THDC from the entry point of the platforms for the 27m platform and approximately 30 meters for the 20m platform but not
more than 40 meters for both women`s and men`s platform, and in a position elevated approximately between three (3)
and six (6) meters above the water level. Special local circumstances may influence the position of the judges.
FR 14.6.1 FINA FC / NEW For the safety, practice and development of high divers and competitions, it is strongly recommended that the
FINA THDC guidelines presented below be incorporated into the facility and placed adjacent to the competitive high diving
area / facilities.
4
Page 100 of 110
HIGH DIVING FACILITIES RULES
FR 14.6.2 FINA FC / NEW Recommended equipment in dry land area
FINA THDC
- 1 x Trampoline, Olympic standard, length 5.2 m, width 3.05 m, height 1.15 m
- 4 x Foam Crash Mats, minimum length 1.4 m, width 1.0 m, height 0.25 m
- 2 x Somersault Boxes, minimum length 1.0 m, width 1.0 m, height 0.3 m
- 25 x Exercise mats, length 1.8 m, width 0.5 m, height 0.02 m
- 5 x Spinning Bikes
Black = existing wording / red = scratch / blue = new rules / new wording
Annexes HD 1 - 5
5
Page 101 of 110
APPLICATIONS AND PROPOSALS FOR ALTERATION OF OR ADDITION TO THE
F F F G
E E
P27 P27
P21-26 P21-26
P20 P20
P10 P10
P7.5 P7.5
P5 P5
P3 P3
A/A
B C C C B A D
L L J
Min 1.8m
M H H M H H K
30° 30°
FINA PLATFORM
Dimensions for High Diving Facilities P3 P5 P7.5 P10 P15 (P11-19) 5) P20 (P21-26) P27
3) 5.00 5.00 5.00 5.00 5.00 5.00 5.00
Length Minimum 5.00
Width Minimum 3) 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00
3.00 5.00 7.50 10.00 15.00 20.00 21.00 - 26.00 27.00
Height
Tolerance 4) + 0.05 / - 0.05 + 0.05 / - 0.05 + 0.05 / - 0.05 + 0.05 / - 0.05 + 0.05 / - 0.05 + 0.05 / - 0.05 + 0.05 / - 0.05 + 0.05 / - 0.05
Horiz Vert Horiz Vert Horiz Vert Horiz Vert Horiz Vert Horiz Vert Horiz Vert Horiz Vert
From plummet Designation A-P3 A-P5 A-P7.5 A-P10 A-P15 A-P20 A-(P21-26) A-P27
A
BACK TO POOL WALL or OBSTACLE Minimum 1.25 1.25 1.25 1.50 1.75 2.00 2.00 2.00
From plummet BACK TO PLATFORM Designation A/A-P5 A/A-P7.5 A/A-P10 A/A-P15 A/A-P20 A/A-(P21-26) A/A-P27
A/A
plummet directly below Minimum 1.00 1.00 1.00 1.00 1.00 1.00 1.00
From plummet to Designation B-P3 B-P5 B-P7.5 B-P10 B-P15 B-P20 B-(P21-26) B-P27
B
POOL WALL or OBSTACLE AT SIDE Minimum 3.50 3.75 4.50 5.50 5.50 6.00 6.50 7.00
From plummet to Designation C-P3 C-P5 C-P7.5 C-P10 C-P15 C-P20 C-(P21-26) C-P27
C
ADJACENT PLUMMET 1) Minimum 2.50 2.50 2.50 2.50 2.50 2.50 2.50 2.50
From plummet to Designation D-P3 D-P5 D-P7.5 D-P10 D-P15 D-P20 D-(P21-26) D-P27
D
POOL WALL or OBSTACLE AHEAD Minimum 9.50 10.25 11.00 13.50 14.00 14.00 15.00 15.00
On plummet, from PLATFORM TO Designation E-P3 E-P5 E-P7.5 E-P10 E-P15 E-P20 E-(P21-26) E-P27
E
CEILING / PLATFORM ABOVE Minimum 4.00 4.00 4.00 4.00 4.00 4.00 4.00 4.00
Clear Overhead BEHIND AND EACH SIDE Designation F-P3 E-P3 F-P5 E-P5 F-P7.5 E-P7.5 F-P10 E-P10 F-P15 E-P15 F-P20 E-P20 F-(P21-26) E-(P21-26) F-P27 E-P27
F
of plummet Minimum 2.75 3.50 2.75 4.00 2.75 4.00 2.75 4.00 2.75 4.00 2.75 4.00 2.75 4.00 2.75 4.00
Designation G-P3 E-P3 G-P5 E-P5 G-P7.5 E-P7.5 G-P10 E-P10 G-P15 E-P15 G-P20 E-P20 G-(P21-26) E-(P21-26) G-P27 E-P27
G Clear Overhead AHEAD of plummet
Minimum 5.00 4.00 5.00 4.00 5.00 4.00 6.00 4.00 6.00 4.00 6.00 4.00 6.00 4.00 6.00 4.00
Designation H-P3 H-P5 H-P7.5 H-P10 H-P15 H-P20 H-(P21-26) H-P27
H DEPTH of Water at plummet 2)
Minimum 3.60 3.80 4.50 5.00 5.50 5.80 5.80 5.80
J DISTANCE and DEPTH AHEAD Designation J-P3 K-P3 J-P5 K-P5 J-P7.5 K-P7.5 J-P10 K-P10 J-P15 K-P15 J-P20 K-P20 J-(P21-26) K-(P21-26) J-P20 K-P27
K of plummet for all stands Minimum 5.50 3.40 6.00 3.60 8.00 4.30 11.00 4.80 11.50 5.30 12.00 5.60 12.00 5.60 12.00 5.60
L DISTANCE and DEPTH EACH SIDE Designation L-P3 M-P3 L-P5 M-P5 L-P7.5 M-P7.5 L-P10 M-P10 L-P15 M-P15 L-P20 M-P20 L-(P21-26) M-(P21-26) L-P27 M-P27
M of plummet Minimum 2.30 3.40 3.50 3.60 4.50 4.30 5.25 4.80 5.50 5.30 6.00 5.60 6.50 5.60 7.00 5.60
Maximum Slope to reduce dimensions beyond full
N 30 DEGREES
requirements for pool depth and ceiling height
Note: The appropiate local authorities must certify that the minimum requirements are observed
Overhead platform distance: Minimum 3.50m, preferred 4.00m
1)
The side distance between platforms must not be less than 0.50m
2)
Legacy pools are pools built prior to December 31, 2017. They are permitted to have a minimum depth of 5 metres
3)
For High Diving events other than FINA World Championships and FINA World Cups the following minimum platform dimensions are accepted: Length 2.0m / width 1.5m; adjacent platform distances
between platforms to be adjusted accordingly with respect the 0.50 m distance between the platforms
4)
in natural surroundings (sea, lakes, rivers etc.) height tolerance: + 0.25 / - 0.25
5)
15.00m is an official height for Junior A competitions and dimensions valid for all heights between 11.00 - 19.00m
F F F G
E E
P27 P27
P20 P20
P10 P10
P7.5 P7.5
P5 P5
B B A/A
A/A
B C C B A D
H H H H H H
P5
A A
P10 P20 P7.5
P27
B C C B
B B
FINA PLATFORM
Dimensions for High Diving temporary round pools P5 P7.5 P10 P20 P27
Round pool diameter 17 m Width Minimum 2.00 2.00 2.00 2.00 2.00
5.00 7.50 10.00 20.00 27.00
Height
Tolearance +0.05/-0.05 +0.05/-0.05 +0.05/-0.05 +0.05/-0.05 +0.05/-0.05
From plummet BACK TO POOL WALL OBSTACLE
A 1.50 1.85 1.85 2.25 3.00
(pool wall)
From plummet BACK TO PLATFORM
A/A 0.75 0.75
plummet direct below
From plummet to obstacle
B 4.80 3.20 3.20 5.70 6.40
POOL WALL AT SIDE
From plummet to
C 2.50 2.50 2.50 2.50 2.50
ADJACENT PLUMMET 1)
From plummet to obstacle
D 14.00 14.00 14.00 14.00 14.00
POOL WALL AHEAD
DEPTH OF WATER
H 5.80 5.80 5.80 5.80 5.80
at plummet
Note: The appropiate local authorities must certify that the minimum requirements are observed.
1)
The side distance between platforms must not be less than 0.50m
The use of temporary round pools (TRP) is restricted to sanctioned FINA competitions.
Comment: With a High Diving Tower configuration as detailed in the Annex HD 3, the resulting dimension B "From
plummet to obstacle pool wall at side" is 5.09m. It is impossible to increase this dimension up to 5.50m not increasing the
pool diameter. For this reason it is suggested to reduce the dimension B to 5.00m.
Comment: The same dimensions and configuration of the platforms can be achieved in a rectangular pool with the
following dimensions: 14.00 m x 17.00 m
F F F G
E E
P27 P27
P21-26 P21-26
P20 P20
P10 P10
P7.5 P7.5
P5 P5
S3 S3 S3 P3 P3 A/A
A/A
P1 S1 S1 A/A
B C C C C C C C B A D
P1
L L J
Min 1.8m Min 1.8m
M H H H M H H K
1
Page 109 of 110
FINA FACILITIES RULES
Diagrams Swiss Arrange the diagrams not at the end of the chapter as annexes but directly in conjunction with the rules to which the
Aquatics diagram belongs.
New FR 5.4 Swiss Judges Seating
Aquatics
FR 5.3.13 Swiss FR 5.4.1 Individual diving
Aquatics
FR 5.3.13.1 Swiss Renumbered FR 5.4.1.1 – 5.4.1.8
FR 5.3.13.8 Aquatics
FR 5.3.14 Swiss FR 5.4.2 Synchronised diving
Aquatics
Black = existing wording / red = scratch / blue = new rules / new wording
2
Page 110 of 110