Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

1 2 3 4 5 6 7 8

=EX0.13
TRANSFORMER-2 BAY
DISTURBANCE FAULT

TO VOLTAGE SELECTION 3PH VT


/042.2E LVTM1-R LVTM1-R RECORDER (DFR) PANEL
/045.6B
(DIA-08)

FROM FUTURE LINE CVT


A DWG:P18009-150-CBB-CIV-

(METERING CORE)
DRW-003
A

CIRCUIT (-KA75L)
/042.3E LVTM1-S LVTM1-S
/045.7B

/042.3E LVTM1-T LVTM1-T


/045.7B

/042.4E LVTM1-N LVTM1-N


/045.8B

SELECTION 1PH VT
CIRCUIT (-KAB75L)
LVTM1-R
/046.7B
B B

TO VOLTAGE
LVTM1-N
/046.8B

-XTVTM1
/042.6E TVTM1-R
5 -X322:1
FROM 20kV SIDE VT
(METERING CORE)

/042.6E TVTM1-S
6 -X322:2

/042.7E TVTM1-T
C 7 -X322:3 C

/042.7E TVTM1-N
8 -X322:4

TO VOLTAGE SELECTION 3PH VT


TVTM1-R
/045.1B 10 11 12 13 -XTVTM1

CIRCUIT (-KA75T)
TVTM1-S
/045.2B

D
TVTM1-T
/045.2B EXISTING D

110V DC PANEL
This document is exclusively property of Schneider Electric and shall not be used or copied without authorization

-XTVTM1
Y0BUA10GH001
TVTM1-N
/045.3B

V1 V2 V3 V4 P402 F2

TO VOLTAGE SELECTION 3PH VT


TVTM1-R
/046.3B
10A -XDC -1020Z

CIRCUIT (-KAB75T)
TVTM1-S L1/+ 1 1
/046.4B
NEW
ENERGY METER
3 3
E
N/-
TVTM1-T
/046.4B
E

TVTM1-N
/046.5B

EXISTING
TVTM1-R
ENERGY METER PANEL A
TO PH-PH VT

/050.2E
AVR(-N90)

TVTM1-S
Y0BAY10GH001
=E08+W1 /050.2F
150/20kV TRANSFORMER-2 BAY, CUTOFF-A & AB CONTROL PANEL (DIA-08)
F F
Contractor : KSO PT. MAHAKAAM JAYA SEJAHTERA, XIAN ELECTRIC ENGINEERING DAN PT. MULYA JATRA SCHEMATIC DIAGRAM OF DIA-08 150/20kV TRANSFORMER-2 BAY, CUTOFF-A & AB Drawn By GHUFRON
Format Scale Date Revision
PT. PLN (Persero) Project Name : PENGADAAN DAN PEMASANGAN PERALATAN BAY GARDU INDUK DI UNIT INDUK
CONTROL PANEL (=E08+W1) Checked By HUGO 05-May-20 C
TRANSMISI JAWA BAGIAN TENGAH - PEKERJAAN EXTENSION TRAFO-2 DI GIS FUTURE LINE CVT & 20kV SIDE VT METERING CORE DISTRIBUTION CIRCUIT
UNIT INDUK TRANSMISI JAWA BAGIAN TENGAH A3 NTS
PUDAK PAYUNG,EXTENSION TRAFO-3 GIS CIBABAT II/LEUWIGAJAH, Appr. By SARAH Sheet Next Sheet
EXTENSION OF EXISTING 150kV GIS PELABUHAN RATU EXTENSION TRAFO-2 GIS PELABUHAN RATU
Customer Order No : 015/PO/PCP/P18009/MJS/III/2019, 28-03/19 PT. SCHNEIDER INDONESIA SCHEMATIC DIAGRAM Drawing No. : E2010-97975-DD-SC-002 044 045

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

=J02 =E08+W1
20kV INCOMING PANEL 150/20kV TRANSFORMER-2 BAY, CUTOFF-A & AB CONTROL PANEL (DIA-08)
DWG:X4028213-301
A SHT:5
A

-X90 -N90
ETB14 REG-DA

LV TRAFO. SIDE
B B
P1

-X31 -XCTM3
1S1 R R 21 22
-X3:1 -X3:11 1 1
1S2 /156.6A
CT1.R
RATIO : 1000-2000/5A -X3:5
CLASS : 0.2S 1S3
-X3:6 2
I1
P1
P2

1S1 S S 23 24 1 S1 S2 3
-X3:2 -X3:12 2 3 /138.4B
1S2 /156.6A
CT1.S -P51
C -X3:7 (**)
RATIO : 1000-2000/5A C
CLASS : 0.2S 1S3
-X3:8 4
P1
P2

1S1 T T 25 26
-X3:3 -X3:13 3 5
1S2 /156.7A
CT1.T
RATIO : 1000-2000/5A -X3:9
1S3 N N 27 28
CLASS : 0.2S
-X3:10 -X3:14 4 6
P2

/156.7A

D -X3:4 D
20kV CB(-Q50) SIDE
PE 7
$
This document is exclusively property of Schneider Electric and shall not be used or copied without authorization

GND

P402
-XCTM4 -XCTM4
I12 IA I11 1 1
2
I22 IB I21 2
3

ENERGY METER PANEL A


IC 4
I32 I31 5 3
E IN E
I42 I41 6 4

Y0BAY10GH001
7
NEW ENERGY METER
EXISTING

NOTE:
INSERTION BRIDGE – EB 10 - 8 - 0202138
2). # - SHORTING LINKS (USB 2-RTK/S - 0311278) OF CT CIRCUITS WILL BE CLOSED WHEN AVR IS OUT OF SERVICE
3). (**) SHORTING LINKS WILL BE AUTOMATICALLY DONE ON PLUG INSERTION
4). $– CT EARTHING TO BE DONE EITHER IN 20KV SIDE / CRP

F F
Contractor : KSO PT. MAHAKAAM JAYA SEJAHTERA, XIAN ELECTRIC ENGINEERING DAN PT. MULYA JATRA SCHEMATIC DIAGRAM OF DIA-08 150/20kV TRANSFORMER-2 BAY, CUTOFF-A & AB Drawn By GHUFRON
Format Scale Date Revision
PT. PLN (Persero) Project Name : PENGADAAN DAN PEMASANGAN PERALATAN BAY GARDU INDUK DI UNIT INDUK
CONTROL PANEL (=E08+W1) Checked By HUGO 05-May-20 C
TRANSMISI JAWA BAGIAN TENGAH - PEKERJAAN EXTENSION TRAFO-2 DI GIS 20kV SIDE CT DISTRIBUTION TO AVR (-N90)
UNIT INDUK TRANSMISI JAWA BAGIAN TENGAH A3 NTS
PUDAK PAYUNG,EXTENSION TRAFO-3 GIS CIBABAT II/LEUWIGAJAH, Appr. By SARAH Sheet Next Sheet
EXTENSION OF EXISTING 150kV GIS PELABUHAN RATU EXTENSION TRAFO-2 GIS PELABUHAN RATU
Customer Order No : 015/PO/PCP/P18009/MJS/III/2019, 28-03/19 PT. SCHNEIDER INDONESIA SCHEMATIC DIAGRAM Drawing No. : E2010-97975-DD-SC-002 040 041

1 2 3 4 5 6 7 8

You might also like