Professional Documents
Culture Documents
6 EE12 - electrical-design-calculations-of-residential-CALCULATION
6 EE12 - electrical-design-calculations-of-residential-CALCULATION
6 EE12 - electrical-design-calculations-of-residential-CALCULATION
Introduction
Purpose
This article is intended for PEE, REE, and RME who are starting to
prepare electrical plans and specifications. The following discussions
contain basic knowledge and requirements in the electrical design of
single storey and single occupancy residential building, and high-rise
residential/commercial condominium buildings.
Reminder
In accordance with the New Electrical Engineering Law
(RA#7920), Professional Electrical Engineer (PEE), Registered
Electrical Engineer (REE), and Registered Master Electrician (RME)
may prepare electrical plans, specifications and other related
documents but only a PEE can sign and seal these plans,
specifications, other related documents, and practice electrical
engineering in its full scope.
2
II. Review of Basic Design Requirements
2.1.0 Definition
The definitions in PEC1 2009 apply in this presentation and
only selected additional definitions which are applicable and
necessary in the design of high-rise residential/commercial
condominium building are presented.
2.1.1. Building
A roofed structure, which stands alone or that is cut-off from
adjoining structures by firewalls with all openings therein are
protected by approved fire doors and which is constructed with
columns, walls and flooring, and intended for the support, shelter
or enclosures of person, animal, chattel, or property of any kind.
3
2.1.2 Classification of Building
Roof
Air space
separation or
Occupant A fire wall Occupant B
Building A Building B
(Elevation) (Elevation)
5
2.1.2.2 Based on the Number of Occupancies
6
ILLUSTRATION # 1B
Roofing
Wall partition
Air Air
space space
Occupant 1 Occupant 2 Occupant 3
Ground
level
Building C
(Elevation)
7
ILLUSTRATION #1C
Firewall Firewall
.4m - 1.0m height
Roofing Roofing Roofing
Air Air
space space
Firewall
Ground
Level
Building D
(Elevation)
8
2.1.2.3 Based on Height or Number of Storeys. National
Building Code (PD1096):
9
Low Rise, Single Occupancy
10
III. Electrical Design of a Single Storey, and Single Occupancy
Residential Building.
3.0 General
Although the electrical design of a low-rise residential
building is already a project design subject in most colleges, it is
discussed here because the design processes, criteria, methods,
requirements of the owners, architect, electric utility, and others
are almost similar to the electrical design of a high-rise
condominium building.
11
Not to Scale
b
Sab
16m
7m
N
DINING
Sc
9m
Residential
Rizal St.
W E
c 9m
Building
S S
18m
Service Equipment 4m 8m 4m
T&B
S LOT
c
BEDROOM
KITCHEN
8m
Figure 3.1A
Architectural Layout
12
3.1.1 Review of the Design Requirements
The design requirements are not just whims/caprices of electrical
designers, electrical utilities, municipal/city electrical engineers or
electricians, and others. The following are some requirements which may
enlighten the user of this handout:
For large projects, the electrical layout for the service drop/lateral,
service entrance, service equipment, feeder/subfeeders, load centers
and panelboards are separated from the branch circuit. For large and
complicated projects, further separation might be necessary. 13
3.1.1.3 Legend or Symbol
These help in understanding the electrical plan. The recommended
symbols are shown in Appendix A of the Philippine Electrical Code Part 1
2009. However, other symbols can be used, especially the local symbols
which are easily understood in the area.
B) Type of wiring
These include service entrance, feeders, subfeeders, and
branch circuit wires for lighting and power load.
D) Methods of grounding
14
E) Type and rating of main disconnecting means, overcurrent protection, and
branch circuit wiring.
This is a standard strip of 40mm height at the bottom of the sheet and
contains the following:
3.1.1.9 Others
The complete requirements are shown in Article 1.3 of PEC 1 2009. 16
3.2 Detailed Design.
3.2.1 Preparations
17
3.2.2 Electrical Calculation (Residential Units)
B) Provide one (1) 20A branch circuit. Although a 15AT circuit breaker is
adequate for the computed load, a 20AT circuit breaker is used to take
care of expected high usage of home appliances. Refer to section
2.40.1.6 for standard ampere trip ratings of circuit breakers.
C) Use 2 # 3.5mm², copper TW, branch circuit conductors. Pls. refer to Table
3.10.1.16 for ampacity.
D) Use 15mm dia. rigid PVC conduit. Refer to Table C10 for size of conduit
which can accommodate 2 #3.5 mm2 copper, TW.
18
3.2.2.2 Small appliance load
B.) Provide one(1) 20A small appliance branch circuit as per Section
2.10.1.11(c)(1) or Section 2.10.3.3(b)(1). Refer also to Section
2.40.1.6 for ampere trip ratings of circuit breakers.
D.) Use 15mm dia. Rigid PVC conduit. Refer to Table C10 for size of
conduit which can accommodate 2 #3.5 mm2 copper, TW.
19
3.2.2.3 Laundry load
B.) Use one (1) 20A branch circuit as per section 2.10.1.11(c)(2).
D.) Use 15mm dia. rigid PVC conduit. Refer to Table C10 for size of
conduit which can accommodate 2 #3.5mm2 copper, TW.
20
3.2.2.4 Sum of connected load for general lighting, small
appliance, and laundry.
Connected load = 1,728VA + 1,500VA + 1,500VA
= 4,728VA
3.2.2.5 Demand load for the three (3) loads above (3.2.2.4)
Demand load = First 3000VA at 100% plus remainder at 35%
= 3000VA x 100% + (4728-3000)VA x 35%
= 3000VA + (1,728VA)35%
= 3000VA + 604.8VA
= 3604.8VA
I (demand load) = 3,604.8VA = 15.7 A
230V
= 15.7A
Where the 100% & 35% demand factors are as per Table 2.20.3.3.
21
3.2.2.6 Other Loads
A.) One (1) 1.5 Hp room ACU, single phase 10A x 230V = 2,300 volt-
amperes
Where 10A is as per Table 4.30.14.2.
C.) Use 2 #3.5 mm2 copper, TW branch circuit conductors. Refer to Table
3.10.1.16 for the ampacity of the conductor.
D.) Use 15 mm dia. rigid PVC conduit. Refer to Table C10 for size of conduit
which can accommodate 2 #3.5mm2 copper, TW.
E.) The room ACU is at 100% demand factor. Refer to Section 2.20.4.3(c)(1).
22
3.2.2.7 Total computed net continuous load
Load = 3,604.8 volt-amperes + 2,300 volt-amperes
= 5,904.8VA
I = 5,904.8VA = 25.7A
230V
23
3.2.2.9 Service Entrance Conductors
B.) Use two(2) # 8mm² copper THW wires. Refer to Table 3.10.1.16
for conductor ampacity. THW insulation is used because the chances of
the service entrance encountering more heat is greater than the branch
circuit inside each unit.
C.) Use 20 mm. dia. PVC conduit except the supply side of service meter,
which shall be galvanized rigid steel conduit as per requirement of Meralco.
Refer to Table C10 for rigid PVC conduit and Table C8 for rigid steel conduit
size which can accommodate 2 #8mm2 copper, THW.
24
3.2.2.10 Service Equipment
A.) Maximum current rating of protective device. Refer to Section 4.30.5.2, Section
4.30.5.3(1), and Section 4.30.5.3(3).
Where 15.7A is the I (demand load) excluding the full load current of the 1.5 Hp ACU,
300% and 250% are as per Table 4.30.4.2 and 10A is the full load current of the 1.5 H.p,
230V, room air conditioner as per Table 4.30.14.2.
B.) One(1) 40AT, 1-pole, 250V circuit breaker is already complying, but there is no need for
main circuit breaker for the service equipment, considering that there are four(4) branch
circuit breakers only. However, this panelboard shall be marked/approved as service
equipment.
Total Connected Load = General lighting & co plus small appliance plus laundry + other loads
= 1,728 VA + 1500VA +1,500VA + 2,300VA = 7,028VA
26
3.2.3 Electrical Plans
27
Service Supply 230V, 2-wire, grounded
Service Supply 230V,
from distribution
2-wire, grounded transformer
rated 100kVA, 19.9kV-230V, grounded
M
Service Entrance 2 #8mm²
copper, THW in 20mm
galvanized rigid steelo conduit.
Sab
SALA
a a a
S
1
T&B
3
S
b
2 BEDROOM
Service Equipment
3-20AT, 1P, 250V
1-30AT, 1p, 250V 4
8m 28
3.2.3.2 Location Plan
This is also the same as the location plan in Figure 3.1A
but it has to be incorporated in the electrical plans.
16m
Residential E
Rizal St.
W
Building 9m
S
18m
4m 8m 4m
LOT
Figure 3.2B
Figure 3.2B
Location Plan 29
3.2.3.3 Legend
Note: This can be included in Electrical Wiring Layout Sheet
30
31
3.2.3.4 General Notes/Specifications
A) All electrical works shall be done in accordance with the Philippine Electrical
Code Part 1, latest edition, the requirements of the municipality of Marilao
and the Manila Electric Company.
32
E) The the service equipment and all other equipment shall be provided
with adequate and proper grounding.
H) Service entrance conduit, from the service head to the electric meter,
shall be exposed galvanized rigid steel conduit.
Farthest outlet
Figure 3.2E
Location of Wiring and Other Requirements
N
M
Service Entrance 2 #8mm²
copper, THW in 20mm Residential E
Rizal St.
W
Building 9m
galvanized rigid steelo conduit.
S
18m
Sab
4m 8m 4m
LOT
SALA
Note: This can be included in the
electrical wiring layout sheet.
a a a
Figure 3.2B
Service Entrance 2 #8mm²
copper, THW in 20mm
PVC conduit
DINING
Location Plan
Sc
9m
c
S
1
Legend
T&B
3
S
b
2 BEDROOM
Service Equipment
3-20AT, 1P, 250V
1-30AT, 1p, 250V 4
8m
General/Notes
A) All electrical works shall be done in accordance with the Philippine Electrical Code Part 1, latest edition, the requirements
of the municipality of Marilao and the Manila Electric Company.
B) The electrical works shall be done by a Registered Master Electrician (RME) or Registered Electrical Engineer (REE) or
Professional Electrical Engineer (PEE) or skilled electrical practitioner but under the supervision of RME, REE, PEE.
C) Materials, devices and equipment shall be new and shall be in conformance with the Philippine Standards or listed by an
organization which is acceptable to the authority having jurisdiction.
D) The electrical service shall be 230V, line to ground, single phase.
E) The service equipment and all other equipment shall be provided with adequate and proper grounding.
F) Conductors and conduits shall be as indicated in the computation load schedule, or single line diagram.
G) All wiring shall be in PVC conduit and shall be embedded when running thru concrete except when otherwise noted.
H) Service entrance conduit, from the service head to the electric meter, shall be exposed galvanized rigid steel conduit.
I) All wiring devices shall be flush mounted and grounding type.
J) Mounting height of convenience outlets shall be 30cm from the floor level.
K) Layout dimension are approximate and intended as installation guides only.
L) All inconsistencies shall be brought to the attention of the PEE who signed and sealed the drawings, computations, load
schedule, specifications, and other documents.
Professional EE: Revision # Project Title: Sheet Contents: Project Owner: Dwg# E-1
Sht# 1 of 2
Scale:
37
3.2.3.9 Final Electrical Plan (Cont)
Figure 3.2F
Location of Load Schedule and Other Requirements
Professional EE: Revision # Project Title: Sheet Contents: Project Owner: Dwg# E-1
Sht# 2 of 2
Scale:
38
3.2.4 Size of Grounding (Pls. refer 3.2.3.7 Panelboard Schematic and
Grounding Diagram)
The size of grounding in a building is covered by the following
Sections and Tables
39
3.2.4.4 Service Equipment Bonding Jumper
Section 2.50.2.9(d), 2.50.5.13(c) and Table 2.50.3.17 – this is based
on the size of the service entrance conductors. The size of the service
entrance conductors is # 8mm² THW or TW and hence, from Table
2.50.3.17, the size of service equipment bonding jumper is 8mm² THW
or TW.
40