Professional Documents
Culture Documents
Fan Static Pressure Calculation For Fire Smoke Exhaust System
Fan Static Pressure Calculation For Fire Smoke Exhaust System
Document Class 2
REVISION HISTORY
Rev. Section Page Description
HOLD List
No. Section Page Description
1 SCOPE
This is Excel Document Template
2 REFERENCE DOCUMENT
The following documents shall be referred to where required.
Document Number Document Title
3.2 Abbreviations
The following definitions shall be applied for this project.
YOC Yokohama Operation Office
HOC Hanoi Operation Center
J-DMS JGC Document Management System
PROJECT NAME VIETNAM NISSHIN TECHNOMIC PHASE 2 Revision: 0
WORK CODE : Date:
TOPIC : PRESSURE CALCULATION FOR FIRE SMOKE EXHAUST SYSTEM Applied Standard:
DESIGNED BY : LÊ VĂN ĐẠT
CHECK BY : NGUYỄN THÀNH TRUNG
APPROVER : NGUYỄN THÀNH TRUNG
Chosse fan
Equipment Tag No SEF-01,2,3,4
Name Equipment Smoke Exhaust fan
Location 1F
Air Flow 80000 m3/h
Pressure 850 Pa
Pressure Caculation
Air Width a Hight b Area F Velocity Equivalent Length Duct pressure Local Summary of Velocity Pressure Section Total
Flow L (mm) (mm) (m2) V diameter L loss coefficient fitting loss pressure loss along pressure Pressure
Duct section (m3/h) (m/s) Dtd (mm) (m) R (Pa/m) Type of fitting ξ coefficient
Pđ the way loss Pcb loss P
ξ (Pa) Pdd (Pa) (Pa)
(Pa)
PRESSURE LOSS BEFORE FAN
SH1-SH2 16000 1,000 800 0.800 5.56 888.89 7.00 0.36 SH 1.80 2.20 9.524 2.52 20.953 23
DAMPER 0.40
SH2-SH3 32000 1,000 800 0.800 11.11 888.89 6.80 1.31 TEE 2.23 2.23 38.028 8.91 84.802 94
SH3-SH4 48000 1,000 800 0.800 16.67 888.89 6.80 2.7 TEE 0.95 1.02 85.613 18.36 87.325 106
REDUCE 0.07
SH4-SH5 64000 1,400 800 1.120 15.87 1018.18 7.00 2.1 TEE 0.57 0.65 77.593 14.70 50.435 65
TRANSITION 0.08
SH5-FAN 80000 1,600 800 1.280 17.36 1066.67 31.50 2.32 TEE 0.38 2.73 92.847 73.08 253.472 327
ELBOW (4 NOS) 1.00
REDUCE 0.25
TRANSITION (2 NOS) 0.60
FAN INLET 0.50
PRESSURE LOSS AFTER FAN
80000 2,100 1,200 2.520 8.82 1250 3.00 2.6 FAN OUTLET 0.50 2.95 23.967 7.80 70.703 78.5
REDUCE 0.50
ELBOW 0.50
TRANSITION 0.45
∑P 693
Chosse fan
Equipment Tag No SEF-05
Name Equipment Smoke Exhaust fan
Location 1F
Air Flow 57000 m3/h
Pressure 900 Pa
Pressure Caculation
Duct section Air Width a Hight b Area F Velocity Equivalent Length Duct pressure Type of fitting Local Summary of Velocity Pressure Section Total
Flow L (mm) (mm) (m2) V diameter L loss coefficien fitting loss pressure loss along pressure Pressure
(m3/h) (m/s) Dtd (mm) (m) R (Pa/m) t ξ coefficient Pđ the way loss Pcb loss P
(Pa) Pdd (Pa) (Pa)
(Pa)
ξ
SH1-SH2 14250 1,500 300 0.450 8.8 500 9.00 1.7 SH 1.80 2.27 23.858 15.30 54.158 69
DAMPER 0.35
REDUCE 0.08
TRANSITION 0.04
SH2- TEE 28500 1,600 300 0.480 16.49 505.26 10.60 5.4 TEE 0.80 1.01 83.774 57.24 84.612 142
ELBOW 0.15
TRANSITION 0.06
TEE- FAN 57000 2,000 450 0.900 17.59 734.69 35.00 3.8 TEE 1.65 3.35 95.324 133.00 319.335 452
ELBOW (4 NOS) 0.80
FAN INLET 0.50
REDUCE 0.15
TRANSITION (2 NOS) 0.25
PRESSURE LOSS AFTER FAN
57000 1,600 1,000 1.600 9.9 1230.77 2.00 0.69 FAN OUTLET 0.50 2.65 30.195 1.38 80.017 81.4
REDUCE 0.30
TRANSITION 0.60
ELBOW (2 NOS) 0.25
INSECT SCREEN 1.00
∑P 745
Chosse fan
Equipment Tag No SEF-06
Name Equipment Smoke Exhaust fan
Location 1F
Air Flow 45000 m3/h
Pressure 800 Pa
Pressure Caculation
Air Width a Hight b Area F Velocity Equivalent Length Duct pressure Local Summary of Velocity Pressure Section Total
Flow L (mm) (mm) (m2) V diameter L loss coefficien fitting loss pressure loss along pressure Pressure
Duct section (m3/h) (m/s) Dtd (mm) (m) R (Pa/m) Type of fitting t ξ coefficient
Pđ the way loss Pcb loss P
(Pa) Pdd (Pa) (Pa)
ξ
(Pa)
PRESSURE LOSS BEFORE FAN
SH1- TEE 11250 800 600 0.480 6.51 685.71 11.00 0.66 SH 1.80 3.00 13.057 7.26 39.171 46
DAMPER 0.40
REDUCE 0.15
TRANSITION 0.20
ELBOW 0.45
TEE- TEE 22500 1,200 600 0.720 8.68 800 11.00 0.93 TEE 0.80 2.97 23.212 10.23 68.94 79
ELBOW (2 NOS) 0.85
TRANSITION 0.80
VALVE 0.52
TEE- TEE 33750 1,400 600 0.840 11.16 840 0.50 1.39 TEE 0.95 0.95 38.371 0.70 36.452 37
TEE-FAN 45000 1,400 600 0.840 14.88 840 39.00 2.4 TEE 0.80 4.92 68.214 93.60 335.613 429
FAN INLET 0.50
VALVE 0.52
REDUCE 0.45
ELBOW (6 NOS) 1.85
TRANSITION (2 NOS) 0.80
PRESSURE LOSS AFTER FAN
45000 1,600 1,000 1.600 7.81 1250 1.00 0.45 FAN OUTLET 0.50 3.75 18.792 0.45 70.47 70.9
REDUCE 1.10
TRANSITION 0.65
ELBOW 0.50
INSECT SCREEN 1.00
∑P 663
Chosse fan
Equipment Tag No SEF-07
Name Equipment Smoke Exhaust fan
Location 1F
Air Flow 54000 m3/h
Pressure 1000 Pa
Pressure Caculation
Air Width a Hight b Area F Velocity Equivalent Length Duct pressure Local Summary of Velocity Pressure Section Total
Flow L (mm) (mm) (m2) V diameter L loss coefficien fitting loss pressure loss along pressure Pressure
Duct section (m3/h) (m/s) Dtd (mm) (m) R (Pa/m) Type of fitting t ξ coefficient
Pđ the way loss Pcb loss P
ξ (Pa) Pdd (Pa) (Pa)
(Pa)
PRESSURE LOSS BEFORE FAN
SH- TEE 13500 1,000 500 0.500 7.5 666.67 10.50 0.89 SH 1.80 3.68 17.33 9.36 63.774 73
DAMPER 0.40
ELBOW (2NOS) 1.20
TEE 0.28
TEE- TEE 27000 1,200 600 0.720 10.42 800 12.00 1.30 TEE 2.00 2.38 33.451 15.60 79.613 95
ELBOW 0.26
REDUCE 0.12
TEE- TEE 54000 1,500 600 0.900 16.67 857.14 28.00 2.85 TEE 0.33 0.78 85.613 79.80 66.778 147
VALVE 0.20
ELBOW 0.25
TEE- FAN 54000 1,500 600 0.900 16.67 857.14 30.00 2.85 TEE 0.57 3.59 85.613 85.53 307.351 393
MOTOR DAMPER 0.52
FAN INLET 0.50
REDUCE 0.24
ELBOW (4 NOS) 1.60
TRANSITION 0.16
PRESSURE LOSS AFTER FAN
54000 1,600 1,000 1.600 9.38 1250 1.00 0.63 FAN OUTLET 0.50 3.75 27.107 0.63 101.651 102.3
TRANSITION 0.65
REDUCE 1.10
ELBOW (2 NOS) 0.50
∑P 810