Power Monitoring and Power Quality Correction

Power Monitoring and Power Quality Correction


A

Energy and Power Meters B


General overview ................................................................................. E-2
PowerLogic™ Overview ...................................................................... E-4
Current Transformers .......................................................................... E-8 C
Panel Instrument .................................................................................. E-26
Basic Energy Metering ........................................................................ E-34
D
iEM2000 ......................................................................................... E-35
iEM2100.......................................................................................... E-38
iEM3000 ......................................................................................... E-42 E
PM3000 .......................................................................................... E-50
PowerTag Energy Series ................................................................ E-56
Wireless Products ................................................................................ E-92 F
PowerTag Control ........................................................................... E-93
HeatTag ......................................................................................... E-97
G
Basic Multi-function Metering .............................................................. E-100
PM5000 Series ............................................................................... E-101
PM5350 .......................................................................................... E-114 H
Multi-circuit Metering ........................................................................... E-118
PowerLogic™ HDPM6000 ............................................................. E-121
PowerLogic™ BCPM...................................................................... E-130 I
Retrofit Products................................................................................... E-144
EM3555........................................................................................... E-145
Insulation Monitoring Devices ............................................................. E-150
VigilOhm Insultation Monitoring Devices ....................................... E-152
EcoStruxure Panel Server ................................................................... E-158

Power Quality Correction


Power Factor Correction ...................................................................... E-170
Power Factor Correction Components ................................................ E-172
VarSet Power Factor Correction .......................................................... E-180
VarPlus Logic Series............................................................................. E-182
AccuSine+ Active Harmonic Filter ...................................................... E-185
PowerLogic Series................................................................................ E-190
Power Quality Solutions........................................................................ E-203

< >
se.com/au Life is On | Schneider Electric | E-1
Switchboard Manufacturers

Energy and Power Meters


General Overview

The new benchmark in


precision metering

PowerLogic™ range
Schneider Electric is the global specialist in energy management and as such it has the most complete
power motoring product line, going from simple indicators (analog meters) and CTs, to world class
accurate energy meters and powerful compact power meters. These proven products come with
multiple options to satisfy any requirement.

Schneider Electric products are safe and reliable. We comply with the most stringent standards,
including IEC, MID, UL, etc., and we thoroughly test all products with third-party laboratories. This gives
our partners the peace of mind and the confidence that they are maintaining a good reputation while
delivering the best value in equipment and service to their customers.

Our products are simple to install, configure, and use. This saves our partners time and money and lets
them deliver the best solutions in a timely and cost-effective manner.

Whatever the size or type of application, the PowerLogic™ product line is an


integral part of smart panels

E-2 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

< >
se.com/au Life is On | Schneider Electric | E-3
Switchboard Manufacturers

PowerLogic™ Range
General Overview

Panorama of the PowerLogic™ range


Use this panorama to select the most efficient products for your application needs

E CTsIp / 5 A iAMP iVLT AMP/VLT iFRE iCH/iCI


current transformer
Function
ammeter, ammeter, ammeter, frequency meter hour counter
voltmeter voltmeter voltmeter pulse counter

Installation Applications
i. Solid Core CTs
• Insulated Cable, Panel instrumentation
diameter 21 to 35 mm
Panel instrumentation I/U I/U I/U F hours/pulses
• busbar through
transformer
• cable connections Energy efficiency & cost
ii. Split Core CTs Sub-billing & cost
• CT installation without allocation
the need to uninstall
and reinstall power Demand & load
conductors management
• Cable and Busbar Billing analysis
connections

Power availability & reliability


Compliance monitoring
Sag/swell, transient
Harmonics

Revenue metering
Revenue meter

Characteristics Characteristics
i. Solid Core CTs Measurement accuracy Class 1.5 ± 0.5 % ± 1 digit Class 1.5 ± 0.5 % ± 1 digit
• transformation ratio: 40/5
A to 6000/5 A Installation DIN rail 4 x 18 DIN rail 2 x 18 flush mounted 72 DIN rail 2 x 18 iCI, iCH: DIN
mm modules mm modules x 72 mm mm modules rail 2 x 18 mm
• accuracy: class 0.5 to 3 96 x 96 mm modules CH: flush
• maximum rated opera- mount
tional voltage: 720 V AC
• tropicalised range 25 °C Measurement iAMP: 30 A direct iVLT: 600 V AC VLT: 500 V AC 400 V AC direct
to +60 °C (1) or external CT direct or external direct or external
VT VT AMP: external
relative humidity > 95 % CT
Warning: some
(1)
Communication ports
products are limited to
+50 °C. Inputs / Outputs
ii. Split Core CTs Memory capacity
• transformation ratio :
100/5A to 4000/5A
• accuracy : class 0.5 to 3
• maximum rated opera-
tional voltage : 720 V AC
• Cable connection : -5°C
to +50°C

relative humidity 5–85 %


• Busbar connection : 5°C
to +40°C

relative humidity 5–85 %

E-4 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

General Overview

Basic energy metering A

iEM2000/iEM2010/ iEM3000 Series PM3000 Series PowerTag Energy


E
iEM2000T/iEM2100 Series
Function
F
kilowatt-hour meter kilowatt-hour meters metering & sub-metering wireless power & energy
Class 0.5S IEC 62053-22 meter
Class 1 IEC 62053-21
Class 2 IEC 62053-23
G
Applications

Panel instrumentation H
Panel instrumentation E I, U, F, P, Q, S, PF, E I, U, F, P, Q, S, PF, E
(Power demand and current (Power demand and current
demand) demand) I
Energy efficiency & cost
Sub-billing & cost allocation cost allocation
Demand & load management
Billing analysis

Power availability & reliability


Compliance monitoring
Sag/swell, transient
Harmonics

Revenue metering
Revenue meter

Characteristics
Measurement accuracy Class 0.5S / Class 1 Class 0.5S / Class 1 Class 0.5 IEC 61557-12 PMD/DD
Class 1 (active energy)
Installation DIN rail 1, 2, 5, or 7 x 18 mm DIN rail DIN rail on product or on cables de-
modules pending on the reference
Voltage measurement 400 V AC direct 50 V to 330 V (Ph-N) 50 V to 330 V AC (Ph-N) up to 277 V AC (Ph-N) / 480 V
80 V to 570 V (Ph-Ph) up to 80 V to 570 V AC (Ph-Ph) AC (Ph-Ph) depending on the
1MV AC (ext VT) up to 1M V AC (ext VT) reference
Current measurement 40 to 125 A direct or external external CT external CT 63 to 2000 A
CT
Communication ports 1 1 Wireless

Inputs / Outputs 2 I/O 2 I/O

Memory capacity

< >
se.com/au Life is On | Schneider Electric | E-5
Switchboard Manufacturers

PowerLogic™ Range
General Overview

Wireless Products Basic multi-function


metering

PowerTag Control HeatTag Smart Sensor PM5000 Series PM5350 Series


E
Function
Circuit monitoring & control Early detection of over- metering & sub-metering Class 0.5S IEC 62053-22
IEC 60364-8-1 heating wire connections or Class 0.5S IEC 62053-22 Class 2 IEC 62053-23
overheating cables Class 1 IEC 62053-21
EN 17267 Class 1 IEC 61557-12
Class 2 IEC 62053-23
ISO 50010

Applications

Panel instrumentation
Panel instrumentation Analysis of gas and mi- I, U, F, P, Q, S, PF, E I, U, F, P, Q, S, PF, E
cro-particles, Temperature, (Power demand and (Power demand and
Humidity current demand) current demand)

Energy efficiency & cost


Sub-billing & cost allocation
Demand & load management
Billing analysis

Power availability & reliability


Compliance monitoring
Sag/swell, transient
Harmonics

Revenue metering
Revenue meter

Characteristics
Measurement accuracy Temperature ±-1.1 °C Hu- Class 0.5S Class 0.5
midity ± 9 RH%
Installation DIN rail DIN rail Flush mount or DIN rail Flush mount
6 x 18 mm modules 96 mm x 96 mm
Voltage measurement 60 V to 400 V AC L-N PM53xx 20-400 V L-N
103.5 to 690 V AC L-L 20-690 V L-L
Current measurement external CT external CT

Communication ports Wireless 1 1

Inputs / Outputs 2 I/O 2 I/O 2 I/O

Memory capacity

E-6 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

General Overview

Wireless Products Basic multi-function A


metering
B

HDPM6000 BCPM BCPM Split core EM3555


E
Function
3-phase power quality meter; branch circuit monitor branch circuit monitor DIN rail power & energy
IEC 61036 IEC 61036 meter
branch-circuit accessory Class 1 Class 1 ANSI 12.20 0.2% accuracy, F
IEC 62053-22 Class 0.2S
module hub for EM35xx models, ANSI
C12.20 0.5% accuracy, IEC
G
Applications

Panel instrumentation H
Panel instrumentation I, U, F, P, Q, S, PF, E I, U, F, P, Q, S, PF, E I, U, F, P, Q, S, PF, E
(Power demand and current (Power demand and current (Power demand and current
demand) demand) demand)
I
Energy efficiency & cost
Sub-billing & cost allocation
Demand & load management
Billing analysis

Power availability & reliability


Compliance monitoring
Sag/swell, transient
Harmonics

Revenue metering
Revenue meter

Characteristics
Measurement accuracy Class 1 (mains active energy) Class 1 (mains active energy) Class 1 (mains active energy)

Installation Panel or enclosure Panel or enclosure Panel or enclosure

Voltage measurement 90 – 277 V L-Nvoltage Inputs 90 – 277 V L-Nvoltage Inputs UL: 90 V L-N to 600 V L-L;
CE: 90 V L-N to 300 V L
Current measurement CT strips for branch circuits CT strips for branch circuits EM35xxA models work exclu-
and external CTs for mains and external CTs for mains sively with Rogowski coil CTs
Communication ports 1 for main 1 for main 1 for main

Inputs / Outputs (see Datasheet)

Memory capacity

< >
se.com/au Life is On | Schneider Electric | E-7
Switchboard Manufacturers

Current Transformers
General Overview

Current transformers

Schneider Electric is the global specialist in energy management with the most complete
power monitoring product line. Current Transformers are essential components designed
to be used with Schneider Electric's extensive power monitoring product portfolio. From
simple energy meters to world class power quality meters, these proven products satisfy
any requirement.
E

METSECT5CC04 METSECT5MB025 METSECT5GD025 METSECT5CYL1 METSECT5HA025

E-8 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

IP/5 A ratio The Ip/5 A ratio current transformer delivers at the secondary a current (Is) of
A
0 to 5 A that is proportional to the current measured at the primary (Ip). This
allows them to be used in combination with measurement equipment:
B
• Ammeters. • Kilowatt-hour meters.
• Measurement units. • Control relays. etc.
C
When the primary is energized, the measurement equipment nearly acts as
a short circuit which keeps the secondary voltage very low. This voltage will
DB416186

increases significantly if the short circuit is removed.


D
Application diagram of a CT.

CT selection - conductor rating aspects E


The choice depends on the conductor profile and the maximum intensity of
the primary circuit.
F

CT with let-through primary


G
Conductor type Cable Mixed, bars or cables Vertical or horizontal Vertical bars
bars
H
Suggested Current DB415986 DB415920 DB415988 DB415989
Transformer and mounting

DB415921 DB415987

Ratings (A) 40 to 250 150 to 800 200 to 4000 5000 to 6000

CT internal Type C Type M Type D (1)


Type V
FF C FF MA FF D FF V2

MA MB MC

FF MD
MD VV

(1) Two secondary connectors (parallel internal wiring - only one secondary winding) for easier cable access. 1 lateral + 1 on one extremity. Warning: only one must be used at a time.

Specific mounting: use of cylinder CT with primary connection by screw and nut (example: use of cylinder with bar or cable)

A cylindrical metallic spacer ensures a proper CT


positioning when the conductor or the CT cannot be
positioned perpendicular. Secured by bolt + nut.

DB416005 DB416006
NOTE: This document is not intended to be used as an installation guide.

< >
se.com/au Life is On | Schneider Electric | E-9
Switchboard Manufacturers

Current Transformers
Functions and characteristics

CT selection - Electrical aspect Ip/5 A


• We recommend that you choose the ratio immediately higher than the maximum measured current (In).
Example: In = 1103 A; ratio chosen = 1250/5.
• For small ratings: From 40/5 to 75/5 and for an application with digital devices, we recommend that you choose a higher rating, for example
100/5. This is because small ratings are less accurate and the 40 A measurement, for example, will be more accurate with a 100/5 CT than with
a 40/5 CT.
• Specific case of the motor starter: to measure motor starter current, you must choose a CT with primary current Ip = Id/2 (Id = motor starting
current).

Validation of measurement solution according to accuracy class


It consists in controlling the right adaptation of the CT on the accuracy class aspect. The accuracy class is specified in the project. The total
dissipated power of the measurement circuit (meter + cables) should not be superior to the specified limit of the CT. This limit is for different
E standard classes. If necessary, the choice of the cable section, the CT or meter should be modified to fit the requirement.

Copper cablecross-section Power per doubled meter at Schneider Electric device Consumption of the current
(mm2) 20°C (VA) input (VA)
1 1 Ammeter 72 x 72 / 96 x 96 1.1

1.5 0.685 Analog ammeter 1.1

2.5 0.41 Digital ammeter 0.3

4 0.254 PM8000 0.15

6 0.169 PM3000 0.3

10 0.0975 PM5000

16 0.062 iEM3000

For each temperature variation per 10 °C bracket, the power drawn up by the cables increases by 4 %.

Application example
Project specification: 200 A, in Ø27 mm cable, accuracy class 1. Our choice is METSECT5MA020.

For this CT selected on the chart (next page), the max acceptable power is 7 VA (for "Accuracy class 1" which is specified in the project).

Internal Cables (mm) Bars (mm) Rating Commercial Accuracy class


profile type Ip5 A reference number
(A) 0.5 1 3
Max. power (VA)

MA
Ø27 10 x 32 150 METSECT5MA015 3 4
15 x 25 200 METSECT5MA020 4 7 -

250 METSECT5MA025 6 8 -

300 METSECT5MA030 8 10 -

400 METSECT5MA040 10 12 -

Control of the conformity of the measurement chain:


Hazard Label

• PM3000 multi-meter: 0.3 VA.


• 4 meters of 2.5 mm2, doubled wires: 0.41 x 4 = 1.64 VA.

Total: 0.3 + 1.64 = 1.94 VA (< 7 VA)


Conclusion: this CT is well adapted as the accuracy class will be
even better than 1.

E-10 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Reference numbers

Presentation of Commercial Reference Numbers Examples: A


MET SE CT 5 CC 008 = 5 A secondary, Cables
MET SE CT X XX XXX only, 75 A primary B
1 = 1 Amp Last 3 digits = primary rating/10
MET SE CT 5 MC 080 = 5 A secondary, mixed
5 = 5 Amp
for cables and bars, 800 A primary C
2 letters = Form Factor

R = Rogowski
MET SE CT R 30 500 = Rogowski CT, 300mm
length, 96mm diameter 50 A to 5000 A D

Type C - solid core current transformer (cable profile) E


Internal profile type Cables (mm) Bars (mm) Rating Ip/5 A (A) Commercial ref number
CC F
FF CC Ø21 - 40 METSECT5CC004
PB112446

50 METSECT5CC005
60 METSECT5CC006
G
75 METSECT5CC008
100 METSECT5CC010 H
125 METSECT5CC013
METSECT5CCppp
150 METSECT5CC015
200 METSECT5CC020
I
250 METSECT5CC025

Type M - current transformers (mixed: cable/bar profile)


MB
PB112461

FF MB Ø26 12 x 40 250 METSECT5MB025


15 x 32
300 METSECT5MB030
METSECT5MBppp 400 METSECT5MB040

MA
FF MA Ø27 10 x 32 150 METSECT5MA015
15 x 25
PB112460

200 METSECT5MA020
250 METSECT5MA025
300 METSECT5MA030
METSECT5MAppp 400 METSECT5MA040

MC
FF MC Ø32 10 x 40 250 METSECT5MC025
20 x 32
PB112462

25 x 25 300 METSECT5MC030
400 METSECT5MC040
500 METSECT5MC050
600 METSECT5MC060
METSECT5MCppp 800 METSECT5MC080

MD
PB112463

FF MD Ø40 12 x 50 500 METSECT5MD050


20 x 40
600 METSECT5MD060
METSECT5MDppp 800 METSECT5MD080

See your Schneider Electric representative for complete ordering information.

< >
se.com/au Life is On | Schneider Electric | E-11
Switchboard Manufacturers

Current Transformers
Reference numbers

Common characteristics
DB415926

Secondary current Is (A) 5A


Maximum voltage rating Ue (V) 720 V
Frequency (Hz) 50/60 Hz
40 to 4000 A: sf y 5
Safety factor (sf)
5000 to 6000 A: sf y 10
Degree of protection IP20
tropicalised range
Operating temperature -25°C to +60°C (1)
Mounting plate installation. relative humidity > 95 %
Storage temperature -40°C to +85°C
IEC 61869-2
Compliance with standards
VDE 0414
E Secondary connection (as per model) by terminals for lug
DB415927

by tunnel terminals
by screws

(1) Warning: some products are limited to +50°C.


DIN rail mounting.

Type C - solid core current transformer (cable profile)


Internal profile type Accuracy class Overall dimensions Fastening mode Accessories
(refer to drawing pages
0.5 1 3 for details) Cylinder
PB112451

PB112452
Max. power (VA) W x H x D (mm)

CC Dimension (mm) Commercial ref no.


FF CC - - 1 44 x 66 x 37 •Adapter for DIN rails. 16550 Included
- 1.25 1.5 •Mounting plate. METSECT5CYL1
- 1.25 2
- 1.5 2.5
2 2.5 3.5
2.5 3.5 4
3 4 5
4 5.5 6
5 6 7
MB
FF MB 3 5 - 60 x 85 x 63 •Adapter for DIN rails. - METSECT5COVER
4 6 - •Mounting plate.
6 8 -
MA
FF MA 3 4 - 56 x 80 x 63 •Adapter for DIN rails. METSECT5CYL2 METSECT5COVER
4 7 - •Mounting plate.
6 8 -
8 10 -
10 12 -
MC
FF MC 3 5 - 70 x 95 x 65 •Adapter for DIN rails. - METSECT5COVER
5 8 - •Mounting plate.
8 10 -
10 12 -
12 15 -
10 12 -
MD
FF MD 4 6 - 70 x 95 x 65 •Adapter for DIN rails. - METSECT5COVER
6 8 - •Mounting plate.
8 12 -

See your Schneider Electric representative for complete ordering information.


NOTE: This document is not intended to be used as an installation guide.

E-12 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Reference Numbers
Type V - current transformers (vertical bar profile)
A
Internal profile Cables (mm) Bars (mm) Rating Ip/5 A (A) Commercial reference
type number
PB112467

VV
- 55 x 165 5000 METSECT5VV500 •
B
6000 METSECT5VV600 •
FF MB
C
METSECT5VVppp
D
Type D - current transformers (vertical or horizontal bar - dual secondary terminals)
E
Internal profile Cables (mm) Bars (mm) Rating Ip/5 A (A) Commercial reference
type number
DA
F
32 x 65 400 METSECT5DA040

500 METSECT5DA050
G
PB112455

600 METSECT5DA060
PB112454

800 METSECT5DA080

1000 METSECT5DA100 H
1250 METSECT5DA125 •

METSECT5DAppp METSECT5DBppp 1500 METSECT5DA150 •


I
DB
- 38 x 127 1000 METSECT5DB100

1250 METSECT5DB125 •

1500 METSECT5DB150 •

2000 METSECT5DB200 •

2500 METSECT5DB250 •
PB112457
PB112456

3000 METSECT5DB300 •

DC
- 52 x 127 2000 METSECT5DC200 •

2500 METSECT5DC250 •
METSECT5DCppp METSECT5DDppp
3000 METSECT5DC300 •

4000 METSECT5DC400 •

DD
- 34 x 84 1000 METSECT5DD100

1250 METSECT5DD125 •

1500 METSECT5DD150 •

DE
PB112459
PB112458

- 54 x 102 1000 METSECT5DE100

1250 METSECT5DE125 •

1500 METSECT5DE150 •

METSECT5DEppp METSECT5DHppp 2000 METSECT5DE200 •

DH
- 38 x 102 1250 METSECT5DH125 •

1500 METSECT5DH150 •

2000 METSECT5DH200 •
• Operating temperature: -25 °C to 50 °C
See your Schneider Electric representative for complete ordering information.

< >
se.com/au Life is On | Schneider Electric | E-13
Switchboard Manufacturers

Current Transformers
Reference numbers
Type V - solid core current transformers (vertical bar profile)
Internal profile Accuracy Overall dimensions Fastening mode Accessories
type class (refer to drawing
0.5 1 3 pages for details) Cylinder Sealable cover

Max. power (VA) WxHx


D (mm)
VV Dimension (mm)
FF MB 60 - - 175 x 273.5 x 110 • Insulated locking screw. - Included

70 - -

E
Type D - solid core current transformers (vertical or horizontal bar - dual secondary terminals)
DA Dimension (mm)
4 8 - 90 x 94 x 90 • Insulated locking screw. Included
8 10 -
8 12 -
12 15 -
15 20 -
15 20 -
20 25 -
DB
6 10 - 99 x 160 x 87 • Insulated locking screw. - Included
8 12 -
10 15 -
15 20 -
20 25 -
25 30 -
DC
25 30 - 125 x 160 x 87 • Insulated locking screw. - Included
30 50 -
30 50 -
30 50 -
DD
10 15 - 96 x 116 x 87 • Insulated locking screw. - Included
12 15 -
15 20 -
DE
12 15 - 135 x 129 x 85 • Insulated locking screw. - Included
15 20 -
20 25 -
20 25 -
DH
12 15 - 98 x 129 x 75 • Insulated locking screw. - Included
12 15 -
20 25 -

• Operating temperature: -25 °C to 50 °C


See your Schneider Electric representative for complete ordering information.

E-14 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

< >
se.com/au Life is On | Schneider Electric | E-15
Switchboard Manufacturers

Current Transformers
Functions and characteristics

Solid core CT dimensions


CC internal profile type MB internal profile type

DB415923
DB416965

MA internal profile type MC internal profile type


DB415922

DB415939

MD internal profile type DA internal profile type


DB416966

DB415932

DB internal profile type DC internal profile type


DB416967

DB416968

E-16 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

DD internal profile type DE internal profile type B


DB416969

DB416970
C

G
DH internal profile type
DB416971

VV internal profile type


DB416972

< >
se.com/au Life is On | Schneider Electric | E-17
Switchboard Manufacturers

Current Transformers
Functions and characteristics

Solid core cylinders dimensions


Cylinders
METSECT5CYL1 METSECT5CYL2

DB416002
DB416004

E
Aluminium Aluminium

16550 16551
DB416000
DB416082

Brass Brass

Covers
METSECT5COVER
DB416008

E-18 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

Split Core CTs A

Hazard Label
B

Common characteristics Cable CT Bus Bar CT


I
Secondary current Is (A) 0.208333333 0.208333333
Maximum voltage rating Ue (V) 720 V 720 V
Frequency (Hz) 50/60 Hz 50/60 Hz
Safety factor (sf) up to 1000 A: sf y 5 up to 1500 A: sf y 5 greater than 1500 A: sf y 10
greater than 1000 A: sf y
10
Degree of protection IP20 IP20
Operating temperature -5°C to +50°C -5°C to +40°C
relative humidity 5-85 % relative humidity 5-85 %
Storage temperature -25°C to +70°C -25°C to +70°C
Compliance with standards IEC 61869-1 IEC 61869-1
IEC 61869-2 IEC 61869-2
Secondary connection (as per model) by terminals for lug by terminals for lug by
by tunnel terminals by tunnel terminals by
screws screws

Split core CT
CT internal Type H Type G
FF C HA HD HG FF V2 GA GD
HJ HP GG GJ

FF HM
HM

< >
se.com/au Life is On | Schneider Electric | E-19
Switchboard Manufacturers

Current Transformers
Reference numbers

Split Core CTs


Type G - split core current transformers (bus car)

Accuracy class CT window Rating Commercial


Max power (VA) dimension (mm) Ip/5A (A) Reference no.
PB119862

0.5 1 3

GA
- - 1.25 100 METSECT5GA010
- - 1.5 150 METSECT5GA015
- - 2.5 200 METSECT5GA020
E METSECT5GAppp 23 x 33
- 1.5 - 250 METSECT5GA025
- 3.75 - 300 METSECT5GA030
1 - - 400 METSECT5GA040
GD
- 1.5 - 250 METSECT5GD025
PB119864

- 2.5 - 300 METSECT5GD030


1 - - 400 METSECT5GD040
2.5 - - 500 METSECT5GD050
55 x 85
2.5 - - 600 METSECT5GD060
2.5 - - 750 METSECT5GD075
METSECT5GDppp
2.5 - - 800 METSECT5GD080
5 - - 1000 METSECT5GD100
GG
- 1.5 - 250 METSECT5GG025
- 2.5 - 300 METSECT5GG030
PB119866

- 2.5 - 400 METSECT5GG040


2.5 - - 500 METSECT5GG050
2.5 - - 600 METSECT5GG060
2.5 - - 85 x 125 750 METSECT5GG075
2.5 - - 800 METSECT5GG080
METSECT5GGppp
5 - - 1000 METSECT5GG100
5 - - 1200 METSECT5GG120
7.5 - - 1250 METSECT5GG125
7.5 - - 1500 METSECT5GG150
PB119868

GJ
10 - - 1000 METSECT5GJ100
10 - - 1200 METSECT5GJ120
10 - - 1500 METSECT5GJ150
10 - - 1600 METSECT5GJ160
85 x 165
10 - - 2000 METSECT5GJ200
METSECT5GJppp
10 - - 2500 METSECT5GJ250
15 - - 3000 METSECT5GJ300
15 - - 4000 METSECT5GJ400

See your Schneider Electric representative for complete ordering information.

E-20 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Reference numbers

A
Type H - split core current transformers (cable)
B
Accuracy class CT window Rating Commercial
Max power (VA) dimension (mm) Ip/5A (A) Reference no.
0.5 1 3
C
HA
- 1 - 18.4 x 19 150 METSECT5HA015 D
PB119870

PB119872

- 1.5 - 150 METSECT5HA020


1 - - 250 METSECT5HA025
HD E
- 1 - 27.9 x 27 250 METSECT5HD025

METSECT5HAppp METSECT5HDppp
- 1.5 - 300 METSECT5HD030
F
- 2.5 - 400 METSECT5HD040
1 - - 500 METSECT5HD050
HG G
- - 1.5 Ø32.5 100 METSECT5HG010
PB119874

- - 2.5 125 METSECT5HG013


- - 3 150 METSECT5HG015
H
- - 3 200 METSECT5HG020
- - 3 250 METSECT5HG025 I
METSECT5HGppp
- 2.5 - 300 METSECT5HG030
- 5 - 400 METSECT5HG040
- 5 - 500 METSECT5HG050
- 5 - 600 METSECT5HG060
PB119876

HJ
- 2.5 - 300 METSECT5HJ030
- 5 42.4 x 43 400 METSECT5HJ040
- 5 - 500 METSECT5HJ050
2.5 - - 600 METSECT5HJ060
METSECT5HJppp
2.5 - - 750 METSECT5HJ075
2.5 - - 800 METSECT5HJ080
-
HM
PB119878

- 2.5 - 42.4 x 85 300 METSECT5HM030


- 5 - 400 METSECT5HM040
- 5 - 500 METSECT5HM050
2.5 - - 600 METSECT5HM060
2.5 - - 750 METSECT5HM075
METSECT5HMppp 2.5 - - 800 METSECT5HM080
HP
- 1.5 - Ø44 250 METSECT5HP025
- 2.5 - 300 METSECT5HP030
PB119880

- 5 - 400 METSECT5HP040
- 5 - 500 METSECT5HP050
- 5 - 600 METSECT5HP060
- 5 - 750 METSECT5HP075
- 5 - 800 METSECT5HP080
METSECT5HPppp
- 5 - 1000 METSECT5HP100

See your Schneider Electric representative for complete ordering information.

< >
se.com/au Life is On | Schneider Electric | E-21
Switchboard Manufacturers

Current Transformers
Functions and characteristics

Solid core CT dimensions


Gx Products
GA Dimensions GD Dimensions
PB119863

PB119865
E

GG Dimensions GJ Dimensions
PB119867

PB119869

E-22 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

Hx Products
B
HA Dimensions HD Dimensions
C
PB119871

PB119873
D

HG Dimensions HJ Dimensions
PB119875

PB119877

< >
se.com/au Life is On | Schneider Electric | E-23
Switchboard Manufacturers

Current Transformers
Functions and characteristics

Solid core CT dimensions Contd


Hx Products
HM Dimensions HP Dimensions
PB119879

PB119881
E

E-24 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Reference numbers

Rogowski CTs A

B
PB118060

METSECTR30500
D

E
PowerLogic Rogowski Current Transformer
Main METSECTR30500 METSECTR46500 METSECTR60500 METSECTR90500 F
Range PowerLogic
Product or component type Current transducer
Accessory / part category Measurement accessory
G
PowerLogic EM3500 - EM3555A EM3502A EM3560 EM3550A EM3560 EM3561A

Range compatibility PowerLogic EM4200 - EM4236 EM4235 H


Acti9 iEM3000 - iEM3555 iEM3565

Current transformer type Flexible core I


Complementary
Electrical connection Flying lead 2.4 m 600 V AC max, voltage L-N sensed conductor
Cable 1000 V AC UL style 21223 cable with 22 AWG leads
Current range 50 A to 5000 A
Network frequency 50/60 Hz
Measurement accuracy ±1 % from 50 A to 5000 A
Installation category 600 V AC Cat IV
Pollution degree 2
Dimensions METSECTR30500 METSECTR46500 METSECTR60500 METSECTR90500
CT core thickness 8 mm diameter 8 mm diameter 8 mm diameter 8 mm diameter
CT core length (open) 300 mm 460 mm 600 mm 900 mm
Diameter (closed) 96 mm 146 mm 191 mm 287 mm
Environment
Standards EN 61010-1, UL 61010-1, EN 61010-2-032, UL 61010-2-032
Product certifications CURus
UL recognized

Ambient air temperature for operation -15 ºC to 60 ºC


Ambient air temperature for storage -40 ºC to 70 ºC
Humidity range 0 to 95 % non-condensing
Altitude 2000 m max
Protection degree IP67
Commercial Reference Numbers
METSECTR25500 Powerlogic - Rogowski current transformer, 250 mm CT core length, 80 mm dia. CT, rope, 600 V AC, 5 kA
METSECTR30500 Powerlogic - Rogowski current transformer, 300 mm CT core length, 96 mm dia. CT, rope, 600 V AC, 5 kA
METSECTR46500 Powerlogic - Rogowski current transformer, 460 mm CT core length, 146 mm dia. CT, rope, 600 V AC, 5 kA
METSECTR60500 Powerlogic - Rogowski current transformer, 600 mm CT core length, 191 mm dia. CT, rope, 600 V AC, 5 kA
METSECTR90500 Powerlogic - Rogowski current transformer, 900 mm CT core length, 287 mm dia. CT, rope, 600 V AC, 5 kA

< >
se.com/au Life is On | Schneider Electric | E-25
Switchboard Manufacturers

Panel Instruments
General Overview

Schneider Electric panel instruments reliably comply with the most stringent standards, including
IEC, MID, UL, etc., and we thoroughly test all products with recognized, third-party laboratories.
Our products are simple to install, configure, and use. This saves our partners time and money and lets them deliver
the best solutions in a timely and cost-effective manner.

Whatever the size or type of application, the PowerLogic™ product line is an integral part of smart panels.
PB101118

PB112024

DB119006

16029 15202 16003

E-26 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

Function
A
iAMP
DB119006

Ammeters measure the current flowing through an electric circuit in amps.


iVLT B
Voltmeters measure the potential (voltage) difference of an electric circuit in volts.

16029
C
Common technical data
• Accuracy: Class 1.5.
D
iAMP.
• Complies with standards IEC 60051-1, IEC 61010-1 and IEC 61000-4.
• Ferromagnetic device.
• Pseudo-linear scale over 90°. E
• Ammeters (except catalog number 16029):
- connection on CT, ratio In/5, to be ordered separately
- interchangeable dials. F
• Temperature:
DB119005

- operating temperature: -25 °C to 55 °C


- reference temperature: 23 °C G
• Influence of temperature on accuracy: ±0.03 %/°C.
• Utilisation frequency: 50 Hz to 60 Hz.
16061
H
• Consumption:
- AMP: 1.1 VA
- VLT catalog number 15060: 2.5 VA I
- VLT catalog number 16061: 3.5 VA.
iVLT.
• Permanent overload:
- AMP: 1.2 In
- VLT: 1.2 Un.
• Maximum overload for 5 s:
- AMP: 10 In - VLT: 2 Un.
• Connection: tunnel terminals for 1.5 to 6 mm2 rigid cables.

Commercial Reference Numbers


Type Scale Connection with CT Width in mod. of 9 mm Comm. ref. no.
iAMP with direct connection
0-30 A no 8 16029
iAMP with connection on CT
Basic device
X/5 8 16030
(delivered without dial)
Dial 0-5 A
0-50 A 50/5 16032
0-75 A 75/5 16033
0-100 A 100/5 16034
0-150 A 150/5 16035
0-200 A 200/5 16036
0-250 A 250/5 16037
0-300 A 300/5 16038
0-400 A 400/5 16039
0-500 A 500/5 16040
0-600 A 600/5 16041
0-800 A 800/5 16042
0-1000 A 1000/5 16043
0-1500 A 1500/5 16044
0-2000 A 2000/5 16045
iVLT
0-300 V 8 16060
0-500 V 8 16061
See your Schneider Electric representative for complete ordering information.

< >
se.com/au Life is On | Schneider Electric | E-27
Switchboard Manufacturers

Panel Instruments
Functions and characteristics

Function
iAMP
PB112024

Ammeters measure in amps the current flowing through an electric circuit.


iVLT
Voltmeters measure in volts the potential (voltage) difference of an electric circuit.
iFRE
15202 Frequency meters measure in hertz the frequency of an electric circuit from 20 to
600 V AC.

Common technical data


iAMP. • Supply voltage: 230 V AC
• Operating frequency: 50 Hz to 60 Hz.
E • Display by red LED: 3 digits, h = 8 mm (0.31 in).
• Accuracy at full-scale : 0.5 % ±1 digit.
PB112023

• Consumption: max. 5 VA or rated 2.5 VA.


• Degree of protection:
- IP40 on front face.
- IP20 at terminal level.
15201
• Connection: tunnel terminals for 2.5 mm2 cables.

Specific data
10 A direct reading ammeter
iVLT. • Minimum value measured: 4 % of rating.
• Measurement input consumption: 1 VA.
Multi-rating ammeter
• Ratings:
- in direct reading: 5 A.
PB112025

- by CT (not supplied) configurable on the front face of the ammeter: 10, 15, 20,
25, 40, 50, 60, 100, 150, 200, 250, 400, 500, 600, 800, 1000, 1500, 2000, 2500,
4000, 5000 A.
• Minimum value measured: 4 % of rating.
15208 • Measurement input consumption: 0.55 VA.
Voltmeter
• Direct measurement: 0...600 V AC
iFRE.
• Input impedance: 2 MW.
• Minimum value measured: 4 % of rating.

Frequency meter
• Minimum value measured: 20 Hz.
• Maximum value measured: 100 Hz.
• Full-scale display: 99.9 Hz.

Compliance with standards


• Safety: IEC/EN 61010-1.
• EMC electromagnetic compatibility: IEC/EN 65081-1 and IEC/EN 65082-2.

Commercial Reference Numbers


Type Scale Connection with CT Width in mod. of 9 mm Comm. ref. no.
Direct reading iAMP
0-10 A No 4 15202
Multi-rating iAMP
0-5000 A As per rating 4 15209
iVLT
0-600 V 4 15201
iFRE
20-100 Hz 4 15208

See your Schneider Electric representative for complete ordering information.

E-28 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

Function
A
The 72 x 72 measurement devices are designed for flush-mounted installation on
doors, wicket doors and front plates of enclosures and cubicles.
AMP B
The ammeters measure in amps the current flowing through an electrical circuit.
PB101118-30_c

VLT
16009
The voltmeter measure in volts the potential difference (voltage) of an electrical C
circuit.

Common technical data


AMP for standard feeder. D
• Accuracy: Class 1.5.
• Compliance with standard IEC 60051-1, IEC 61010-1 and IEC 61000-4.
• Ferromagnetic device. E
• Scale length: 62 mm over 90°.
• Mounting in enclosure or in cubicle.
F
• Degree of protection: IP52.
PB101119-30_c

• Maximum operating position: 30° / vertical.

16006
• Temperature: G
- operation: -25 °C to 50 °C.
- reference: 23 °C.
AMP for motor feeder. • Influence of temperature on accuracy: ±0.003 %/ °C. H
• Utilisation frequency: 50 Hz to 60 Hz.

I
AMP Specific technical data
• Needs a In/5 CT to be ordered separately.
• Interchangeable dials to be ordered separately.
PB101116-30_c

• Consumption: 1.1 VA.


16005
• Permanent overload: 1.2 In.
• Maximum overload for 5 s: 10 In.

VLT Specific technical data


VLT.
• Consumption: 3 VA.
• Permanent overload: 1.2 Un.
• Maximum overload for 5 s: 2 Un.

Commercial Reference Numbers


Type Scale Connection on CT Comm. ref. no.
AMP for standard feeder
Basic device (delivered without dial) X/5 16004
1.3 In dial 0-50 A 50/5 16009
0-100 A 100/5 16010
0-200 A 200/5 16011
0-400 A 400/5 16012
0-600 A 600/5 16013
0-1000 A 1000/5 16014
0-1250 A 1250/5 16015
0-1500 A 1500/5 16016
0-2000 A 2000/5 16019
AMP for motor feeder
Basic device (delivered without dial) X/5 16003
3 In dial 0-30-90 A 44711 16006
0-75-225 A 75/5 16007
0-200-600 A 200/5 16008
VLT
0-500 V 16005

See your Schneider Electric representative for complete ordering information.

< >
se.com/au Life is On | Schneider Electric | E-29
Switchboard Manufacturers

Panel Instruments
Functions and characteristics

Function
The 96 x 96 measurement devices are designed for flush-mounted installation on
doors, wicket doors and front plates of enclosures and cubicles.
PB101118-40_c

AMP
The ammeters measure in amps the current flowing through an electrical circuit.
VLT
The voltmeter measure in volts the potential difference (voltage) of an electrical circuit.

16079 Common Technical Data


AMP for standard feeder. • Accuracy: class 1.5.
• Compliance with standard IEC 60051-1, IEC 61010-1 and IEC 61000-4.
• Ferromagnetic device.
E • Scale length: 80 mm over 90°.
• Mounting in enclosure or in cubicle.
PB101119-40_c

• Degree of protection: IP52.


• Maximum operating position: 30° / vertical.
• Temperature:
- operation: -25 °C to 50 °C.
- reference: 23 °C.
16076
• Influence of temperature on accuracy: ±0.003 % / °C.
• Utilisation frequency: 50 Hz to 60 Hz.
AMP for motor feeder.

AMP specific technical data


• Needs a In/5 CT to be ordered separately.
• Interchangeable dials to be ordered separately.
• Consumption: 1.1 VA.
PB101116-40_c

• Permanent overload: 1.2 In.


• Maximum overload for 5S: 10 In.

VLT specific technical data


• Consumption: 3 VA.
• Permanent overload: 1.2 Un.
16075 • Maximum overload for 5S: 2 Un
VLT.

Commercial Reference Numbers


Type Scale Connection on CT Comm. ref. no.
AMP for standard feeder
Basic device (delivered without dial) X/5 16074
1.3 In dial 0-50 A 50/5 16079
0-100 A 100/5 16080
0-200 A 200/5 16081
0-400 A 400/5 16082
0-600 A 600/5 16083
0-1000 A 1000/5 16084
0-1250 A 1250/5 16085
0-1500 A 1500/5 16086
0-2000 A 2000/5 16087
0-2500 A 2500/5 16088
0-3000 A 3000/5 16089
0-4000 A 4000/5 16090
0-5000 A 5000/5 16091
0-6000 A 6000/5 16092
AMP for motor feeder
Basic device (delivered without dial) X/5 16073
3 In dial 0-30-90 A 44711 16076
0-75-225 A 75/5 16077
0-200-600 A 200/5 16078
VLT
0-500 V 16075

See your Schneider Electric representative for complete ordering information.

E-30 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

Function A
iCMA
This 4-position ammeter selector switch uses a single ammeter (using current
PB107119

transformers) for successive measurement of the currents of a three-phase circuit. B


iCMV
This 7-position voltmeter selector switch uses a single voltmeter for successive
measurement of voltages (phase-to-phase and phase-to-neutral) of a three-phase C
15126 circuit.

iCMA. Common technical data D


• Rotary handle.
• Maximum operating voltage: 440 V, 50/60 Hz.
• Nominal thermal current: 10 A. E
• Operating temperature: -20 °C to 55 °C.
PB107118

• Storage temperature: -25°C to 80°C.


F
• Mechanical durability (AC21A-3 x 440 V): 2,000,000 operations.
• Degree of protection:
- IP66 on front face. G
- IP20 at terminal level.
15125 • Electrical durability: 1,000,000 operations.

iCMV.
• Connection: jumper terminals with captive screws, for cables up to 1.5 mm2. H
• Complies with standards: IEC/EN 60947-3.

I
Commercial Reference Numbers
Type Rating (A) Voltage (V AC) Width in mod. of 9 mm Comm. ref. no.

iCMA 10 415 4 15126

iCMV 10 415 4 15125

See your Schneider Electric representative for complete ordering information.

Connection

iCMA

iCMV

See appropriate Installation Guide for this product.

< >
se.com/au Life is On | Schneider Electric | E-31
Switchboard Manufacturers

Panel Instruments
Functions and characteristics

Function
PB112026

Electromechanical counter that counts the operating hours of a machine or piece


of electrical equipment. Giving a precise indication of operating time, the counter is
used to decide when to carry out preventive maintenance.

Common technical data


15440
• Electromechanical display.
• Maximum display: 99999.99 hours.
• Display accuracy: 0.01 %.
• Without reset.
E iCH "DIN" • Storage temperature: -25 °C to 85 °C.
• Connection: tunnel terminals for 2.5 mm2 cable.

Specific technical data


iCH "DIN"
• Consumption: 0.15 VA.
DB119003

• Operating temperature: -10 °C to 70 °C.


• Mounting on DIN rail.

CH "48 x 48"
15607
• Consumption:
- 15607: 0.25 VA
- 15608: 0.15 VA
- 15609: 0.02 VA to 12 V and 0.3 VA to 36 V.
• Operating temperature: -20 °C to 70 °C.
CH "48 x 48"
• Degree of protection: IP65 on front face.
• Mounting on front face of monitoring switchboards.

Commercial Reference Numbers


Type Voltage (V) Width in mod. of 9 mm Comm. ref. no.
iCH "DIN" 230 V AC ± 10 %/50 Hz 4 15440

CH "48 x 48" 24 V AC ± 10 %/50 Hz 15607

230 V AC ± 10 %/50 Hz 15608

12 to 36 V DC 15609

See your Schneider Electric representative for complete ordering information.

Connection
DB11426
DB11426

load
load

iCH "DIN" CH "48 x 48"

See appropriate Installation Guide for this product.

E-32 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

Analog ammeters and 48 x 48 CMA and CMV selector switches A


voltmeters iAMP, iVLT
B
DB103473

DB103477
C

Digital ammeters, voltmeter and iCL impulse counter and iCH hour counter
E
frequency meter iAMP, iVLT
F
DB103479
DB103474

ICMA and iCMV selector switches 48 x 48 CH hour counters I


DB109825
DB103475

72 x 72 analog ammeters and voltmeter


Protection cover
Terminal
M4
DB103476

96 x 96 analog ammeters and voltmeter


Protection cover
Terminal
M4
DB103481

See appropriate Installation Guide for this product.

< >
se.com/au Life is On | Schneider Electric | E-33
Switchboard Manufacturers

Basic Energy Metering


General Overview

Basic energy meters comply with a variety of applications: Range


single-phase or three-phase circuits, basic kWh meters for
PowerLogic iEM2000 series
elementary applications, to full-featured, dual tariff energy meters
and power metering for network monitoring applications. Data is PowerLogic iEM2100 series
visible locally or accessible remotely. Wireless communication energy PowerLogic iEM3000 series
sensors with compact design allow to optimize panel size. PowerLogic PM3000 series
PowerLogic PowerTag Energy series
A9MEM1521

PB117510

PB108410

PB115001

PB108401

A9MEM2000 A9MEM2100 A9MEM3100 A9MEM2000 A9MEM1521

E-34 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Acti9 iEM2000 Series


General Overview
The Acti9 iEM2000 series energy meters offer a cost-attractive, competitive range of single-phase DIN
rail-mounted energy meters ideal for sub-billing and cost allocation applications. A

Applications
B
• Monitor power consumption for each floor, office sector, or unit
C
• Allocate energy cost to lower cost of operations, optimise your building’s power efficiency
• Connect to power management software to take full advantage of the IoT digital power installation
D

G
PB105289

A9MEM2000

< >
se.com/au Life is On | Schneider Electric | E-35
Switchboard Manufacturers

Acti9 iEM2000 Series


Functions and characteristics

The solution for: Energy management system:


All markets that can benefit from a solution that includes PowerLogic iEM2000 To get the most effective use from
series meters: your Schneider Electric measurement
• Buildings and metering devices, we offer a
• Industry range of dedicated data loggers and
gateways for your building energy
• Data Centre & networks
management.
• Infrastructures (airport, road tunnels, telecom).

Benefits Conformity of standards


E The Acti9 iEM2000 series meters are economical and easy to install in • IEC 62053-21
panelboards and switchboards: • EN 50470-3
• DIN rail mounted, compact size
• Accurate data measurement with Class 1 accuracy

Advantages
• Active energy Class 1 accuracy, with LCD display
• Modbus RS-485 and pulse output
• Direct connect, self-powered
• MID approved
• Two tariffs

iEM2000 feature selection


iEM2000T iEM2000 iEM2010 iEM2050 iEM2055
Self-powered

Display

(6 digit LCD) (6 digit LCD)

Width (mm) 18 18 18 17.5 17.5

Current input 40 A 40 A 40 A 45 A 45 A

Multi-tariff 2 tariffs 2 tariffs

Communication Modbus Modbus


Class 1 Class 1 Class 1
Class 1 Class 1
Active Energy accuracy IEC 62053-21 IEC 62053-21 IEC 62053-21
IEC 62053-21 IEC 62053-21
Class B EN 50470-3 Class B EN 50470-3 Class B EN 50470-3
Digital outputs 1 P/O 1 P/O 1 P/O 1 P/O

MID for billing application

Commercial reference number A9MEM2000T A9MEM2000 A9MEM2010 A9MEM2050 A9MEM2055

See your Schneider Electric representative for complete ordering information.

E-36 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

iEM2000 series technical specifications A

Technical specifications
B
iEM2000T iEM2000 iEM2010 iEM2050 iEM2055
COMM reference number A9MEM2000T A9MEM2000 A9MEM2010 A9MEM2050 A9MEM2055
C
Direct connection Up to 40 A Up to 40 A Up to 40 A Up to 45 A Up to 45 A
10000, 2000, 1000, 100, 10, 1, 0.1, 0.01
Pulse output operation 100 pulses/kwh (120ms long)
pulses/kWh D
9999.99 kWh
Display capacity 999999.9 kWh
(switching to 99999.9 when over this value)
E
Voltage range (L-N) 184 to 276 V AC 195 to 253 V AC

Operating frequency 50/60 Hz 50 Hz

Meter constant LED 3200 flashes per KWh 10000 flashes per KWh
F
Wiring capacity (Power) 4 mm2 2.5 mm2

Wiring capacity (Communications) 10 mm2 8-10 mm2 G


Consumption <10 VA

IP protection IP40 front panel and IP20 casing IP51 front panel H
Temperature -10°C to 55°C -25°C to 55°C

Active energy I
Reactive energy

Active power

Reactive power

Power Factor

Current and voltage

Frequency

iEM2050/iEM2055 dimensions iEM2000 dimensions


DB116734
PB115426

Maximum diameter power connection clamps 8 mm2 (solid Maximum diameter power connection clamps 8 mm2 (solid
copper). See the appropriate product Installation Guide for copper). See the appropriate product Installation Guide for
complete instructions. complete instructions.

< >
se.com/au Life is On | Schneider Electric | E-37
Switchboard Manufacturers

Acti9 iEM2100 Series


General Overview

The Acti9 iEM2100 series energy meters are ideal for basic kWh metering and billing applications and
support two protocols (Modbus and M-bus) that allow them to integrate seamlessly into your customers’
existing networks.

Applications
• Monitor the power consumption of each sector, unit, workshop…
• Manage an electrical installation and optimise your building’s power efficiency
• Various business, industrial and residential applications

E
PB118059

A9MEM2100

E-38 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

The solution for Energy management system: A


All markets that can benefit from a solution that includes PowerLogic To get the most effective use
iEM2100 series meters: from your Schneider Electric B
• Buildings measurement and metering devices,
we offer a range of dedicated data
• Industry
loggers and gateways for your C
• Data Centre & networks building energy management.
• Infrastructures (airport, road tunnels, telecom).
D
Benefits Conformity of standards
The Acti9 iME kilowatt-hour meters are specially economic and easy to • IEC 62052-11 E
install in all switchboards.
• IEC 62053-21
F
Competitive advantages
• IEC 62053-23
• Compact size
G
• MID compliant (selected models) providing certified accuracy and • EN 50470-1
data security
• EN 50470-3 H
• Four quadrant measurement
• Electrical parameter measurement eg. V, I, P, PF
• Onboard Modbus or M-bus communication I
• A complete range of energy meters
• Compatible with Acti9 range

iEM2100 feature selection


iEM2100 iEM2105 iEM2110 iEM2135 IEM2150 iEM2155
Self-powered

Display

Width (mm) 36 36 36 36 36 36

Current input 63 A 63 A 63 A 63 A 63 A 63 A

Active Energy accuracy Class 1 Class 1 Class 1 Class 1 Class 1 Class 1

Reactive Energy accuracy Class 2 Class 2 Class 2 Class 2 Class 2 Class 2

Four quadrant Energy measurement

Multi-tariff 2 2 2

Digital inputs 1 (tariff switching) 1 (tariff switching) 1 (tariff switching)

Digital outputs 1 P/O 2 P/O's

Communication protocol M-bus Modbus RS-485 Modbus RS-485

MID for billing application

Commercial reference number A9MEM2100 A9MEM2105 A9MEM2110 A9MEM2135 A9MEM2150 A9MEM2155

< >
se.com/au Life is On | Schneider Electric | E-39
Switchboard Manufacturers

Acti9 iEM2100 Series


Functions and characteristics

Technical specifications
Technical specifications

iEM2100 iEM2105 iEM2110 iEM2135 IEM2150 iEM2155


Direct connection 63 A 63 A 63 A 63 A 63 A 63 A
1 to 1000 pulses /
1 pulse/kwh
Pulse output operation kwh or kvarh (30 to
(200ms long) 100ms long)
Display capacity 99999 KWh or 999.99 MWh 999999.99KWh

Voltage range (L-N) 184 to 276 V AC 92 to 276 V AC


E Operating frequency 50/60 Hz

Meter constant LED 1000 flashes per KWh

Wiring capacity (Top) 6 mm 2


4 mm2

Wiring capacity (Bottom) 32 mm2 (16 mm2 iEM2100/iEM2105)

Consumption 2.5 VA 3 VA

IP protection IP40 front panel and IP20 casing

Temperature -25°C to 55°C

Active energy

Reactive energy

Active power

Reactive power

Power Factor

Current and voltage

Frequency

iEM2100/iEM2105 dimensions iEM2110/iEM2135/iEM2150/iEM2155 dimensions


PB115003
DB103483

See the appropriate


product Installation
Guide for complete
instructions.

E-40 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

A
iEM2000 and iEM2100 series commercial reference numbers
B
Comm. reference number Product
A9MEM2000T iEM2000T basic energy meter, no display

A9MEM2000 iEM2000 basic energy meter C


A9MEM2010 iEM2010 energy meter, kWh pulse output

A9MEM2100 iEM2100 basic energy meter D


A9MEM2150 iEM2150 energy meter, Modbus communication, four quadrant energy measurement

A9MEM2155 iEM2155 energy meter, Modbus communication, four quadrant energy measurement, two tariffs, MID certified E

See your Schneider Electric representative for complete ordering information.


F

< >
se.com/au Life is On | Schneider Electric | E-41
Switchboard Manufacturers

Acti9 iEM3000 Series


General Overview

The Acti9 iEM3000 series energy meters is a cost-attractive, feature-rich energy metering offer for DIN
rail, modular enclosures. With Modbus and BACnet serial communication protocol support, you can easily
integrate these meters into commercial and non-critical buildings to add simple energy management
applications to any BMS, AMR or EMS system.

Applications
Cost management applications
• Bill checking to verify that you are only charged for the energy you use
• Sub-billing individual tenants for their energy consumption, including WAGES (NMI Pattern Approved references)
E • Aggregation of energy consumption, including WAGES, and allocating costs per area, per usage, per shift, or per time within
the same facility

Network management applications

• Basic metering of electrical parameters to better understand the behaviour of your electrical distribution system
PB108418

A9MEM3100

E-42 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

More than just kWh meters, the Acti9 iEM3000 series meters provide a full view of both energy consumption and on-site
generation with full four-quadrant measurement of active and reactive energy delivered and received. Additionally, extensive A
real-time measurements (V, I, P, PF) give customers greater detail on their energy usage, and multiple tariffs give customers the
flexibility to match the billing structure of their utility.
B

C
The solution for Competitive advantages
All markets that can benefit from a solution that includes PowerLogic iEM3000 • Compact size
series meters: D
• NMI compliant (selected models)
• Buildings & industry providing certified accuracy and
• Data centres and networks data security E
• Infrastructure (airports, road tunnels, telecom) • Programmable digital inputs/
ouputs
F
• Multi-tariff capability
Benefits • Onboard Modbus RS485 or
Optimise your energy consumption & enable energy efficiency practices BACnet serial communication G
• A complete range of energy
• Collect and analyse energy consumption data from each area for each type
meters H
of load or circuit
• Compatible with Acti9 range
• Gain an accurate understanding of business expenses by allocating the
energy-related costs Energy management system: I
• Use information to implement actions designed to reduce energy To get the most effective use
consumption from your Schneider Electric
measurement and metering devices,
we offer a range of dedicated data
Monitor the energy consumption of your tenants or customers and establish loggers and gateways for your
accurate invoices building energy management.

• Drive energy-efficient behaviour Conformity of standards


• Allow building owners to bill tenants for individual measured utility usage • IEC 61557-12 • EN 50470-3
• Give accurate and achievable objectives for energy savings • IEC 62053- 21/22 • EN 50470-1
• IEC 62053-23 • IEC 61036
• IEC 61010
• NMI M 6-1

< >
se.com/au Life is On | Schneider Electric | E-43
Switchboard Manufacturers

Acti9 iEM3000 Series


Functions and characteristics

iEM3000 feature selection


iEM3100 iEM3110 iEM3150 iEM3135 iEM3155 iEM3165
iEM3115
iEM3200 iEM3210 iEM3250 iEM3235 iEM3255 iEM3265
iEM3215
iEM3300 iEM3310 iEM3350 iEM3335 iEM3355 iEM3365
Self-powered

Width (18mm module) 39207 39207 44686 39207 39207 39207 39207

Direct measurement (up to) 63 A/-/125 A 63 A/-/125 A 63 A/- 63 A/-/125 A 63 A/-/125 A 63 A/-/125 A 63 A/-/125 A
Measurement input through CTs
-/ /- -/ /- -/ -/ /- -/ /- -/ /- -/ /-
(1A, 5A)
Measurement input through VTs -/ /- -/ /- -/ /- -/ /-
E Active Energy measurements class 1/0.5S/1 1/0.5S/1 1/0.5S 1/0.5S/1 1/0.5S/1 1/0.5S/1 1/0.5S/1

Four Quadrant Energy measurement


Electrical parameter measurements
(I, V, P,...)
Multi-tariff (internal clock) 4 4 4 4

Multi-tariff (external control) 4 2 2 2

Measurement display (no. of line) 3 3 3 3 3 3 3


Programmable
(Tariff control or 1 1 1
Digital inputs WAGES input)
Tariff control only 2
Programmable
(Kwh pulse or KW 1 1 1
Digital outputs overload alarm)
Kwh pulse only 1

M-bus

Modbus
Communication
protocols
BACnet

Lon

MID (legal metrology certification)

A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3135 A9MEM3155 A9MEM3165

Commercial reference numbers A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3235 A9MEM3255 A9MEM3265

A9MEM3300 A9MEM3310 A9MEM3350 A9MEM3335 A9MEM3355 A9MEM3365

See your Schneider Electric representative for complete ordering information.

How to read table: If a cell contains a single value, that value applies to all meter models identified in the header cell(s). For cells with multiple values, the
values correspond from left to right with the meter models listed from top to bottom for each associated header cell. For example, a cell with

“A / B / C” means A for iEM31xx models, B for iEM32xx models, and C for iEM33xx models

E-44 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

EM3400/iEM3500 technical specifications A


iEM3455 iEM3465 iEM33555 iEM3565
Max current 0.333V-1.0V LVCTs 0.333V-1.0V LVCTs Rogowski coils Rogowski coils
B
Meter constant LED 5000/kWh
Pulse output frequency Up to 500p/kWh
Multi-tariff 4 tariffs
C
Communication Modbus BACnet Modbus BACnet
DI/DO 1/1

Network
1P+N, 3P, 3P+N
D
support LVCTs, Rogowski coils, and VTs
Wiring capacity 6 mm² for currents and 4 mm² for voltages
Display max LCD 99999999.9kWh or 99999999.9MWh
E
Voltage (L-L) 3 x 100/173 V AC to 3 x 277/480 V AC (50/60 Hz)
IP protection IP40 front panel and IP20 casing
Temperature -25°C to 70°C (K55) F
Product size 5 steps of 18 mm
Overvoltage & measurement Category III, Degree of pollution 2
kWh G
kVARh
Active power
Reactive power H
Currents & voltages
Overload alarm
Hour counter I

Acti9 iEM3100/iEM3300 series technical specifications


iEM3100 iEM3110 iEM3150 iEM3135 iEM3155 iEM3165
iEM3115
iEM3300 iEM3310 iEM3350 iEM3335 iEM3355 iEM3365
Max current (direct connec- 63 A for iEM3100 models, 125 A for iEM3300 models
tion)
Meter constant LED 500/kWh
Up to 1000 p/ Up to 1000 p/ Up to 1000 p/
Pulse output kWh kWh kWh
Multi-tariff 4 tariffs 4 tariffs 4 tariffs
Communication Modbus Modbus Modbus BACnet
DI/DO 0/1 2/0 44562 44562 44562
MID (EN50470-3)
Network 1P+N, 3P, 3P+N
Accuracy class Class 1 (IEC 62053-21 and IEC 61557-12) Class B (EN 50470-3)
Wiring capacity 16 mm² for iEM3100 models, 50 mm2 for iEM3300 models
Display max. LCD 99999999.9kWh
Voltage (L-L) 3 x 100/173 V AC to 3 x 277/480 V AC (50/60 Hz)
IP protection IP40 front panel and IP20 casing
Temperature -25°C to 55°C (K55)
Product size 5 x 18 mm for iEM3100 models, 7 x 18 mm for iEM3300 models
Overvoltage and measure- Category III, Degree of pollution 2
ment
kWh
kVARh
Active power
Reactive power
Currents and voltages
Overload alarm
Hour counter

See your Schneider Electric representative for complete ordering information.

< >
se.com/au Life is On | Schneider Electric | E-45
Switchboard Manufacturers

Acti9 iEM3000 Series


Functions and characteristics

Acti9 IEM3200 series technical specifications


iEM3200 iEM3210 iEM3215 iEM3250 iEM3235 iEM3255 iEM3265
Max current (1A/5A CT connected) 0.25

Meter constant LED 5000/kWh


Up to 500p/ Up to 500p/ Up to 500p/
Pulse output frequency kWh kWh kWh
Multi-tariff 4 tariff 4 tariffs 4 tariffs

Communication Modbus Modbus Modbus BACnet

DI/DO 0/1 2/0 44562 44562 44562


E
MID (EN50470-3) (1)

1P+N, 3P, 3P+N 1P+N, 3P, 3P+N


Network
support CTs support CTs &VTs
Accuracy class Class 0.5S (IEC 62053-22 and IEC61557-12) Class C (EN50470-3) (1)

Wiring capacity 6 mm² for currents and 4 mm² for voltages

Display max. LCD 99999999.9kWh or 99999999.9MWh

Voltage (L-L) 3 x 100/173 V AC to 3 x 277/480 V AC (50/60 Hz)

IP protection IP40 front panel and IP20 casing

Temperature -25°C to 55°C (K55)

Product size 5 steps of 18 mm

Overvoltage & measurement Category III, Degree of pollution 2

kWh
kVARh

Active power

Reactive power

Currents and voltages

Overload alarm

Hour counter

(1)
If used for MID purposes, iEM32xx must use CT secondary set to 5 A.

E-46 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

iEM3000/iEM3200 series dimensions A

B
PB105302

PB105303
C

PB105313
E

F
Acti9 iEM3100/iE M3200 Series front flaps open and closed
G

Acti9 iEM3000 Series parts


H
PB105305

PB105306

1. Digital inputs for tariff control (iEM3115 / iEM3215)


2. Display for measurement and configuration
3. Pulse out for remote transfer (iEM3110 / iEM3210)
4. Cancellation I
5. Confirmation
6. Selection
7. Flashing yellow meter indicator to check accuracy
8. Green indicator: on/off, error

iEM3300 series dimensions


PB113599_m

PB1053241

Acti9 iEM3000 Series parts


PB113598_m

1. Digital inputs for tariff control (iEM3115 / iEM3215)


2. Display for measurement and configuration
3. Pulse out for remote transfer (iEM3110 / iEM3210)
4. Cancellation
5. Confirmation
6. Selection
7. Flashing yellow meter indicator to check accuracy
8. Green indicator: on/off, error

Please see the appropriate Installation Guide for accurate and complete information on the installation of this product.

< >
se.com/au Life is On | Schneider Electric | E-47
Switchboard Manufacturers

Basic Energy Metering


Reference numbers

Kilowatt hour meters – single and three phase

iEM2000 Watt hour meters – 1 pole


Model Description Reference
A9MEM2050

iEM2000 40A direct connect kWh meter A9MEM2000


iEM2010 40A direct connect kWh meter with pulse output A9MEM2010
iEM2050 45A direct connect kWh meter with pulse output and RS485 Modbus A9MEM2050
Note: Class 1 accuracy

E
iEM2100 Watt hour meters – 1 phase digital (direct connect up to 63 A)
Model Description Reference
A9MEM2150

iEM2100 kWh meter A9MEM2100


iEM2105 kWh meter with pulse output A9MEM2105
iEM2110 kWh meter with pulse output and four quadrant measurement A9MEM2110
iEM2150 kWh meter with RS485 Modbus with four quadrant measurement A9MEM2150
Note: Class 1 accuracy

iEM3100 kWh meter – 3 phase digital (direct connect up to 63 A)


Model Description Reference
iEM3100 kWh meter A9MEM3100
A9MEM3155

iEM3110 kWh meter with pulse output A9MEM3110


iEM3115 kWh meter with multi-tariff capability A9MEM3115
iEM3150 kWh meter & electrical parameter with RS485 Modbus A9MEM3150
iEM3155 Advanced multi-tariff kWh meter & electrical parameter with RS485 Modbus A9MEM3155
Advanced multi-tariff kWh meter & electrical parameter with RS485
iEM3155 NMI A9MEM3155-NMI
Modbus,M6-1 Pattern Approved
iEM3165 Advanced multi-tariff kWh meter & electrical parameter with RS485 BACNet A9MEM3165
Note: Class 1 accuracy

iEM3200 kWh meter – 3 phase digital (CT connected)


Model Description Reference
iEM3200 kWh meter A9MEM3200
A9MEM3255

iEM3210 kWh meter with pulse output A9MEM3210


iEM3215 kWh meter with multi-tariff capability A9MEM3215
iEM3250 kWh meter & electrical parameter with RS485 Modbus A9MEM3250 A9MEM3250
iEM3255 Advanced multi-tariff kWh meter & electrical parameter with RS485 Modbus A9MEM3255
Advanced multi-tariff kWh meter & electrical parameter with RS485 Modbus
iEM3255 NMI A9MEM3255-NMI
M6-1 Pattern Approved A9MEM3255-NMI
Advanced multi-tariff kWh meter & electrical parameter with RS485 BACnet
iEM3265 A9MEM3265
A9MEM3265
Advanced multi-tariff kWh meter & electrical parameter with RS485 BACNet
iEM3265 NMI A9MEM3265-NMI
M6-1 Pattern Approved

Note: Class 0.5s accuracy

E-48 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Reference numbers

Kilowatt hour meters – three phase A

iEM3300 kWh meter – 3 phase digital (direct connect up to 125A) B


Model Description Reference
A9MEM3300

iEM3300 kWh meter A9MEM3300


iEM3310 kWh meter with pulse output A9MEM3310
C
iEM3350 kWh meter & electrical parameters with RS485 Modbus A9MEM3350

iEM3355
advanced multi-tariff kWh meter & electrical parameters with RS485
Modbus
A9MEM3355 D
iEM3355 advanced multi-tariff kWh meter & electrical parameter with RS485
Modbus A9MEM3355-NMI
(NMI) NMI M6-1 Pattern Approved E
advanced multi-tariff kWh meter & electrical parameter with RS-485
iEM3365 A9MEM3365
BACnet

Note: Class 1 accuracy F

iEM3400 kWh meters – 3 phase digital (using 0.333V - 1.0V low voltage CTs) G
Model Description Reference
A9MEM3455

iEM3455 kWh meter & electrical parameters with pulse output and RS485 Modbus A9MEM3455
H
iEM3465 kWh meter & electrical parameters with pulse output and RS485 BACnet A9MEM3465

Note: Class 0.5s accuracy


Refer to page E9 for the low voltage CTs I

iEM3500 kWh meters – 3 phase digital (using Rogowski coils)


Model Description Reference
iEM3555 kWh meter & electrical parameters with pulse output and RS485 Modbus A9MEM3555
iEM3565 kWh meter & electrical parameters with pulse output and RS485 BACnet A9MEM3565

Note: Class 0.5s accuracy

Rope-style current transformers for iEM3500 KWh meters


METSECTR25500

Current range (A) CT core length (mm) Diameter when closed (mm) Reference
50 to 5000 250 80 METSECTR25500
300 96 METSECTR30500
460 146 METSECTR46500
600 191 METSECTR60500
900 287 METSECTR90500

EcoStruxure Power Commission (EPC) software


• Simplify commissioning and maintenance
• Set up and test switchboards equipped with smart devices
• Reduce commissioning time
• Speed up FAT and SAT delivery
• Improve preventive maintenance with protection settings/checking, warnings and alarms, trip history, and
maintenance reports

< >
se.com/au Life is On | Schneider Electric | E-49
Switchboard Manufacturers

PM3000 series
General Overview

The PowerLogic PM3000 series power meters are a cost-attractive, feature-rich range of DIN rail- mount-
ed power meters that offers all the measurement capabilities required to monitor an electrical installation.

Ideal for power metering and network monitoring applications that seek to improve the availability and reliability of your electrical
distribution system, the meters are also fully capable of supporting sub-metering and cost allocation applications.

Applications
Cost management applications

• Bill checking to verify that you are only charged for the energy you use
• Aggregation of energy consumption, including WAGES, and cost allocation per area, per usage, per shift or per time within the
E same facility
• Energy cost and usage analysis per zone, per usage or per time period to optimise energy usage

Network management applications

• Metering of electrical parameters to better understand the behaviour of your electrical distribution system
PB108447

METSEPM3250

E-50 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

The solution for Power management solutions A


All markets that can benefit from a solution that includes PowerLogic PM3000 Schneider Electric provides
series meters: innovative power management
solutions to increase your energy B
• Buildings
efficiency and cost savings,
• Industry
maximise electrical network reliability
• Data centres and networks C
and availability, and optimise
• Infrastructure (e.g. airports, road tunnels, telecom) electrical asset performance.
D
Benefits Conformity of standards
Optimise your energy consumption & enable energy efficiency practices • IEC 61557-12 • IEC 62053-23 E
• Collect and analyse energy consumption data from each area for each type of • IEC 61326-1 • EN 50470-1
load or circuit
• IEC 62052-11 • EN 50470-3 F
• Gain an accurate understanding of business expenses by allocating the
• IEC 62053-21 • IEC 61010-1
energy-related costs
• IEC 62053-22 • EN 55022
• Identify savings opportunities G
• Use information to implement actions designed to reduce energy consumption

H
Competitive advantages
Connectivity advantages
• Programmable digital input I
- External tariff control signal (4 tariff)
- Remote reset partial counter
- External status like breaker status
- Collect WAGES pulses
• Programmable digital output
- Alarm (PM3255)
- KWh pulses
• Graphic LCD display
• Modbus RS-485 with screw terminals
Multi-tariff capability
The PM3000 series allows users to arrange KWh consumption in four different
registers. This can be controlled by:
• Digital inputs. Signal can be provided by PLC or utilities
• Internal clock programmable by HMI
• Through communication

This function allows users to:


• Make tenant metering for dual source applications to differentiate backup
source or utility source
• Understand well the consumption during peak time and off-peak time,
weekdays and weekends, holiday and working days etc.
• Follow up feeders consumption in line with utility tariff rates

< >
se.com/au Life is On | Schneider Electric | E-51
Switchboard Manufacturers

PM3000 series
Functions and characteristics

PM3000 series feature selection

PM3200 PM3210 PM3250 PM3255

Performance standard
IEC61557-12 PMD/Sx/K55/0.5
General
Use on LV and HV systems
Number of samples per cycle 32 32 32 32
CT input 1A/5A
VT input

E Multi-tariff 4 4 4 4
Multi-lingual backlit display
Instantaneous rms values
Current, voltage Per phase and average
Active, reactive, apparent power Total and per phase
Power factor Total and per phase
Energy values
Active, reactive and apparent energy; import and export
Demand value
Current, power (active, reactive, apparent) demand; present
Current, power (active, reactive, apparent) demand; peak
Power quality measurements
THD Current and voltage
Data recording
Min/max of the instantaneous values
Power demand logs
Energy consumption log (day, week, month)
Alarms with timestamping 5 5 15
Digital inputs/digital outputs 0/1 44594
Communication
RS-485 port
Modbus protocol
Commercial reference number METSEPM3200 METSEPM3210 METSEPM3250 METSEPM3255

See your Schneider Electric representative for complete ordering information.

PM3200 power meters (Class 0.5s)


Model Description Reference
PM3200 Power meter – basic METSEPM3200
PM3210 Power meter with pulse output METSEPM3210
PM3250 Power meter with RS485 modbus METSEPM3250
PM3255 Power meter with 2 digital inputs, 2 digital outputs, RS485 modbus, memory for load profile METSEPM3255

E-52 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

PM3000 technical specifications A


Type of measurement True rms up to the 15th harmonic on three-phase (3P,3P+N) and single-phase AC systems. 32 samples per cycle
Measurement accuracy B
Current with x/5A CTs 0.3 % from 0.5 A to 6 A
Current with x/1A CTs 0.5 % from 0.1 A to 1.2 A
C
Voltage 0.3 % from 50 V to 330 V (Ph-N), from 80 V to 570 V (Ph-Ph)
Power factor ±0.005 from 0.5 A to 6 A with x/5 A CTs; from 0.1A to 1.2 A with x/1 A CTs and from 0.5 L to 0.8 C
Active/Apparent Power with x/5A CTs Class 0.5 D
Active/Apparent Power with x/1A CTs Class 1
Reactive power Class 2
Frequency 0.05 % from 45 to 65 Hz
E
Active energy with x/5A CTs IEC 62053-22 Class 0.5s
Active energy with x/1A CTs IEC 62053-21 Class 1 F
Reactive energy IEC 62053-23 Class 2
Data update rate
Update rate 1s G
Input-voltage characteristics
50 V to 330 V AC (direct / VT secondary Ph-N) 80 V to 570 V AC (direct / VT secondary Ph-Ph) up to 1 MV AC (with
Measured voltage external VT) H
Frequency range 45 Hz to 65 Hz
Input-current characteristics
CT primary Adjustable from 1 A to 32767 A
I
CT secondary 1 A or 5 A
Measurement input range with x/5A CTs 0.05 A to 6 A
Measurement input range with x/1A CTs 0.02 A to 1.2 A
Permissible overload 10 A continuous, 20 A for 10s/hour
Control Power
AC 100/173 to 277/480 V AC (+/-20%), 3 W/5 VA; 45 Hz to 65 Hz
DC 100 to 300 V DC, 3 W
Input
Digital inputs (PM3255) 11 to 40 V DC, 24 V DC nominal, <=4mA maximum burden, 3.5kVrms insulation
Output
Digital output (PM3210) Optocoupler, polarity sensitive, 5 to 30 V, 15 mA max, 3.5kVrms insulation
Digital outputs (PM3255) Solid state relay, polarity insensitive, 5 to 40 V, 50 mA max, 50 Ω max, 3.5kVrms insulation

< >
se.com/au Life is On | Schneider Electric | E-53
Switchboard Manufacturers

PM3000 series
Functions and characteristics
Mechanical characteristics
Weight 0.26 kg

IP degree of protection (IEC 60529) IP40 front panel, IP20 meter body

Dimension 90 x 95 x 70 mm

Environmental conditions
Operating temperature -25 ºC to 55 ºC

Storage temperature -40 ºC to 85 ºC

Humidity rating 5 to 95% RH at 50 ºC (non-condensing)

Pollution degree 2

Metering category III, for distribution systems up to 277/480 V AC

E Dielectric withstand As per IEC61010-1, Doubled insulated front panel display

Altitude 3000 m max

Electromagnetic compatibility
Electrostatic discharge Level IV (IEC 61000-4-2)

Immunity to radiated fields Level III (IEC 61000-4-3)

Immunity to fast transients Level IV (IEC 61000-4-4)

Immunity to surge Level IV (IEC 61000-4-5)

Conducted immunity Level III (IEC 61000-4-6)

Immunity to power frequency magnetic fields 0.5mT (IEC 61000-4-8)

Conducted and radiated emissions Class B (EN 55022)

Safety
CE as per IEC 61010-1g

Communication
RS-485 port Half duplex, from 9600 up to 38400 baud, Modbus RTU (double insulation)

Display characteristics
Dimensions (VA) 43 mm x 34.6 mm

Display resolution 128 x 96 dots

Standard compliance
IEC 61557-12, EN 61557-12
IEC 61010-1, UL 61010-1
IEC 62052-11, IEC 62053-21, IEC 62053-22, IEC 62053-23
EN 50470-1, EN 50470-3

g Protected throughout by double insulation

E-54 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

PM3200 series front of meter A

B
PB105440

Front of meter parts


1. Control power C
2. Display with white backlight
3. Flashing yellow meter indicator (to check
accuracy) D
4. Pulse output for remote transfer (PM3210)
5. Cancellation
6. Confirmation E
7. Up
8. Down
F

H
PM3200 series dimensions
I
PB105302

PB105447

PM3200 top and lower flaps

PM3200 series easy installation


PB105446

Please see the appropriate Installation Guide for accurate and complete information on the installation of this product.

< >
se.com/au Life is On | Schneider Electric | E-55
Switchboard Manufacturers

PowerLogic™ PowerTag Energy Series


General Overview

PowerTag Energy is a wireless-communication energy sensor


PowerTag Energy is designed specifically for Energy Management, Load Monitoring and Power
Availability applications. Associated to a concentrator or a gateway, PowerTag Energy provides
a full wireless class 1 solution to monitor energy at any level of a distribution panel.

Applications:
• Monitors your electrical installation from main incomer down to load level
• Suitable for various businesses, buildings, industrial and residential applications
E with easy integration in upper systems
• Supports and enables Energy Efficiency programs and standards such as:
• European Energy Efficiency Directive (EED)
- Energy Performance of Buildings Directive (EPBD)
- IEC 60364-8-1 “Low Voltage Electrical installations - Energy Efficiency”
- EN 17267 “Energy Measurement and Monitoring plan”
- ISO 50001 “Energy Management System”
A9MEM1570

A9MEM1571

LV434020

PowerTag Energy Monoconnect 250 A (M250)

PowerTag Energy PowerTag Energy


Flex 63 A (F63) PhaseNeutral 63 A (P63)
A9MEM1590
A9MEM1580

A9MEM1521

PowerTag Energy Rex 160 A (F160) PowerTag Energy Monoconnect 63A (M63) PowerTag Energy Rope 2000 A (R2000)

PowerTag Energy

E-56 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

The solution for Energy management system A


Markets that benefit from a solution that includes PowerLogic PowerTag Energy To get the most effective use from
series: your Schneider Electric measurement B
• Residential and metering devices, we offer
a range of dedicated gateways/
• Small business
concentrators depending on your C
• Medium & large buildings application.
• Industrial sites
D
Advantages
• Wireless-communication
Benefits E
• Range up to 2000 A
PowerTag Energy sensor incorporates all features required to perform accurate
real-time measurements (U, V, I, P, PF) and energy values up to 2000 A. • Voltage loss alarming
• Class 1 accuracy
F
Different designs of PowerTag Energy are available to ensure it fits the protective • Compact design
device on which it is mounted. G
• Easy installation and
commissioning
• PowerTag Energy Monoconnect (M): can be mounted directly on the device, no
• Scalable solution H
additional wiring is required
• Perfect for retrofit or new panels
• PowerTag Energy PhaseNeutral (P): for DIN offers with 9 mm pitch between
phase and neutral I
Conformity of standards
• PowerTag Energy Flex (F): can be mounted on a wide range of protective • IEC 61557-12
devices thanks to its design • IEC 61010-1
• IEC 61010-2-030
• PowerTag Energy Rope (R) thanks to its openable current sensors can
be easily installed on busbars or wires in new installations and in retrofit • IEC 61326-1
applications • ETSI EN 300 328

• PowerTag Energy sensor is acting as an autonomous meter. Energy counters


are stored inside PowerTag Energy sensor

< >
se.com/au Life is On | Schneider Electric | E-57
Switchboard Manufacturers

PowerLogic™ PowerTag Energy Series


Functions and characteristics

Feature selection

A9MEM15•• A9MEM15•• A9MEM15•• A9MEM1580 LV434020/LV434021


Product name M63 P63 F63 F160 M250
Max current (I Max) A 63 63 63 160 250
Starting current (Ist) 40 mA 40 mA 40 mA 100 mA 160 mA
E Design Monoconnect PhaseNeutral Flex Flex Monoconnect
Mounting type On device On device On wires On wires On device
Current sensors type Solid core Solid core Solid core Solid core Solid core
Poles 1P + W / 1P+N / 3P / 1P+N / 3P+N 1P+N / 3P / 3P+N 3P / 3P+N 3P / 3P+N
3P+N
Self-powered
Voltage (L-N) Depends on ref 200 - 240 V AC Depends on ref 100 - 277 V AC 230 V AC
Measurements*
Nb quadrant 2 2 2 4 4
Active Energy Class 1 Class 1 Class 1 Class 1 Class 1
Reactive Energy
Apparent Energy
Active Power
Reactive Power
Apparent Power
Power Factor
Frequency
Current and Voltage
* Data availability depending on the concentrator / gateway

LV434022/LV434023 A9MEM1590 A9MEM1591 A9MEM1592 A9MEM1593


Product name M630 R200 R600 R1000 R2000
Max current (I Max) A 630 200 600 1000 2000
Starting current (Ist) 400 mA 120 mA 400 mA 600 mA 1.2 A
Design Monoconnect Rope Rope Rope Rope
Mounting type On device On wires On wires On wires On wires
Current sensors type Solid core Split core Split core Split core Split core
Poles 3P / 3P+N 3P / 3P+N 3P / 3P+N 3P / 3P+N 3P / 3P+N
Self-powered
Voltage (L-N) 230 V AC 100 - 277 V AC 100 - 277 V AC 100 - 277 V AC 100 - 277 V AC
Measurements*
Nb quadrant 4 4 4 4 4
Active Energy Class 1 Class 1 Class 1 Class 1 Class 1
Reactive Energy
Apparent Energy
Active Power
Reactive Power
Apparent Power
Power Factor
Frequency
Current and Voltage
* Data availability depending on the concentrator / gateway

E-58 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

Connection Possibilities A
Source Source
1 PowerTag Energy • When breaker is OFF,
Connected Upstream PowerTag Energy is B
de-energized. PowerTag
Power Flow

Power Flow
(U and I)
Energy sends Voltage loss
alarm before complete stop.
• When breaker is OFF, C
PowerTag Energy remains
energized.
PowerTag Energy
Connected Downstream D
Load Load
2 (U and I)

Load
3
PowerTag Energy Load
• When breaker is OFF,
F
Connected Downstream
PowerTag Energy remains
(U and I)
energized.

G
Power Flow
• When breaker is OFF,
Power Flow

PowerTag Energy is
de-energized. PowerTag
Energy sends Voltage
loss alarm before com- H
plete stop. PowerTag Energy
Connected Upstream
4 (U and I)
Source Source
I
Note:
• In association with a contactor, a Variable Speed Drive or a motor starter: PowerTag Energy can ONLY be installed UPSTREAM these devices.
• Some PowerTag Energy can be installed either on the TOP or on the BOTTOM of the protective devices.
• Check the possible mounting position as indicated in the “Catalog numbers” chapter.

Connection (Voltage and Current) Features


Upstream • Energy management: consumption in kWh
• Load monitoring: real-time measurements
Downstream • Energy management: consumption in kWh
Preferred installation to take full benefit of voltage loss alarming in diagnosing • Load monitoring: real-time measurements
the load
• Power availability: voltage loss alarming

Main associated concentrators / gateways (*)


For Commercial & Building applications
PowerTag Link PowerTag Link HD Smartlink SI B
PB119988

A9XMWD20

A9XMWD100

PB113286

A9XMWD20 (1) A9XMWD100 A9XMZA08


(1) Replace Smartlink SI D (A9XMWA20)

For Small Business For Residential For Industrial applications


applications applications
PowerTag Link C Wiser IP Module Harmony Hub
PowerTag Link C+ Wiser IP Module+
A9XMWD20

ZBRN1
A9XELC10

EER31800

A9XELC10 EER31800 ZBRN1, ZBRN2,


(*) Refer to Selection Guide for complete compatibility pages 95 to 102.
Refer to the concentrator catalogs for more information (CA907030, CA907032, CA907035).

< >
se.com/au Life is On | Schneider Electric | E-59
Switchboard Manufacturers

PowerLogic™ PowerTag Energy


General Overview

63 A
IEC 61557-12 PMD-I/DD/K55/1
As per the above standard:
With its compact design and innovative concept, PowerTag Energy 63 A fits directly on the protective device and as a result has
no impact on DIN rail occupancy and switchboard size.
It is therefore well adapted to be mounted from head of group down to final circuits.
Since voltage and current are measured directly at the same point on the circuit to be monitored, it provides accurate
measurement and relevant information such as voltage loss.
PowerTag Energy is compatible with SE product ranges as per the selection guide CA908058.
E
Main characteristics
PowerTag Energy measures the following values in accordance with the IEC 61557-12 standard PMD-I/DD/K55/1:
• Energy:
- Active energy (kWh): total and partial, delivered and received.
• Real-time measurement values:
- Voltages (V): phase-to-phase and phase-to-neutral.
- Currents (A): per phase.
- Power:
- Active power (W): total and per phase.
- Apparent power (VA): total.
- Power factor.
• Voltage loss alarms:
- PowerTag Energy sends a “voltage loss” alarm and the current-per-phase value before being de-energized.
- At “voltage loss”, PowerTag Energy adds an overload alarm if the current is higher than the rated current of the associated
protective device.
Note: Functions listed above depends on Concentrator/Gateway.
PB104437

PB107143

PB120058

PowerTag Energy
Flex 63 A (F63)
A9MEM1522

A9MEM1572

PowerTag Energy
Monoconnect 63 A (P63)

E-60 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

Product selection A
Neutral position
Some references of PowerTag Energy 63 A (Monoconnect and PhaseNeutral) exist in Top or Bottom version. B
This is linked to the position of the neutral of the PowerTag Energy.
C

D
PowerTag Energy
"Top" • Designed to be
mounted on the
Bottom of the circuit
E
• Designed to be breaker.
mounted on the Top F
of the circuit breaker.
PowerTag Energy
"Bottom" G

H
Note:
• Some PowerTag Energy can be installed either on the TOP or on the BOTTOM of the protective devices.
• Check the possible mounting position as indicated in the “Catalog numbers” chapter. I
• In association with a contactor, a Variable Speed Drive or a motor starter: PowerTag Energy can ONLY be installed UPSTREAM
these devices.

Number of poles
Choose the PowerTag Energy according to the number of poles of the protective device: one PowerTag Energy per protective
device.
Ex.: 3 Pole PowerTag Energy 63 A for a 3 pole CB.

< >
se.com/au Life is On | Schneider Electric | E-61
Switchboard Manufacturers

PowerLogic™ PowerTag Energy


Functions and characteristics

Main characteristics
Rated voltage 1P+N / 1P+W Un Phase-to-neutral 200… 240 V AC ± 20 %

3P Un Phase-to-phase 380… 415 V AC ± 20 %

3P+N Un Phase-to-neutral 220… 240 V AC ± 20 %

Phase-to-phase 380… 415 V AC ± 20 %

A9MEM1543 Un Phase-to-phase 200… 240 V AC ± 20 %

A9MEM1564 Un Phase-to-neutral 100… 127 V AC ± 20 %

A9MEM1574 Un Phase-to-neutral 120… 137 V AC ± 20 %

Phase-to-phase 208… 240 V AC ± 20 %


E
Frequency 50/60 Hz

Maximum current Imax 63 A

Basic current Ib 0.416667

Saturation current 130 A


Maximum consumption 1P+N y 1 VA

3P/3P+N y 2 VA

Starting current Ist 40 mA

Additional characteristics
Operating temperature -25°C to +60°C

Storage temperature -40°C to +85°C

Overvoltage category As per IEC 61010-1 Cat. III

Measuring category As per IEC 61010-2-030 Cat. III

Pollution degree 3

Altitude y 2000 m
Degree of protection Device only IP20

IK 5

Radio-frequency communication
ISM band 2.4 GHz 2.4 GHz to 2.4835 GHz

Channels As per IEEE 802.15.4 11 to 26

Isotropic Radiated Power Equivalent (EIRP) 0 dBm

Maximum transmission time < 5 ms

Channel occupancy Messages sent every 5 seconds minimum

Characteristics of measuring functions


Function Symbol Performance category as per IEC Measuring range
61557-12 (PMD-I/DD/K55/1)
Class
Active power P 1 9 W to 63 kW

Active energy Ea 1 Total and partial 0 to 99999999.9 kWh

Current I 1 40 mA to 63 A

Voltage U 0.5 Un ± 20 %

Power factor PFA 1 0 to 1

E-62 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

less than or equal to 63 A


A9MEM1520

A9MEM1521
A
Commercial Type Mounting Description
reference number

A9MEM1520 A9MEM1521 A9MEM1520 1P+wire Top or bottom PowerTag Energy M63 1PW B
A9MEM1521 Top PowerTag Energy M63 1PN T
A9MEM1540

A9MEM1522

1P+N
A9MEM1522 Bottom PowerTag Energy M63 1PN B C
A9MEM1540 Top or bottom PowerTag Energy M63 3P
3P
A9MEM1540 A9MEM1522 A9MEM1543 (1) PowerTag Energy M63 3P 230V LL
D
A9MEM1541 Top PowerTag Energy M63 3PN T
A9MEM1543

3P+N
A9MEM1542 Bottom PowerTag Energy M63 3PN B
E
Designed to fit the following devices: iC60, Reflex iC60, DT60, iID.
A9MEM1543 For additional information and the list of Schneider Electric compatible devices and Concentrators/Gateways, refer
to the Selection Guide pages 95 to 102.
F
A9MEM1541

A9MEM1542

(1) Not compatible with Acti9 Smartlink SI D (A9XMWA20) and Acti9 Smartlink SI B (A9XMZA08)

G
A9MEM1541 A9MEM1542
PowerTag Energy PhaseNeutral 63 A
H
Commercial reference numbers
PowerTag Energy for Acti9 and Multi9 PhaseNeutral offers: «Single-terminal» circuit
A9MEM1561

A9MEM1562

A9MEM1563

breakers, RCDs and switches at pitch of 9 mm between phase and neutral, rating I
less than or equal to 63 A.

Commercial Type Mounting Description


reference number
A9MEM1561 A9MEM1562 A9MEM1563
A9MEM1561 1P+N Top PowerTag Energy P63 1PN T

A9MEM1562 1P+N Bottom PowerTag Energy P63 1PN B


PowerTag Energy P63 1PN B RCBO
A9MEM1571

A9MEM1572

A9MEM1563 1P+N RCBO Bottom 18mm


A9MEM1571 3P+N Top PowerTag Energy P63 3PN T

A9MEM1572 3P+N Bottom PowerTag Energy P63 3PN B

Designed to fit the following devices: DT40, iDPN, C40, i DPN Vigi.
For additional information and the list of Schneider Electric compatible devices and Concentrators/Gateways, refer
A9MEM1571 A9MEM1572 to the Selection Guide pages 95 to 102.

PowerTag Energy Flex 63 A Commercial reference numbers


A9MEM1560

A9MEM1564

A9MEM1573

PowerTag Energy Flex for other devices and specific installations, rating less than or equal to 63 A.

Commercial Type Mounting Description


reference number
A9MEM1560 1P+N Top or bottom PowerTag Energy F63 1PN
A9MEM1560 A9MEM1564 A9MEM1573
A9MEM1564 (2) 1P+N Top or bottom PowerTag Energy F63 1PN 110V

A9MEM1573 (2) 3P Top or bottom PowerTag Energy F63 3P


A9MEM1570

A9MEM1574

A9MEM1570 3P+N Top or bottom PowerTag Energy F63 3PN

A9MEM1574 (2) 3P+N Top or bottom PowerTag Energy F63 3PN 127/220V

Designed to fit the following devices: Vigi iDT40, Vigi iC40, Vigi iC60, iC60 double terminal, iID double terminal.
For additional information and the list of Schneider Electric compatible devices and concentrators/ gateways, refer
to the Selection Guide pages 95 to 102.

A9MEM1570 A9MEM1574 (2) Not compatible with Acti9 PowerTag Link C (A9XELC10), Smartlink SI D (A9XMWA20) and Smartlink SI B
(A9XMZA08)

Contact your Schneider Electric representative for complete ordering information.

< >
se.com/au Life is On | Schneider Electric | E-63
Switchboard Manufacturers

PowerLogic™ PowerTag Energy


Functions and characteristics

PowerTag Energy Monoconnect 63 A connection


Stripping Copper cables
length
Rigid Flexible Flexible with ferrule
DB407926

DB122945

DB112804

DB123553

DB112805

DB123554

DB123008
18 mm 1.5 to 16 mm2 2 x 1.5 to 2.5 mm2 1.5 to 16 mm2 2 x 1.5 to 2.5 mm2 1.5 to 16 mm2 2 x 1.5 to 2.5 mm2
AWG: 16...6 AWG: 16...14 AWG: 16...6 AWG: 16...14 AWG: 16...6 AWG: 16...14

Mounting with 18 mm ferrule recommended.

PowerTag Energy Monoconnect 63 A dimensions (mm)


DB407922

DB407924

DB407923

DB407925
ø 8.5 ø 8.5 ø 8.5 ø 8.5
43 43 43 43

4.5 10.5 4.5 10.5 4.5 4.5


10.5 10.5
?] 18 18
16 16 16 16
1000

18 36 54 72

1P+wire 1P+N 3P 3P+N

PowerTag Energy Monoconnect 63 A weight

Type Weight (g)


1P+wire 16.4
1P+N 17.5
3P 28
3P+N 35

Please refer to PowerTag Energy 63 A Installation Sheet for accurate and complete information on the installation of this product.

E-64 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

PowerTag Energy PhaseNeutral 63 A connection A


Copper cables
Rigid Flexible Flexible with ferrule
B
DB428718

DB123553

DB112805

DB123554

DB123008
DB122945

DB112804
C

1.5 to 16 mm2 2 x 1.5 to 2.5 mm2 1.5 to 16 mm2 2 x 1.5 to 2.5 mm2 1.5 to 16 mm 2 x 1.5 to 2.5 mm2
D
AWG: 16...6 AWG: 16...14 AWG: 16...6 AWG: 16...14 AWG: 16...6 AWG: 16...14

Stripping length: respect the stripping length stated on the device the PowerTag Energy is associated with.
E

PowerTag Energy PhaseNeutral 63 A dimensions (mm) G


18 20 20 54 19.5
H
DB428606
DB428605

18
I
ø 8.5
44.5
ø 8.5
43

200
200

9 28.5 27

8 8
3
11 11
18
3 5 3.5
18 48 42
5
9

1P+N/ 1P+N RCBO 1P+N 1P+N RCBO


54
11
8
3P+N

PowerTag Energy PhaseNeutral 63 A weight


Type Weight (g)
1P+N 18

3P+N 48

Please refer to PowerTag Energy 63 A Installation Sheet for accurate and complete information on the installation of this product.

< >
se.com/au Life is On | Schneider Electric | E-65
Switchboard Manufacturers

PowerLogic™ PowerTag Energy


Functions and characteristics

PowerTag Energy Flex 63 A connection


Copper cables
DB428719

Rigid Flexible Flexible with ferrule

DB123008
DB122945

DB112804

DB123553

DB112805

DB123554
1.5 to 16 mm2 2 x 1.5 to 2.5 mm2 1.5 to 16 mm2 2 x 1.5 to 2.5 mm2 1.5 to 16 mm 2 x 1.5 to 2.5 mm2
AWG: 16...6 AWG: 16...14 AWG: 16...6 AWG: 16...14 AWG: 16...6 AWG: 16...14

E Stripping length: respect the stripping length stated on the device the PowerTag Energy is associated with.

PowerTag Energy Flex 63 A dimensions (mm)

18 20 54 19.5
DB428604
DB428603

DB428604_2

54 19.5

18
ø 8.5 ø .85
44.5 43
18
ø 8.5
43

200 200

200

70 70

70
12
12

12
3 1 3 1

3 1

1P+N 3P 3P+N

PowerTag EnergyFlex 63 A weight


Type Weight (g)
1P+N 16
3P 38
3P+N 40

Please refer to PowerTag Energy 63 A Installation Sheet for accurate and complete information on the installation of this product.

E-66 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

< >
se.com/au Life is On | Schneider Electric | E-67
Switchboard Manufacturers

PowerLogic™ PowerTag Energy


General Overview

Flex 160 A
IEC 61557-12 PMD-II/DD/K70/1
As per the above standard:
With its flex design this PowerTag Energy can be used on many products or group of loads up to 160 A on 3P or 3P+N networks.
Its removable spring connector for voltage picking facilitates its installation, and shapes for brackets allows to mount and maintain
it where needed in a panel.

E Main characteristics
PowerTag Energy Flex 160 A measures the following values in accordance with the IEC 61557-12 standard PMD-II/DD/K70/1:
• Energy (4 quadrants):
- Active energy (kWh): total and partial, delivered and received.
- Active energy per phase (kWh): total and partial, delivered and received.
- Reactive energy (kVARh): total and partial, delivered and received.
- Reactive energy per phase (kVARh): total and partial, delivered and received.
- Apparent energy (kVAh): total and partial.
- Apparent energy per phase (kVAh): total and partial.
• Real-time measurement values:
- Voltages (V): phase-to-phase (U12, U23, U31) and phase-to-neutral (V1N, V2N, V3N).
- Currents (A): per phase (I1, I2, I3), calculated neutral current when connected (IN) .
- Power:
- Active power (W): total and per phase.
- Reactive power (VAR): total and per phase.
- Apparent power (VA): total and per phase.
- Frequency (Hz).
- Power factor: total and per phase.
• Voltage loss alarms:
- PowerTag Energy Flex sensor sends a “voltage loss” alarm and the current-per-phase value before being de-energized.
- At “voltage loss”, PowerTag Energy Flex adds an overload alarm if the current is higher than the rated current of the
associated protective device
Note: Functions listed above depends on Concentrator/Gateway.
A9MEM1580

PowerTag Energy Flex 160 A

E-68 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

Installation A
PowerTag Energy Flex 160 A can be installed in a panel directly on cables or busbars, associated to a product or not. Voltage
pickings removable spring terminal has to be wired by 1 copper wire per phase with following characteristics:
B

Wire Range
C
Solid Stranded Stranded with terminal ends
0.2...1.5 mm² 0.2...2.5 mm² 0.25...1.5 mm²
D
24...16 AWG 24...14 AWG 24...16 AWG

E
Neutral picking shall be connected to have phase-to-neutral voltages, energy per phase and power per phase provided.

PowerTag Energy Flex 160 A is mainly advised for ComPact NSXm, ComPact INS160, F
Acti9 NG125, Acti9 C120, PowerPact B, TeSys GV4, and all other devices with a rating between 63 A and 160 A.

H
PB120394

< >
se.com/au Life is On | Schneider Electric | E-69
Switchboard Manufacturers

PowerLogic™ PowerTag Energy


Functions and characteristics

Technical specifications
Main characteristics (as per IEC 61557-12)
Rated voltage Un Phase-to-neutral 100...277 V AC ± 20 %

Phase-to-phase 173...480 V AC ± 20 %

Frequency 50/60 Hz

Maximum current Imax 160 A

Maximum operating current 1.2 x Imax

Saturation current 2 x Imax

Maximum consumption 3 VA

Starting current Ist 100 mA


E
Basic current Ib 25 A

Additional characteristic
Operating temperature -25 °C to +70 °C

Storage temperature -40 °C to +85 °C

Overvoltage category As per IEC 61010-1 Cat. IV

Measuring category As per IEC 61010-2-030 Cat. IV

Pollution degree 3

Altitude Up to 2000 m without derating (1)


Degree of protection device IP20

IK05

Radio-frequency communication
ISM band 2.4 GHz 2.4 GHz to 2.4835 GHz

Channels As per IEEE 802.15.4 11 to 26

Isotropic Radiated Power Equivalent (EIRP) 0 dBm

Maximum transmission time < 5 ms

Channel occupancy For 1 device messages sent every 5 seconds

Characteristics of measuring functions


Function Symbol Performance category as per IEC 61557-12 Measuring range
(PMD-II/DD/K70/1)
Class Measuring range
Total active power P 1 2.5 to 160 A 24 W (8 W) to 192 kW
(Active power per phase)
Total reactive power QA 2 30 VAR (10 VAR) to 192 kVAR
(Reactive power per phase)
Total apparent power SA 2 38 VA (13 VA) to 192 kVA
(Apparent power per phase)
Active Energy: Ea 1 0 to 281.109 kWh
per phase, total, partial, delivered and received
Reactive energy: ErA 2 0 to 281.109 kVARh
per phase, total, partial, delivered and received
Apparent energy: EapA 2 0 to 281.109 kVAh
per phase, total, partial
Frequency f 0.5 50 / 60 Hz ± 2 % 45 to 65 Hz

Phase current I 1 5 to 160 A 100 mA to 320 A


Neutral current INC 2
Voltages (Line to Line) U 0.5 Un ± 20 % 138 to 576 V AC

Power factor PFA 1 From 0.5 inductive to 0.8 capacitive -1 to 1


(per phase, total)

(1) Above 2000 m, please consult Schneider Electric.

E-70 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

PowerTag Energy Flex 160 A A


Commercial reference numbers
A9MEM1580

Commercial reference Type Description


number
B
A9MEM1580 F160 3P/3P+N PowerTag Energy Flex 160 A 3P / 3P+N

C
For the list of Schneider Electric compatible devices and concentrators, refer to the
Selection Guide pages 95 to 102.
Contact your Schneider Electric representative for complete ordering information. D

E
PowerTag Energy Flex 160 A dimensions
mm F
DB436016

in

38.9
1.53
G
21.4
0.83

ø17 I
ø0.67
DB436017

<%
J7KK

27 27
1.06 1.06
90.8
3.57

PowerTag Energy Flex 160 A weight


Type Weight (g)
F160 3P/3P+N 100

Please refer to PowerTag Energy Flex 160 A Installation Sheet for accurate and complete information on the installation of this product.

< >
se.com/au Life is On | Schneider Electric | E-71
Switchboard Manufacturers

PowerLogic™ PowerTag Energy


General Overview

Monoconnect 250 A & 630 A


IEC 61557-12 PMD-II/DD/K70/1
As per the above standard:
PowerTag Energy M250/M630 is designed for Molded Case Circuit Breakers and Switches (ComPact and TeSys) for 3P and
3P+N electrical networks. This PowerTag Energy is mounted directly on the bottom side of the circuit breaker or the Vigi add-
on if any. Thanks to its integrated design, it does not require any specific wiring, and is compatible with the same connection
accessories than the device it is mounted on.

E Main characteristics
PowerTag Energy M250/M630 measures the following values in accordance with the IEC 61557-12 standard PMD-II/DD/K70/1:
• Energy (4 quadrants):
- Active energy (kWh): total and partial, delivered and received.
- Active energy per phase (kWh): total.
- Reactive energy (kVARh): partial, delivered and received.
• Real-time measurement values:
- Voltages (V): phase-to-phase (U12, U23, U31) and phase-to-neutral (V1N, V2N, V3N).
- Currents (A): per phase (I1, I2, I3).
- Power:
- Active power (W): total and per phase.
- Reactive power (VAR): total.
- Apparent power (VA): total.
- Frequency (Hz).
- Power factor.
• Voltage loss alarms:
- PowerTag Energy sends a “voltage loss” alarm and the current-per-phase value before being de-energized.
- At “voltage loss”, PowerTag Energy adds an overload alarm if the current is higher than the rated current of the associated
protective device.
Note: Functions listed above depends on Concentrator/Gateway.
LV434020

PowerTag Energy Monoconnect 250 A

E-72 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

Installation A
The module is self-powered and is installed for fixed devices directly on the bottom side of the circuit
breaker or Vigi add-on terminals. For plug-in devices, it has to be installed on the base itself, top or B
bottom.

PowerTag Energy M250/M630 3P has to be used with 3P devices, and an external neutral voltage tap C
is provided in case of the installation has a neutral to provide phase-to-neutral voltages, active energy
per phase and power per phase.
D
PowerTag Energy M250/M630 3P+N has to be used with 4P devices and with ComPact INS/INV
switches.
E
Powertag 3P Powertag 3P+N
N L1 L2 L3 N L1 L2 L3 F

G
ComPact ComPact
NS, NSX, NS, NSX,
INS, INV INS, INV
PowerTag NSX
H
PowerTag NSX
DB432583

DB432582

PowerTag M250/M630 modules are compatible with ComPact NSX100/160/250, ComPact NSX400/630,
ComPact INS250-100A to 250A, ComPact INS320/400/500/630, ComPact INV100/160/200/250,
ComPact INV320/400/500/630, ComPact NS100/160/250, ComPact NS400/630, TeSys GV5, TeSys GV6
and TeSys GV7.

In case of retrofit, following points have to been checked:


• Clearance to be able to add PowerTag Energy module and to respect bending radius of cables.
• Condition of power connectors: to be replaced if damaged.
• Tightening torques depending of the connector used.
LV434020

< >
se.com/au Life is On | Schneider Electric | E-73
Switchboard Manufacturers

PowerLogic™ PowerTag Energy


Functions and characteristics

Technical specifications
Main characteristics
Rated voltage Un Phase-to-neutral 230 VAC ± 20 %

Phase-to-phase 400 VAC ± 20 %

Frequency 50/60 Hz

Maximum current Imax 250 A / 630 A

Maximum operating current 1.2 x Imax

Saturation current 2 x Imax

Maximum consumption 3.7 VA

Starting current Ist 160 mA / 400 mA


E
Basic current Ib 40 A / 100 A

Additional characteristic
Operating temperature -25 °C to +70 °C

Storage temperature -50 °C to +85 °C

Overvoltage category As per IEC 61010-1 Cat. IV

Measuring category As per IEC 61010-2-030 Cat. III

Pollution degree 3

Altitude Up to 2000 m without derating (1)


Degree of protection device IP20

IK07

Radio-frequency communication
ISM band 2.4 GHz 2.4 GHz to 2.4835 GHz

Channels As per IEEE 802.15.4 11 to 26

Isotropic Radiated Power Equivalent (EIRP) 0 dBm

Maximum transmission time < 5 ms

Channel occupancy For 1 device messages sent every 5 seconds

Characteristics of measuring functions


Function Symbol Performance category as per IEC 61557-12 Measuring range (250 A / 630 A)
(PMD-II/DD/K70/1)
Class Measuring range (250 A / 630 A)
Total active power (Active power P 1 4 to 250 A / 10 to 630 A 88 W (29 W) to 416 kW /
per phase)
222 W (74 W) to 1048 kW

Total reactive power QA 2 88 VAR to 416 kVAR /

221 VAR to 1048 kVAR

Total apparent power SA 2 88 VA to 416 kVA / 221 VA to 1048


kVA
Active Energy: Ea 1 0 to 281.109 kWh

per phase, total, partial

Total reactive Energy ErA 2 0 to 281.109 kVARh

Frequency f 1 45 to 55 Hz 45 to 65 Hz

Phase current I 1 8 to 250 A / 20 to 630 A 160 mA to 500 A / 400 mA to 1260 A

Voltages (Line to Line) U 0.5 Un ± 20 % 320 to 480 VAC

Power factor PFA 1 From 0.5 inductive to 0.8 capacitive -1 to 1

(1) Above 2000 m, please consult us.

E-74 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

PowerTag Energy Monoconnect 250 A & 630 A A


LV434020

LV434021
Commercial reference numbers
Commercial Type Description Connection adapter
reference for mounting on
B
number plug-in base only
LV434020 M250 3P PowerTag Energy 250 A 3P LV429306 C
LV434023
LV434022

LV434021 M250 3P+N PowerTag Energy 250 A 3P+N LV429307

LV434022 (1) M630 3P PowerTag Energy 630 A 3P LV432584


D
LV434023 (1) M630 3P+N PowerTag Energy 630 A 3P+N LV432585

E
For the list of Schneider Electric compatible devices and concentrators, refer
to the Selection Guide pages 95 to 102.
F
Contact your Schneider Electric representative for complete ordering
PB120429

information.

(1) For plug-in devices only: when plate mounted, need to add an intercalary wedging plate under
G
the PowerTag Energy module with following dimensions:

I
DB432580

45 45 2Ø6

65
3P
37

45 90
2 ø6
DB432581

65

3P+N 37

180
4

< >
se.com/au Life is On | Schneider Electric | E-75
Switchboard Manufacturers

PowerLogic™ PowerTag Energy


Functions and characteristics

NSX100-250 / NSX400-630
3P 4P
A I I
B J
H J
DB426008

DB436010_1
H
(1)

X
X
K
D
L
E (1)

E M
(1)

F G
Y Z Y Y

(1) Only for PowerTag M630

A 3P 4P
B I I

H J J
DB436015

DB436010_2

X
X X K

L
D

E M
(1)

Y Y

F G (1) Only for PowerTag M630


Y Z

mm A H I J
B C D E F G K L M
in 3P 4P 3P 4P 3P 4P 3P 4P
NSX100-250
105 140 52.5 80.5 201 120.5 72 14 3 Ø6 6 Ø6 35 70 17. 5 17. 5 125 62.5 40
3 6
4.13 5.51 2.06 3.17 7.91 4.74 2.83 0.55 1.34 2.75 0.68 0.68 4.92 2.46 1.57
Ø0.23 Ø0.23
NSX400-630
140 185 70 127.5 320 192.5 96 14 6 Ø6 6 Ø6 45 90 22.5 22.5 200 100 65
6 6
5.51 7.28 2.75 5.02 12.59 7.57 3.78 0.55 1.77 3.5 0.88 0.88 7.87 3.93 2.56
Ø0.23 Ø0.23
NSX100-250
105 140 52.5 109 260 151 72 14 3 Ø6 6 Ø6 35 70 17. 5 17. 5 155 77.5 55
with plug-in base
3 6
4.13 5.51 2.06 4.29 10.23 5.94 2.83 0.55 1.34 2.75 0.68 0.68 6.1 3.05 2.16
Ø0.23 Ø0.23
NSX400-630
140 185 70 153 406 253 100 14 4 Ø06 6 Ø6 45 90 22.5 22.5 250 125 83
with plug-in base
4 6
5.51 7.28 2.75 6.02 15.98 9.96 3.93 0.55 1.77 3.5 0.88 0.88 9.84 4.92 3.26
Ø0.23 Ø0.23

Please refer to PowerTag Energy 250 A & 630 A Installation Sheet for accurate and complete information on the installation of this product.

E-76 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

INS250 / INV100-250
A
INS320-630 / INV320-630

A B
DB436009

DB436012
I
B
J
C
H
C
X X D
X
K
D
L
E E
M

Y F Z G F
Y

G
mm in A B C D E F G H I J K L M
INS250 140 70 68 176 108 72 14 6 Ø6 70 35 100 50 40
INV100-250
5.51 2.75 2.67 6.93 4.25 2.83 0.55 6 Ø0.23 2.75 1.37 3.93 1.96 1.57 H
INS320-630 185 92.5 102.5 270 167.5 96 14 6 Ø6 90 45 150 75 65
INV320-630
7.28 3.64 4.03 10.62 6.59 3.78 0.55 6 Ø0.23 3.5 1.77 5.9 2.95 2.56
I

PowerTag Energy Monoconnect 250 A & 630 A weight


Type Weight (g)
M250 3P 250
M250 3P+N 300
M630 3P 800
M630 3P+N 1000

< >
se.com/au Life is On | Schneider Electric | E-77
Switchboard Manufacturers

PowerLogic™ PowerTag Energy


General Overview

Rope 200 A to 2000 A


IEC 61557-12 PMD-II/DD/K70/1
As per the above standard:
With its flexible and openable current sensors, this PowerTag Energy Rope can be installed easily on busbars and cables without
having to disconnect the conductors, and is suitable for 3P or 3P+N networks. Its removable spring connector for voltage picking
facilitates its installation, and the module can be mounted on a DIN rail or maintained with brackets where needed in a panel.

Main characteristics
E PowerTag Energy Rope measures the following values in accordance with the IEC 61557-12 standard PMD-II/DD/K70/1:
• Energy (4 quadrants):
- Active energy (kWh): total and partial, delivered and received.
- Active energy per phase (kWh): total and partial, delivered and received.
- Reactive energy (kVARh): total and partial, delivered and received.
- Reactive energy per phase (kVARh): total and partial, delivered and received.
- Apparent energy (kVAh): total and partial.
- Apparent energy per phase (kVAh): total and partial.
• Real-time measurement values:
- Voltages (V): phase-to-phase (U12, U23, U31) and phase-to-neutral (V1N, V2N, V3N).
- Currents (A): per phase (I1, I2, I3), calculated neutral current when connected (IN).
- Power:
- Active power (W): total and per phase.
- Reactive power (VAR): total and per phase.
- Apparent power (VA): total and per phase.
- Frequency (Hz).
- Power factor: total and per phase.
• Voltage loss alarms:
- PowerTag Energy Rope sensor sends a “voltage loss” alarm and the current-per-phase value before being de-energized.
- At “voltage loss”, PowerTag Energy Rope adds an overload alarm if the current is higher than the rated current of the
associated protective device.
Note: Functions listed above depends on Concentrator/Gateway.
A9MEM1590

PowerTag Energy Rope

E-78 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

Installation
A
PowerTag Energy Rope 18 mm module can be mounted on DIN rail or fastened with brackets anywhere in a panel. Then its
openable current sensors have to be installed around conductors, cables or busbars, whatever they are insulated or not. Voltage
pickings removable spring terminal has to be wired by 1 copper wire per phase with following characteristics: B
Wire range
Solid Stranded Stranded with terminal ends C
0.2...1.5 mm² 0.2...2.5 mm² 0.25...1.5 mm²

24...16 AWG 24...14 AWG 24...16 AWG


D

E
Neutral picking shall be connected to have phase-to-neutral voltages, energy per phase and power per phase provided.
PowerTag Energy Rope is mainly advised for ComPact NS, MasterPact NT and NW,
MasterPact MTZ NA and HA, for retrofit, for group of loads, and for all other devices with a rating up to 2000 A. F

H
PB120437

< >
se.com/au Life is On | Schneider Electric | E-79
Switchboard Manufacturers

PowerLogic™ PowerTag Energy


Functions and characteristics

Technical specifications
Main characteristics (as per IEC 61557-12)
Rated voltage Un Phase-to-neutral 100...277 VAC ± 20 %
Phase-to-phase 173...480 VAC ± 20 %
Frequency 50/60 Hz
Maximum current Imax 200 A / 600 A / 1000 A / 2000 A
Maximum operating current 1.2 x Imax
Saturation current 2 x Imax
Maximum consumption 3 VA
Starting current Ist 120 mA / 400 mA / 600 mA / 1.2 A
Basic current Ib 30 A / 100 A / 150 A / 300 A
Additional characteristic
E
Operating temperature -25 °C to +70 °C
Maximum primary conductor temperature 100 °C
Storage temperature -40 °C to +85 °C
Overvoltage category As per IEC 61010-1 Cat. IV
Measuring category As per IEC 61010-2-030 Cat. IV
Pollution degree 3
Altitude Up to 2000 m without derating (1)
Degree of protection device IP20 (IP40 front face)
IK05
Radio-frequency communication
ISM band 2.4 GHz 2.4 GHz to 2.4835 GHz
Channels As per IEEE 802.15.4 11 to 26
Isotropic Radiated Power Equivalent (EIRP) 0 dBm
Maximum transmission time < 5 ms
Channel occupancy For 1 device messages sent every 5 seconds
Characteristics of measuring functions
Function Symbol Performance category as per IEC 61557-12 Measuring range
(PMD-II/DD/K70/1) (200 A / 600 A / 1000 A / 2000 A)
Class Measuring range
(200 A / 600 A / 1000 A / 2000 A)
Total active power P 1 3 to 200 A / 10 to 600 A / 29 W (10 W) to 240 kW / 96 W (32 W) to 720 kW /
(Active power per phase) 15 to 1000 A / 30 to 2000 A 144 W (48 W) to 1200 kW / 288 W (96 W) to 2400 kW
Total reactive power QA 2 36 VAR (12 VAR) to 240 kVAR /
(Reactive power per phase) 120 VAR (40 VAR) to 720 kVAR /
180 VAR (60 VAR) to 1200 kVAR /
360 VAR (120 VAR) to 2400 kVAR
Total apparent power SA 2 46 VA (15 VA) to 240 kVA /
(Apparent power per phase) 154 VA (51 VA) to 720 kVA /
231 VA (77 VA) to 1200 kVA /
461 VA (154 VA) to 2400 kVA
Active Energy: Ea 1 0 to 281.109 kWh
per phase, total, partial, delivered
and received
Reactive energy: ErA 2 0 to 281.109 kVARh
per phase, total, partial, delivered and
received
Apparent energy: EapA 2 0 to 281.109 kVAh
per phase, total, partial
Frequency f 0.5 50 / 60 Hz ± 2 % 45 to 65 Hz
Phase current I 1 6 to 200 A / 20 to 600 A / 120 mA to 400 A / 400 mA to 1200 A /
Neutral current INC 2 30 to 1000 A / 60 to 2000 A 600 mA to 2000 A / 1.2 A to 4000 A
Voltages (Line to Line) U 0.5 Un ± 20 % 138 to 576 VAC
Power factor PFA 1 From 0.5 inductive to 0.8 capacitive -1 to 1
(per phase, total)

(1) Above 2000 m, please consult us.

E-80 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

Commercial reference numbers A


Commercial Type Description
reference number
B
A9MEM159p

A9MEM1590 R200 3P/3P+N PowerTag Energy Rope 200 A 3P /


3P+N
A9MEM1591 R600 3P/3P+N PowerTag Energy Rope 600 A 3P /
3P+N C
A9MEM1592 R1000 3P/3P+N PowerTag Energy Rope 1000 A 3P /
3P+N
A9MEM1593 R2000 3P/3P+N PowerTag Energy Rope 2000 A 3P /
3P+N
D

E
For the list of Schneider Electric compatible devices and concentrators, refer
to the Selection Guide pages 95 to 102.
F
Contact your Schneider Electric representative for complete ordering
information.
G

H
PowerTag Energy Rope 200 A to 2000 A dimensions

18 Ø100 I
PT_Rope

67.5 0.7 Ø3.93


2.63
mm
in.

105 45
4.13 1.77

1m
3.28 ft

Type Weight (g)


R200 3P/3P+N 360

R600 3P/3P+N

R1000 3P/3P+N

R2000 3P/3P+N

Please refer to PowerTag Energy Rope 200 A to 2000 A Installation Sheet for accurate and complete
information on the installation of this product.

< >
se.com/au Life is On | Schneider Electric | E-81
Switchboard Manufacturers

PowerLogic™ PowerTag Energy


Reference Numbers

Selection guide for product compatibility*


(Compatibility for terminal not equipped with comb busbar)

PowerTag Energy 63 A

Products Mounting A9 M63 A9 P63 A9 P63 A9 F63


(AC network) position RCBO
Acti9/Multi9
Circuit breakers
iC60/iK60/DT60 Top - - -
Bottom - - -
iC60 (double terminal) Top - - -
Bottom - - -
iC40 Top - - -
Bottom - - -
DT40/iDPN/C40 Top - - -
Bottom - - -
C120 y 63 A Top - - - -1
NG125 y 63 A Bottom - - - -1
iC65N-K (China) Top - - -
iC65 (China) Bottom - - -
iDPN (China) Top - - -
Bottom - - -
iKQ Top NA - - -
(1P+W PowerTag on each pole) Bottom (1P+W only) - - -
N40 Top - - -
Bottom - - -
Reflex iC60 Top - - -
Bottom - - -
Reflex XC40 Top - - -
Bottom - - - -1
C32/C45/C60/C65/K60/T60/ Top - - -
Multi9 OEM (C60N/H/L) Bottom - - -
Circuit breakers equipped with Vigi module
iC60/iC65/iC60/iC65N-K Top (CB) - - -
with Vigi module Bottom - - - (1) (Vigi)
iC40 Top CB - (CB) - -
with Vigi iCG40 Top (Vigi) - 2) (Vigi 1P+N) - -
Bottom (Vigi) - - - (Vigi 3P+N)
iC40 Top - (CB) - -
with "outgoer" Vigi module Bottom - - - (Vigi)
DT40/DPN/C40 Top CB - (CB) - -
with "group feeder" Vigi module Top Vigi - (Vigi 1P+N) - (Vigi 3P+N)
DT40/DPN/C40 Top - (CB) - -
with "outgoer" Vigi module Bottom - - - (Vigi)
DT60 Top CB (CB) only A9MEM1541 - - -
with Vigi TG60 Top Vigi - - - (1) (Vigi)
(1) You may need to change the voltage measurement cable terminals of the PowerTag Energy F63 by other cable ends (wire AWG22/0.33 mm2) for a more suitable connection to this product.
(2) Product usually associated with a comb busbar

(*) Refer to the product catalog for technical characteristics

E-82 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Reference Numbers

Selection guide for product compatibility*


(Compatibility for terminal not equipped with comb busbar)
A

PowerTag Energy 63 A B

Products Mounting A9 M63 A9 P63 A9 P63 A9 F63


position RCBO
F
(AC network)
Acti9/Multi9
Circuit breakers equipped with Vigi module (cont’) G
C120 y 63 A Top - - - (1) (CB)
NG125 y 63 A
with Vigi module Bottom - - - (1) (Vigi)

Residual current devices H


iID/iID K Top - - -
Bottom - - -
iID (double terminal) Top - - - I
Bottom - - -
iID40 Top - (2) (1P+N) - (2) (3P+N)
Bottom - - -
iDPN Vigi "outgoer" 1P+N Top - - -
Bottom - - -
iC60H RCBO/iC60H2 RCBO/ Top NA (fishbone) - - -
IKQE RCBO Bottom - - -
iC60 RCBO Top - - -
Bottom - - -
iCV40 "outgoer" 1P+N Top - - -
Bottom - - -
iCV40 "outgoer" 3P+N Top - - -
Bottom - - -
DPN Vigi/DT40 Vigi/C40 Vigi Top - - -
"outgoer" 1P+N Bottom - - -
DPN Vigi/DT40 Vigi/C40 Vigi/ iDPN Top - - -
Vigi "outgoer" 3P+N Bottom - - -
DPN Vigi K Top - - - (1)
Bottom - - - (1)
N40 Vigi Top - - -
"outgoer" Bottom - - -
iDc/ITG40/C40 Top Left - - -
Top Right - - -
DCP Vigi Top - - -
Bottom - - -
C60H RCBO (Multi9) Top NA (fishbone) - - -
Bottom - - -
ID y 63 A/ID K biconnect/ Top - - -
ID Type B y 63 A Bottom - - -
RED/REDs/REDTest Top - - - (1)
Bottom - - - (1)
(1) You may need to change the voltage measurement cable terminals of the PowerTag Energy F63 by other cable ends (wire AWG22/0.33 mm2) for a more suitable connection to this product.
(2) Product usually associated with a comb busbar

(*) Refer to the product catalog for technical characteristics

< >
se.com/au Life is On | Schneider Electric | E-83
Switchboard Manufacturers

PowerLogic™ PowerTag Energy


Reference Numbers

Selection guide for product compatibility*


(Compatibility for terminal not equipped with comb busbar)

PowerTag Energy 63 A

Products Mounting A9 M63 A9 P63 A9 P63 A9 F63


(AC network) position RCBO
Acti9/Multi9
Switches
Top - - -
iSW y 63 A
Bottom - - -
Top - - -
iSW-NA y 63 A
Bottom - - -
Top - - -
iSW 20/32 A
Bottom - - -
Top - - -
i-NA y 63 A
Bottom - - -
Top - - - (1)
NG125 NA y 63 A
Bottom - - - (1)
Fuse disconnectors
Top - - -
STI
Bottom - - -
Top - - - (1)
SBI 14x51/SBI 22x58 y 63 A
Bottom - - - (1)
Top - - - (1)
D01/D02
Bottom - - - (1)
TeSys
Motor circuit breakers
Top - - - (1) (2)
GV2
Bottom - - - (1) (2)
Top - - - (1) (2)
GV3 y 63 A
Bottom - - - (1) (2)
Contactors
Top - - - Upstream only (1)
TeSys D y 63 A
Bottom - - -
Top - - - Upstream only (1)
TeSys K
Bottom - - -
Motor starter
Top - - - Upstream only (1)
TeSys U
Bottom - - -

(1) You may need to change the voltage measurement cable terminals of the PowerTag Energy F63 by other cable ends (wire AWG22/0.33 mm2) for a more suitable connection to this product.
(2) PowerTag Energy sensors withstand motor starting in-rush currents. Environmental mission profile : Buildings as per 60721-3-3.

(*) Refer to the product catalog for technical characteristics

E-84 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Reference Numbers

Selection guide for product compatibility*


(Compatibility for terminal not equipped with comb busbar)
A

PowerTag Energy 160 A B

Products (AC network) Mounting position F160 3P / 3P+N


D
Acti9
Circuit breakers E
C120 (with or without Vigi module) 3P / 3P+N Top / Bottom

NG125 (with or without Vigi module) 3P / 3P+N Top / Bottom


F
Residual current devices
iID > 63 A 3P+N Top / Bottom

RCCB-ID 125 A 3P+N Top / Bottom


G
Fuse disconnectors
SBI > 63 A 3P / 3P+N Top / Bottom H
Switches
NG125 NA 3P / 3P+N Top / Bottom
I
iSW > 63 A 3P / 3P+N Top / Bottom

iSW NA > 63 A 3P+N Top / Bottom

ComPact
Circuit breakers
NSXm 3P / 3P+N Top / Bottom -5
Switches
NSXm NA 3P / 3P+N Top / Bottom -5

INS 80/100/125/160 3P / 3P+N Top / Bottom

PowerPact
Circuit breakers
B 3P / 3P+N Top / Bottom -6

TeSys
Motor circuit breakers
GV3 > 65 A 3P Top / Bottom

GV4 3P Top / Bottom

Contactors
63 A < TeSys D y 160 A 3P / 3P+N Top Upstream only

TeSys F y 160 A 3P / 3P+N Top Upstream only

(5) It is advised to use EverLink connectors with control wire terminal (LV426970 for 3P / LV426971 for 4P)
(6) It is advised to use EverLink connectors with control wire terminal (LV426974 for 3P / LV426975 for 4P)

(*) Refer to the product catalog for technical characteristics

< >
se.com/au Life is On | Schneider Electric | E-85
Switchboard Manufacturers

PowerLogic™ PowerTag Energy


Reference Numbers
Selection guide for product compatibility*
(Compatibility for terminal not equipped with comb busbar)

PowerTag Energy 250 A PowerTag Energy 630 A

Products Mounting M250 3P M250 3P+N M630 3P M630 3P+N


(AC network) position
E ComPact
Circuit breakers
NSX100/160/250 3P Bottom - - -
B/F/N/H/S/L/R/NA Fixed 4P Bottom - - -
NSX400/630 3P Bottom - - -
F/N/H/S/L/R/NA Fixed 4P Bottom - - -
Top /
NSX100/160/250 3P - - -
Bottom
B/F/N/H/S/L/R/NA Plug-In
(mounted on the base) Top /
4P - (3) - -
Bottom
Top /
NSX400/630 3P - - (4) -
Bottom
F/N/H/S/L/R/NA Plug-In
(mounted on the base) Top /
4P - - - (3) (4)
Bottom
NS100/160/250 3P Bottom - - -
N/SX/H/L/NA Fixed 4P Bottom - - -
NS400/630 3P Bottom - - -
N/H/L/NA Fixed 4P Bottom - - -
Top /
NS100/160/250 3P - - -
Bottom
N/SX/H/L/NA Plug-In
(mounted on the base) Top /
4P - (3) - -
Bottom
NS400/630 Top /
3P - - (4) -
Bottom
N/H/L/NA Plug-In
Top /
(mounted on the base) 4P - - - (3) (4)
Bottom
Circuit breakers equipped with Vigi block
NSX100/160/250 3P Bottom - - -
B/F/N/H/S/L/R/NA Fixed 4P Bottom - - -
NSX400/630 3P Bottom - - -
F/N/H/S/L/R/NA Fixed 4P Bottom - - -
NSX100/160/250 3P Top - - -
B/F/N/H/S/L/R/NA Plug-In
(mounted on the base)
NSX400/630 3P Top - - (4) -
F/N/H/S/L/R/NA Plug-In
(mounted on the base)
Switches
INS250/INV - 3P Bottom - - -
100/160/200/250
Top /
4P - (3) - -
Bottom
INS/INV - 320/400/500/630 3P Bottom - - -
Top /
4P - - - (3)
Bottom
TeSys
Motor circuit breakers
GV5, GV7 3P Bottom - - -
GV6 3P Bottom - - -

(3) neutral on the right when mounted on top side


(4) when plate mounted, need to add a 4 mm intercalary under the PowerTag module (see ComPact NSX catalog)

(*) Refer to the product catalog for technical characteristics

E-86 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Reference Numbers
Selection guide for product compatibility*
(Compatibility for terminal not equipped with comb busbar) A

B
PowerTag Energy Rope
C

D
Products Mounting R200 3P / 3P+N R600 3P / 3P+N R1000 3P / 3P+N R2000 3P / 3P+N
position
(AC network) E
ComPact
Circuit breakers
NS 630b 3P / 3P+N Top / Bottom - - - F
NS 800/1000 3P / 3P+N Top / Bottom - - -
NS 1250/1600/1600b/2000 3P / 3P+N Top / Bottom - - -
Switches G
INS/INV 630b 3P / 3P+N Top / Bottom - - -
INS/INV 800/1000 3P / 3P+N Top / Bottom - - -
INS/INV 1250/1600/2000 3P / 3P+N Top / Bottom - - - H
NS 630b NA 3P / 3P+N Top / Bottom - - -
NS 800/1000 NA 3P / 3P+N Top / Bottom - - -
NS 1250/1600/1600b/2000
I
3P / 3P+N Top / Bottom - - -
NA
MasterPact
Circuit breakers
NT 06 3P / 3P+N Top / Bottom - - -
NT 08/10 3P / 3P+N Top / Bottom - - -
NT 12/16 3P / 3P+N Top / Bottom - - -
NW 08/10 3P / 3P+N Top / Bottom -
NW 12/16/20 3P / 3P+N Top / Bottom - - -
Switches
NT 06 HA 3P / 3P+N Top / Bottom - - -
NT 08/10 HA 3P / 3P+N Top / Bottom - - -
NT 12/16 HA 3P / 3P+N Top / Bottom - - -
NW 08/10 NA/HA/HF 3P / 3P+N Top / Bottom - - -
NW 12/16/20 NA/HA/HF 3P / 3P+N Top / Bottom - - -
MTZ1 06 HA 3P / 3P+N Top / Bottom - - -
MTZ1 08/10 HA 3P / 3P+N Top / Bottom - - -
MTZ1 12/16 HA 3P / 3P+N Top / Bottom - - -
MTZ2 08/10 NA/HA/HA10 3P / 3P+N Top / Bottom - - -
MTZ2 12/16/20 NA/HA/HA10 3P / 3P+N Top / Bottom - - -
TeSys
Contactors
TeSys D > 160 A 3P / 3P+N Top Upstream only - - -
160 A < TeSys F y 2000 A 3P / 3P+N Top Upstream only Upstream only Upstream only Upstream only
Others
Circuit breakers / Switches / Motor circuit breakers
All products below 200 A 3P / 3P+N Top / Bottom - - -
All products between 200 A 3P / 3P+N Top / Bottom - - -
and 600 A
All products between 600 A 3P / 3P+N Top / Bottom - - -
and 1000 A
All products between 1000 A 3P / 3P+N Top / Bottom - - -
and 2000 A

(*) Refer to the product catalog for technical characteristics

< >
se.com/au Life is On | Schneider Electric | E-87
Switchboard Manufacturers

PowerLogic™ PowerTag Energy


Reference Numbers

Selection guide for concentrators / gateways


compatibility*
Concentrators / gateways

E
Wiser IP module PowerTag Link C Smartlink SI B PowerTag Link
Wiser IP module+ PowerTag Link C+ A9XMZA08 A9XMWD20
EER31800 A9XELC10 Smartlink SI D PowerTag Link HD
A9XMWA20 A9XMWD100
PowerTag Energy M63
A9MEM1520

A9MEM1521

A9MEM1522

A9MEM1540

A9MEM1541

A9MEM1542

A9MEM1543 -

PowerTag Energy M63 Resi9


R9M20 - - -

R9M21 - - -

R9M22 - - -

R9M40 - - -

R9M41 - - -

R9M42 - - -

R9M43 - - -

PowerTag Energy P63


A9MEM1561

A9MEM1562
A9MEM1563

A9MEM1571

A9MEM1572

PowerTag Energy F63


A9MEM1560

A9MEM1564 - - -

A9MEM1570

A9MEM1573 - - -

A9MEM1574 - - -

PowerTag Energy F63 Resi9


R9M60 - - -

R9M70 - - -

(*) Refer to the product catalog for technical characteristics

E-88 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Reference Numbers

Selection guide for concentrators / gateways A

compatibility* B

Concentrators / gateways
C

Harmony Hub EcoStruxure™ Panel Wireless Panel Server for


E
ZBRN1 Server PrismaSeT Active
ZBRN2 Universal
ZBRN32 PAS600p
F
PowerTag Energy M63
A9MEM1520 - G
A9MEM1521 -

A9MEM1522 -
H
A9MEM1540 -

A9MEM1541 -

A9MEM1542 - I
A9MEM1543 - -

PowerTag Energy M63 Resi9


R9M20 - - -

R9M21 - - -

R9M22 - - -

R9M40 - - -

R9M41 - - -

R9M42 - - -

R9M43 - - -

PowerTag Energy P63


A9MEM1561 -

A9MEM1562 -

A9MEM1563 -

A9MEM1571 -

A9MEM1572 -

PowerTag Energy F63


A9MEM1560

A9MEM1564 - -

A9MEM1570

A9MEM1573

A9MEM1574 - -

PowerTag Energy F63 Resi9


R9M60 - - -

R9M70 - - -

(*) Refer to the product catalog for technical characteristics

< >
se.com/au Life is On | Schneider Electric | E-89
Switchboard Manufacturers

PowerLogic™ PowerTag Energy


Reference Numbers

Selection guide for concentrators / gateways


compatibility*
Concentrators / gateways

E
Wiser IP module PowerTag Link C Smartlink SI B PowerTag Link
Wiser IP module+ PowerTag Link C+ A9XMZA08 A9XMWD20
EER31800 A9XELC10 Smartlink SI D PowerTag Link HD
A9XMWA20 A9XMWD100
PowerTag Energy F160

A9MEM1580 - (PowerTag Link C+ only) -

PowerTag Energy M250-M630


LV434020

LV434021

LV434022

LV434023

PowerTag Energy R200-R600-R1000-R2000


A9MEM1590 - (PowerTag Link C+ only) -
A9MEM1591 - (PowerTag Link C+ only) -
A9MEM1592 - (PowerTag Link C+ only) -
-
A9MEM1593 - (PowerTag Link C+ only)

(*) Refer to the product catalog for technical characteristics

E-90 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Reference Numbers

Selection guide for concentrators / gateways A

compatibility* B

Concentrators / gateways
C

Harmony Hub EcoStruxure™ Panel Server Wireless Panel Server for


E
ZBRN1 Universal PrismaSeT Active
ZBRN2 PAS600p
ZBRN32 F
PowerTag Energy F160

A9MEM1580
G

PowerTag Energy M250-M630 H


LV434020

LV434021

LV434022
I
LV434023

PowerTag Energy R200-R600-R1000-R2000


A9MEM1590

A9MEM1591

A9MEM1592

A9MEM1593

(*) Refer to the product catalog for technical characteristics

< >
se.com/au Life is On | Schneider Electric | E-91
Switchboard Manufacturers

Wireless Products
General Overview

PowerLogic™ PowerTag Control,


wirelessly manage your connected
circuit breakers

PowerLogic™ HeatTag smart sensor,


cable overheating detection

Schneider Electric offers a range of wireless products designed for new


builds or retrofit installations. These are reliable, low-cost and easy to
use wireless solutions with long battery life that does not compromise
performance.

E-92 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

PowerLogic™ PowerTag Control


General Overview

PowerTag Control monitors circuits wirelessly, collecting status of daisy-chained circuit breakers and notifying the A
data concentrator of information status, such as OF, SD, Contractor or Impulse Relay position indication. These wire-
less input/ output modules allow circuit control and status monitoring. Designed for use in commercial and building
applications, they quickly and easily turn your distribution board into a connected panel. B

PowerTag Control also connects to pulse relays or contactors for remote control within a building management system for non- C
critical loads, such as lighting.

Applications: D
• Monitors your electrical installation from main incomer down to load level
• Suitable for various business, buildings, industrial and residential applications with easy integration in upper systems E
• Supports and enables Energy efficiency programs and standards such as:

• European Energy Efficiency Directive (EED) F


• Energy Performance of Buildings Directive (EPBD)
• IEC 60364-8-1 “Low Voltage Electrical installations - Energy Efficiency” G
• EN 17267 “Energy Measurement and Monitoring plan”
• ISO 50001 “Energy Management Sytem”
H

I
A9XMC2D3

< >
se.com/au Life is On | Schneider Electric | E-93
Switchboard Manufacturers

PowerLogic™ PowerTag Control


Functions and characteristics

Technical specifications
Main characteristics
Power supply 230 V AC ± 20%
DB123309

Frequency 50/60 Hz
Maximum consumption IO y 2 VA
2DI y 3 VA
Operating temperature -25°C to +60°C
Storage temperature -40°C to +85°C
Clip on DIN rail 35 mm
Relative humidity (60068-2-78) 93 % at 40°C
Overvoltage category As per IEC 61010-1 Cat. III
E Altitude y 2000 m
Pollution degree 3
DB123311

Degree of protection according to IEC 60529 Front face IP40


Casing IP20
IK 5
Characteristics of inputs and outputs
Indifferent position of installation Digital input
IP20
IP20 IP40
IP40Type 230 V AC, dry contact
Digital output
IP20 IP40
IP20 IP40 Type 230 V AC, dry contact
Relay type Normally open or normally
DB123313

closed (3)
Applicable voltage on output 230 V AC ± 20%
Minimum/maximum current on output 10 mA / 2 A
Type of output order Pulse or latch (3)
Pulse length in control mode with impulse relay Nominal: 300 ms
Radio-frequency communication
ISM band 2.4 GHz 2.4 GHz to 2.4835 GHz
Channels As per IEEE 802.15.4 11 to 26
Isotropic Radiated Power Equivalent (EIRP) 0 dBm
Channel occupancy Messages sent b On event
b Periodically (5s nominal)

(3) Setting adjustable


62
62
18 44
18 44

Dimensions (mm) 62
18 44 62
18 44 PowerTag C
DB429445

PowerTag C IO 230 V 80
85 45
85 45
PowerTag C 2DI 230 V 75
85 45
85 45

Connection Terminals Tightening Copper Cables


Power torque Rigid Flexible Flexible with ferrule
supply
DB430161

14mm
PZ2
6.5mm

Power supply 2 N.m 1 to 16 mm2 (AWG: 18...6) 0.5 to 10 mm2 (AWG: 21...8) -
(Top)
Input/Output 1 N.m 1x: 1 to 6 mm2 (AWG: 18...10) 1x: 0.5 to 4 mm2 (AWG: 1x: 0.5 to 4 mm2 (AWG:
(Bottom) 21...12) 21...12)
2x: 1.5 to 2.5 mm (AWG:
2

9mm PZ1 16...14) 2x: 1.5 to 2.5 mm2 (AWG: 2x: -


16...14)
Input/ 4mm
Output

E-94 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

A
PowerTag C IO module
B

DB430239
C
• Compatible with horizontal comb
busbars 9mm modules
• Assembly and disassembly by
• Automatic cable guiding in the correct operating toggle latches at the top D
position: terminals with guard and bottom of the products

E
Status LED
A9XMC1D3

• Provide information about F


PowerTag C status

• Insulated terminals IP20 G


DB430240

H
DB430241

Logo
• Wireless communication device
Push button
• Local output control
• Decommissioning

Monitoring/Backloop circuit
• "I" digital input terminal
DB430238

• "C" common powered terminal 230 V AC

Control circuit
• Logical output relay
• "O" output terminals 230 V AC - 2 A max.

< >
se.com/au Life is On | Schneider Electric | E-95
Switchboard Manufacturers

PowerLogic™ PowerTag Control


Functions and characteristics

PowerTag C 2DI module

DB430243
• Compatible with horizontal comb
busbars 9mm modules
• Assembly and disassembly by
• Automatic cable guiding in the correct operating toggle latches at the top
position: terminals with guard and bottom of the products

E
Status LED
A9XMC2D3

• Provide information about


PowerTag C status

• Insulated terminals IP20


DB430244

DB430245

Logo
• Wireless communication device

Flush mounted push button


• Decommissioning
DB430242

Monitoring circuits
• "I" digital input terminal
• "C" common powered terminal 230 V AC

E-96 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

PowerLogic™ HeatTag
General Overview

Wireless Sensor for early A


detection of overheating cables
B
The PowerLogic HeatTag sensor analyzes gas and airborne particles helping facility manag-
er to anticipate and act before smoke appears or an electrical fire starts. C

Electrical fires generate huge losses in commercial and industrial buildings, interrupting production D
and delaying service delivery. These losses can be prevented if early detection of component over-
heating is accurately detected and alarmed.
E
PowerLogic HeatTag helps prevent electrical cabinets from being damaged by analyzing airborne gas
and particles and sending alerts before smoke appears or an electrical fire starts. HeatTag is much
more than a fire or smoke detector - it scientifically detects overheating in electrical installations before F
any damage is done.

I
PB120568

< >
se.com/au Life is On | Schneider Electric | E-97
Switchboard Manufacturers

PowerLogic™ HeatTag
Functions and characteristics

The solution for Power management solutions


Markets that can benefit from a solution that includes PowerLogic HeatTag Schneider Electric provides
smart sensors: innovative power management
solutions to increase your energy
• Buildings efficiency and cost savings,
• Industry maximize electrical network reliability
• Healthcare and availability, and optimize
• Data Center and networks electrical asset performance.
• Infrastructure

Benefits
Conformity of standards
E System integrators’ benefit
• IEC/UL 61010-1
• Ease of integration
• IEC 61010-2-201
• Ease of setup
• IEC 61326-1
• Cost effectiveness
• IEC61326-2-3
• Seamless integration with EcoStruxure™ solutions
• ETSI EN 301 489-1
• ETSI EN 301 489-17
Panel builders’ benefit
• ETSI EN 300 328
• No settings
• EN 62311
• Nominal environment auto-learning to avoid false alerts
• EN IEC 63000
• Concentrator auto-discovery
• IEEE 802.15.4 protocol
• Alerts generated by a powerful algorithm integrated in HeatTag
• FCC and IC certified

End users’ benefit


• Ease of use
• Prevents fire damage and associated costs
• Comprehensive, consistent and superior performance
• Maximize uptime, eliminate faults, and enhance safety

Competitive advantages
• Easy to install and operate
• Suitable for non forced ventilated cabinets ≥ IP31
• Immediately detects overheating in cables and connections
• More than a smoke detector or heat sensor
• 3 levels of alert recording
• Monitors air quality index
• Continous improvements of algorithms

E-98 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

A
Sensor Characteristics
Temperature measurement Measurement range -15 °C / +70 °C (5 °F to 158 °F)
B
PB120568

Measurement accuracy -1.1 °C / +1.1 °C


60 seconds (higher in case of high
Default transmission period wireless data traffic)
Humidity measurement Measurement range 15–90 % C
Measurement accuracy ±9 RH %
60 seconds (higher in case of high
Default transmission period wireless data traffic) D
Air quality Index (0 to 10), alert generation when index ≥10
Test alert after pairing During first 30 minutes
PowerLogicTM HeatTag sensor Environment auto-learning phase 8 hours after the first 30 minutes E
Mechanical Characteristics
Dimensions (W x H x D) 108 x 107 x 55 mm
F
PB120569

Weight 270 g
Degree of protection (IEC 60529) IP 20
Electrical Characteristics
Supply voltage 110–277 V AC, -15 % / +15 % G
Frequency 50–60 Hz
Max. consumption 0.1 A
Operating temperature -15 °C / +70 °C (5 °F to 158 °F) H
Storage temperature -20 °C / +85 °C (-4 °F to 185 °F)
HeatTag rear view showing fan
Relative humidity in operation 15–90 %
Altitude of use 0–2000 m (0–6500 ft) I
Degree of pollution (IEC 60664-1) 3
Overvoltage category OVC III
Commercial Reference Number
PB120570

PowerLogic HeatTag Sensor SMT10020


PB120573

HeatTag sensor DIN mounted

HeatTag sensor dimensions. See the appropriate Installation Guide.


PB120572

Q1
110–277
V~
2A
C Curve or Fast-acting fuse

HeatTag simulation algorithm display

NOTE: Do not use HeatTag as a safety device or to replace fire protection devices. Please see the appropriate User Guide for this product.

< >
se.com/au Life is On | Schneider Electric | E-99
Switchboard Manufacturers

Basic Multi-function Metering


General Overview

PowerLogic™ PM5000
PowerLogic™ PM5350

A range of meters designed for cost management and simple network


management. Affordable to buy and easy to choose, the highly-capable
PowerLogic PM5000 and PM5350 series meters are designed to provide
the best combination of features to match all your energy cost management
needs.

As well as pin-point energy savings, optimal equipment efficiency and


utilisation, basic multi-function meters perform a high level assessment of
the power quality in an electrical network. METSEPM5560

E-100 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

PM5000 Series
General Overview

The PowerLogic PM5000 series power meters are the new benchmark in affordable,
precision metering. A
The value you want, the precision you need. Compact, affordable power meters with high-end cost
capabilities and basic mobile energy management. B

Applications C

Capable of essential cost management:


D
• Sub-billing/tenant metering
• Equipment sub-billing
E
• Energy cost allocation

F
Also ideal for electrical network management:
• Track real-time power conditions
G
• Monitor control functions
• Provide basic power quality values
H
• Detect and capture voltage sag and swell events
• Monitor residual current
I
• Analyze equipment and network status
• BACnet/IP, EtherNet/IP, and DNP3.0 protocol support
PB118061

METSEPM5760

< >
se.com/au Life is On | Schneider Electric | E-101
Switchboard Manufacturers

PM5000 Series
Functions and characteristics

The solution for Power management solutions


Markets that can benefit from a solution that includes PowerLogic PM5000 Schneider Electric provides
series meters: innovative power management
solutions to increase your energy
• Buildings efficiency and cost savings,
• Industry maximize electrical network reliability
• Healthcare and availability, and optimize
• Data Center and networks electrical asset performance.
• Infrastructure
Conformity of standards
Benefits • IEC 61557-12
E System integrators’ benefit • IEC 62053-22
• IEC 62053-24
• Ease of integration
• Ease of setup • IEEE 802.3
• Cost effectiveness • EN 50470-1
• EN 50470-3
Panel builders’ benefit
• IEC/UL/EN 61010-1
• Ease of installation • IEC 62052-11
• Cost effectiveness • FCC part 15 Class B
• Aesthetically pleasing • EN 55022 Class B
• Simplified ordering
• ODVA certification
End users’ benefit • ANSI C12.1-2008 (PM55xx)
• ANSI C12.20 Class 0.2 & 0.5
• Ease of use • Align with cyber security
• Precision metering & sub-billing guidelines as per IEC 62443
• Billing flexibility
• Comprehensive, consistent and superior performance
• Maximize uptime, eliminate faults, and enhance safety

Competitive advantages
• Easy to install and operate
• Easy for circuit breaker monitoring and control
• Data logging up to 16 parameters
• Power quality analysis
• Load management combined with alarm and timestamping
• High performance and accuracy
• Residual Current Monitoring
• Voltage sag and swell detection with waveform capture
• MID ready compliance for legal billing application
• BACnet/IP, EtherNet/IP, and DNP3.0 protocol support

E-102 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

PowerLogic™ PM5100, PM5300 and PM5500 series A


The PowerLogic™ PM5000 power meter is the ideal fit for cost management applications. Designed for use in both
energy management systems and building management systems, it provides the measurement capabilities needed
to allocate energy usage, perform tenant metering and sub-billing, pin-point energy savings, optimize equipment B
efficiency and utilization, and perform a high level assessment of the power quality of the electrical network.
In a single 96 x 96 mm unit, with a graphical display, (plus optional remote display) all three phases, neutral and
ground can be monitored simultaneously. C
The bright, anti-glare display features large characters and powerful backlighting or easy reading even in
extreme lighting conditions and viewing angles. Easy to understand menus, text in 8 selectable languages,
PB111777

icons and graphics create a friendly environment to learn about your electrical network. Ethernet gateway and D
enhanced cyber security. These are highly accurate devices with global billing certifications.

Applications E
Cost management: Cost saving opportunities become clear once you understand how and when your facility
uses electricity. The PowerLogic™ PM5000 series meters are ideal for:
• Sub-billing / tenant metering: allows a landlord, property management firm, condominium association, home-
F
owners association, or other multi-tenant property to bill tenants for individual measured utility (electricity)
PowerLogicTM PM5563
remote display usage. MID approved meters for billing applications across Europe.
G
• Cost allocation: allocate energy costs between different departments (HVAC, indoor and outdoor lighting,
refrigeration, etc.), different parts of an industrial process or different cost centres. Cost allocation systems can
help you save money by making changes to your operation, better maintaining your equipment, taking advan-
H
tage of pricing fluctuations, and managing your demand.
Network management: Improving reliability of the electrical network is key for success in any business.
Monitoring values such as voltage levels, harmonics distortions, voltage unbalance, residual current, voltage sag I
and swell will help you to ensure proper operation and maintenance of your electrical network and equipment.
PowerLogic™ PM5000 series meters are the perfect tool for:
• Basic Power Quality monitoring: power quality phenomena can cause undesirable effects such as heating in
transformers, capacitors, motors, generators and misoperation of electronic equipment and protection devices.
• Min/Max monitoring (with timestamp): understanding when electrical parameters, such as voltage, current
and power demand, reach maximum and minimum values will give you the insight to correctly maintain your
electrical network and assure equipment will not be damaged.
PB111784

• Alarming: alarms help you to be aware of any abnormal behaviour on the electrical network in the moment it
happens.
• WAGES monitoring: take advantage of the input metering on PM5000 meters to integrate measurements from
third party devices such as water, air, gas, electricity or steam, meters.
• Residual current monitoring: measures leakage current flowing in TN & TT network system.
• Voltage sags and swells: measures and captures wave form in the event of voltage sags and swells in the network.
PowerLogicTM PM5563
remote display Main characteristics
Easy to install
Mounts using two clips, in standard cut out for DIN 96 x 96 mm, no tools required. Compact meter with 72 mm
(77 mm for PM5500) depth connectable up to 690 V L-L without voltage transformers for installations compliant
with category III. Optional remote display (PM5563). Ethernet gateway functionality via RS-485 port.
Easy to operate
Intuitive navigation with self-guided, language selectable menus, six lines, four concurrent values. Two LEDs on
the meter face help the user confirm normal operation with a green LED - heartbeat/communications indicator,
and the amber LED - customizable either for alarms or energy pulse outputs. Onboard web pages (PM5500)
show real-time and logged information, and verify communications.
Easy circuit breaker monitoring and control
The PM5300 provides two relay outputs (high performance Form A type) with capability to command most of
the circuit breaker coils directly. For Digital Inputs, monitored switches can be wired directly to the meter without
external power supply by using whetting output voltage.
PM5500 series have 4 status inputs (digital) and 2 digital output (solid state) to use for WAGES monitoring,
control and alarm annunciation.
Accurate energy measurement for precise cost allocation:
PM5100 PM5300 PM5500 PM5600 PM5700
IEC 62053-22 (Active Energy) Class 0.5S Class 0.5S Class 0.2S Class 0.2S Class 0.2S

< >
se.com/au Life is On | Schneider Electric | E-103
Switchboard Manufacturers

PM5000 Series
Functions and characteristics

Native multi-protocol support


The PM55/PM56/PM5700 is now easier than ever to integrate into new and existing BMS systems. With
native BACnet/IP protocol support, meters can simultaneously communicate via BACnet and Modbus in
applications where multiple software systems are used (building management and energy management
PB111777

systems).

The PM55/PM56/PM5700 series has been tested and certified in accordance with
BACnet Testing Laboratories (BTL) requirements.

PM55/PM56/PM5700 Direct metering of neutral current


The PM55/PM56/PM5700 has a fourth CT for measuring neutral current. In demanding IT applications, where
loads are non-linear (i.e. switching power supplies on computers/servers), measuring neutral current is
essential to avoid overload and resulting outage.

E Power Quality analysis


PowerLogicTM PM5500 meter The PM5000 offers Total Harmonic Distortion (THD/thd), Total Demand Distortion (TDD) measurements and
individual harmonics (odd) magnitudes and angles for voltage and current:
PM5100 PM5300 PM55/56/5700
Individual Harmonics magnitudes up to 15th magnitudes up to 31st magnitudes &
angles up to 63rd

These types of power quality parameters help to identify the source of harmonics
that can harm transformers, capacitors, generators, motors and electronic equipment.
PB111772

Load management
Peak demands with time stamping are provided. Predicted demand values can be used in combination
with alarms for basic load shedding applications.

Alarming with time stamping


A different combination of set point driven alarms and digital alarms with 1s time stamping are available in
the PM5000 family:

PM5100 PM5300 PM55/56/5700


PowerLogicTM PM5300 meter Set point driven alarms 29 29 29 or 33*
Unary 4 4 4
Digital – 2 4 or 2
Boolean / Logic – – 10
Custom defined – – 5

*Applicable in specific meter models. 2 alarms for disturbance (Sag/ Swell)

Alarms can be visualized as Active (the ones that have picked up and did not drop out yet) or Historical (the
ones that happened in the past). Alarms can be programmed and combined to trigger digital outputs and
PB111768

mechanical relays (PM5300).


The PM5000 series keeps an alarm log with the active and historical alarms with date and time stamping.
SMTP protocol for receiving alarm conditions via email and text. SNTP protocol for date/time network
synchronization.

Load timer
A load timer can be set to count load running hours based on a minimum current withdraw, adjustable to
monitor and advise maintenance requirements on the load.
PowerLogicTM PM5100 meter
High Performance and accuracy
IEC 61557-12 Performance measuring and monitoring devices (PMD).
Defines the performance expectation based on classes. It defines the allowable error in the class for real and
reactive power and energy, frequency, current, voltage, power factor, voltage unbalance, voltage and current
harmonics (odds), voltage THD, current THD, as well as ratings for temperature, relative humidity, altitude,
start-up current and safety. It makes compliant meters readings comparable - they will measure the same
values when connected to the same load.

Meets IEC 61557-12 PMD/[SD|SS]/K70/0.5 for PM5100 and PM5300 Meets IEC 61557-12 PMD/[SD|SS]/
K70/0.2 for PM5500

Legal billing compliance


MID compliance is compulsory for billing applications across Europe.
In addition to billing applications, for facility managers responsible for energy cost MID means same level
of quality as a billing meter.

E-104 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

PM5000 series feature selection


A
PM5100 PM5300
PM5100 PM5110 PM5310 PM5310R PM5320 PM5320R PM5330 PM5340
Installation B
Fast installation, panel mount
with integrated display
Fast installation, DIN rail
– – – – – – – –
C
mountable
Accuracy CL 0.5S CL 0.5S CL 0.5S CL 0.5S CL 0.5S CL 0.5S CL 0.5S CL 0.5S
Display
D
Backlit LCD, multilingual, bar
graphs, 6 lines, 4 concurrent
values E
Power and energy metering
3-ph voltage, current, power,
demand, energy, frequency, F
power factor
Multi-tariff – – 4 4 4 4 4 4
MID ready compliance, G
EN50470-1/3, Annex B & Annex – PM5111 – – – – PM5331 PM5341
D Class C
Power quality analysis H
THD, thd, TDD

Harmonics, individual (odd) up to 15th 15th 31st 31st 31st 31st 31st 31st I
Waveform capture & sag/ swell
– – – – – – – –
detection
I/Os and relays
I/Os 1DO 1DO 2DI/2DO 2DI/2DO 2DI/2DO 2DI/2DO 2DI/2DO 2DI/2DO

Relays 0 0 0 0 0 0 2 2

Analog inputs – – – – – – – –

Residual Current inputs – – – – – – – –

Alarms and control


Alarms 33 33 35 35 35 35 35 35

Set point response time, seconds 1 1 1 1 1 1 1 1

Single and multi-condition alarms – –

Boolean alarm logic – – – – – – – –

Memory for data logging – – 256KB 256KB 256KB 256KB 256KB 256KB

Communications
Serial ports with modbus pro- – 1 1 1 – – 1 –
tocol
Ethernet port with Modbus TCP – – – – 1 1 – 1
protocol
BACnet/IP protocol – – – – –

EtherNet/IP protocol – – – – – – – –

DNP3.0 over Ethernet – – – – – – – –


Onboard web server with web – – – – – – – –
pages
Serial to Ethernet gateway – – – – – – – –

Short ref. numbers PM5100 PM5110 PM5310 PM5310R PM5320 PM5320R PM5330 PM5340

(See table below for complete commercial reference numbers)

< >
se.com/au Life is On | Schneider Electric | E-105
Switchboard Manufacturers

PM5000 Series
Functions and characteristics

PM5000 series feature selection

PM5500 PM5600 PM5700


PM5560 PM5563 PM5563RD PM5570 PM5580 PM5650 PM5660 PM5760
Installation
Fast installation, panel
mount with integrated – –
display
Fast installation, DIN rail
– – – – – –
mountable
Accuracy CL 0.2S CL 0.2S CL 0.2S CL 0.2S CL 0.2S CL 0.2S CL 0.2S CL 0.2S
Display
Backlit LCD,
E multilingual, bar

graphs, 6 lines, 4
concurrent values
Power and energy
metering
3-ph voltage, current,
power, demand, energy,
frequency, power factor
Multi-tariff 8 8 8 8 8 8 8 8
MID ready compliance,
EN50470-1/3, Annex B PM5561 – – – – – PM5661 PM5761
& Annex D Class C
Power quality analysis
THD, thd, TDD
Harmonics, individual 63rd 63rd 63rd 63rd 63rd 63rd 63rd 63rd
(odd) up to
Waveform capture & 8 cycles @ 128 8 cycles @ 128
– – – – – –
sag/ swell detection samples/cycle samples/cycle
I/Os and relays
I/Os 4DI/2DO 4DI/2DO 4DI/2DO 2DI/2DO 4DI/2DO 4DI/2DO 2DI/2DO 2DI/2DO

Relays 0 0 0 0 0 0 0 0

Analog inputs 0 0 0 2 0 0 0 0

Residual Current inputs 0 0 0 0 0 0 2 2

Alarms and control


Alarms 52 52 52 50 52 54 54 56
Set point response time, 1 1 1 1 1 1 1 1
seconds
Single and multi-condi-
tion alarms
Boolean alarm logic
Memory for data 1.1 MB 1.1 MB 1.1 MB 1.1 MB 1.1 MB 1.1 MB 1.1 MB 1.1 MB
logging
Communications
Serial ports with 1 1 1 1 1 1 1 1
Modbus protocol
Ethernet port with 2g 2g 2g 2g 2g 2g 2g 2g
Modbus TCP protocol
BACnet/IP protocol

EtherNet/IP protocol

DNP3.0 over Ethernet


Onboard web server
with web pages
Serial to Ethernet
gateway
Short ref. numbers PM5560 PM5563 PM5563RD PM5570 PM5580 PM5650 PM5660 PM5760

(See table below for complete commercial reference numbers)

E-106 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

PM5000 technical specifications


A
PM5100 PM5300 PM5500
Use on LV and MV systems
Basic metering with THD and min/max readings B
Instantaneous rms values
Current per phase, neutral and ground
C
(PM5500)
Voltage Total, per phase L-L and L-N
Frequency D
Real, reactive, and
Total and per phase Signed, Four Quadrant
apparent power
True Power Factor Total and per phase Signed, Four Quadrant E
Displacement PF Total and per phase Signed, Four Quadrant
% Unbalanced I, V L-N, V L-L
Direct monitoring of neutral current
F
Energy values
Accumulated Active, Reactive and Apparent Energy Received/Delivered; Net and absolute; Time Counters G
Demand value
Current average Present, Last, Predicted, Peak, and Peak Date Time
Active power Present, Last, Predicted, Peak, and Peak Date Time H
Reactive power Present, Last, Predicted, Peak, and Peak Date Time
Apparent power Present, Last, Predicted, Peak, and Peak Date Time
I
Peak demand with timestamping D/T for current and
powers
Sliding, fixed and rolling block,
Demand calculation
thermal methods
Synchronisation of the measurement window to
input, communication command or internal clock
Settable Demand intervals
Demand synchronization with pulse input
Other measurements
I/O timer
Operating timer
Load timer
Alarm counters and alarm logs
Power quality measurements
THD, thd (Total Harmonic Distortion) I, VLN, VLL I,VLN, VLL
TDD (Total Demand Distortion)
Individual harmonics (odds) 15th (PM5110) 31st 63rd
Neutral Current metering with ground current
calculation
Data recording
Min/max of instantaneous values, plus phase iden-
tificationg
Alarms with 1s timestampingg
2 fixed parameters
kWh and kVAh with
configurable interval
Up to 14 selectable parameters with configurable interval and
Data logging & duration (e.g. 2
duration (e.g. 6 parameters for 90 days at 15-minute intervals)
parameters for 60
days at 15-minute
intervals)
Min/max log
Maintenance, alarm and event logs
Customisable data logs

g Stored in non-volatile memory

< >
se.com/au Life is On | Schneider Electric | E-107
Switchboard Manufacturers

PM5000 Series
Functions and characteristics

PM5000 technical specifications


PM5100 PM5300 PM5500
Inputs / Outputs / Mechanical Relays
Digital inputs 2 4 in PM5560, PM5563, PM5580

Digital outputs 1 (kWh only) 2 2

Form A Relay outputs 2

Analog inputs 2 for PM5570

Residual Current inputs


Timestamp resolution in 1 1 1
seconds
Whetting source 24 V DC, 8 mA
E Type of measurement: True rms on three-phase (3P, 64 samples per cycle 128 samples per cycle
3P + N)
IEC 61557-12 PMD/[SD|SS]/K70/0.5 PMD/[SD|SS]/K70/0.2

Active Energy Class 0.5S as per IEC 62053-22 Class 0.2S as per IEC 62053-22

Reactive Energy Class 2 as per IEC 62053-23 Class 2 as per IEC 62053-23

Active Power Class 0.5 as per IEC 61557-12 Class 0.2 as per IEC 61557-12

Apparent Power Class 0.5 as per IEC 61557-12


Measurement accuracy
Current, Phase Class 0.5 as per IEC 61557-12 ±0.15 %

Voltage, L-N Class 0.5 as per IEC 61557-12 ±0.1 %

Frequency ±0.005 %

Power Factor ±0.005 count


MID Directive EN50470-1, Annex B and Annex D (Optional model references) Class C
EN50470-3
Nominal Measured 20 V L-N / 35 V L-L to 400 V L-N /690 V L-L 20 V L-N / 20 V L-L to 400 V L-N /690 V L-L
Input-voltage (up to Voltage range absolute range 35 V L-L to 760 V L-L absolute range 20 V L-L to 828 V L-L
1.0 MV AC max, with Impedance 5 MΩ
voltage transformer)
Frequency nom 50 or 60 Hz ±5 % 50 or 60 Hz ±10 %
Input-current
(configurable for 1 or 5 I nom 5A
A secondary CTs)
Measured Amps with over Starting current: 5 mA Operating range: Starting current: 5 mA Operating range: 50 mA to 10 A
range and Crest Factor 50 mA to 8.5 A
Withstand Continuous 20 A, 10 s/hr 50 A, 1s/hr 500 A

Impedance < 0.3 mΩ

Frequency nom 50 or 60 Hz ±5 % 50 or 60 Hz ±10 %

Burden <0.026 VA at 8.5 A


AC control power Operating range 100 - 277 V AC L-N / 415 V L-L +/-10 % 100-480 V AC ±10 %
CAT III 300V class per IEC 61010 CAT III 600V class per IEC 61010

Burden <5 W,11 VA at 415V L-L <5W/16.0 VA at 480 V AC

Frequency 45 to 65 Hz
80 mS typical at 120V AC and maximum
burden. 35 ms typical at 120 V L-N and
100 mS typical at 230 V AC and maximum maximum burden
Ride-through time
burden 129 ms typical at 230 V L-N and
100 mS typical at 415 V AC and maximum maximum burden
burden
DC control power Operating range 125–250 V DC ±20 % (100 to 300 V DC)

Burden <4 W at 250 V DC typical 3.1W at 125 V DC, max. 5W

Ride-through time 50 mS typical at 125 V DC and maximum burden


20-60 V DC ±10 % CAT
LV DC control power PM5580
III Burden 4.1 W max.

E-108 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

PM5000 technical specifications


A
PM5100 PM5300 PM5500
0.5 Hz maximum
Max output fre- (1 second ON / 1
quency second B
OFF - min times)
250 V AC at 8.0
Amps, 25 k C
cycles, resistive
Relay 30 V DC at 2.0
Switching current Amps,
75 k cycles,
D
resistive 30 V DC
at 5.0 Amps, 12.5
k cycles, resistive
E
Isolation 2.5 kV rms
30 V AC / 40 V DC PM5570, PM5560, PM5561, PM5760,
Max load voltage 40 V DC PM5761
Outputs
Max load current 20 mA 125 mA
F
On Resistance 50 Ω max 8Ω
Meter constant from 1 to 9,999,999 pulses per kWh G
Pulse width for
50 % duty cycle
Digita Output
Pulse frequency for
25 Hz max. H
Digital Output
Leakage current 0.03 micro Amps 1 micro Amps
Isolation 5 kV rms 2.5 kV rms I
Pulse width (LED) 200 ms
Optical outputs Pulse frequency 2.5 kHz. max 2.5 kHz. max
Meter constant from 1 to 9,999,999 pulses per k_h
ON Voltage 18.5 to 36 V DC 30 V AC / 60 V DC max
OFF Voltage 0 to 4 V DC
Input Resistance 110 k Ω 100 k Ω
2 Hz (T ON min
Maximum Frequency = T OFF min = 25 Hz (T ON min = T OFF min = 20 ms)
Status Inputs 250 ms)
Response Time 20 ms
Opto Isolation 5 kV rms 2.5 kV rms
24 V DC/ 8 mA
Whetting output max
Input Burden 2mA @24V DC 2 mA @ 24 V AC/DC
4 - 20 mA DC
(nominal) Accu-
racy: 1% of full-
Analog inputs scale reading <
20 ohm Operating
voltage: 24 V DC
max

Product weight 380 g 430 g 450 g

IP degree of protection (IEC 60529) IP54 front display, IP30 rear side, IP65 front side with Optional accessory kit METSEIP65OP96X96FF.

Dimensions W x H x D [protrusion from cabinet] 96 x 96 x 72 mm (77 mm for PM5500) (depth of meter from housing mounting flange) [13 mm]

Mounting position Vertical

Panel thickness 6 mm maximum

< >
se.com/au Life is On | Schneider Electric | E-109
Switchboard Manufacturers

PM5000 Series
Functions and characteristics

PM5000 technical specifications


PM5100 PM5300 PM5500
Environmental characteristics
Operating temperature Operating temperature -25 °C to 70 °C
Display (Display func-
tions to
-25 °C to 70 °C
-25 º C with reduced 
performance)
Storage temp. -40 °C to 85 °C

Humidity range 5 to 95 % RH at 50 °C (non-condensing)

Pollution degree 2

E Altitude 2000 m CAT III / 3000 m


CAT II
Electromagnetic compatibility
Harmonic current emissions IEC 61000-3-2

Flicker emissions IEC 61000-3-3

Electrostatic discharge IEC 61000-4-2

Immunity to radiated fields IEC 61000-4-3

Immunity to fast transients IEC 61000-4-4

Immunity to surge IEC 61000-4-5

Conducted immunity 150 kHz to 80 MHz IEC 61000-4-6

Immunity to magnetic fields IEC 61000-4-8

Immunity to voltage dips IEC 61000-4-11

Radiated emissions FCC part 15, EN 55022 Class B

Conducted emissions FCC part 15, EN 55022 Class B

Safety
Europe CE, as per IEC 61010-1 Ed. 3, IEC 62052-11 & IEC 61557-12

U.S. and Canada cULus as per UL 61010-1 (3rd Edition)

Measurement category (Voltage & Current inputs) CAT III up to 400 V L-N / 690 V L-L

Dielectric As per IEC/UL 61010-1 Ed. 3

Protective Class II, Double insulated for user accessible parts

Communication
RS-485 port Modbus RTU, Modbus ASCII  (7 or 8 2-Wire, 9600,19200 or 38400 baud, Parity - Even, Odd, None, 1 stop bit if parity
bit), JBUS Odd or Even, 2 stop bits if None;  (Optional in PM51x and PM53x)
2 (daisy chain only, 1 IP
Ethernet port: 10/100 Mbps; Modbus TCP/IP 1 Optional address)
Native Ethernet/IP & DNP3.0 over Ethernet Yes

Firmware and language file update Meter firmware update via the communication ports

Isolation 2.5 kVrms, double insulated

Human machine interface


Display type Monochrome Graphics LCD

Resolution 128 x 128

Backlight White LED

Viewable area (W x H) 67 x 62.5 mm

Keypad 4-button

Indicator Heartbeat / Comm activity Green LED

Energy pulse output / Active alarm (configurable) Optical, amber LED

Wavelength 590 to 635 nm

Maximum pulse rate 2.5 kHz

E-110 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

PM5000 Series meter flush mounting


A

B
PB111276m

PM5000 Series meter dimensions


H

I
PB111279_m

PB111289

PB111279A

PM5000 PM5100 / PM5300 PM5500 / PM5600


PB111278

PB111277

PB111291

PM5000

PM5000 meter parts PM5500 / PM5600 meter parts PM5100 / PM5300 meter parts
A. Menu selection buttons E. Voltage inputs E. Relay output (PM5300 only)
B. LED indicators F. RS-485 comms F. Voltage inputs
C. Navigation or menu selections G. Digital inputs G. Control power
D. Maintenance and alarm - H. Current inputs H. Current inputs

I. Digital outputs I. Status inputs/digital outputs


notification area
J. Communications port: Ethernet (PM5300
J. Ethernet ports
only) or RS-485)
K. Control power

Please see the appropriate Installation Guide for accurate and complete information on the installation of this product.

< >
se.com/au Life is On | Schneider Electric | E-111
Switchboard Manufacturers

PM5000 Series
Reference Numbers

PM5000 series commercial reference numbers

Comm ref numbers Description


METSEPM5110 Power Meter range 72 mm depth, control power to 415 V AC, Cl 0.5S, 15th harmonic, RS-485 Modbus, 1DO

METSEPM5310 Power Meter range 72 mm depth, control power to 415 V AC, Cl 0.5S, 31st harmonic, 256 kB, RS-485 Modbus, 2DI/2DO

METSEPM5310R Power Meter range 72 mm depth, control power to 415 V AC, Cl 0.5S, 31st harmonic, 256 kB, RJ45 LVCT, RS-485 Modbus, 2DI/2DO

METSEPM5320 Power Meter range 72 mm depth, control power to 415 V AC, Cl 0.5S, 31st harmonic, 256 kB, Ethernet, 2DI/2DO

METSEPM5320R Power Meter range 72 mm depth, control power to 415 V AC, Cl 0.5S, 31st harmonic, 256 kB, RJ45 LVCT, Ethernet, 2DI/2DO

METSEPM5330 Power Meter range 72 mm depth, control power to 415 V AC, Cl 0.5S, 31st harmonic, 256 kB, RS-485 Modbus, 2DI/2DO, 2Relay

METSEPM5340 Power Meter range 72 mm depth, control power to 415 V AC, Cl 0.5S, 31st harmonic, 256 kB, Ethernet, 2DI/2DO, 2Relay
E METSEPM5560 Power Meter range 77 mm depth, control power to 480 V AC, Cl 0.2S, 63rd harmonic, 1.1 MB, Modbus and Ethernet, 4DI/2DO

METSEPM5563 Power Meter range 77 mm depth, control power to 480 V AC, Cl 0.2S, 63rd harmonic, 1.1 MB, DIN mount, no display, 4DI/2DO

METSEPM5563RD Power Meter range 77 mm depth, control power to 480 V AC, Cl 0.2S, 63rd harmonic, 1.1 MB, DIN mount, remote display, 4DI/2DO

METSEPM5580 Power Meter range 77 mm depth, control power 24-60 VDC, Cl 0.2S, 63rd harmonic, 1.1 MB, Modbus and Ethernet, 4DI/2DO

E-112 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Reference Numbers

PM5000 series commercial reference numbers


A
Comm. ref numbers Description
0.333V 3-in-1 CTs with RJ45 for PM53x0R
B
METSECTV25006 LVCT SolidC 3in1 RJ45 25mmCtr 60A:1/3V

METSECTV25010 LVCT SolidC 3in1 RJ45 25mmCtr 100A:1/3V

METSECTV25013 LVCT SolidC 3in1 RJ45 25mmCtr 125A:1/3V


C
METSECTV25016 LVCT SolidC 3in1 RJ45 25mmCtr 160A:1/3V

METSECTV35006 LVCT SolidC 3in1 RJ45 35mmCtr 60A:1/3V D


METSECTV35010 LVCT SolidC 3in1 RJ45 35mmCtr 100A:1/3V

METSECTV35012 LVCT SolidC 3in1 RJ45 35mmCtr 120A:1/3V


E
METSECTV35013 LVCT SolidC 3in1 RJ45 35mmCtr 125A:1/3V

METSECTV35015 LVCT SolidC 3in1 RJ45 35mmCtr 150A:1/3V

METSECTV35016 LVCT SolidC 3in1 RJ45 35mmCtr 160A:1/3V


F
METSECTV35020 LVCT SolidC 3in1 RJ45 35mmCtr 200A:1/3V

METSECTV35025 LVCT SolidC 3in1 RJ45 35mmCtr 250A:1/3V G


METSECTV45025 LVCT SolidC 3in1 RJ45 45mmCtr 250A:1/3V

METSECTV45030 LVCT SolidC 3in1 RJ45 45mmCtr 300A:1/3V


H
METSECTV45040 LVCT SolidC 3in1 RJ45 45mmCtr 400A:1/3V

METSECTV45050 LVCT SolidC 3in1 RJ45 45mmCtr 500A:1/3V

METSECTV45060 LVCT SolidC 3in1 RJ45 45mmCtr 600A:1/3V I


METSECTV45063 LVCT SolidC 3in1 RJ45 45mmCtr 630A:1/3V

METSECTV29006 LVCT SolidC 3in1 RJ45 29mmCtr 60A:1/3V

METSECTV29010 LVCT SolidC 3in1 RJ45 29mmCtr 100A:1/3V

METSECTV29012 LVCT SolidC 3in1 RJ45 29mmCtr 120A:1/3V

METSECTV29013 LVCT SolidC 3in1 RJ45 29mmCtr 125A:1/3V

METSECTV29015 LVCT SolidC 3in1 RJ45 29mmCtr 150A:1/3V

METSECTV29016 LVCT SolidC 3in1 RJ45 29mmCtr 160A:1/3V

METSECTV29020 LVCT SolidC 3in1 RJ45 29mmCtr 200A:1/3V

METSECTV70080 LVCT SolidC 3in1 RJ45 70mmCtr 800A:1/3V

METSECTV70100 LVCT SolidC 3in1 RJ45 70mmCtr 1000A:1/3V

METSECTV70125 LVCT SolidC 3in1 RJ45 70mmCtr 1250A:1/3V

Cables
DCEPCURJ03GYM Category 5e, Patch Cord, UTP, 3 M, Grey

DCEPCURJ10GYM Category 5e, Patch Cord, UTP, 10 M, Grey

Other related products


METSEPM5RD Remote display for PM5563

METSEPM51HK Hardware kit for PM51xx

METSEPM53HK Hardware kit for PM53xx

METSEPM51_3RSK Revenue sealing kit for PM51XX & PM53XX

METSEPM55RSK Revenue sealing kit for PM55XX

METSEPM55HK Hardware kit for PM55xx

METSEPM5CAB3 Remote Display cable

See your Schneider Electric representative for complete ordering information.

< >
se.com/au Life is On | Schneider Electric | E-113
Switchboard Manufacturers

PowerLogic™ PM5350
General Overview

The PowerLogic PM5350 power meter is the new benchmark in affordable, precision metering.
The PowerLogic PM5350 power meter offers all the measurement capabilities required to monitor an electrical installation in a
space-efficient, single 96 x 96 mm unit with small depth. DNC certifies for marine applications.

Applications
• Panel instrumentation.
• Cost allocation or energy management
• Electrical installation remote monitoring
E • Sophisticated alarming
• Circuit beaker monitoring and control
PB117510

METSEPM5350P

E-114 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

The solution for Power management solutions A


Markets that can benefit from a solution that includes PowerLogic PM5350 Schneider Electric provides
series meters: innovative power management
solutions to increase your energy
B
• Buildings efficiency and cost savings,
• Industry maximize electrical network reliability
and availability, and optimize
C
• Healthcare
• Data Centre and networks electrical asset performance.
• Infrastructure D
Conformity of standards
Benefits • IEC 62053-22
E
System integrators’ benefit • IEC 61557-12

• Ease of integration • IEC 62053-23


F
• Ease of setup • IEC/UL 61010-1
• Cost effectiveness • IEC 61326-1
• UL 61010-1 G
Panel builders’ benefit
• IEC 61000-3-3
• Ease of installation • FCC part 15 Class A H
• Cost effectiveness
• Aesthetically pleasing • DNV GL certified
• Simplified ordering I
End users’ benefit

• Ease of use
• Precision metering & sub-billing
• Billing flexibility
• Comprehensive, consistent and superior performance

Competitive advantages
• Easy to install and operate
• Easy for circuit breaker monitoring and control
• Power quality analysis
• Load management combined with alarm and timestamping
• High performance and accuracy
• Mulit-tariff capabilities
• Individual harmonics up to the 31st

< >
se.com/au Life is On | Schneider Electric | E-115
Switchboard Manufacturers

PowerLogic™ PM5350
Functions and characteristics

The PowerLogic PM5350 series power meter soffer electrical installation measurement
capabilities in a single 96 x 96 mm unit. Three-phases and neutral can be monitored
simultaneously using a bright, anti-glare display with large characters and
backlighting. Menus are intuitive and the meter supports English, Chinese, Hebrew,
PB117511

and Spanish languages. Its compact size and high performance make the PowerLogic
PM5350 sereis suitable for many applications.

Applications
• Panel instrumentation.
• Cost allocation or energy management.
• Electrical installation remote monitoring.
• Alarming with under/over, digital status, control power interruption, meter reset,
E self diagnostic issue.
• Circuit Breaker monitoring and control with relay outputs and whetted digital
inputs.

Main characteristics
• Easy to install
Front display of PowerLogic PM5350P front display
Mounts using two clips, no tools required. Ultra compact meter with 44 mm depth
connectable up to 480 V L-L without voltage transformers for installations compli-
ant with category III, as per IEC 61010-1. See specification table for UL voltage
limits.
PB117512

• Easy to operate
Intuitive navigation with self-guided, language selectable menus, six lines, four
concurrent values. Two LEDs help confirm normal operation.

• Easy circuit breaker monitoring and control


Two relay outputs (high performance) to command most circuit breaker coils
directly. Monitored switches can be wired directly without external power supply.

• System status at a glance


Bright, anti-glare, backlit display plus two LEDs; orange for energy pulse or alarm
and green for heartbeat/communications indication.

• IEC 62053-22 class 0.5S accuracy for active energy


Accurate energy measurement for cost allocation.
Rear view of PowerLogic PM5350P
• Power Quality analysis
The PM5350P offers THD and TDD measurements as standard. Total Demand Dis-
tortion is based on a point of common coupling (PCC), which is a common point
that each user receives power from the power source. The TDD compares the
contribution of harmonics versus the maximum demand load. In addition, it has
individual harmonics (odd) measurement up to 31st harmonics. These types of
power quality parameters help to identify the source of harmonics that can harm
transformers, capacitors, generators, motors and electronic equipment.
Commercial
Description
reference number
Load management
METSEPM5350 RS-485 Modbus, THD, 4DI, 2Relay

• Peak demands with Timestamping are provided. Predicted demand values can be
used in basic load shedding applications.
• Alarming with timestamping
• Over 30 alarm conditions, such as under/over conditions, digital input changes,
and phase unbalance inform you of events. A time-stamped log maintains a
record of the last 40 alarm events.
• Load timer setpoint adjustable to monitor and advise maintenance requirements.
• Performance Standard Meets IEC 61557-12 PMD/Sx/K70/0.5.

E-116 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

A
PE86279

PE86275
B

Rear view retainers - installation E


PE86274

G
For detailed installation instructions see the product's Installation Guide.
H

I
PE113626
PB113626

PM5350 / PM5350P meter parts


A Retainer clips.
B Control power supply connector.
C Voltage inputs.
D Digital outputs.
E RS-485 port (COM1).
F Digital input.
G Optical revenue switch.
H Current inputs.

For detailed Installation instructions see the product's Installation Guide.

< >
se.com/au Life is On | Schneider Electric | E-117
Switchboard Manufacturers

Multi-circuit Metering
General Overview

PowerLogic™ HDPM6000
PowerLogic™ BCPM
This is an integrated solution for monitoring multi-circuits and mains by
using a single meter. The meter is designed for use in both new build and
retrofit and is used for critical power operations in data centers and energy
management in buildings.

The ideal solution for data center managers, energy or facility managers,
engineers and operational executives who are responsible for delivering
power to critical applications.

In corporate and hosted data center facilities, this technology helps you
plan and optimise the critical power infrastructure to meet the demands of
continuous availability

BCPMA084S

E-118 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

General Overview

Flexible metering system for A


new construction or retrofit
B
The HDPM6000 multi-circuit power metering system is modular,
scalable and adaptable to almost any situation. It is the perfect high-
density metering solution for main circuits and branch circuits in any C
Direct Webpage Remote System

type of electrical panel or busway system. Its flexible and innovative


design minimizes installation times and integration costs and the D
system can be expanded easily at any time.

Retrofit Enclosure Panelboard Installation Busway Installation H

Enable electrical network management


in new installations
Panelboard solutions

HDPM6000 panelboard metering solutions are intended for new construction when energy
and power quality monitoring is required down to the branch-circuit level. They are well-suited
for panelboards, power distribution units (PDUs) and remote power panels (RPPs).

The HDPM6000 head unit measures 3-phase power feeding the panelboard, and the
metering modules measure power on all the outgoing branch circuits. The head unit is
mounted beside the main breaker, connected to instrument current transformers (CTs)
installed on each phase of the main incoming circuit.

Panelboard metering modules are mounted vertically beside branch-circuit breakers and
are connected to CTs installed on each branch-circuit via click-in connectors. HDPM6000
panelboard metering modules have two Ethernet ports for connecting to other metering
modules.

Each HDPM6000 head unit can support a daisy-chain up to 8 (4 pairs) panelboard metering
modules for a total of 168 circuits.

< >
se.com/au Life is On | Schneider Electric | E-119
Switchboard Manufacturers

Multi-circuit Metering
General Overview

Retrofit into any type of electrical panel


Retrofit solutions

HDPM6000 retrofit metering solutions are designed to


add main, feeder and branch-circuit metering to any
type of electrical distribution panel, without the need for
mechanical or electrical design changes to the existing
panels.

CTs installed on the main incoming circuit are connected


E directly to the head unit, while CTs installed on any
downstream feeder and branch circuits are connected
to retrofit metering modules. There are three HDPM6000
retrofit metering module options: 24 circuit, 42 circuit and
84 circuit. Each head unit can support up to 192 circuits
from downstream retrofit metering modules.

HDPM6000 retrofit metering enclosures containing a


head unit and multiple retrofit modules are an effective
way to achieve power quality monitoring and high-density
metering for any type of electrical panel that did not have
any metering capabilities previously.

Add metering to any busway configuration


Busway solutions

HDPM6000 busway metering solutions are engineered


for new construction or retrofit when energy and power
quality monitoring are needed on every circuit feeding
loads from a busway distribution system.

HDPM6000 head units monitor the power feeding each


busway trunk, and busway metering modules monitor the
outgoing power from each tap box.

Head units are connected to CTs installed in main trunk


breaker boxes, while busway metering modules are
connected to CTs installed on outgoing circuits in tap
boxes.

There are two HDPM6000 busway metering module


options: 4 circuit and 8 circuit. Metering modules have LOADS LOADS
two Ethernet ports so they can be connected in a daisy-
chain. Each head unit can support up to 192 circuits
from downstream busways metering modules.

E-120 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

PowerLogic™ HDPM6000 series


General Overview

Accurate and adaptable A


branch circuit metering
B
PowerLogic HDPM6000 high-density multi-circuit power meters enable
customized panelboard solutions for cost and network management in C
critical facilities.

With a modular platform approach to minimize integration costs, start-


D
up time and operational expenses, HDPM6000 meters provide insight,
accuracy and results. The HDPM6000 head unit provides voltage waveform E
capture, data logging and full Ethernet communication. HDPM6000S, with
strip technology for branch circuit monitoring and click-in CT design, is
perfect for new installations. The modular HDPM6000R is highly adaptable F
and can be retrofited into any switchgear, distribution panel or cabinet with a
high density of circuits.
G

Applications Robust communications H


• Energy cost allocation • Support for MODBUS, SNMP and BACnet
» Accurately correlate and/or bill for circuit- and process-specific TCP IP
costs, keep users accountable for energy use I
• Energy monitoring Cybersecurity
» Gather and analyze consumption data to identify patterns, target • Helps minimize vulnerabilities to critical
energy efficiency measures and verify results, identify waste and power assets and systems and reinforce
opportunities to reduce energy security strategy
• Power quality monitoring per circuit (THD + waveform capture)
» Analyze and interpret power quality data into useful information, Data logging
improve system-wide performance, help determine causes of • On-board memory for data logging
equipment malfunction
• Meet the needs of robust code compliance
• Energy billing applications
• » View current and historic circuit-focused energy bills, compare
use across circuits, discover trends over time Modular and scalable
• Compliance • Adapts to expanding electrical networks
» ASHRAE 90.1-2019, Seattle energy code, Title 24, etc.*
• Scalable, future-proof capabilities
• Simplified installation for reduced wiring
Asset management
issues
• Monitor up to 192 circuits
• Identify increased harmonics in the rack servers to detect a Panelboard solution
potential failure (THD/circuit, waveform capture/circuit) • Embedded web page for configuration and
monitoring

* Contact your Schneider Electric sales representative for confirmation on


• Touch screen HMI (optional) for data display
compliance to other local standards not mentioned here
• EcoStruxure™ Power integration

< >
se.com/au Life is On | Schneider Electric | E-121
Switchboard Manufacturers

PowerLogic™ HDPM6000 series


Functions and characteristics

Switchboard configuration
HDPM6000 head unit
The HDPM6000 head unit serves as a stand-alone 3-phase power quality meter and the foundational unit for the entire
HDPM6000 range of devices. With 1% accuracy, THD metrics and waveform capture, the meter helps monitor and manage
critical circuits with greater reliability. CTs can be added or removed after the system is deployed and are available in any size
from 20A to 4000A (250mV rating).*

* Contact your Schneider Electric sales representative for ratings above 4000A

E
HDPM6000R HDPM6000S
• Retrofit or new installations • Perfect for new installations
• 24, 42 or 84 circuit modules; up to 192 circuits • 21 circuits per strip; maximum of eight strips connected to
• Metering system parameters: V, I, PF, kW, kWh, kVAr, one HDPM6000 head unit
kVArh, kVA, kVAh, THDv, THDi • Metering system parameters: V, I, PF, kW, kWh, kVAr, kVArh,
• Voltage and current waveform capture (optional) kVA, kVAh, THDv, THDi
• Voltage and current waveform capture (optional)

HDPM6000 HDPM6000R HDPM6000


head unit head unit

HDPM6000S HDPM6000S

Panelboard 1 Panelboard 2

Panelboard 1 Panelboard 2

E-122 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

General Overview

Accurate and adaptable A


busway metering
B
PowerLogic HDPM6000 high-density, multi-circuit power meters
provide an all-in-one solution for today’s modular and distributed
architectures in large and critical power applications C

The HDPM6000’s flexible platform helps to minimize integration costs, start- D


up time and operational expenses, as well as provide insight, accuracy
and results. The HDPM6000 head unit provides voltage waveform capture,
data logging and full Ethernet communication. The adaptable HDPM6000B E
communicates with the head unit and can be installed or retrofitted into any
busway configuration with a high density of circuits.
F

Applications Robust communications H


• Energy cost allocation • Support for MODBUS, SNMP and BACnet
» Accurately correlate and/or bill for circuit- and process-specific TCP IP
costs, keep users accountable for energy use I
• Energy monitoring Cybersecurity
» Gather and analyze consumption data to identify patterns, target • Helps minimize vulnerabilities to critical
energy efficiency measures and verify results, identify waste and power assets and systems and reinforce
opportunities to reduce energy security strategy
• Power quality monitoring per circuit (THD + waveform capture)
» Analyze and interpret power quality data into useful information, Data logging
improve system-wide performance, help determine causes of • On-board memory for data logging
equipment malfunction
• Meet the needs of robust code compliance
• Energy billing applications
• » View current and historic circuit-focused energy bills, compare
use across circuits, discover trends over time Modular and scalable
• Compliance • Adapts to expanding electrical networks
» ASHRAE 90.1-2016, Seattle energy code, Title 24, etc.*
• Scalable, future-proof capabilities
• Simplified installation for reduced wiring
Asset management
issues
• Monitor up to 192 circuits
• Identify increased harmonics in the rack servers to detect a Busway solution
potential failure (THD/circuit, waveform capture/circuit)
• Embedded web page for configuration and
monitoring

* Contact your Schneider Electric sales representative for confirmation on


• Touch screen HMI (optional) for data display
compliance to other local standards not mentioned here
• EcoStruxure™ Power integration

< >
se.com/au Life is On | Schneider Electric | E-123
Switchboard Manufacturers

PowerLogic™ HDPM6000 series


Functions and characteristics

Busway configuration
Modular and distributed design suitable for large and critical applications

HDPM6000 head unit HDPM6000B features


The HDPM6000 head unit serves as a stand- • Four or eight circuit modules
alone 3-phase power quality meter and the • Waveform capture (six cycles)
foundational unit for the entire HDPM6000
• Metering system parameters: V, I,
range. With 1% accuracy, THD metrics and
PF, kW, kWh, kVAr, kVArh, kVA, kVAh,
E waveform capture, the meter helps monitor
THDv, THDi
and manage critical circuits with greater
reliability. CTs can be added or removed after • Combine up to 48 four-circuit tap
the system is deployed and are available in cards, 24 eight-circuit tap cards, or
any size from 20A to 4000A (250mV rating).* any combination of the two types
of tap card units, totaling up to a
* Contact your Schneider Electric sales maximum of 192 circuits in a single
representative for ratings above 4000A chain
Optional inside
mounted HDPM6000B

Busway monitoring solution


Access the meter via IP address to commission, setup,
configure alarms, view power quality data and waveforms.
Use touch screen HMI display to view real time meter data,
and integrate with EcoStruxure Power applications via Power
Monitoring Expert or Power SCADA Operations.

E-124 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

The PowerLogic™ HDPM6000 sets a new standard for Power Quality Meters as both a standalone three-phase PQM and the
foundation for an entire suite of devices: HDPM6000R, HDPM6000S, and HDPM6000B
A

The HDPM6000 is both a standalone 3-phase power quality meter (PQM) and the hub for Schneider Electric’s branch circuit B
accessory modules (HDPM6000R, HDPM6000S, HDPM6000B). It can monitor loads up to 4000 A with utility grade system
accuracy, delivers a complete range of power quality metrics (vTHD, iTHD), and provides waveform capture functionality without
the need for additional proprietary software. The HDPM6000 can also maintain multiple, concurrent sessions with EPMS, DCIM
C
or BMS applications via the Modbus, SNMP and BACnet IP protocols. Dual Ethernet ports allow multiple HDPM6000 head units
to be daisy-chained in a single run. D
Thanks to open protocols, the HDPM6000 is easily integrated into any data center or building management information system.
Gateways or additional hardware are not required and the platform offers most standard forms E
of data connectivity. The on-board environmental communications port enables one-wire sensors to detect abnormal
temperature and humidity conditions so adjustments can be made before problems occur.
F
Applications
Ideal for large critical and non-critical building applications such as data centers, industrial facilities, infrastructure and other G
similar environments.connectivity.

I
PB120560

< >
se.com/au Life is On | Schneider Electric | E-125
Switchboard Manufacturers

PowerLogic™ HDPM6000 series


Functions and characteristics

Market solutions Power management solutions


Markets that benefit from a solution that includes HDPM6000S: Schneider Electric provides
innovative power management
• Data centers solutions to increase your energy
• Industrial facilities efficiency and cost savings.
• Healthcare facilities Maximize electrical network reliability
• Manufacturing and availability, and optimize
• Many other critical and non-critical facilities electrical asset performance.

Benefits
E
• Modular platform approach provides scalability and minimizes integration Standards
costs, start up time and operational expenses.
• EN 55011/CISPR11
• Provides power quality metrics down to the branch circuit allowing users to
• EN 61326-1
effectively monitor circuit loads, manage power consumption, allocate energy
costs and maximize uptime across their facilities. • IEC 61000-4-2
• Makes energy and power quality data immediately actionable and relevant to • IEC 61000-4-3
operational and sustainability goals • IEC 61000-4-4
• IEC 61000-4-5
Competitive advantages • IEC 61000-4-6
• IEC 61000-4-11
• Asset management
- Identify increased harmonics in the rack servers to detect a potential • IEC 61010-1
disruption • IEC 61010-030
- Total Harmonics Distortion • UL. 61010-1
- Waveform capture
• UL 61010-2-030
• Display and web page visualization
- Optional touchscreen display accesses meter data
- User-friendly web interface allows configuration of branch circuits and
commissioning of meter system
• Data logging and software monitoring
- Data logging and on-board memory storage
- EcoStruxure™ PME and PSO integration

E-126 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

Measurements
A
• Current per branch and sum of all phases
PB120553

• Energy (kWh) per branch and sum of all phases


B
• Real Power (kW) per branch and sum of all phases
• Apparent Power (kVA) per branch and sum of all phases
• Reactive Power (kVAR) per branch and sum of all phases
C
• Current waveform capture (optional)
• Total Harmonic Distortion (THD) D
• Power factor (signed, to show leading or lagging current), per branch
and average of all phases for multi-phase logical circuits. E
HDPM6000 head unit with modules
F

Features Guide G
Power quality analytics Waveform capture and voltage and current THD

Web interface For configuration and live data access


H
PB120548

Supported protocols Modbus TCP/IP, SNMP, BACnet

Data storage and logging 8 GB Class 10 SD card included

Alarms On-board user-configurable alarms and alerts


I

HDPM6000 head unit Technical specifications

Electrical characteristics

20-4000 A with internal burdened resister and 250 mV


CT support signal (no shorting blocks required)

Solid-core or split-core type current transformers with a


maximum voltage of 480 V. CTs are accurate from 1-100%
CT options
PB120549

of the range and are factory calibrated to ensure system


accuracy.

Environmental characteristics
Operating temperature -20 to 60 °C

Storage temperature -40 to 85 °C

Relative humidity 5 to 90% non-condensing

Maximum operating altitude 2,000 m

Non-operating altitude 15,000 m

Noise level < 65 dba at six feet from the PQM


HDPM6000 I/O module Mounting location Not suitable for wet locations. For indoor use only.

< >
se.com/au Life is On | Schneider Electric | E-127
Switchboard Manufacturers

PowerLogic™ HDPM6000 series


Functions and characteristics

HDPM6000 Enclosure
PowerLogic™ HDPM6000 Enclosure Size Options
PB120557

PB120558
E

PowerLogic™ HDPM6000 large size enclosure PowerLogic™ HDPM6000 medium size enclosure
PB120559

PB120553

PowerLogic™ HDPM6000 detail dimensions

7.84”
(199.14 mm)
PB120556

PowerLogic™ HDPM6000 small size enclosure 5.82”


(147.83 mm)

Commercial reference numbers


A complete list of HPDM commercial reference numbers
appears in the Commercial Reference Numbers section of
the PowerLogic Catalog. Contact your Schneider Electric HMI detail dimensions
representative for complete ordering information

E-128 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

< >
se.com/au Life is On | Schneider Electric | E-129
Switchboard Manufacturers

PowerLogic™ BCPM
General Overview

The PowerLogic BCPM is a highly accurate, full-featured metering product designed for the unique, multi-circuit and
minimal space requirements of a high-performance power distribution unit (PDU) or remote power panel (RPP).

It offers class 1 (1 %) power and energy system accuracy (including 50 A or 100 A CTs) on all branch channels. The BCPM
monitors up to 84 branch circuits and the incoming power mains to provide information on a complete PDU. Full alarming
capabilities ensure that potential issues are dealt with before they become problems.

Applications
• Maximise uptime and avoid outages
• Optimise existing infrastructure
E • Improve power distribution efficiency
• Track usage and allocate energy costs
• Enable accurate sub-metering

BCPMA084S

E-130 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

The solution for Power management solutions A


Markets that can benefit from a solution that includes PowerLogic BCPM Schneider Electric provides
series meters: innovative power management
B
• Data centres solutions to increase your energy
efficiency and cost savings,
• Buildings
maximise electrical network reliability C
and availability, and optimise
Benefits electrical asset performance.
The flexible BCPM fits any PDU or RPP design and supports both new and
D
retrofit installations. It has exceptional dynamic range and accuracy, and Conformity of standards
optional feature sets to meet the energy challenges of mission critical data E
• ANSI C12.1
centres.
• IEC 61010-1
• IEC 62053-21 Class 1 F
Competitive advantages
• UL508
• Fit any PDU or RPP design for both new and retrofit projects
• Class 1.0 system accuracy G
• Ethernet communication
H

< >
se.com/au Life is On | Schneider Electric | E-131
Switchboard Manufacturers

PowerLogic™ BCPM
General Overview

Main characteristics
• Monitor up to 84 branch circuits with a single BCPM.
PE86281

• Ideal for installation in both new PDUs and retrofit projects


• New installations:
BCPM with solid core CTs monitors up to 84 branch circuits using
2 or 4 CT strips. Solid core CTs are rated to 100 A CTs and are
mounted on strips to simplify installation. CT strips are available with
12, 18 or 21 CTs per strip on 18 mm spacings. 21 CT strips with 3/4in
or 1in spacings are also available.

• Retrofit projects:
BCPMSC with split-core CTs is ideal for retrofits. Any number of split-
E core CTs, up to 84 maximum, can be installed with a single BCPM.
Three sizes of CT are supported (50 A, 100 A, and 200 A) and all
three CT sizes can be used on a single BCPM. Adapter boards with
terminals for split-core CTs can be mounted using DIN-rail, Snaptrack
or on a common mounting plate with the main board (42 ch Y63
models only).
PB113664

• IEC Class 1 metering accuracy


Accurately monitor very low current levels, down to a quarter-Amp.
Easily differentiate between the flow of low current and a trip where
no current flows.
• Class 1.0 system accuracy for Revenue Grade measurements
Branch Power and Energy measurements fully meet ANSI and IEC
class 1 accuracy requirements with 50 or 100 A CTs included. No
need to de-rate meter branch accuracy to allow for CTs. Voltage and
current measurement accuracy is 0.5 % and currents are measured
down to 50mA. Easily differentiate between the flow of low current
and a trip where no current flows.

Class 1.0 system accuracy for Revenue Grade measurements

Branch Power and Energy measurements fully meet ANSI and IEC
class 1 accuracy require
PB113645

PB113648

• Power quality: obtain basic power quality data thanks to the


measurement of Total Harmonic Distortion percentages on voltages
and current. (V L-L, V L-N, I L-N).

• Designed to fit any PDU or RPP design


PB113646

Lowers your total installation costs as well as the cost per meter point
by supporting both new and retrofit installations.

• Communicates with your various systems: BCPMA, and BCPMSCA


have a Modbus RTU connection BCPME, and BCPMSCE, have a serial
PB113647

connection for either Modbus RTU or BACnet MS/TP. And there is an


ethernet connection for Modbus TCP, BACnet IP and SNMP at the
same time. Allowing the concurrent use of an Energy Management
System, a Building Management System and an IT system.

• Compatible with PowerLogic power monitoring software


PB113649

Easily turn the large amount of data collected by the devices into
useful decision-making information.

• Flexible Configuration capability


Set the ordering and orientation of CT strips, assign individual
CT size and phases, support for 1, 2, and 3-pole breakers in any
configuration.

E-132 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

A
PE86167

Feature selection BCPMA BCPME


General

Use on LV systems
B
Power and energy measurements

Mains C
Branch circuits

Instantaneous rms values


D
Voltage, frequency

Current

Active power Total and per phase


E
PowerLogic BCPM Power factor Total and per phase

1. 50-pin ribbon cable connectors Energy values F


(data acquisition board). Active energy
2. Auxiliary inputs. Demand values
3. Control (mains) power connection. G
Total active power Present and max. values
4. Control power fuse.
Power quality measurements
5. Alive LED.
THD % (V L-L, V L-N, I L-N) H
6. Voltage taps.
7. Communications address DIP Detection of over-voltage/under-voltage
switches. Sampling rate points per cycle 2560 Hz 2560 Hz I
8. Communications settings DIP Alarming
switch.
Alarms
9. RS-485 2 connection. 10 RS-485
Power supply
LEDs.
90-277 100-277
AC version
V AC V AC
Communication

RS-485 port
Modbus RTU RTU

Modbus TCP 1g

BACnet IP 1g

BACnet MS/TP 1g

SNMP protocol 1g

Ethernet Port 1g

g1 Add E8951 Gateway

< >
se.com/au Life is On | Schneider Electric | E-133
Switchboard Manufacturers

PowerLogic™ BCPM
General Overview

BCPM part numbers

BCPM with solid core CTs


PE86168

Item Code Description


BCPM with solid core CTs. Highly accurate
meter that monitors branch circuits and
1 Model BCPM
Example BCPM with solid core CTs part the incoming power mains and includes full
alarming capabilities
number
Advanced - Monitors power & energy per
1. Model circuit & mains, Modbus RTU only (add
2. Feature set A E8951 for other protocols), Meter Main
3. CT spacing (solid core models only) Board comes on an aluminum mounting
2 Feature set plate
4. Number of circuits
Advanced, with Ethernet - Monitors power &
5. Brand E energy per circuit & mains, Meter Main Board
E is partially enclosed in a metal housing

0 3/4in (19 mm) CT spacing


The PowerLogic BCPM uses .333 V AC output
split-core CTs for the auxiliary inputs. These
CTs are ordered separately from the BCPM. 3 CT spacing 1 1in (26 mm) CT spacing

2 18 mm CT spacing
PB113664

24 circuits, (2) 12-CT strips (18 mm spacing


24 only)

36 circuits, (2) 18-CT strips (18 mm spacing


36 only)

42 42 circuits, (2) 21-CT strips


4 Number of circuits
48 circuits, (4) 12-CT strips (18 mm spacing
48 only)

72 circuits, (4) 18-CT strips (18 mm spacing


72 only)

84 84 circuits, (4) 21-CT strips

5 Brand S Schneider Electric


PB113665

* Quantity and style of CT strips and cables


included varies by model

E-134 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

BCPM part numbers (contd.) A


PB113735

BCPM with split-core CTs BCPM with split-core CTs


BCPM with split-core CTs. Highly accurate meter
that monitors branch circuits and the incom-
B
1 Model BCPMSC ing power mains and includes full alarming
capabilities
Example BCPMSC with split-core CTs Advanced - Monitors power and energy per
circuit and mains, Modbus RTU only (add E8951
C
part number. A for other protocols), Meter Main Board comes on
an aluminum mounting plate
1. Model.
B
Intermediate - Monitors current per circuit, pow-
er and energy per mains, Modbus RTU only (add D
2. Feature set. E8951 for other protocols), Meter Main Board
3. Number of circuits. 2 Feature set comes on an aluminum mounting plate
4. Brand. Basic - Monitors current only per circuit and
C mains, Modbus RTU only (add E8951 for other E
protocols), Meter Main Board comes on an alu-
minum mounting plate
Advanced, with Ethernet - Monitors power &
E energy per circuit & mains, Meter Main Board is F
enclosed in a metal housing
42 circuit main and adapter boards (no branch
1
PB113666

CTs or ribbon cables, order separately)


84 circuit main and adapter boards (no branch
G
2 CTs or ribbon cables, order separately)

30 30 split-core CTs (50 A)


H
3 Number of circuits 42 42 split-core CTs (50 A)

60 60 split-core CTs (50 A) I


84 84 split-core CTs (50 A)

42 circuits – main and adapter boards on single


Y63 mounting plate (no branch CTs or ribbon, order
separately) - Feature set A only

4 Brand S Schneider Electric

*The BCPMSC models with 1, 2 or Y63 as the number of circuits DO NOT INCLUDE ANY branch
CTs or ribbon cables (they include only the Main board and adapater board assemblies). These
models are provided to allow users to order a specific combination of CT quantities, CT sizes, CT
lead lengths and ribbon cable styles and lengths. The CTs and cables must be ordered separately.

The PowerLogic BCPMSC uses .333 V AC output split-core CTs for the auxiliary inputs. These CTs are
PB113730

ordered separately from the BCPMSC.

< >
se.com/au Life is On | Schneider Electric | E-135
Switchboard Manufacturers

PowerLogic™ BCPM
Reference Numbers

BCPM part numbers for solid and split-core CTs (contd.)


BCPM with split-core CTs
PE86284

Commercial Description
ref. no.
BCPMA042S 42-circuit solid core power & energy meter, 100 A CTs (2 strips), 19 mm spacing

BCPMA084S 84-circuit solid core power & energy meter, 100 A CTs (4 strips), 19 mm spacing

BCPMA142S 42-circuit solid core power & energy meter, 100 A CTs (2 strips), 25 mm spacing

Flat ribbon cable BCPMA184S 84-circuit solid core power & energy meter, 100 A CTs (4 strips), 25 mm spacing

BCPMA224S 24-circuit solid core power & energy meter, 100 A CTs (2 strips), 18 mm spacing
E BCPMA236S 36-circuit solid core power & energy meter, 100 A CTs (2 strips), 18 mm spacing

BCPMA242S 42-circuit solid core power & energy meter, 100 A CTs (2 strips), 18 mm spacing

CBL016 BCPMA248S 48-circuit solid core power & energy meter, 100 A CTs (4 strips), 18 mm spacing

BCPMA272S 72-circuit solid core power & energy meter, 100 A CTs (4 strips), 18 mm spacing

BCPMA284S 84-circuit solid core power & energy meter, 100 A CTs (4 strips), 18 mm spacing
PB113650

BCPME042S 42-circuit solid core power & energy meter w/Ethernet, 100 A CTs (2 strips), 19 mm spacing

BCPME084S 84-circuit solid core power & energy meter w/Ethernet, 100 A CTs (4 strips), 19 mm spacing

BCPME142S 42-circuit solid core power & energy meter w/Ethernet, 100 A CTs (2 strips), 25 mm spacing

BCPME184S 84-circuit solid core power & energy meter w/Ethernet, 100 A CTs (4 strips), 25 mm spacing
Round ribbon cable
BCPME224S 24-circuit solid core power & energy meter w/Ethernet, 100 A CTs (2 strips), 18 mm spacing

BCPME236S 36-circuit solid core power & energy meter w/Ethernet, 100 A CTs (2 strips), 18 mm spacing

BCPME242S 42-circuit solid core power & energy meter w/Ethernet, 100 A CTs (2 strips), 18 mm spacing

BCPME248S 48-circuit solid core power & energy meter w/Ethernet, 100 A CTs (4 strips), 18 mm spacing
CBL022

BCPME272S 72-circuit solid core power & energy meter w/Ethernet, 100 A CTs (4 strips), 18 mm spacing

BCPME284S 84-circuit solid core power & energy meter w/Ethernet, 100 A CTs (4 strips), 18 mm spacing

Cabling and connection

Flat ribbon cables are recommended for use when


the BCPM printed circuit board will be mounted
inside of the PDU that is being monitored. Round
ribbon cables are the prefered choice when the
ribbon cable will be threaded through conduit.

E-136 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Reference Numbers

BCPM part numbers for solid and split-core CTs (contd.) A


BCPM with split-core CTs
PB113651

Commercial Description
ref. no. B
BCPMSCA1S 42-circuit split-core power and energy meter, CTs and cables sold separately

BCPMSCA2S 84-circuit split-core power and energy meter, CTs and cables sold separately
C
BCPMSCA1S

BCPMSCA30S 30-circuit split-core power and energy meter, (30) 50 A CTs & (2) 1.2 m cables
D
BCPMSCxY63S 42-circuit split-core models BCPMSCA42S 42-circuit split-core power and energy meter, (42) 50 A CTs & (2) 1.2 m cables
come with the main board, (2) adapter boards
and ribbon cables all mounted on a backplate, E
to simplify installation. BCPMSCA60S 60-circuit split-core power and energy meter, (60) 50 A CTs & (4) 1.2 m cables

BCPMSCAY63S 42-circuit split-core power and energy meter, all boards on backplate, CTs and cables
sold separately
F
PE86183

BCPMSCA84S 84-circuit split-core power and energy meter, with (84) 50 A CTs & (4) 1.2 m cables
G
BCPMSCE1S 42-circuit split-core power and energy meter w/Ethernet, CTs and cables sold separately

BCPMSCE2S 84-circuit split-core power and energy meter w/Ethernet, CTs and cables sold separately H
BCPMSCE30S 30-circuit split-core power and energy meter w/Ethernet, (30) 50 A CTs & (2) 1.2 m
cables
I
BCPMSCE42S 42-circuit split-core power and energy meter w/Ethernet, (42) 50 A CTs & (2) 1.2 m
cables
LVCT00050S
BCPMSCE60S 60-circuit split-core power and energy meter w/Ethernet, (60) 50 A CTs & (4) 1.2 m
PowerLogicTM LVCT0xxxxS Split-core Low- cables
voltage (1/3V) CTs for Aux inputs (Mains) are
ideal for retrofit applications BCPMSCE84S 84-circuit split-core power and energy meter w/Ethernet, (84) 50 A CTs & (4) 1.2 m
cables

The PowerLogicTM BCPM uses .333 V AC output split-core CTs for the auxiliary inputs. These CTs are
ordered separately from the BCPM.
PB113652

PB113657
PB113658

LVCT20050S

PowerLogicTM LVCT2xxxxS Low-voltage (1/3V)


solid core CTs for Aux inputs (Mains) are ideal
for panel builders (small, medium, large)

< >
se.com/au Life is On | Schneider Electric | E-137
Switchboard Manufacturers

PowerLogic™ BCPM
Reference Numbers

Commercial ref. no.


BCPM split-core branch CTs and adapter boards

BCPMSCADPBS BCPM adapter boards, quantity 2, for split-core BCPM

BCPMSCCT0 BCPM 50 A split-core CTs, Quantity 6, 1.8 m lead lengths

BCPMSCCT0R20 BCPM 50 A split-core CTs, quantity 6, 6 m lead lengths

BCPMSCCT1 BCPM 100 A split-core CTs, Quantity 6, 1.8 m lead lengths

BCPMSCCT1R20 BCPM 100 A split-core CTs, Quantity 6, 6 m lead lengths

BCPMSCCT3 BCPM 200 A split-core CTs, Quantity 1, 1.8 m lead lengths

BCPMSCCT3R20 BCPM 200 A split-core CTs, Quantity 1, 6 m lead lengths

E Commercial ref. no.


Additional accessories for use with BCPM products

BCPMCOVERS BCPM circuit board cover

BCPMREPAIR CT repair kit for solid core BCPM (includes one CT)

CBL016 Flat Ribbon cable (quantity 1) for BCPM, length = 1.2 m

CBL017 Flat Ribbon cable (quantity 1) for BCPM, length = 1.5 m

CBL018 Flat Ribbon cable (quantity 1) for BCPM, length = 1.8 m

CBL020 Flat Ribbon cable (quantity 1) for BCPM, length = 3.0 m

CBL021 Flat Ribbon cable (quantity 1) for BCPM, length = 6.1 m

CBL022 Round Ribbon cable (quantity 1) for BCPM, length = 1.2 m

CBL024 Round Ribbon cable (quantity 1) for BCPM, length = 6.1 m

1/3 V low-voltage Split-core CTs for Aux inputs (Mains)


Commercial ref. no. Amperage rating Inside dimensions
LVCT00050S 50 A 10 mm x 11 mm

LVCT00101S 100 A 16 mm x 20 mm

LVCT00202S 200 A 32 mm x 32 mm

LVCT00102S 100 A 30 mm x 31 mm

LVCT00202S 200 A 30 mm x 31 mm

LVCT00302S 300 A 30 mm x 31 mm

LVCT00403S 400 A 62 mm x 73 mm

LVCT00603S 600 A 62 mm x 73 mm

LVCT00803S 800 A 62 mm x 73 mm

LVCT00804S 800 A 62 mm x 139 mm

LVCT01004S 1000 A 62 mm x 139 mm

LVCT01204S 1200 A 62 mm x 139 mm

LVCT01604S 1600 A 62 mm x 139 mm

LVCT02004S 2000 A 62 mm x 139 mm

LVCT02404S 2400 A 62 mm x 139 mm

1/3 V low-voltage Solid core CTs for Aux inputs (Mains)


Commercial ref. no. Amperage rating Inside dimensions
LVCT20050S 50 A 10 mm

LVCT20100S 100 A 10 mm

LVCT20202S 200 A 25 mm

LVCT20403S 400 A 31 mm

E-138 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics


Technical specifications
Electrical characteristics
A
Type of measurement
Accuracy Power/energy 1 % system accuracy (including 50A or 100A branch CTs) B
Voltage ±0.5 % of reading

Current ±0.5 % of reading


C
Minimum “ON” current 50mA

Sampling rate Points per cycle 2560 Hz

Data update rate 1.8 seconds (Modbus), 14 seconds (BACnet) 20 sec (SNMP)
D
Input-voltage characteristics Measured voltage 150 – 480 V AC L-L (1)

90 – 277 V AC L-N (1) E


Measurement range 150 – 480 V AC L-L (1)

90 – 277 V AC L-N (1)


F
Power supply AC 100 – 277 V AC (50/60 Hz)

Auxiliary CT Current Input Range 0-0.333V; CTs must be rated for use with Class 1 voltage inputs

Mechanical characteristics
G
Weight 1.5 kg

Dimensions A/B/C model Circuit board 288 x 146 mm H


E model housing (w/brackets on long sides) 253 mm W x 307 mm H x 71 mm D

E model housing (w/brackets on short ends) 210 mm W x 353 mm H x 71 mm D


I
Environmental conditions
Operating temperature 0 to 60 ºC

Storage temperature -40 ºC to 70 ºC

Installation category CAT III, pollution degree 2

Safety
Europe IEC 61010

U.S. and Canada UL 508 Open type device

Communication
RS-485 (A/B/C models) Baud rate: DIP-switch selectable 9600, 19200, 38400
DIP-switch selectable 2-wire or 4-wire RS-485. Parity selectable: Even, Odd or None.
Baud rate: configured via Web-server. Baud selectable: 9600, 19200, 38400. Parity selectable:
RS-485 (A models) Even, Odd or None. 2-wire RS-485.
Ethernet (E models) 10/100 Mbit Ethernet. RJ-45 connection. Static IP or DHCP.
Modbus RTU on all models, BCPME models also support Modbus TCP, SNMP, BACnet IP & BACnet
Protocols MS/TP
Firmware characteristics
Detection of over-voltage/under- User-defined alarm thresholds for over-voltage and under-voltage detection
voltage
Four alarm levels: high-high, high, low and low-low (users define the setpoints for each). Each
Alarms alarm has a latching status to alert the operator that an alarm has previously occurred. High and
Low alarms have instantaneous status to let the operator know if the alarm state is still occurring.
Firmware Update Update via Modbus

< >
se.com/au Life is On | Schneider Electric | E-139
Switchboard Manufacturers

PowerLogic™ BCPM
Functions and characteristics

1/3 V low-voltage CT (LVCT) for Mains - Technical specifications

Electrical characteristics
1 % from 10 % to 100 % of rated current(LVCT0xxxx0S/1S/2S/3S/4S [split-core])
Accuracy
0.5 % from 5 % to 100 % of rated current (LVCT2xxxx0S/2S/3S [solid core])

Frequency range 50/60 Hz

Leads 18 AWG, 600 V AC, 1.8m standard length

Max. voltage L-N sensed conductor 300 V AC (LVCT0xxxx0S)

600 V AC (LVCT0xxxx1S/2S/3S/4S, LVCT2xxxxxS)

Environmental conditions
E 0 ºC to 70 ºC (LVCT0xxxx0S/1S)

-15 ºC to 60 ºC (LVCT0xxxx2S/3S/4S less than 2400A)


Operating temperature
-15 ºC to 60 ºC (LVCT02404S [2400A])

-40 ºC to 85 ºC (LVCT2xxxx0S/2S/3S [solid core])

-40 ºC to 105 ºC (LVCT0xxxx0S/1S)

Storage temperature -40 ºC to 70 ºC (LVCT0xxxx2S/3S/4S)

-50 ºC to 105 ºC (LVCT2xxxx0S/2S/3S [solid core])

Humidity range 0 to 95 % non-condensing

E-140 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

PowerLogic BCPM dimensions


A

B
PE86286_m

PE862169
C

F
PowerLogic BCPM adapter board (one board per 21
split- core branch CTs)
G

I
PB113662

PB113661

< >
se.com/au Life is On | Schneider Electric | E-141
Switchboard Manufacturers

PowerLogic™ BCPM
Functions and characteristics

50 A-200 A Split-core CT dimensions


PB113659

PB113659

PB113659
These dimensions apply to both BCPMSCCTxx (branch CTs) and
LVCT0xxxx0S/1S (for Mains) 50 A-200 A CT families.

Solid core CT dimensions


PB113660_m

Model L A B C D E
LVCT20050S 1.8 m 33 mm 38 mm 18 mm 21 mm 10 mm

LVCT20100S

LVCT20202S 1.8 m 59 mm 66 mm 18 mm 31 mm 25 mm

LVCT20403S 1.8 m 70 mm 82 mm 25 mm 36 mm 31 mm

1/3 V low-voltage CT form factor


Small form factor Medium form factor Medium form factor
100/200/300 Amp 400/600/800 Amp 800/1000/1200/1600/2000/2400 Amp
A = 96 mm A = 125 mm A = 125 mm
PB113663

B = 30 mm B = 73 mm B = 139 mm
C = 31 mm C = 62 mm C = 62 mm
D = 30 mm D = 30 mm D = 30 mm
E = 100 mm E = 132 mm E = 201 mm
F = 121 mm F = 151 mm F = 151 mm

E-142 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

PowerLogic BCPM with solid core CT strips installation details


A

Circuit monitoring 4 CT strips


monitor up to 84 circuits B
Mains monitoring
(CTs ordered separately)
C
PE86171

Transducers (1/3 Vac) E

F
BCPM PCB

I
PowerLogic BCPM with split-core CTs installation details
PE86287

< >
se.com/au Life is On | Schneider Electric | E-143
Switchboard Manufacturers

Retrofit products
General Overview

The advantages of using retrofit products throughout your power monitoring system are numerous and proven.
Whether you install these products as part of an upgrade or as add-on modules in a new build environment, ease
of installation and commissioning will reap huge economic benefits. The PowerLogic range is designed to retrofit
existing switchboards and enhance the energy efficiency of buildings for many years.

These products are:


• Easy and cost-effective to install
• Able to collect a broad scop of electrical data
• Able to utilize a variety of meters to measure WAGES (Water, Air, Gas, Electricity, Steam) usage
E • Transmit all data to a centralized data concentrator for detailed analysis

EM3555 series
The EM3555 DIN Rail Meter combines exceptional
performance and easy installation to deliver a cost-
effective solution for power monitoring applications.

The EM3555 can be installed on standard DIN rail or


surface mounted as needed. Pulse output and phase
PB115451

alarms provide additional versatility.

Applications
Capable of essential cost management:
• Energy monitoring in building automation systems
• Renewable energy monitoring
PB105431

• Commercial sub-metering
• Energy management
• Industrial monitoring
• Accurate cost allocation

METSEEM3502

E-144 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Retrofit products EM3555 series


General Overview

The solution for Power management solutions A


Schneider Electric provides
Markets that can benefit from a solution that includes PowerLogic
innovative power management
EM3500 series meters:
solutions to increase your energy B
• Buildings efficiency and cost savings,
• Industry maximise electrical network reliability
C
• Healthcare and availability, and optimise
electrical asset performance.
• Data Centre and networks
D
• Infrastructure
Conformity of standards
Benefits • IEC 61557-12 • IEC 61000-4-4 E
System integrators’ benefit • IEC 62053-22 • IEC 61000-4-5
• Ease of integration • IEC 62053-24 • IEC 61000-4-6
F
• Ease of setup • IEC 61010-1 • IEC 61000-4-8
• Cost effectiveness • IEC 61000-4-2 • Etc.
• IEC 61000-4-3
G
Panel builders’ benefit
• Ease of installation H
• Cost effectiveness
• Aesthetically pleasing
I
• Simplified ordering

End users’ benefit


• Ease of use
• Precision metering & sub-billing
• Billing flexibility
• Comprehensive, consistent and superior performance

Competitive advantages
• DIN rail mounting option; easy installation
• Real energy output and phase loss alarm output
• 90-600 V AC; application versatility with fewer models to stock
• Bright backlit LCD; easy visibility in dark enclosures
• Data logging capability safeguard during power failures
• EM35xx models compatible with LVCTs from 5 A to 32000 A
• User-enabled password protection prevents tampering
• Native BACnet MS/TP support (no gateway)

< >
se.com/au Life is On | Schneider Electric | E-145
Switchboard Manufacturers

Retrofit products EM3555 series


Functions and characteristics

The data logging capability (EM3555) protects data in the event of a power failure.
Modbus, pulse output, and phase alarms are all provided to suit a wide variety of
applications. Additional pulse inputs provide an easy way to incorporate simple flow
sensors to track gas, water, steam, or other energy forms us- ing a BACnet system in
PB105431

addition to full monitoring of electrical energy.

The EM3555 models adds a bi-directional monitoring feature designed expressly for
renewable energy applications, allowing measurement of power imported from the
utility grid as well as power exported from the renewable energy source (e.g. solar
panels). In this way, a facility administrator track all energy data, ensuring accuracy in
billing and crediting.

E
• Features
PowerLogicTM EM3555 - All Models: A compact solution for panelboard monitoring
- DIN rail mounting option; easy installation
- IEC 62053-22 Class 0.2S for all 35xx models; great for cost allocation
- IEC 62053-22 Class 0.5S for EM35xxA models
- Real energy output and phase loss alarm output; one device serves multiple
PB113727

applications
- 90-600 VAC; application versatility with fewer models to stock
- Bright backlit LCD; easy visibility in dark enclosures
- Data logging capability EM3555; safeguard during power failures
- EM3555 models compatible with LVCTs from 5 A to 32000 A; wide range of
service types
- User-enabled password protection; prevents tampering
- System integration via Modbus EM3555, convenient compatibility with ......
existing systems

- EM3555 Models: An essential solution for Solar and other renewable


energy applications
- Bi-directional metering (4-quadrant); allows net metering
- Data logging capability; ensures long term data retrieval
PB113728

EM3555 parts and connection terminals

E-146 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics


Selection guide
Electrical characteristics A
Inputs Control Power, AC 50/60 Hz; 5 VA max.; 90 V min.;
UL Maximums: 600 V L-L (347V L-N ); CE
Maximums: 300 V L-N (520V L-L ) B
PB105437

3W max.; UL and CE: 125 to 300 V DC


Control Power, DC (external DC current limiting required)

Voltage Input UL: 90 V L-N to 600 V L-L ; CE: 90 V L-N


to 300 V L
C
5 A to 32,000 A Non “A” models only 20 A
Current Input Scaling to 5000 A for “A” models only

Input Range 1/3V and 1V nominal LVCT (selectable) D


Non “A” models only
Rogowski coil CTs only for “A” models

Pulse Inputs Two sets of contact inputs to pulse accu-


mulators
E
EM3555 in enclosure with door open
(EM3560 & EM3560A)
0.2 % (ANSI C12.20, IEC 62053-22 Class
Accuracy Real Power and Energy 0.2S) F
EM35xx models only
0.5 % (ANSI C12.20, IEC 62053-22 Class
0.5S) G
EM35xxA models only
All Models (EM3560, Real Energy Pulse: N.O. static; Alarm
Outputs EM3560A, EM3561 &
EM3561A) contacts: N.C. static H
EM3502 Reactive energy pulse 30 VAC/DC
EM3550, EM3555, RS-485 2-wire Modbus RTU (1200 baud
to 38.4 kbaud)
I
EM3550A
EM3560, EM3560A, RS-485 2-wire BACnet MS/TP (9600 baud
EM3561, EM3561A to 115.2 kbaud)

Mechanical characteristics
Mounting DIN Rail or 3-point screw mount
Environmental conditions
Operating tempera- -30 °C to 70 °C
ture Range
Storage Tempera- -40 °Cto 85°C
ture Range
Humidity Range <95 % RH non-condensing
Accessories
NEMA 4x enclosure (EM3500-ENC, pictured)
Split-core low voltage CTs (LVCTxx)
Fuse kits (EFP1, EFP2, EFP3)
Safety
US and Canada (cULus) UL508 (open type device)/CSA 22.2 No. 14-05
Europe (CE) EN61010-1:2001

Feature selection
Commercial reference number Model Description
METSEEM3555 EM3555 Modbus - 4 quadrant with logging

Display Screen Diagram


Screen Name or Units
Alive Indicator
PB105436

Diagnostic
Alert

Export

Import

Transmit Data
Receive Data
Receive Data Error
Numeric Data

< >
se.com/au Life is On | Schneider Electric | E-147
Switchboard Manufacturers

Retrofit products EM3555 series


Functions and characteristics

EM3555 dimensions
PB105420

PB10542
E
PB105439

Bottom View (DIN Mount Option)

E-148 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

< >
se.com/au Life is On | Schneider Electric | E-149
Switchboard Manufacturers

Insulation Monitoring Devices


General Overview

VigilOhm Insultation
Monitoring Devices

An IT earthing system allows your electrical distribution


system to continually operate, even in the presence of an
insulation fault, without endangering people or property.

Required as part of an IT earthing system, an insulation


monitoring device (IMD) detects the initial fault so you can
make repairs before a second fault occurs, which could
trigger protective devices and halt operations.

E-150 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

General Overview

Insulation Monitoring of IT / Ungrounded Networks A

Unlike the TT or TN earthing systems, the neutral of the transformer B

PB118029
is isolated from the ground for an IT earthing system (also called
Ungrounded system).
C
This is applicable to both Low Voltage systems ( up to 1000VAC,
1500VDC) and medium Voltage (up to 63 kV on IMDs only) D

The main interest of IT systems is that in case of one insulation fault.


H
• Enhanced continuity of service of the network (no trip if there is
PB118030

one insulation fault on the network).


• Reduced risk of electric shock. I
• Reduced risk of fire or explosion (low faulty current in case of
insulation fault).
• Reduced stress on the network and increased equipment life (low
faulty current in case of insulation fault).

• In TT or TN systems, in a situation with an insulation fault, the


faulty current will not be negligible and will cause trip of the
PB118031

protections.
• For this reason, Insulation Monitoring Devices are used on IT
networks in order to detect a first insulation fault so that the fault
can be repaired; hence avoiding situations with several insulation
faults and maintaining the continuity of service on the network.
• Using an Insulation Fault Locator (IFL) allows the operator to
locate the fault in multiple feeders installations.

Example of simple insulation monitoring system

The Vigilohm catalog offers a range of products suitable for these various applications, from the
simplest insulation monitoring systems to the most advanced ones, including individual insulation
monitoring per feeder and communication with supervision.

< >
se.com/au Life is On | Schneider Electric | E-151
Switchboard Manufacturers

Vigilohm Range
Functions and characteristics

Insulation Monitoring of IT / Ungrounded Networks


IT earthing systems are used for applications requiring continuity of service, such as:
• Healthcare: critical rooms in medical premises such as operating theaters, intensive care units,
recovery rooms.
• Industry: critical processes in cement, steel, aluminium, oil and gas, chemical factories, food
processing, car manufacturing, (painting area, other...) water, and waste water.
• Infrastructure: control tower and take-off path in airports, railways, seaports, tunnels, and signaling
networks in rail.
• Utilities: power plants and control command systems.
• Photovoltaic: solar farms.
• Marine: electrical distribution of any type of ship.
E • DC applications such as electrical vehicle charging stations.
• Medium Voltage: cable monitoring, distribution in industrial sites, MV loads-transformers and motors.

Vigilohm Range Overview for Low Voltage Networks, Except Healthcare


Product LV MV
IMD IMD-IM9 IMDIM400THR
IMD-IM10 IMDIM400LTHR *
IMD-IM20 I
MD-IM400
IMDIM400L *
IMD-IM400C **
LV > 480 V AC IM20 + IM20-1700 1460872 (P1N)
IM400 + IM400-1700
IM400C+ IM400-1700C
IMD with Fault Locator
IM400 / 400L /400C + PHT1000
and IFL12MC series + IFL12VA1T
IFL IMDIFL12 None
IMDIFL12L *
IMDIFL12C ***
IMDIFL12MC ***
IMDIFL12LMC *
IMDIFL12MCT ****
TOROIDS 50437 (TA30) 50438 (PA50) None
50439 (IA80) 50440 (MA120)
50441 (SA200)
50442 (GA300)
50420 (TOA80)
50421 (TOA120)
HRG, 50278, (XRM) Voltage Transformers
Cardew 50282, (XGR) 03811728N0 (6.6 kV)
Mobile Locators 50494,498, 499 (Open CTs) 03811746N0 (22 kV)
50159 (ZX Imp -HRG) 03811749N0 (33 kV)
50170, 171, 172, 183 (Cardew)

L* Power supply 24-48 V AC/DC


C ** Tropicalized (conformal coated)
C *** Communication
MC *** Measurement & Communication
MCT **** Measurement & Communication & Tropicalized (conformal coated)

E-152 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

Retrofit products EM3555 series A


Vigilohm Range Overview for Low Voltage Networks, Except Healthcare
B
A simple range to meet your needs
Industrial networks
C

Monitoring and Control D


Power Monitoring & SCADA system

Communication and Simple Monitoring


H
Gateway, Data logger & Web Server

Insulation Monitoring Devices


Identification of a leakage to ground
in the complete system

Insulation Fault Locators


Identification of the faulty feeder

Toroids
Used along with the fault locators

< >
se.com/au Life is On | Schneider Electric | E-153
Switchboard Manufacturers

Vigilohm Range
Functions and characteristics

Vigilohm Range Overview for Medium Voltage Networks

A simple range to meet your needs


Industrial networks

Monitoring and Control


Power Monitoring & SCADA system

Communication and Simple Monitoring


Gateway, Data logger & Web Server

Insulation Monitoring Devices


Identification of a leakage to ground
in the complete system

Voltage adaptor

Voltage transformer

E-154 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

Retrofit products EM3555 series A


Vigilohm Range Overview for Healthcare
B
Example of Healthcare network monitored by Vigilohm Insulation Monitoring Devices in compliance with IEC 60364-7-710.

The same hospital may have differing architectures, as shown below. C


Operating Theater 1 uses Link 150 to send data to the supervision system.
Operating Theater 2 uses Smartlink to send data to the supervision system,knowing that Smartlink can also collect data from the
circuit breaker, tripped or not. D

E
PB118032

Medical staff is informed of electrical faults in the operating theater room through the local HMI

Technical staff is informed of any fault in the various operating theaters via a supervision system such as EcoStruxure Power
Monitoring Expert.

This range of products, dedicated to Medical premises, meets requirements from IEC61364-7-710. IMD and IFL are also “MED” certified, as they
meet their product standard:

• IEC61557-8, annex A & B for IMDs and the remote panel


• IEC61557-9, annexA for IFLs

Commercial reference numbers required for the healthcare application:


Isolation Transformer IMD-IT-S63-H,or IMD-IT-S80-H, or IMD-IT-S100-H

IMDs IMD-IM10-H, or IMDIM15H, or IMD-IM20/-H

Remote panel 50168 (HRP) or IMDLRDH

Locator IMDIFL12H

Toroids with IM20-H: METSECT5CC004 or METSECT5CC005 with IFL: 50437 (TA30)

Gateway Link150 Link150

< >
se.com/au Life is On | Schneider Electric | E-155
Switchboard Manufacturers

Vigilohm Range
Reference Numbers

Commercial ref. no. Description


Insulation Monitoring

Vigilohm Insulation Monitoring

50159 ZX impedance

50168 HOSPITAL REMOTE PANEL

50169 CARDEW Holder

50170 CARDEW 250V CA Surge arestor

50171 CARDEW 440V CA Surge arestor

50172 CARDEW 660V CA Surge arestor

50183 CARDEW 1000V CA Surge arestor


E
50248 PHT1000

50278 XRM

50281 XGR 115-127VCA

50282 XGR 220-240VCA

50283 XGR 380-415VCA

50420 TOA80 open toroid

50421 TOA120 open toroid

50437 TA30 toroid

50438 PA50 toroid

50439 IA80 toroid

50440 MA120 toroid

50441 SA200 toroid

50442 GA300 toroid

50494 XP15 Open CT for XRM

50498 XP50 Open CT for XRM

50499 XP100 Open CT for XRM

1460872 Voltage Adaptor P1N

IMDCP100 Current Probe 100mm

IMDCP15 Current Probe 15mm

IMDCP50 Current Probe 50mm

IMDIFL12 Ins Fault locator Entry

IMDIFL12C Ins Fault locator Entry Com

IMDIFL12H Ins Fault locator HC

E-156 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Reference Numbers

Commercial ref. no. Description A


IMDIFL12L Ins Fault locator Entry 24-48VDC

IMDIFL12LMC Ins Fault locator Adv 24-48VDC


B
IMDIFL12MC Ins Fault locator Adv

IMDIFL12MCT Ins Fault locator Adv Tropic


C
IMDIFL12VA1T Voltage Adaptor for IFL12MC series_1000V

IMDIFLK1 Mobile Ins Fault locator 1 feeder

IMDIFLK12 Mobile Ins Fault locator 12 feeders


D
IMD-IM10 IM10

IMD-IM10-H IM10 H E
IMDIM15H IM15 H

IMD-IM20 IM20 F
IMD-IM20-1700 VoltaIge Adaptor for IM20

IMD-IM20-H IM20 H G
IMD-IM400 IM400

IMD-IM400-1700 Voltage adaptor for IM400 H


IMD-IM400-1700C Voltage adaptor for IM400 Conformal coated

IMD-IM400C IM400C
I
IMDIM400L IM400L

IMDIM400LTHR IM400LTHR

IMDIM400THR IM400THR

IMD-IM400VA2 Voltage adaptor for PV application Coated

IMD-IM9 IM9

IMD-IM9-OL IM9OL

IMD-IT-S63-H Single Phase, Isolated Transformer, 6,3KVA

IMD-IT-S80-H Single Phase, Isolated Transformer, 8KVA

IMD-IT-S100-H Single Phase, Isolated Transformer, 10KVA

IMDLRDH Remote Display Hospital

< >
se.com/au Life is On | Schneider Electric | E-157
Switchboard Manufacturers

EcoStruxure™ Panel Server


General Overview

IoT for an intelligent power network


The EcoStruxure™ Panel Server is the next generation of gateway, providing a seamless connection of wired or
unwired smart IoT devices to your edge control software or advisor. It is a foundational enabler for Schneider Electric
EcoStruxure™ solutions.

Electrical safety
E Panel Server is an integral part of Schneider Electric’s continuous thermal monitoring application, helping reduce risk of electrical fires, increase
people and assets protection. Implement the thermal monitoring of your electrical panel by connecting thermal and heat sensors to your Panel
Server.

Power availability
Electrical distribution monitoring and power event analysis help avoid unplanned downtime caused by electrical failure. Panel server collects real-
time data and alarms, presenting information through embedded webpages, making it available to edge control software or advisor for electrical
system diagnostics. Use embedded webpages for first-level monitoring or monitor from your edge control.

Optimize energy efficiency


Improve your facility’s energy efficiency and reduce energy consumption with energy usage analysis and performance tracking. Panel Server
collects and shares energy data to help achieve your energy conservation initiatives. It is certified as part of an energy data management system
according to ISO 50001, 50002, 50006.

Cybersecurity
Guarding your electrical assets and systems against cyber attacks is vital. Panel server
is an IEC 62443 compliant device and is central to the IEC 62443-3-3 SL1 certified
EcoStruxure™ Power system. Use Cybersecurity Admin Expert to manage user
accounts, define your cybersecurity policy and retrieve security logs.

EcoStruxure™ Panel Server gives you access to


the information you need to protect, maximize
and optimize your power system.

Help keep people


and assets safer

Maximize power availability

Optimize energy efficiency


DB410983

@ Improve cybersecurity

E-158 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

General Overview

All-in-one gateway
• Separates your OT network from your IT network
A
• Wireless data concentrator
• Modbus RS485 to Modbus TCP B
• Supports multiple Ethernet connections for serving information to edge
control software and cloud applications
C
Simple commissioning
• EcoStruxure Power Commission software
• Device auto discovery D
• Generation of acceptance reports to validate gateway configuration
• Commission via Bluetooth® or WiFi
E
Intuitive operation
• User-friendly webpages offer first-level monitoring F
• Contextualized data and operational insights
• Simple alarm setup for email notification
• Standardized IEC 62974-1 compliant datalogger and energy server G

I
Architecture overview

< >
se.com/au Life is On | Schneider Electric | E-159
Switchboard Manufacturers

EcoStruxure™ Panel Server


Functions & Characteristics

Panel Server Entry


Functions
• Optimized gateway to retrieve data your wireless devices.
• Connect to your monitoring and control software such as EcoStruxure™ Power
• Monitoring Expert, EcoStruxure™ Power Operation or to your Building Management
System.
• Connect to Schneider cloud applications such as Facility Expert or Asset Advisor.
• Ease of commissioning with EcoStruxure™ Power Commission software, enabling
E device plug-and-play and auto-discovery features.
• Ease of operation with user friendly embedded webpages, and data contextualiza-
tion for more relevant analytics.

Main features
• Power Supply 110…277 V AC/DC
• Designed to match with electrical switchboard environment (temperature, humidity
electromagnetic compatibility)
• One Ethernet 10Base-T/100Base-T port
• Wi-Fi
• Bluetooth communication for commissioning
DB410978

• IEEE 802.15.4 wireless communication


• Modbus TCP/IP server
• Support of HTTPS, NTP, SNTP, DHCP client with proxy management
Panel Server Entry - Front ISO view • Wireless devices concentrator to Modbus/TCP
• Designed through a Secured Development Life Cycle in accordance to IEC 62443-
4-1
• Commissioning through EcoStruxure™ Power Commission or through Embedded
Standards & certifications
Web-Pages
• IEC 61010-1 Ed.2010 • Speed-up commissioning through device list import and configuration export to the
• UL 61010-1 Ed.2012 monitoring software
• IEC 61974 • Fully integrated in Cybersecurity Admin Expert tool to facilitate the management of
• IEC 62443 cybersecurity in your electrical network’s (User Management with Role Base Access
and other security features such as enabling/disabling communication means).
• Embedded web server for real-time measurement visualization, power consumption
by usage
• Customizable alarm with alarm log
• Alarms can be viewed in the web-pages and notified by e-mail

C US
Comm. Reference Description
LISTED PAS400 Panel Server Entry 110..277 V AC/DC

E-160 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions & Characteristics

Panel Server Entry A

Technical data EcoStruxure™ Panel Server Entry


Commercial Reference PAS400
B
Power Supply
Voltage 110-277 V AC/DC
Tolerance ± 10%
C
Frequency 45-65 Hz
Maximum consumption 3 W, 10 VA
Ethernet & Wi-Fi
D
Ethernet 10/100base T Number of Ports Single RJ45 Port
PoE 802.3af & 802.3at Class 0 N.A.
Wi-Fi Supported Frequency 2.4 & 5 GHz E
TCP/IP Yes
IP V4 / IP V6 Yes
DPWS Yes F
DHCP Client Yes
Server (Separate Nework) No
Modbus/TCP Server Max. number of client connection 64 (2) G
Modbus/TCP Client Max. number of TCP/Modbus devices N.A.
Schneider Cloud Services Yes
HTTPS Yes H
External Wi-Fi/Bluetooth Antenna N.A.
Wireless Devices (IEEE 802.15.4)
Number of devices Total 20 devices I
PowerTag Energy & Ambient (1) 20 devices
Other type of devices (1) 20 devices
External IEEE 802.15.4 Antenna No
Serial Ports
Modbus RS-485 Master Max. number of devices w/o repeater N.A.
Max. number of devices with repeater N.A.
Maximum Length N.A.
Baudrate N.A.
Functionality
Data Buffering for cloud applications 1 month
Data Logger and Web-Server Data Logging No
Event logging Yes (2)
Simple Monitoring Web-Pages Yes
Monitoring Web-Pages with historical data No
Time Management TimeUpdate (NTP & SNTP) Yes
Digital inputs
Two DI WAGES & Dry-Contact No
Environmental
Protection Degree Front Face IP40
Others IP20
OverVoltage Category OVC III
Polution Degree 2
Temperature Operation -25 °C to +60 °C
Storage -40 °C to +85 °C
Altitude Max. 2000 m
Relative Humidity ≤ 93%
Mechanical
Form factor Acti9
Installation Din Rail
Width 54 mm
Weight TBC
Standard & Certification
Certifications CE, CULus, RCM, UKCA, FCC, IC
Standards IEC 61010-2, UL 61010-2, CSA C22.2, IEC 62974-1, IEC 62443-4-1, IEC 61326-1, EN
301-489, EN 55032, CISPR 11, EN 300-328, IEEE 802.15.4, IEEE 802.11 a/b/g/n
(1) Consult the User Manual or other documentations to check the limit applicable to your wireless device.
(2) Lower limits may apply depending the firmware version, consult the User Manual, Release Notes or other documentations.

< >
se.com/au Life is On | Schneider Electric | E-161
Switchboard Manufacturers

EcoStruxure™ Panel Server


Functions & Characteristics

Panel Server Entry


Panel Server Entry dimensions

40.0
mm
(inch) (1.57)

E Panel Server
PAS400

45.5 85.0 103.1


93.0
(1.79) (3.34) (4.05)
(3.66)
DB410980

40.0
54
(1.57) 64.7
(2.12) (2.54)
70.2
(2.76)

Panel Server Entry physical descriptions


E F

A A Power supply terminal block

B EcoStruxure™ Panel Server status LED

C Bluetooth/Restart button

D QR code to product information

Panel Server E Ethernet LED 1: Speed


B
PAS400

C F Ethernet LED 2: Activity


G
D G Ethernet communication port
ETH
DB410979

Please see the appropriate Installation Guide for accurate and complete information on the installation of this product.

E-162 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions & Characteristics

Panel Server Universal A

Functions B
• An all-in-one gateway to retrieve data from both your IEEE 802.15.4 and Modbus
devices. C
• Connect to your monitoring and control software such as EcoStruxure™ Power
Monitoring Expert, EcoStruxure™ Power Operation or to your Building Management
System. D
• Connect to Schneider cloud applications such as Facility Expert or Asset Advisor.
• Ease of commissioning with EcoStruxure™ Power Commission software, enabling
device plug-and-play and auto-discovery features.
E
• Ease of operation with user friendly embedded webpages, and data contextualiza-
tion for more relevant analytics.
F
Main features
G
• Power Supply 24 V DC, 110..240 V AC/DC, 110…277 V AC/DC
• Designed to match demanding electrical switchboard environment (temperature,
humidity electromagnetic compatibility) H
DB410983

• Two Ethernet 10Base-T/100Base-T port (supporting switched or separated network


topology)
• Wi-Fi I
Panel Server Universal - Front ISO view
• Bluetooth communication for commissioning
• Modbus RS-485 serial communication
• IEEE 802.15.4 wireless communication
Standards & certifications • Modbus TCP/IP server and client
• IEC 61010-1 Ed.2010 • Support of HTTPS, NTP, SNTP, DHCP client and server with proxy management
• UL 61010-1 Ed.2012 • Modbus RS-485 to Modbus/TCP Gateway
• IEC 61974 • Wireless devices concentrator to Modbus/TCP
• IEC 62443 • Two digital inputs (24VDC version only) for contact information or WAGES pulse
meter
• Designed through a Secured Development Life Cycle in accordance to IEC 62443-
4-1
• Commissioning through EcoStruxure™ Power Commission or through Embedded
Web-Pages
• Speed-up commissioning through device list import and configuration export to the
C US monitoring software
LISTED • Fully integrated in Cybersecurity Admin Expert tool to facilitate the management of
cybersecurity in your electrical network’s (User Management with Role Base Access
and other security features such as enabling/disabling communication means)
• Embedded web server for real-time measurement visualization, power consumption
by usage
• Customizable alarm with alarm log
• Alarms can be viewed in the web-pages and notified by e-mail

Compatible accessories
• Wi-Fi/Bluetooth external antenna (PASA-ANT1)

Comm. Reference Description


PAS600L Panel Server Universal with 24 V DC power supply
PAS600 Panel Server Universal with 100-277 V AC/DC power supply

< >
se.com/au Life is On | Schneider Electric | E-163
Switchboard Manufacturers

EcoStruxure™ Panel Server


Functions & Characteristics

Panel Server Universal


Technical data EcoStruxure™ Panel Server Universal
Commercial Reference PAS600L PAS600T PAS600
Power Supply
Voltage 24 V DC 110-240 V AC/DC 110-277 V AC/DC
Tolerance ± 10% ± 10% ± 10%
Frequency N.A. 47-63 Hz 45-65 Hz
Maximum consumption 3W 3 W, 10 VA 3 W, 10 VA
Ethernet & Wi-Fi
Ethernet 10/100base T Number of Ports Two RJ45 ports Two RJ45 ports Two RJ45 ports
PoE 802.3af & 802.3at Class 0 No No No
E Wi-Fi Supported Frequency 2.4 GHz 2.4 GHz 2.4 GHz
TCP/IP Yes Yes Yes
IP V4 / IP V6 Yes Yes Yes
DPWS Yes Yes Yes
DHCP Client Yes Yes Yes
Server (Separate Nework) Yes Yes Yes
Modbus/TCP Server Max. number of client connection 64 (2) 64 (2) 64 (2)
Modbus/TCP Client Max. number of TCP/Modbus devices 64 (2) 64 (2) 64 (2)
Schneider Cloud Services Yes Yes Yes
HTTPS Yes Yes Yes
External Wi-Fi/Bluetooth Antenna PASA-ANT1 PASA-ANT1 PASA-ANT1
Wireless Devices (IEEE 802.15.4)
Number of devices Total 100 devices (2) 100 devices (2) 100 devices (2)
PowerTag Energy & Ambient (1)
100 devices (2)
100 devices (2)
100 devices (2)
Other type of devices (1) 20 devices (2) 20 devices (2) 20 devices (2)
External IEEE 802.15.4 Antenna Yes (2022) Yes (2022) Yes (2022)
Serial Ports
Modbus RS-485 Master Max. number of devices w/o repeater 32 devices 32 devices 32 devices
Max. number of devices with repeater 128 devices 128 devices 128 devices
Maximum Length 1000 m 1000 m 1000 m
Baudrate 1200, 4800, 9600, 19200, 38400, 57600, 115200
Functionality
Data Buffering for cloud applications 1 month 1 month 1 month
Data Logger and Web-Server Data Logging No No No
Event logging Yes (2) Yes (2) Yes (2)
Simple Monitoring Web-Pages Yes Yes Yes
Monitoring Web-Pages with historical data No No No
Time Management RTC (with battery) Yes Yes Yes
TimeUpdate (NTP & SNTP) Yes Yes Yes
Digital inputs
Two DI WAGES & Dry-Contact Yes No No
Environmental
Protection Degree Front Face IP40 IP40 IP40
Others IP20 IP20 IP20
OverVoltage Category N.A. OVC III OVC III
Polution Degree 3 2 2
Temperature Operation -25 °C to +70 °C -25 °C to +70 °C -25 °C to +70 °C
Storage -40 °C to +85 °C -40 °C to +85 °C -40 °C to +85 °C
Altitude Max. 2000 m 2000 m 2000 m
Relative Humidity ≤ 93% ≤ 93% ≤ 93%
Mechanical
Form factor Acti9 Acti9 Acti9
Installation Din Rail Din Rail Din Rail
Width 72 mm 72 mm 72 mm
Weight TBC TBC TBC
Standard & Certification
Certifications CE, CULus, RCM, UKCA, FCC, IC
Standards IEC 61010-2, UL 61010-2, CSA C22.2, IEC 62974-1, IEC 62443-4-1, IEC 61326-1, EN
301-489, EN 55032, CISPR 11, EN 300-328, IEEE 802.15.4, IEEE 802.11 a/b/g/n
(1) Consult the User Manual or other documentations to check the limit applicable to your wireless device.
(2) Lower limits may apply depending the firmware version, consult the User Manual, Release Notes or other documentations.
E-164 | Life is On | Schneider Electric
< > se.com/au
Power Monitoring and Power Quality Correction

Functions & Characteristics

Panel Server Entry A

Panel Server Entry dimensions B

C
mm 40.0
(1.57)
(inch)
D

Panel Server
PAS600L
E
45.5 85.0 104.2
93.0 (1.79) (3.34) (4.10)
(3.66)
F

40.0
G
72 (1.57) 64.7
(2.83) (2.54)
70.2 H
(2.76)

I
Panel Server Entry physical descriptions
B A G H G H L
A Power supply terminal block

B Digital input terminal block (PAS600L only)

C EcoStruxure™ Panel Server status LED

C
Panel Server
PAS600L D Bluetooth/Restart button
D E QR code to product information
E
F RS-485 Modbus communication port

Wi-Fi
G Ethernet LED 1: Speed
antenna
ETH1 ETH2

H Ethernet LED 2: Activity


F 7 8
D1/+ D0/-
9 10
0V

RS485 I Wi-Fi external antenna port

I J K J Ethernet 1 communication port

K Ethernet 2 communication port

L Grounding connection

Please see the appropriate Installation Guide for accurate and complete information on the installation of this product

< >
se.com/au Life is On | Schneider Electric | E-165
Switchboard Manufacturers

EcoStruxure™ Panel Server


Functions & Characteristics

Panel Server Advanced


Functions
• An all-in-one gateway to retrieve data from both your wireless IEEE 802.15.4 devices
and Modbus devices.
• Connect to your monitoring and control software such as EcoStruxure™ Power
Monitoring Expert, EcoStruxure™ Power Operation or to your Building Management
System.
• Connect to Schneider cloud applications such as Facility Expert or Asset Advisor.
• Ease of commissioning with EcoStruxure™ Power Commission software, enabling
E device plug-and-play and auto-discovery features.
• Ease of operation with user friendly embedded webpages, and data contextualiza-
tion for more relevant analytics.

Main features
• Power Supply 24 V DC, 110…277 V AC/DC, PoE-PD (CLASS 0,IEEE802.3af/at)
• Designed to match demanding electrical switchboard environment (temperature,
humidity electromagnetic compatibility)
• Two Ethernet 10Base-T/100Base-T port (supporting switched or separated network
DB410992

topology)
• Wi-Fi
• Bluetooth communication for commissioning
Panel Server Advanced- Front ISO view
• Modbus RS-485 serial communication
• IEEE 802.15.4 wireless communication
• Modbus TCP/IP server and client
Standards & certifications • Support of HTTPS, NTP, SNTP, DHCP client and server with proxy management
• IEC 61010-1 Ed.2010 • Modbus RS-485 to Modbus/TCP Gateway
• UL 61010-1 Ed.2012 • Wireless devices concentrator to Modbus/TCP
• IEC 61974 • Two digital inputs (24 V DC version only) for contact information or WAGES pulse
• IEC 62443 meter
• Designed through a Secured Development Life Cycle in accordance to IEC 62443-4-1
• Commissioning through EcoStruxure™ Power Commission or though Embedded
Web-Pages
• Speed-up commissioning through device list import and configuration export to the
monitoring software
• Fully integrated in Cybersecurity Admin Expert tool for security settings (Role Base
C US
Access and other security features such enabling/disabling communication means)
LISTED • Embedded web server for real-time measurement and alarm visualization, energy &
power consumption by usage and location, 3 years historical trending and dash-
boarding
• 3 years Data Logger with 32 GB memory
• Customizable alarm with alarm log
• Alarms can be viewed in the web-pages and notified by e-mail

Compatible accessories
• Wi-Fi/Bluetooth external antenna (PASA-ANT1)
• IEEE 802.15.4 external antenna (PASA-ANT1)

Comm. Reference Description


PAS800L Panel Server Advanced with 24 V DC power supply
PAS800P Panel Server Advanced with PoE power supply
PAS800 Panel Server Advanced with 100-277 V AC/DC power supply

E-166 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions & Characteristics

Panel Server Advanced A


Technical data EcoStruxure™ Panel Server Universal
Commercial Reference PAS800L PAS800P PAS800 B
Power Supply
Voltage 24 V DC PoE 110-277 V AC/DC
Tolerance ± 10% - ± 10% C
Frequency N.A. N.A. 45-65 Hz
Maximum consumption 3W 3.5 W 3 W, 10 VA
Ethernet & Wi-Fi
D
Ethernet 10/100base T Number of Ports Two RJ45 ports Two RJ45 ports Two RJ45 ports
PoE 802.3af & 802.3at Class 0 No 1 port (PD) No
Wi-Fi Supported Frequency 2.4 & 5 GHz 2.4 & 5 GHz 2.4 & 5 GHz
TCP/IP Yes Yes Yes
E
IP V4 / IP V6 Yes Yes Yes
DPWS Yes Yes Yes
DHCP Client Yes Yes Yes F
Server (Separate Nework) Yes Yes Yes
Modbus/TCP Server Max. number of client connection 64 (2) 64 (2) 64 (2)
Modbus/TCP Client Max. number of TCP/Modbus devices 64 (2) 64 (2) 64 (2) G
Schneider Cloud Services Yes Yes Yes
HTTPS Yes Yes Yes
External Wi-Fi/Bluetooth Antenna PASA-ANT1 PASA-ANT1 PASA-ANT1
H
Wireless Devices (IEEE 802.15.4)
Number of devices Total 100 devices (2)
100 devices (2)
100 devices (2)

PowerTag Energy & Ambient (1) 100 devices (2) 100 devices (2) 100 devices (2)
Other type of devices (1) 20 devices (2) 20 devices (2) 20 devices (2)
I
External IEEE 802.15.4 Antenna PASA-ANT1 PASA-ANT1 PASA-ANT1
Serial Ports
Modbus RS-485 Master Max. number of devices w/o repeater 32 devices 32 devices 32 devices
Max. number of devices with repeater 128 devices 128 devices 128 devices
Maximum Length 1000 m 1000 m 1000 m
Baudrate 1200, 4800, 9600, 19200, 38400, 57600, 115200
Functionality
Data Buffering for cloud applications 1 month 1 month 1 month
Data Logger and Web-Server Data Logging 3 years 3 years 3 years
Event logging Yes (2) Yes (2) Yes (2)
Simple Monitoring Web-Pages Yes Yes Yes
Monitoring Web-Pages with historical data Yes Yes Yes
Time Management RTC (with battery) Yes Yes Yes
TimeUpdate (NTP & SNTP) Yes Yes Yes
Digital inputs
Two DI WAGES & Dry-Contact Yes No No
Environmental
Protection Degree Front Face IP40 IP40 IP40
Others IP20 IP20 IP20
OverVoltage Category N.A. OVC III OVC III
Polution Degree 3 2 2
Temperature Operation -25 °C to +70 °C -25 °C to +70 °C -25 °C to +70 °C
Storage -40 °C to +85 °C -40 °C to +85 °C -40 °C to +85 °C
Altitude Max. 2000 m 2000 m 2000 m
Relative Humidity ≤ 93% ≤ 93% ≤ 93%
Mechanical
Form factor Acti9 Acti9 Acti9
Installation Din Rail Din Rail Din Rail
Width 72 mm 72 mm 72 mm
Weight TBC TBC TBC
Standard & Certification
Certifications CE, CULus, RCM, UKCA, FCC, IC
Standards IEC 61010-2, UL 61010-2, CSA C22.2, IEC 62974-1, IEC 62443-4-1, IEC 61326-1, EN
301-489, EN 55032, CISPR 11, EN 300-328, IEEE 802.15.4, IEEE 802.11 a/b/g/n
IEEE 802.3 af/at
(1) Consult the User Manual or other documentations to check the limit applicable to your wireless device.
(2) Lower limits may apply depending the firmware version, consult the User Manual, Release Notes or other documentations.

< >
se.com/au Life is On | Schneider Electric | E-167
Switchboard Manufacturers

EcoStruxure™ Panel Server


Functions & Characteristics

Panel Server Advanced


Panel Server Entry dimensions

40,0
1.57

E PAS800L

45,5 85,0 104,2


93,0 1.79 3.34 4.10
3.66

72 40,0
1.57 64,7
2.83 2.54

Panel Server Entry physical descriptions


B A G H G H L M A Power supply terminal block (PAS800 &
PAS800L only)
B Digital input terminal block (PAS800L only)
C EcoStruxure™ Panel Server status LED
D Bluetooth/Restart button

C
Panel Server
PAS800L E QR code to product information
D F RS-485 Modbus communication port
E G Ethernet LED 1: Speed
H Ethernet LED 2: Activity
Wi-Fi
antenna
I Wi-Fi external antenna port
ETH1 ETH2(PoE)

J Ethernet 1 communication port


F 7 8 9 10
K Ethernet 2 communication port (PAS800 &
D1/+ D0/- 0V

RS485
PAS800L only) / Ethernet 2 communication
port - PoE (PAS800P only)
I J K
L Grounding connection
M IEE802.15.4 external antenna port

Please see the appropriate Installation Guide for accurate and complete information on the installation of this product

E-168 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Power Quality Correction


General Overview

Reduce your risk of


power loss and gain lower
electricity bills
Power Factor Correction and harmonics mitigation both
provide immediate benefits in terms of reduced power
losses and reduced electricity bills. In addition, both
encourage the use of total system capacity in electrical
installations thereby increasing payback on investment.

Range

• Power Factor Correction Components


• VarSet Power Factor Correction
• AccuSine Active Harmonic Filter

< >
se.com/au Life is On | Schneider Electric | E-169
Switchboard Manufacturers

Power Factor Correction


General Overview

Components for Power Factor Correction Systems

VarPlus Can capacitors


• Complies with IEC 60831-1 & 2
- Withstand capability of 10% over-voltage for 8 hours in every 24 hours, as per IEC 60831 table III.
- Can withstand over-current of up to 1.8 x IN.
• Available in 480V and 525V
Var Plus Can capacitors
• Total losses < 0.5 W/kVAr (discharge resistor included).
• Capacitance tolerance: -5%, +10%
E • Normal switching frequency of up to 7000/year
• Mean life expectancy of up to 130,000 hours
• Working conditions:
- Ambient temperature: -25°C, +55°C Humidity: 95%
- Altitude: up to 2,000m above sea level
- Dry technology allows for upright & horizontal mounting
• Protection: IP20 indoor
• Optimised geometric design for improved thermal performance through heavy edge, slope
metallization and wave-cut profiling features.
Pressure Sensitive
Disconnector (PSD) • Each capacitor element is manufactured with metallized polypropylene film as the dielectric.
• RoHS (Restriction of Hazardous Substances) compliant. VarPlus Can capacitors don’t contain any
substances with concentrations exceeding the limits fixed by the RoHS Organisation.
• Environmentally friendly with non-PCB, sticky biodegradable resin impregnation
• Safety:
- Pressure-sensitive disconnector on all three phase
- Self-healing and discharge resistors fitted (50V in 1min)

Poor power factor costs money!

Financial
• Penalties applied by most utilities for low power factor and higher maximum kVA demand
• Higher CO2 emissions
• Increased energy consumption within the installations
• Energy is wasted through additional losses

Plant & Reliability


• Need for oversized transmission and distribution networks by utilities
• Additional I2R losses in cables
• Need for oversized equipment (e.g. transformer, cables)

E-170 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

VarPlus Can Capacitors


A
Built in an extruded aluminium can casing, the VarplusCan HDuty capacitor is a safe, reliable and high-
performing solution for power factor correction in heavy-duty operating conditions.
B
VarPlus Can Capacitors
480V, 50Hz, 3ph
Equiv. kVAr 415V Rated kVAr 480V Reference
C
Capacitors
12.5 17 BLRCH170A204B48
D
25 33.9 BLRCH339A407B48

Proposed Assembly

50 2 x BLRCH339A407B48
E

525V, 50Hz, 3ph


Equiv. kVAr 415V Rated kVAr 525V Reference
F
Capacitors
Equiv. kvar 415V 6.6 10.6 BLRCH106A127B52
VarPlus Can 25kVAr 525V G
BLRCH400A480B52 12.5 20 BLRCH200A240B52

25 40 BLRCH400A480B52

Proposed Assembly H
50 2 x BLRCH400A480B52

I
Note:
• Harmonic pollution on the distribution network can reduce capacitor life. Contact Schneider Electric for advice on
limiting the effect of harmonic pollution.
• Capacitors can absorb audio-frequency signals; rejection coils may be necessary if the power utility uses an
audio-frequency signalling system.
• Refer to Chapter 3 for type LC1D•K capacitor-switching contactors.
• For further information refer to the Reactive Energy Management Low Voltage Components - PFCED310003EN
• VarplusCan HDuty capacitors

VarPlus Can 12.5kVAr 525V 116 ± 1+5


BLRCH200A240B52 M10 STUD type
terminal
43 ± 2

In-built resistor type

116 ±1 + 5 90 ± 1 + 5

Finger proof Finger proof


30
30

ClampTite™ terminal ClampTite™ terminal


278 ± 3

In-built resistor type In-built resistor type


212 ± 3

212 ± 3

116 ±

116 ±1 90 ±1
16 +1

M12
Toothed washer M12
16 +1

Hex nut Toothed washer M12


16 +1

Hex nut Toothed washer


Hex nut

Tightening
15

Tightening Tightening
15

Torque = 12Nm
Torque = 2.5Nm Torque = 2.5Nm
15

15

47 ±1

Case code: XC Case code: TC Case code: RC


BLRCH400A480B52 BLRCH200A240B52 BLRCH170A204B48
BLRCH339A407B48

< >
se.com/au Life is On | Schneider Electric | E-171
Switchboard Manufacturers

Power Factor Correction Components


Functions and characteristics

VarPlus Logic Series Intelligent Power Factor Controllers


General characteristics
Voltage and current Input
Direct supply voltage 90 – 550 V, 1ph, 50/60 Hz
VA Burden: 6 VA
300 V LN / 519 V LL CAT III or 550 V CAT II
Type of input connection Phase to phase or phase to neutral
Protection against voltage dips Automatic disconnection of steps for dips > 15 ms (protection of capacitor)
CT secondary 1A or 5A compatible
CT primary range Up to 9600 A
Current 15 mA – 6 A, 1PH,
VA Burden : < 1 VA
E Connection terminals Screw type, pluggable. Section: 0.2 – 2.5 mm2 (0.2 – 1 mm 2 for Modbus and
digital inputs)
Power factor settings & algorithm selection
Regulation setting - Programmable From Cos Phi 0.7c to 0.7i
Reconnection time - Programmable From 1 to 6500 s
Response time - Programmable From 1 to 6500 s
Possibility of dual cos Phi target Yes, through digital input or if export power detected
Program algorithm AUTOMATIC (best fit) - Default
LIFO
PROGRESSIVE
Import export application compatibility 4- Quadrant operation for generator application
Program intelligence
Automatic Initialization and Automatic bank Yes
detection
Detection and display of power, number of Yes
switching & derating of all connected steps
Capacitor bank step sequence Any sequence. No restriction/limitation on sequence
Alarm and control
Control outputs (step output) VL6: 6 relays VL12: 12 relays ( NO contact)
250 V LN or LL (CAT III)
DC Rating : 48 V DC / 1 A
AC Rating : 250 V AC / 5 A
Common root: 10 A max.
Dedicated fan control relay Yes. Normal open contact (NO)
48 V DC /1 A, 250 V AC /5 A
Alarmcontact The relay contact is open whenthecontroller is energized with no alarmand will
close in the event of an alarm.The relay is a NC (Normally Close) whenthecon-
troller is not energized.
Rating : 48 V DC /1 A, 250 V AC /5 A
Digital input for Cos phi2 target Dry contact (internal supply 5 V, 10mA)
Modbus RS-485 serial port (RTU) Line polarization / termination, not included
Communication protocol Modbus
Interface TTL Service port. Only for internal use
Internal temperature probe Yes. Temperature offset is programmable.

VarPlus Logic N Power Factor Correction Controller


Reference
VL6 6-step Relay VPL06N
VL12 12-step Relay VPL12N

Dimensions
144 dimensions shown in mm
VarPlus Logic VL12 5.66
137
VarPlusLogic
5.39
98
3.85
VL12

144 137 47
5.66 5.39 1.85

ESC OK

12
0.47
59
2.32

E-172 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Reference Numbers

Detuned Reactor, Capacitor Duty Contactor


A
Detuned Reactors
The detuned reactors (DR) are designed to protect the capacitors and prevent amplification of the harmonics B
present on the network.
• three-phase, dry, magnetic circuit, impregnated
• cooling: natural C
• degree of protection: IP00, indoor
• standards: IEC 60289, EN 60289 rated voltage: 400/415 V three-phase 50 Hz
• tuning order (relative impedance): 3.8 (6.9 %)
D
• inductance tolerance per phase: ± 5%
• insulation level: 1.1kV, class H
E
• thermal withstand Isc: 25 x Ie, 2 x 0.5 second
• dynamic withstand: 2.2 Isc (peak value)
Detuned Reactor
F
Tuning order: 3.8 (190Hz)
Power restored by the L (mH) IMP (A) Power losses Reference
assembly reactor-capacitor (W) G
6.5kVAr/400V - 50Hz 5.8 11 100 LVR07065A40T
12.5 kVAr/400 V - 50Hz 3 22 150 LVR07125A40T
25 kVAr/400 V - 50Hz 1.5 43 200 LVR07250A40T H
50 kVAr/400 V - 50Hz 0.75 86 300 LVR07500A40T

I
Dimensions
Power restored by the Fixing centre distance (mm) Maximum Dimensions (mm) Weight (kg)
assembly reactor-capacitor
Normally closed H W D
dry contact
12.5 kVAr/400 V - 50Hz 205 x 110 230 245 140 10
25 kVAr/400 V - 50Hz 205 x 110 230 240 140 18
50 kVAr/400 V - 50Hz 205 x 120 or 205 x 130 270 260 160 27

Capacitor Switching Contactors


Capacitor control is accompanied by transient operating conditions resulting from the capacitor load which,
amongst other things, generates a very high overcurrent equivalent to a short-circuit of short duration. The use
of standard contactors may compromise the safety of persons and installations. Comply with IEC 60947-4-1,
according to AC-6b.
The LC1-D•K contactors are specially designed for capacitor control. They are fitted with a contact block allowing
the current to pass on closing and with damping resistors limiting the current on energisation.This technology, which
is unique, has been patented.

Capacitor switching contactors IEC 60831-1 compliance


Mounting Pole tightening kVAR at Auxiliary contact N/C Reference
Equivalent torque (N.m) 415V 40°C fitted as standard
Contactor N/O
LC1D12 1.2 11 1 1 LC1DFKii
LC1D18 1.7 15 1 1 LC1DGKii
LC1D25 1.85 20 1 1 LC1DLKii
LC1D32 2.5 25 1 1 LC1DMKii
LC1D40 5 30 1 2 LC1DPKii
LC1DLKii LC1D50 5 40 1 2 LC1DTKii
LC1D80 9 60 1 2 LC1DWK12ii

Standard coil voltages


Volts AC 24 110 240 415
50/60Hz B7 F7 U7 N7

< >
se.com/au Life is On | Schneider Electric | E-173
Switchboard Manufacturers

Power Factor Correction Components


Reference Numbers

PFC controllers Combination Guide

VarPlus Logic range

Type Number of step output contacts Supply voltage (V) Reference


VL6 6 90-550 VPL06N
VL12 12 90-550 VPL12N

Dimensions
H W D1 D2 Weight (kg)
(mm) (mm) (mm) (mm)
E
VL6 / 12 144 144 59 47 0.6
RT6 / 8 / 12 143 143 67 57 1

H
138

138 D2
W D1

Combination Guide
VarPlus Can + Detuned Reactor + Contactor

Effective power (kVar) Capacitor Detuned reactor Contactor


Qty Reference Qty Reference Qty Reference
6.5 1 BLRCH106A127B52 1 LVR07065A40T 1 LC1DFKU7
12.5 1 BLRCH200A240B52 1 LVR07125A40T 1 LC1DGKU7
25 1 BLRCH400A480B52 1 LVR07250A40T 1 LC1DMKU7
50 2 BLRCH400A480B52 1 LVR07500A40T 1 LC1DWK12U7
PE90154

Protection options
NSX circuit breakers

kVar rating Frame Reference Trip unit Reference


6.5 NSX100F LV429003 TM16D LV429037
12.5 NSX100F LV429003 TM25D LV429036
25 NSX100F LV429003 TM50D LV429033
50 NSX100F LV429003 TM100D LV429030

E-174 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

VARPACT Range A
Technical data
• capacitor rated voltage: 525 V & three-phase 50 Hz • ambient temperature around the capacitor bank
• tuning order: 3.8 (190 Hz) (electrical room): B
• capacitance value tolerance: -5, +10 % - maximum temperature: 40 °C
• insulation level: 0.69 kV withstand 50 Hz, 1 min : 3 kV - average temperature over 24 hours: 35 °C
- average annual temperature: 25°C C
• maximum permissible overloads:
- overcurrent (max):19 % at 400 V - minimum temperature: -5°C
- overvoltage: 10 % (8 hours over 24 hours as per
IEC 60831)
• losses: < 9 W/kVAr (with detuned reactor); D
525V version with Fuse - < 2W/kVAr (without detuned reactor)
Protection and Detuned Reactor • standard: IEC 60831-1, 2.
- [based on a 50kVAr functional plate]
• protection device: Compact NSX circuit breaker with E
thermo magnetic trip unit Fupact
• Fuse-switch disconnector with DIN fuses
F
Product references - eg. V50C52CR
V 50 C 52 F R
VARPACT kVAr@415V Capacitor type Capacitor Protection Reactors G
rated voltage
series 12 12.5kVAr C Can capacitor 52 525V AC C Circuit breaker protection R with reactors on
capacitor plate - 190Hz
H
25 25kVAr capacitor

50 50kVAr capacitors

Note:
I
* Using a different voltage rating for the capacitors will change the kVAr rating of the plate. Please check with
Schneider Electric before ordering.

VARPACT 525V functional plates


Description (input detuned reactors) Reference
AUSTRALIA

VARPACT 12.5kVAr, 525V, Circuit Breaker protection V12C52CR


VARPACT 25kVAr,525V,Circuit Breakerprotection V25C52CR
B U I LT I N VARPACT 50kVAr, 525V, Circuit Breaker protection V50C52CR

Accessories / spares
Description Reference
VARPACT fishplate for interconnection offunctional plates (set of3 fishplates) FISHPLATES_VARP
Spare shroud for functional plate SHROUD_VARP

Dimensions

259

425

208
562

282.500 258 278.500 281

< >
se.com/au Life is On | Schneider Electric | E-175
Switchboard Manufacturers

Power Factor Correction Components


Functions and characteristics

Comprehensive range for multiple


applications
Do you need an easy solution to immediately boost your facility’s energy efficiency
and productivity?

Are products that blend superior quality, performance, and flexibility with excellent
value difficult to find?

Do you require the expertise, support, and reach of a global leader with the
E responsiveness of a local supplier?

Quality and reliability

• Continuity of service thanks to the high performance and long life expectancy of
capacitors.
• Routine testing in manufacturing plant.
• Design and engineering with the highest international standards.

Safety

• Over-pressure system for safe disconnection at the end of life.


• All materials and components are free of PCB pollutants.

Efficiency and productivity

• Product development including innovation in ergonomics and ease of installation


and connection.
• Specially designed components to save time on installation and maintenance.
• All components and solutions available through a network of distributors and
partners in more than 100 countries.

Ensure reliability and safety


on installations

Thanks to the know-how developed over 50 years, Schneider Electric ranks as the
global specialist in Energy management providing a unique and comprehensive
portfolio.

Schneider Electric helps you to make the most of your energy with innovative,
reliable and safe solutions.

E-176 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

VarSet offer A
Certified LV power factor correction capacitor banks
B

I
Technical data Technical data
General characteristics Electrical
Standards Compliance/ Certification AS/NZS 61439.1 & 2, Compensation type Automatic or Fixed
IEC 61439-
Capacitor type VarPlus Can (aluminium type)
1 & 2, IEC 61921
Capacitor rated voltage 525Vac
Installation Indoor
Discharge rate 50V, 1min
Capacitor operating conditions -5°C to +55°C
Compatible network 415Vac, 50Hz
Ambient temperature in electrical room +35°C
Short circuit rating (steps) 36kA
Ambient temperature around capacitors +45°C over 24hr
Rated conditional short-circuit current up to 150kA with incomer protection
+55°C max. (using NS or NSX type-L circuit
Humidity Up to 95% breakers)
Max. effective kvar S: 250kvar D: 500kvar
Mechanical
Physical steps (max) without incomer protection S: 6 steps
Ventilation Fan forced, 600m3/hr
per column (nominal) Connectivity
Mounting Floor standing Modbus communication Modbus RS485
Cable connection Top Feed Modbus TCP Using Com'X range
Colour RAL 2000 Physical steps (max) without incomer protection S : 6 steps
Ingress protection IP31 D: 12 steps
Degree of mechanical resistance Enclosure IK10 Detuned reactor 7%, 3.8th order, 190Hz
Accessories IK08 Step protection Circuit breaker
Enclosure types S: up to 250kvar / 5 Main incomer protection Circuit breaker or none
steps D: up to 500kvar /
10 steps Extended rotary handle Included (with main incomer
Dimensions* (H x W x D)mm S: 2190 x 865 x 640 protection)
D: 2190 x 1515 x 640 Max. dissipated power 8-9 W/kvar
Weight (max) S: 400kg D: 800kg Disconnection on generator supply Volt-free connection terminals
available

< >
se.com/au Life is On | Schneider Electric | E-177
Switchboard Manufacturers

Power Factor Correction Components


Functions and characteristics

VarSet offer
Certified LV power factor correction capacitor banks
Certified VarSet: Offer Range
VarSet Reference Power (kvar) Tuning factor Main Incomer Max. fault IP31 Cable Feed Rotary handle Controller 6/12 steps
number 3.8 (190Hz) Circuit Breaker level Top

VSA31S150TD220MF 150 • - 36kA • • - 6

VSA31S150TC220MF 150 • • 36kA • • - 6

VSA31S200TD400MF 200 • - 36kA • • - 6

VSA31S200TC400MF 200 • • 36kA • • - 6

VSA31S225TD410MF 225 • - 36kA • • - 6


E
VSA31S225TC410MF 225 • • 36kA • • - 6

VSA31S250TD500MF 250 • - 36kA • • - 6

VSA31S250TC500MF 250 • • 36kA • • - 6

VSA31D300TC600MF 300 • • 50kA • • • 12

VSA31D350TC700MF 350 • • 50kA • • • 12

VSA31D400TC800MF 400 • • 50kA • • • 12

VSA31D450TC900MF 450 • • 50kA • • • 12

VSA31D500TCA00MF 500 • • 50kA • • • 12

• SCPD provided by default

Certified VarSet: : Physical & Electrical Steps


VarSet reference number Power (kvar) Max. Fault Min. Step Resolution No. Physical No. Electrical Sequence Expansion Frame Type
level size (kvar) steps steps Capacity*

VSA31S150TD220MF 150 36kA 25 2 x25 + 2x50 4 5 1.2.2 2

VSA31S150TC220MF 150 36kA 25 2 x25 + 2x50 4 5 1.2.2 1

VSA31S200TD400MF 200 36kA 50 4 x50 4 4 1.1.1.1 2

VSA31S200TC400MF 200 36kA 50 4 x50 4 4 1.1.1.1 1


S
VSA31S225TD410MF 225 36kA 25 1 x25 + 4x50 5 9 1.2.2.2 1

VSA31S225TC410MF 225 36kA 25 1 x25 + 4x50 5 9 1.2.2.2 0

VSA31S250TD500MF 250 36kA 50 5 x50 5 5 1.1.1.1 0

VSA31S250TC500MF 250 36kA 50 5 x50 5 5 1.1.1.1 0

VSA31D300TC600MF 300 50kA 50 6 x50 6 6 1.1.1.1 4

VSA31D350TC700MF 350 50kA 50 7 x50 7 7 1.1.1.1 3

VSA31D400TC800MF 400 50kA 50 8 x50 8 8 1.1.1.1 2 D


VSA31D450TC900MF 450 50kA 50 9 x50 9 9 1.1.1.1 1

VSA31D500TCA00MF 500 50kA 50 10 x50 10 10 1.1.1.1 0

*Maximum effective kvar per frame type: 250kvar (S), 500kvar (D) Maximum physical steps per frame type: 6 steps (S), 12 steps (D)

Certified to

IEC 61439 1&2

E-178 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

Typical GA drawing: top feed cable entry, with incomer protection circuit breaker
A

e.g. VSA31S250TC500MF Frame type: S 1-5 steps


250kvar max
Front view - door removed Front view - with door B
VARSET
AUTOMATIC
POWER FACTOR CORRECTION BANK

C
VARSET
AUTOMATIC
POWER FACTOR CORRECTION BANK

Step 5
50kVAr
Step 5

D
50kVAr

Step 4
50kVAr
Step 4
50kVAr
Top view
Gland Plate Top view
Gland Plate
Bottom view

E
Step 3
50kVAr
Step 3
50kVAr

Step 2
50kVAr
Step 2
50kVAr

Step 1
50kVAr
Step 1
50kVAr
F
PLINTH
PLINTH
PLINTH
PLINTH

e.g. VSA31D500TCA00MF Frame type: D 1-10 steps H


500kvar max

I
Step 10
50kVAr
Step 10
50kVAr

Step 9
50kVAr
Step 9
50kVAr

Step 8 Step 7
50kVAr 50kVAr
Step 8 Step 7
50kVAr 50kVAr

Step 6 Step 5
50kVAr 50kVAr
Step 6 Step 5
50kVAr 50kVAr

Step 4 Step 3
50kVAr 50kVAr
Step 4 Step 3
50kVAr 50kVAr

Step 2 Step 1
50kVAr 50kVAr
Step 2 Step 1
50kVAr 50kVAr

PLINTH PLINTH
PLINTH PLINTH

Front view - door removed Front view - with door

TOP GLAND PLATE


HOOD TOP GLAND PLATE
HOOD

Top view Bottom view

< >
se.com/au Life is On | Schneider Electric | E-179
Switchboard Manufacturers

Power Factor Correction Varset


Functions and characteristics

VarSet typical schematic drawing - without main protective device

Example: VSA31S225TD410MF
Typical schematic shown here for a PFC unit with the following configuration:

• Qeff at 415Vac: 225kvar


• No. of physical steps: 5
• No. of electrical steps: 9
• Step configuration: 1x25 + 4x50kvar
• Step protection: circuit breaker
• Main protection: none
• PF controller: 6-step relay with modbus communications
• Max fault level of assembly: 36kA

Note:
CT connection to VarPlus Logic controller to be supplied by installer
Main protective device not within PFC cubicle provided in MSB upstream
VarPlus 525V capacitors fitted with detuned reactors and circuit breaker step protection
Remove jumper A at terminals 1L3 and 2L3 for volt free contact for generator automatic disconnection

E-180 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

Wall Mounted A
Low voltage power factor correction capacitor banks
Part number referencing – wall mounted B
Part number kvar @ 415V Physical steps Electrical steps Enclosure size Typ. Dimension †
Weight (kg)
(kvar) (kvar) (mm) HxWxD
HxWxD C
VS025WA00B00C02TCC 25 12.5, 12.5 12.5, 25 800x600x400 900x600x450 69

VS037WA00B01C01TCC 37.5 12.5, 25 12.5, 25, 37.5 1000x600x400 1100x600x450 90


D
VS050WA00B01C02TCC 50 12.5, 12.5, 25 12.5, 25, 37.5, 50 1200x800x400 1300x600x450 110

VS075WA01B01C00TCC 75 25, 50 25, 50, 75 1200x800x400 1300x600x450 111

VS087WA01B01C01TCC 87.5 12.5, 25, 50 12.5, 25, 37.5, 50, 1200x800x400 1300x600x450 124 E
62.5, 75, 87.5
VS100WA01B02C00TCC 100 25, 25, 50 25, 50, 75, 100 1200x800x400 1300x600x450 132
F
†: includes roof ventilation hood, door grill cover and incoming breaker rotary handle

All VarSet are equipped with: G


• auxiliary transformer
• detuned reactor.
H
Technical data
General characteristics I
Reference standards IEC/EN 61439-1 & 2, IEC 61921

Installation Indoor

Temperature -5°C to +55°C

Humidity Up to 95%

Electrical

Compensation type Automatic or Fixed

Capacitor model VarPlus Can

Capacitor type Extruded aluminium can, dry biodegradable resin

Compatible network 50Hz, 415Vac

Short circuit withstand Isc 10kA

VarSet wall mounted Qeff per enclosure Min: 25kvar; Max: 100kvar

Physical steps Min: 2 ; Max: 3

Capacitor rated voltage 525Vac

Detuned reactor 7%, 3.8th order, 190Hz

Step protection Circuit breaker

Main protective device Main incomer circuit breaker

Max. dissipated power 8-9 W/kvar

Mechanical

Ventilation Fan forced

Mounting Wall mounted

Cable connection Top entry

Enclosure Ingress protection IP54

Enclosure Impact protection IK10

< >
se.com/au Life is On | Schneider Electric | E-181
Switchboard Manufacturers

Power Factor Correction VarPlus Logic Series


Functions and characteristics

VarPlus Logic series - VL6. VL12


Intelligent Power Factor controllers

VarPlus Logic has all what you need for the simple and efficient Do more with VarPlus Logic
operation of your automatic power factor correction equipment • Programmable alarms with last 5 alarms log.
to maintain your power factor. It is a simple and intelligent relay
• Suitable for medium voltage applications.
which measure, monitor and controls the reactive energy. Easy
commissioning, step size detection and monitoring makes it • Suitable for 4 quadrant operations.
different from others in the market. • Dual cos phi control through digital inputs or export power
detection.
E Capacitor bank step monitoring • Dedicated alarm and fan control relays.
• Monitoring of all the connected capacitor steps • Advance expert programming Menu to configure the
controller the way you need.
• Real time power in “kvar” for the connected steps
• New control algorithm designed to reduce the number of
• Remaining step capacity per step as a % of the original
switching operations and quickly attain the targeted power
power since installation.
fact
• Remaining step power in kvar since installation
• Number of switching operations of every connected step.
Alarms
• Faulty Step
System Measurement and monitoring
• Configurable alarm for step derating
• THD(u) and THD(u) Spectrum 3rd to 19th - Measurement,
Display and Alarm • THDu Limit alarm
• Measurement of ∆Q – “kvar” required to achieve target cos • Temperature alarm
phi • Self correction by switching off the steps at the event of
• Present cabinet temperature and maximum recorded THDu alarm, temperature alarm and overload limit alarm
temperature • Under compensation alarm
• System parameters – Voltage, Current, Active, reactive and • Under/Over Voltage Alarm
apparent power • Low/High Current Alarm
• Large LCD display to monitor real step status and other • Overload limit alarm
parameters.
• Hunting alarm
• Maximum operational limits - Time and number of switching.
Easy Commissioning
• Automatic Initialization and automatic step detection to do a
auto commissioning
• Automatic wiring correction – voltage and current input
wiring correction
• 1A or 5A CT secondary compatible.

Flexibility to the panel builder and retrofitting


• No step sequence restriction like in the traditional relays
• Any step sequences with auto detect. No programming
needed
• Easy to retrofit the faulty capacitor with different power
• Quick and simple mounting and wiring
• Connect to the digitized Schneider solutions through RS485
communication in Modbus protocol
• Seamless connection to the Schneider software and
VarPlus Logic VL6, VL12
gateways.

E-182 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

VarPlus Logic series - VL6. VL12 A


Technical Specifications

Range Phase-to-Phase with VTs (3PH3W) B


Type Number of step output contacts Part number
L1
VL6 6 VPL06N
C
S1 S2
L2
L3
VL12 12 VPL12N N
PE

C C

D
B E E
Auxiliary (Control) Transformer

General characteristics ≤ 250 VAC ≤ 480 VAC


K1 K2 …
Voltage and current Input D PE A

E
U1
Direct supply voltage 90 – 550 V, 1ph, 50/60 Hz
90V - 550V
U2
S1
15mA - 6A
S2
VA Burden: 6 VA F1
F2

300 V LN / 519 V LL CAT III or 550 V CAT II C

F
TTL 1 K1
2 K2
Type of input connection Phase to phase or phase to neutral 0V
3


4
5
Protection against voltage dips Automatic disconnection of steps for dips > 15 ms D0- 6

(protection of capacitor) D1+


8
7

CT secondary 1A or 5A compatible
I1
I2
AL1
9
10
11
G
AL2 12 K12
CT primary range Up to 9600 A
Current 15 mA – 6 A, 1PH,
VA Burden : < 1 VA
H
Connection terminals Screw type, pluggable. Section: 0.2 – 2.5 mm2 (0.2 –
1 mm 2 for Modbus and digital inputs)
Power factor settings & algorithm selection I
Regulation setting – Programmable From Cos Phi 0.7c to 0.7i Phase-to-Neutral with VTs (3PH4W)
Reconnection time – Programmable From 1 to 6500 s
L1
Response time – Programmable From 1 to 6500 s L2
S1 S2

L3
Possibility of dual cos Phi target Yes, through digital input or if export power detected
PE

Program algorithm AUTOMATIC (best fit) - Default C C


B E E
LIFO Auxiliary (Control) Transformer
≤ 250 VAC ≤ 480 VAC
PROGRESSIVE K1 K2 …
D PE A
Import export application compatibility 4 - Quadrant operation for generator application 90V - 550V
U1
U2

Program intelligence 15mA - 6A


S1
S2
F1
Automatic Initialization and Automatic bank Yes F2

detection
C
TTL 1 K1
2 K2
Detection and display of power, number of Yes 3

switching & derating of all connected steps


0V 4
5
D0- 6
Capacitor bank step sequence Any sequence. No restriction/limitation on sequence D1+ 7
8
I1 9
Alarm and control I2 10
AL1 11
K12
Control outputs (step output) VL6: 6 relays VL12: 12 relays ( NO contact) AL2 12

250 V LN or LL (CAT III)


DC Rating : 48 V DC / 1 A
AC Rating : 250 V AC / 5 A
A. Upstream protection Voltage input: 2A
Common root: 10 A max.
certified circuit breakers or fuses
Dedicated fan control relay Yes. Normal open contact (NO) B. Shorting block for CT
48 V DC / 1 A, 250 V AC / 5 A C. VT primary fuses and disconnect
Alarm contact The relay contact is open when the controller is switch
energized with no alarm and will close in the event
of an alarm.The relay is a NC (Normally Close) when D. Output relays: 10 A (max.) certified
the controller is not energized.
circuit breakers or fuses (Applicable
Rating : 48 V DC / 1 A, 250 V AC / 5 A
for applications with voltage
Digital input for Cos phi2 target Dry contact (internal supply 5 V, 10 mA)
transformers only).
Modbus RS-485 serial port (RTU) Line polarization / termination, not included
E. Capacitor primary fuses or CB’s
Communication protocol Modbus
Interface TTL Service port. Only for internal use
Internal temperature probe Yes. Temperature offset is programmable.

< >
se.com/au Life is On | Schneider Electric | E-183
Switchboard Manufacturers

E-184 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Power Quality PowerLogic™ AccuSine+


General Overview

A
The AccuSine+ platform continues to bring
industry accolades. For the second time, Schneider B
Electric is the winner of the coveted 2020 Frost &
Sullivan Award. The flagship product captured top
honors in Global Product Leadership for its high- C
performance, technologically advanced range of
AccuSine+ power correction solutions.
D
Winning the award demonstrates Schneider
Electric’s exceptional commitment to innovation,
with the AccuSine+ platform bringing premium E
refinement, flexible designs and ultra-fast,
highly accurate harmonic cancellation and
reactive current compensation for power quality F
management.

As a provider of competitive and innovative products, Schneider


G
Electric tailors its operations to meet customer requirements with
the gold standard of products and services. The company services H
the global market for power correction where reliability, availability,
scalability, efficiency, cost, and control are critical.
I

< >
se.com/au Life is On | Schneider Electric | E-185
Switchboard Manufacturers

Power Quality PowerLogic™ AccuSine+


General Overview

Power Quality
Power quality problems are one of the major causes of unscheduled downtime,
equipment malfunction, and damage. Reliability and consistency of electricity supply

PB502832
are critical to businesses, from industrial plants, medical facilities, data centers
to office buildings. When power quality is imperfect due to disturbances such as
interruptions, voltage dips or harmonic pollution, your business suffers.

It is an area of growing concern for end users due to the frequency of occurrence
and financial impact of issues: 30 – 40 percent of all unscheduled downtime today
is related to power quality problems. In the industry sector, for example, the cost of
E poor power quality can reach four percent of annual turnover and is often equivalent
to the total balance payable on a facility’s energy bill.

A capital investment in power factor correction and harmonic filtering equipment can
result in a healthy return of investment. This return depends on the utility’s demand
rate structure; production quality cost related to harmonics; the cost of downtime
and interruptions due to voltage fluctuations in the distribution system.

Today, electrical installations are exposed to a great deal of power quality problems;
80 percent of these disturbances are typically generated by installed equipment.

PB502827
In industrial facilities, for example, such disturbances can be caused by non-linear
loads like arc welders or variable speed drives, capacitor switching, or large motor
starts. In commercial buildings, electronic equipment like computers, UPS, and
servers may also generate additional power quality disturbances.

The other 20 percent of power quality disturbances come from the energy
provider: even the most advanced transmission and distribution systems are not
able to guarantee 100 percent energy availability. Even with 99.99 percent energy
availability, the equivalent interruption time amounts to 52 minutes every year.

Where used by application


Buildings Industry
Retail Commercial Healthcare Water Food & Automotive Metal, Petro- Glass Semiconductor
& building wastewater beverage Minerals & chemical
Mining
AccuSine Office Office Office Process &
PCSn loads, LED/ loads, LED/ loads, LED/ production
CFL lights, CFL lights, CFL lights, lines
escalators, escalators, medical
lifts lifts equipment,
escalators,
lifts
AccuSine HVAC loads HVAC loads HVAC loads, Pumps & Process & Process & Process & Process Process & Process,
PCS+ pumps & fans with/ production production heating pumps heating heating &
fans without lines HVAC lines production lines
backup loads pumps & fans
generators
AccuSine PFC in PFC in PFC in PFC in
PFV+ harmonic harmonic harmonic harmonic
rich & flicker rich & flicker rich & rich &
control for control for dynamic dynamic
dynamic dynamic environment. environment.
environment. environment.

E-186 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

General Overview

AccuSine solutions solve a wide range of power A


quality problems
B
AccuSine PFV+ is an electronic VAR compensation (EVC) employing a multi-level IGBT
technology with advanced control systems platform to perform leading or lagging power C
factor correction (PFC) and flicker mitigation. It is the ideal solution for PFC applications
subject to high voltage distortion or subject to dynamic fast changing loads. It offers an
D

AccuSine_PCSn
ultra-fast response, is resonance free, and provides an infinite resolution of compensation
compared to conventional PFC solutions.

AccuSine PCSn and AccuSine PCS+ are flexible, high performance solutions to stabilize
E
electrical networks by providing harmonic mitigation and power factor correction, and load
balancing. F
AccuSine PCS+ is specifically designed for harsh electrical conditions, for heavy industrial
applications including mission critical environments. G
In addition to 3-phase mitigation, AccuSine PCSn has the ability to compensate for neutral
harmonic currents, typically present in building and commercial environments where single- H
phase non-linear loads are present.

I
The quality and performance you expect

All our power quality solutions provide an excellent return on investment because they are
designed and manufactured by Schneider Electric, by using advanced manufacturing
methods and premium materials. They are optimized to match your application needs and
are engineered to provide superior performance.

Where used by function


Phase Neutral Power factor Mains current Volt – VAR Flicker Environmental conditions
harmonics harmonics correction balancing support
AccuSine PCS+ Harsh and heavy industrial

AccuSine PCSn Commercial and light industrial

AccuSine PFV+ Harsh and heavy industrial

Infrastructure IT & Telco Renewable


Textile Ski lift / Marine Airport Railway & Oil & Gas Datacentre Solar Wind
Amusement park Tunnels
Office loads, Office loads, HVAC, office Load harmonics
LED/CFL lights LED/CFL lights, loads, LED/CFL on UPS & SMPS
baggage lights from blade
systems, servers
escalators, CCR
runway lights,
navigation
instruments
Process Load harmonics Propellors, CCR runway Pumps & fans Drilling, Load harmonics CSP: solar Load
& heating, on chair lift, PFC pumps & fans lights, pumps & pumping, on UPS, cooling mirrors (VSD harmonics
pumps & fans (VSD driven) fans, HVAC, with/ processing system and driven) from converter
without backup HVAC
generators
Flicker mitigation, Dynamic PF Traction sub- Dynamic PF Leading PF Voltage Hybrid VAR
dynamic VAR correction station load correction correction (for support via compensation
injection to improve balancing, PF to Improve backup genera- VAR injection (with process
generator correction, VAR generator tors & UPS) (with or without logic system)
prime mover support prime mover process logic)
efficiencies efficiencies

< >
se.com/au Life is On | Schneider Electric | E-187
Switchboard Manufacturers

Power Quality PowerLogic™ AccuSine PCSn


Functions and characteristics

The Schneider Electric solution for active harmonic filtering in building and commercial installations.
Electrical Characteristics
Standard RMS output current ratings Chassis: 20 A, 30 A, 50 A, 60 A
Wall: 20 A, 30 A, 50 A, 60 A
Rack: 30 A, 60 A
Nominal voltage 208 - 415 Vac, -15%/+10%
Nominal frequency 50 / 60 Hz, ±3 Hz auto sensing
AccuSine_PCSn

Connection type 3ph/3wire or 3ph/4wire


Compensation type 3ph only or 3ph + Neutral
Earthing systems TT, TN-C, TN-S, TN-C-S, IT, corner ground, centre-tapped delta, and
HRG

E Network voltage distortion Max. 20% phase to phase (up to 30th order)
Voltage notch limits Notch depth: 10%, Notch area (AN): 13,667 Vµs @ 400 V as per IEEE
519-2014, Annex C
Technical Product Characteristics
Power electronics 3-level IGBT
Control Topology Digital harmonic FFT
Digital instantaneous reactive power
Efficiency & Losses 208 Vac ≥ 95% 3ph compensation: ≤ 17.7 W/A
3ph + N compensation: ≤ 19.7 W/A
380 - 415 Vac ≥ 97% 3ph compensation: ≤ 20.4 W/A
AccuSine PCSn wall mount -
main unit (CE version) 3ph + N compensation: ≤ 22.6 W/A
Current transformer Any ratio with 1 A or 5 A secondary; Class 1.0 accuracy;
50/60 or 400 Hz rated (instrument rated or better); Grounded; can be
shared with other devices.
CT VA loading 1 A: 0.04 VA
5 A: 1 VA
Quantity of CT 2or 3 CTs for 3-phase loads
3CTs are required for 4-wire with neutral connected loads
CT position Grid or load sense
Control basis Closed or open loop
Spectrum cancellation & selection 2nd to 51st harmonic order; discrete, fully selectable adjustable per
harmonic order (amplitude % and ON/OFF).
Modes of operation Multi-modes simultaneously or discrete
-phase harmonic correction
-neutral harmonic correction user-adjustable up to 3 time unit rating
-power factor correction (cos )
AccuSinePCSnRM

-mains current load balancing


Operational features Current control (target THDi)
Voltage control (target THDv)
Reactive power control (target PF, target kvar)
Harmonic attenuation & THDi < 3% in closed loop control; max 20:1 THDi
filtering performance (typical reduction with load harmonic above 50% unit rating) Requires
AccuSine PCSn rack mount - 3% or higher inductive impedance per non-linear load
main unit (CE version) Power factor correction Optimize PF and Target PF (cos ) programmable
leading (capacitive) or lagging (inductive).
Mains current load balancing Negative and zero sequence; selectable individually or simultaneously.
Resonance avoidance Output at specific harmonic order turned off if resonance or lack of
impedance detected or manually turned off.
Paralleling Characteristics
Scalability & Expandability Upto 12 units in parallel per set of CT; any size unit combination
possible (max nth order subject to network characteristics).
Parallel operation options Master/Slave, Multi-master, Multi-master/Multi-slave (masters receive
CT connection).
Main units (master capable): 20 A, 30 A, 50 A, 60 A Expansion units
(slave only - no CT connection): 60 A
Paralleling architecture Distributed redundancy with no independent controller required.
Parallel sequence options Load share: all operating units function at the same ouput percentage.
Cascade: lead/lag with unit rotation; one unit operates to full capacity
before next unit turns on; timed rotation.
Unit ID assignment Automatic parallel ID assignment capability or can be set manually.

E-188 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

AccuSine PCSn Technical Specifications


Parallel redundancy Any unit with CT connections will automatically become master if the controling
A
master is taken offline. Automatic increase in ouput of all units to make up capacity
of any offline unit.
Parallel HMI control The main unit permits viewing and changing parameter settings of the complete
system or any other unit in the parallel system. B
Control and Communications
Parallel communications Proprietary communication bus between operating units (shielded CAT5e or higher
required with RJ-45 connectors). C
Control response time 40 - 60 μs typical
AccuSine_PCSn_UL

Harmonic correction time ≤ 2 cycles


Reactive correction time ≤ 1/2 cycle
D
Communications protocol Main units: Modbus RTU and Modbus TCP/IP Expansion units: Modbus RTU
Discrete I/O 4 inputs, 4 outputs assignable
E
Environmental Conditions
Operating temperature 0 °C to +45 °C (full performance, continuous operation without derating).
Derate 2% per °C up to +50 °C F
Relative humidity 0 - 95%, noncondensing
Operating altitude 1000 m (full performance, continuous operation). Derate 1% per 100 m above.
Above 3000 m requires solid ground.
G
Absolute max altitude: 4800 m.
Ambient temperature Automatic temperature roll back based upon real-time over temperature monitoring.
safety
Absolute shutdown if air inlet temperature reaches +51 °C.
H
Preset output limits (rms) Programmable set limit due to altitude or ambient temperature - becomes fixed output
limit.
Storage (in original Temperature: -20 °C to +60 °C, Relative humidity: to 95 %, noncondensing, clean, I
shipping packaging) dry, and protected. No conductive particles permitted.
Contaminant Levels Chemical Class 3C2, Mechanical Class 3S2 No conductive particles permitted.
- operating (IEC 60721-
3-3)
AccuSine PCSn wall mount - Contaminant levels Chemical Class 3C3, Mechanical Class 3S3 (stored in original shipping packaging).
main unit (UL version) - transport and storage No conductive particles permitted.
(IEC 60721-3-3)
Standards and Certification
Design reference IEC 62477-1, IEC 61439-1, EN 61000-6-2, EN 61000-6-4 Class A,
ISO 9001, IEE Std 519-2014, UL-508
EMC compliance EN 61000-6-4 Class A (Emissions), EN 61000-6-2 (Immunity).
Seismic compliance IBC 2015, ICC-ES AC156 (SDS = 2.47 g) excluding UL Type 1 model.
Product certification CE, CULUS (UL508 , CSA 22.2 No.14), RCM, EAC, ABS, DNV-GL
Mechanical and Installation Characteristics
Mounting configuration Indoor
Vertical: chassis and wall mount. Horizontal: 19" rack mount Floor standing possible
using chassis unit.
Ingress protection Chassis mount: IP00,
Wall mount: IP20, UL Type 1, Rack mount: IP20
PCBA protection Conformal coating on all PCBAs. Pollution degree 2.
Incoming circuit None - supplied by others external to AccuSine PCSn unit (refer to AccuSine PCSn
protection installation manual for further information).
Recommended earth leakage protection: 500 mA
Cable entry Chassis and wall mount: bottom entry Rack mount: front entry
Cooling configuration Variable speed controlled forced ventilation. High heat plenum. Air
flow: 560 m3/hr (329 cfm)
Chassis and wall mount: bottom to top Rack module: front to back
No conductive particles permitted, no corrosive gases.
Noise level 63 dB(A) typical
Dimensions (H x W x Chassis and wall mount: 960 x 440 x 265 mm; Wall mount UL Type 1: 1440 x 445 x
D) mm 265 mm Rack mount: 265 x 440 x 960 mm (6 U) (1 U = 1.75" = 44.45 mm)
Colour and material Galvanized steel enclosure Wall & rack mount front door and grill: Powder coated Lt.
grey RAL7035

< >
se.com/au Life is On | Schneider Electric | E-189
Switchboard Manufacturers

Power Quality PowerLogic™


Functions and characteristics

AccuSine PCSn Technical


HMI and Service Provisions
Display Magelis STU HMI, high definition color touchscreen TFT QVGA 64 k

Operator interface Chassis mount: 144 mm (5.7") supplied for mounting remotely Wall mount: 144 mm (5.7")
Rack mount: 90 mm (3.5")
Expansion units: no HMI required
User interface options Plain language, no cryptic code.
Multiple languages: English, French, Spanish, Portuguese, Chinese, Korean, German, Russian, and Polish.
Service port 2 x USB ports for firmware update, diagnostics file, and event log download, connection to PC.
Diagnostics can be downloaded via PC even if the unit is de-energized.
Commissioning features On-board step-by-step commissioning wizard via HMI.
E On-board commissioning report for download - no additional software required. Automatic CT calibration, polarity
detection and correction.
Phase sequence insusceptible.
Automatic unit neutral connection check.
Interoperability and Integration
Floor standing enclosures Using chassis module, ensuring air flow requirement is met.

Rack system integration Suitable for 19" wide rack systems, ensuring rack density requirement is met.

Edge control EPMS / SCADA integration EcoStruxure™ Power ready; native driver to Power Monitoring Expert 8.2 and later releases Compatible for operation
with AccuSine PCS+/PFV+ range;
Suitable for integration in 3rd party EPMS/SCADA through modbus mapping.

Typical Applications

Building LED / CFL Loads Research and Commecial Retail Hotel and Casino Healthcare
Life Sciences

• Airport terminal • Casino


• Railway terminal • Datacenter SMPS loads
• University facilities and accommodation • Commercial space SMPS loads
• Hospital • LED and CFL loads

Selection Table
AccuSine PCSn 208-415 V, 50/60 Hz
Rated Neutral rated Rated kVAR Catalogue Ingress Protection Mounting type Unit type Cable Frame Mass
current (A) current (A) @ 415 V number entry (kg)
20 60 14 PCSN020Y4CH00 IP00/Type OPEN* Chassis Main Bottom 12 61

30 90 22 PCSN030Y4CH00 IP00/Type OPEN*

50 150 36 PCSN050Y4CH00 IP00/Type OPEN* 75

60 180 43 PCSN060Y4CH00 IP00/Type OPEN*

60 180 43 PCSN060Y4CH00E IP00/Type OPEN* Expansion

20 60 14 PCSN020Y4W20 IP20 Wall mount Main Bottom 12 61

30 90 22 PCSN030Y4W20 IP20

50 150 36 PCSN050Y4W20 IP20 75

60 180 43 PCSN060Y4W20 IP20

60 180 43 PCSN060Y4W20E IP20 Expansion

30 90 22 PCSN030Y4R19 IP20 19" rack mount Main Front 14 61

60 180 43 PCSN060Y4R19 IP20 75

60 180 43 PCSN060Y4R19E IP20 Expansion

E-190 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Reference Numbers

Accessories and Rack Enclosure Systems


Catalogue number Description Mass (kg) Dimensions (mm) A
Height Width Depth

AR3100 NetShelter SX 42U x 600 mm Wide x 1070 mm Deep with doors 125 1991 600 1070 B
AR3300 NetShelter SX 42U x 600 mm Wide x 1200 mm Deep with doors 134 1991 600 1200

AR8136BLK NetShelter SX 1U toolless snap-in blanking panel, 10 pieces per pack 0.1 45 483 28 C
AR8108BLK NetShelter SX 1U standard metal blanking panel, 2 pieces per pack 0.1 44 483 3

AR8101BLK NetShelter SX 1U, 2U, 4U, 8U, blanking panel kit 3 - 483 3 D
AR7700 NetShelter SX stabilization plate to prevent tipping when sliding out equip- 4.5 75 351 207
ment
AR7701 NetShelter SX bolt-down kit — meets IBC seismic requirements for moder- 0.7 73 70 62 E
ate seismic zones
AR7701A-S NetShelter SX bolt-down kit — meets IBC seismic requirements for high 1 70 320 50
seismic zones
PCSNBTMKIT01 AccuSine PCSn terminal box for chassis & wall mount 7 430 550 290
F
PCSNFUSKIT230 AccuSine PCSn fuse kit for 20 A & 30 A chassis & wall mount 2 73 70 62
G
PCSNFUSKIT560 AccuSine PCSn fuse kit for 50 A & 60 A chassis & wall mount 2 70 320 50

H
For more information on NetShelter SX, please refer to: http://www.se.com/en/product-category/7500-it-racks-and-accessories
I
1U = 1.75” = 44.45 mm - Each PCSn rack module is 6U high + 1U space for cabling accessory (supplied with each unit).
Included in packaging: PCSn rack module, 1U cable plate and a pair of mounting rails for installation in NetShelter SX rack enclosures.

Note: Rack enclosure and accessories are not included in the PCSn module and must be ordered separately using the commercial references provided in the table
above.
Cable access roof
Air sealing: covers open space to
Easily adjustable prevent air recirculation and reduce
vertical mounting bypass airflow to improve cooling
rails efficiency.

Integrated baying
brackets

AR8101BLK
AR8136BLK
Toolless, zero-U Bolt-down and stabilization: prevents tip-over
accessory channel
in stand-alone rack applications and meet
specific anchoring requirements.

Half-height side
panels

AR7701 amd AR7701-S

Preinstalled leveling
feet and castors

NetShelter SX AR3100 or AR3300

< >
se.com/au Life is On | Schneider Electric | E-191
Switchboard Manufacturers

Power Quality PowerLogic™


Functions and characteristics
AccuSine PCS+ Technical Specifications
Active harmonic filtering solution for industrial and heavy-duty applications
Electrical characteristics
Standard RMS output current 208 - 240 Vac: 60 A, 120 A, 200 A, 300 A
ratings 380 - 480 Vac: 60 A, 120 A, 200 A, 300 A
480 - 600 Vac: 47 A, 94 A, 157 A, 235 A
600 - 690 Vac: 40 A, 80 A, 133 A , 200 A
Nominal voltage 208 - 240 Vac, + 10% / -10%
PB502824_R

380 - 480 Vac; + 10% / -15%


480 - 600 Vac; + 10% / -15%
600 - 690 Vac; + 10% / -15%
Nominal frequency 50 / 60 Hz, ±3 Hz auto sensing
Connection type 3ph/3wire (neutral connection not required)
Compensation type 3ph only (for neutral compensation, use AccuSine PCSn)
E Earthing systems TT, TN-C, TN-S, TN-C-S, IT, corner ground, centre-tapped delta and HRG
Voltage notch limits Notch depth: 20%, Notch area (AN): 22,800 Vµs @ 480 V (19,000 Vµs @ 400 V) as per IEEE
519-2014, Annex C
Technical Product Characteristics
Power electronics 3-level IGBT
Control Topology Digital harmonic FFT
Digital instantaneous reactive power.
Efficiency & Losses 208 - 480 Vac > 97% 400 Vac up to 97.7% (≤ 19.6W/A)
600 - 690 Vac > 95% 480 Vac up to 97.8% (≤ 22W/A)
Current transformers Any ratio with 1 A or 5 A secondary Class 1.0 accuracy
50/60 or 400 Hz rated (Instrument rated or better)
Grounded; can be shared with other devices.
CT VA loading 1 A: 0.04 VA, 5 A: 1 VA
Quantity of CT 2or 3 for 3-phase loads
3CTs are required if L-N connected loads are present
PB115718

CT position Grid sense (at mains) or load sense


Control basis Closed or open loop
Spectrum cancellation & selection 2nd to 51st harmonic order; discrete, fully selectable adjustable per harmonic order (amplitude
% and ON/OFF)
Modes of operation Multi-modes simultaneously or discrete
-phase harmonic correction
-power factor correction (cos )
-mains current load balancing
Operational features Current control (target THDi) Voltage control (target THDv)
Model 6 MCC (UL and Reactive power control (target PF, target kvar)
CSA approved) Harmonic attenuation & filtering THDi < 3% in closed loop control; max 20: 1 THDi typical (reduction with load harmonic
performance above 50% unit rating) requires 3% or higher inductive impedance per nonlinear load
Power factor correction Target PF (cos ) programmable
leading (capacitive) or lagging (inductive)
Mains current load balancing Negative sequence current
Resonance avoidance Output at specific harmonic order turned off if resonance or lack of impedance detected; or
manually turned off
Paralleling Characteristics
Scalability & Expandability up to 10 units in parallel per set of CT; any size unit combination possible
(max nth order subject to network characteristics) contact us for more
PD405100

than 10 units in parallel


Parallel operation options Master/slave, Multi-master, Multi-master/multi-slave (masters receive CT connection)
Paralleling architecture Distributed redundancy with no independent controller required.
Parallel sequence options Load Share: All operating units function at the same ouput percentage.
Cascade: Lead/lag with unit rotation: one unit operates to full
capacity before next unit turns on; timed rotation.
Unit ID assignment Automatic parallel ID assignment capability or can be set manually
Parallel redundancy Any unit with CT connections will automatically become master if the controling master is
taken offline. Automatic increase in ouput of all units to make up capacity of any offline unit.
Parallel HMI control Any main unit permits viewing and changing parameter settings of complete system or any
other unit in parallel system
Control & Communications
Parallel communications Proprietary communication bus between operating units (shielded CAT5e or higher required
with RJ-45 connectors)
Control response time 25 μs typical
Harmonic correction time ≤ 2 cycles
Reactive correction time ≤ 1/4 cycle
Communications protocol Modbus RTU & Modbus TCP/IP
Discrete I/O 4 inputs, 4 outputs assignable

E-192 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics


AccuSine PCS+ Technical Specifications
Environmental Conditions
A
Operating temperature Without derating - full performance, continuous duty
0 °C to +45 °C: 60 A, 120 A, 200 A (IP00/UL type Open and IP20/UL Type 1) 0 °C to +40 °C: all other models
With derating - 2% per °C above +40 °C/+45 °C
up to +50 °C max: all models B
Relative humidity 0-95%, noncondensing
Operating altitude 1000m (full performance, continuous operation). Derate 1% per 100 m above Above 3000m requires solid ground. Absolute max
altitude: 4800 m C
Ambient temperature safety Automatic temperature roll back based upon real-time over temperature monitoring. Absolute shutdown if air inlet temperature
reaches +51 °C
Preset output limits (rms) Programmable set limit due to altitude or ambient temperature - becomes fixed output limit
Storage (in original shipping Temperature: -20 °C to +60 °C, Relative humidity: to 95 %, noncondensing Clean, dry, and protected. No conductive particles
D
packaging) permitted.
Contaminant Levels - operating Chemical Class 3C2, Mechanical Class 3S2 No conductive particles permitted
(IEC 60721-3-3) E
Contaminant levels - transport Chemical Class 3C3, Mechanical Class 3S3 (stored in original shipping packaging) No conductive particles permitted
and storage (IEC 60721-3-3)
Standards & Certification
Design reference IEC 62477-1, IEC 61439-1, EN 61000-6-2, EN 61000-6-4 Class A, ISO 9001, UL 508, IEEE Std 519-2014
F
EMC compliance EN 61000-6-4 Class A (Emissions), EN 61000-6-2 (Immunity)
Seismic compliance IBC 2015, ICC-ES AC156 (SDS = 2.47 g)
floor standing models require top constraint - use NSYSFWFIX. G
Product Certification CE, CULUS (UL 508, CSA 22.2 No.14-18), CNAS, RCM, EAC, RoHS, ABS, DNV-GL
Mechanical & Installation Characteristics
Mounting configuration Indoor. H
Vertical: chassis & wall mount. Free standing: floor standing enclosures
Ingress protection Chassis (IP00) & Wall mount (IP20 / UL type 1)
Floor standing enclosures (IP31, IP54, UL type 1, UL type 2, UL type 12) I
PCBA protection Conformal coating on all PCBAs. Pollution degree 2
Incoming circuit protection Chassis & Wall mount: none, supplied by others external to equipment Floor standing models:
to 240 Vac - 200 kA CULUS; 150 kA IEC, to 415 Vac - 200 kA CULUS; 125 kA IEC to 480 Vac - 200 kA CULUS; 75 kA IEC, to 600 Vac -
100 kA CULUS; 20 kA IEC
to 690 Vac - No CULUS; 100 kA IEC
Cable entry Chassis & Wall mount: bottom entry. Floor standing models: top and bottom entry through gland plates
Cooling configuration Combination of natural and forced ventilation; separate air plenums for heat sink and PCBA sections.
Heat sink plenum: inlet bottom, exhaust top. All internal components rated ≥ IP54
PCBA plenum: inlet bottom, exhaust top. Air supply must be clean and dry No conductive particles permitted, no corrosive gases
Noise level < 70 dB(A) typical
Dimensions & Weight see Selection table and Dimensions guidelines on following pages
Colour & material Chassis & Wall mount: Galvanised steel. Floor standing enclosures: Powder coated Lt. grey RAL7035
HMI & Service Provisions
Display & Operator interface Magelis STU HMI, 144 mm (5.7") high definition colour touchscreen TFT QVGA 64 k
User interface options Plain language, no cryptic code.
Multiple languages: English, French, Spanish, Portuguese, Chinese, Korean, Russian, Polish & German
Service port 2 x USB ports for firmware update, diagnostics file & event log download, connection to PC
Diagnostics can be downloaded via PC even if unit is de-energised
Commissioning features On-board step-by-step commissioning protocol via HMI
On-board commissioning report for download - No additional software required Automatic CT calibration, polarity detection and
correction
Phase sequence insusceptible
Interoperability and Integration
iMCC integration Validated design in Okken / Blokset
Custom enclosure integration Using IP00 chassis to integrate in any custom enclosure
Edge control EPMS / SCADA EcoStruxure™ Power ready
integration Native driver to PME 8.2 and above
Compatible for operation with AccuSine PCSn and AccuSine PFV+ ranges Suitable for integration in 3rd party EPMS/SCADA through
modbus mapping

Typical Applications

Oil and gas Water Cement HVAC Building Wind turbines


• Oil and gas platforms • Automotive
• Port cranes • Process plants, pulp, and paper
• Steel • Wind and solar farms
• Water/wastewater • Lifts (ski or building)
• HVAC • Marine vessels

< >
se.com/au Life is On | Schneider Electric | E-193
Switchboard Manufacturers

Power Quality PowerLogic™


Reference Numbers

AccuSine PCS+ 380 - 480 V, 50/60 Hz


Rated KVAR rating Catalog number Rating Enclosure Style Cable entry Frame Weight
current @ voltage kg
39.5 @ 380 PCSP060D5IP00 IP00 (chassis) Wall mount Bottom 1 88

41.6 @ 400 PCSP060D5IP31 IP31 Floor standing Top or Bottom 2 277


60
43.1 @ 415
49.9 @ 480 PCSP060D5IP54 IP54 291

79.0 @ 380 PCSP120D5IP00 IP00 (chassis) Wall mount Bottom 3 113


83.1 @ 400 PCSP120D5IP31 IP31 Floor standing Top or Bottom 4 279
120
86.3 @ 415 PCSP120D5IP54 IP54 293
E 99.8 @ 480
131.6 @ 380 PCSP200D5IP00 IP00 (chassis) Wall mount Bottom 5 171
138.6 @ 400 PCSP200D5IP31 IP31 Floor standing Top or Bottom 6 384
200
143.8 @ 415 PCSP200D5IP54 IP54 402
166.3 @ 480
197.5 @ 380 PCSP300D5IP00 IP00 (chassis) Wall mount Bottom 7 210
207.8 @ 400 PCSP300D5IP31 IP31 Floor standing Top or Bottom 8
300
215.6 @ 415 422
249.4 @ 480
PCSP300D5IP54 IP54 436

Note:
60 A IP20 configuration requires ordering two items: PCSP060D5IP00 and PCSPWMKIT60A; adds 232 mm to IP00 length and 8.7 kg.
120 A IP20 configuration requires ordering two items: PCSP120D5IP00 and PCSPWMKIT120A; adds 232 mm to IP00 length and 9.3 kg.
200 A IP20 configuration requires ordering two items: PCSP200D5IP00 and PCSPWMKIT300A; adds 273 mm to IP00 length and 8.6 kg.
300 A IP20 configuration requires ordering two items: PCSP300D5IP00 and PCSPWMKIT300A; adds 273 mm to IP00 length and 8.6 kg.

AccuSine PCS+ 600 - 690 V, 50/60 Hz


Rated KVAR rating Catalog number Rating Enclosure Style Cable entry Frame Weight
current @ voltage kg
47.8 @ 690 PCSP040D7IP31 IP31 Floor standing Top or Bottom 9 483
40
PCSP040D7IP54 IP54 483
95.6 @ 690 PCSP080D7IP31 IP31 Floor standing Top or Bottom 9 533
80
PCSP080D7IP54 IP54 533

159.0 @ 690 PCSP133D7IP31 IP31 Floor standing Top or Bottom 10 709


133
PCSP133D7IP54 IP54 709

239.0 @ 690 PCSP200D7IP31 IP31 Floor standing Top or Bottom 10 827


200
PCSP200D7IP54 IP54 827

AccuSine+ Wall Mount IP20/UL Type 1 Conversion Kit


• Converts IP00 (UL Type Open) to IP20 (UL Type 1) wall mounted enclosed assemblies.
• Includes HMI mounting plate and cable entry

Assembled dimensions - IP20 IP20 Cable entry


assembly enclosure
Wall mount kit Unit rating Height Width Depth Weight (kg) Weight (kg)
reference (A)
PCSPWMKIT60A 60 1530 421 349 97.3 8.7

PCSPWMKIT120A 120 1630 421 384 122 9.3

PCSPWMKIT300A 200 1642 575 435 180 8.6

PCSPWMKIT300A 300 1882 575 435 218.6 8.6

E-194 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Power Quality PowerLogic™


Functions and characteristics

AccuSine PFV+ Technical Specifications


Reactive current compensation solution for specific and high-performance systems.
Electrical System Characteristics A
Standard RMS output current ratings 208 - 240 Vac: 60 A, 120 A, 200 A, 300 A
380 - 480 Vac: 60 A, 120 A, 200 A, 300 A
480 - 600 Vac: 47 A, 94 A, 157 A, 235 A
B
PB502824_R

600 - 690 Vac: 40 A, 80 A, 133 A , 200 A


Nominal voltage 208 - 240 Vac, +10%/-10%
C
380 - 480 Vac; +10%/-15%
480 - 600 Vac; +10%/-15%
600 - 690 Vac; +10%/-15% D
Nominal frequency 50/60 Hz, ±3 % auto sensing
Number of phases 3-phase, with or without neutral
Technical Product Characteristics E
Power electronics IGBT; 3 level inverter
Control Topology Digital 1/4 cycle response
Losses At 480 Vac < 3 %; at 690 Vac < 5 % F
Efficiency to 480 Vac >97%; to 690 Vac >95%
Current transformers (CT) Any ratio with 1 or 5 ampere secondary; Type 1 accuracy;
50/60 or 400 Hz rated (Instrument rated or better);
G
Grounded;can be shared with other devices.
Quantity of CT 2or 3 for 3-phase loads
H
3required for 4-wire with neutral connected loads
CT VA loading 40 mΩ
PB115718

Control basis Closed and open loop. I


CT position Grid sense (at mains) or load sense
Parallel operation Upto 25 units per set of CT any size combination.
Parallel operation options Master/Master (masters receive CT); Master/Slave; Multi-master/Multi-slave.
Parallel sequence options Cascade: Lead/lag with unit rotation: one unit operates to full capacity before next
unit turns on; timed rotation
Load Share: All operating units function at the same ouput
percentage
Parallel redundancy Any unit with CT connections will automatically become master if
Model 6 MCC (UL and
CSA approved) the controling master is taken offline.
Automatic increase in ouput of all units to make up capacity of any
offline unit.
Parallel HMI control Any unit permits viewing and changing parameter settings of the complete system
or any other unit in the parallel system.
Power factor correction Optimized PF correction, leading (capacitive) or lagging (inductive) power factor
(Cos ø) to target.
Mains current load balancing Negative sequence current injected to balance fundamental current on the mains
due to load imbalance (inherently corrects displacement PF (Cos φ)).
Voltage support (Volt-VAR mode) Mains voltage support via VAR injection: Maintain defined set point voltage by
PD405100

injecting leading VARs to raise voltage and lagging VARs to lower voltage; includes
speed of adjustment.
Control response time 25 μs
Reactive correction time ≤ 1/4 cycle
Display 145 mm QVGA TFT 7-color touchscreen
Operators Magelis HMI STU touch panel screen
Display parameters 100's: includes oscilloscope for viewing many selected parameters, phasor
diagrams, load power, measured currents for Is, If, I neg seq, PF (Cos φ), injected
currents for I reactive, I neg seq, etc.
Communications capability Modbus RTU, Modbus TCP/IP
Discrete input/outputs 4 input and 4 output dry contacts; assignable
Noise level < 70 db(A) typical
Color RAL7035 Enclosure; RAL7022 Plinth (floor standing units)
Earthing (Grounding) systems Suitable for most earthing (grounding) systems;
IT switch on EMC filter for IT earthing (ground), high resistance
Okken / Blokset
earthing (ground) or corner earthed (grounded) systems.
(IEC61439 certified)

< >
se.com/au Life is On | Schneider Electric | E-195
Switchboard Manufacturers

Power Quality PowerLogic™


Functions and characteristics
AccuSine PFV+ Specifications
Electrical System Characteristics
Operating temperature 60 A, 120 A, and 200 A: IP00 (UL Type Open) and IP20 (UL Type N1 wall mount): 0...45 °C; All others: 0...40 °C;
Derate 2% per °C upto 50 °C.
Relative humidity 0-95 %, noncondensing

Seismic rating Complies with IBC and ASCE7 (Requires top anchorage for all floor standing models - rec. use NSYSFWFIX).

Operating altitude 1000 m, (derate 1% per 100 m above)

Ambient temperature safety Automatic temperature roll back based upon any device OT. Absolute shutdown if air inlet temperature reaches 51 °C.

Preset output limits (rms) Programmable set limit due to altitude or ambient temperature - becomes fixed output limit.

Storage (in original shipping Temperature: -20...60 °C;


container) Relative humidty: to 95 %, noncondensing; Clean, dry, and protected;
E No conductive particles permitted.
"Contaminant levels - operating Chemical Class 3C2; Mechanical Class 3S2;
(IEC 60721-3-3)" No conductive particles permitted.
"Contaminant levels - transport and Chemical Class 3C3; Mechanical Class 3S3;
storage (IEC 60721-3-3)" When stored in original shipping container; No conductive particles permitted.
Reference Standards
Design CE EMC Certification IEC/EN 61439-1, EN 61000-6-4 Class A, EN 61000-6-2

Protection (enclosure) IP31, IP54, UL Type 1, UL Type 2, and UL Type 12

Standards compliance/ cULus (UL508 , CSA 22.2 No. 14)


certification CE Certified, ABS, other local standards
Installation
Wall mount IP00 (UL Type Open) and IP20 (UL Type 1) configurations

Free standing IP31, IP54, UL Type 2, and UL Type 12

Circuit protection IP00 and IP20 - external means required. Supplied by others.
Free standing enclosures - Incoming circuit breaker with mechanical door interlock.
AIC rating (applies to input to 240 Vac - 200 kA cULus; 150kA IEC
circuit breaker ratings for free to 415 Vac - 200 kA cULus; 125 kA IEC
to 480 Vac - 200 kA cULus; 75 kA IEC
standing model enclosures)
to 600 Vac - 100 kA cULus; 20 kA IEC
to 690 Vac - No cULus; 100 kA IEC
Cable Entry Wall mount: UL Type open, IP00, UL Type 1, and IP20 - bottom only. Free standing: top and bottom entry through gland
plates.
PCBA protection Conformal coating on all PCBAs.

Cooling configuration Natural and forced ventilation;


Separate air plenums for heat sink section and PCBA section; Heat sink plenum input from bottom with exhaust out top;
All components in heat sink plenum rated IP54 or better => no filtering required;
PCBA air supply must be clean and dry (filtering may be required);
No conductive particles permitted.
Service provisions
HMI (Magelis STU) Plain language output (no cryptic codes).
Languages: English, French, Spanish, Portuguese, and Chinese.
USB port for upload of new software and download of operational records.
Service port USB port: commission, program, or diagnostics via a laptop computer when power is on or off; laptop provides power to
control board when no unit power is present.
Commissioning On-board step-by-step commissioning protocol via HMI; CT automatic sizing, phase rotation, and polarity; external trans-
former ratio and phase shift; heat test, and more.

Typical Applications

Oil and gas Water Cement HVAC Building Wind turbines

• Oil and gas platforms • Automotive


• Port cranes • Process plants, pulp, and paper
• Steel • Wind and solar farms
• Water/wastewater • Lifts (ski or building)
• HVAC • Marine vessels
E-196 | Life is On | Schneider Electric
< > se.com/au
Power Monitoring and Power Quality Correction

Reference Numbers

AccuSine PFV+ 380 - 480 V, 50/60 Hz


A
Rated current KVAR rating Catalog number Enclosure Style Cable entry Frame Weight
@ voltage Rating kg

39.5 @ 380 EVCP060D5IP00 IP00 (chassis) Wall mount Bottom 1 88


B
41.6 @ 400 EVCP060D5IP31 IP31 Floor standing Top or Bottom 2 277
60
43.1 @ 415 EVCP060D5IP54 IP54 291 C
49.9 @ 480
79.0 @ 380 EVCP120D5IP00 IP00 (chassis) Wall mount Bottom 3 113

120
83.1 @ 400 EVCP120D5IP31 IP31 Floor standing Top or Bottom 4 279 D
86.3 @ 415 EVCP120D5IP54 IP54 293
99.8 @ 480
EVCP200D5IP00 IP00 (chassis) Wall mount Bottom 5 171 E
131.6 @ 380
EVCP200D5IP31 IP31 Floor standing Top or Bottom 11 363
138.6 @ 400
200
143.8 @ 415
6 384 F
166.3 @ 480 EVCP200D5IP54 IP54 402

197.5 @ 380
EVCP300D5IP00 IP00 (chassis) Wall mount Bottom 7 210 G
207.8 @ 400 EVCP300D5IP31 IP31 Floor standing Top or Bottom 11 402
300
215.6 @ 415 8 422
H
249.4 @ 480 EVCP300D5IP54 IP54 436

Note:
60 A IP20 configuration requires ordering two items: EVCP060D5IP00 and PCSPWMKIT60A; adds 232 mm to length and 8.7 kg. I
120 A IP20 configuration requires ordering two items: EVCP120D5IP00 and PCSPWMKIT120A; adds 232 mm to length and 9.3 kg.
200 A IP20 configuration requires ordering two items: EVCP200D5IP00 and PCSPWMKIT300A; adds 273 mm to length and 8.6 kg.
300 A IP20 configuration requires ordering two items: EVCP300D5IP00 and PCSPWMKIT300A; adds 273 mm to length and 8.6 kg.

AccuSine PFV+ 600 - 690 V, 50/60 Hz


Rated current KVAR rating  Catalog number Enclosure Style Cable entry Frame Weight
@ voltage Rating kg
EVCP040D7IP31 IP31 Floor standing Top or Bottom 9 483
40 47.8 @ 690
EVCP040D7IP54 IP54 483

EVCP080D7IP31 IP31 Floor standing Top or Bottom 9 533


80 95.6 @ 690
EVCP080D7IP54 IP54 533

EVCP133D7IP31 IP31 Floor standing Top or Bottom 10 709


133 159.0 @ 690
EVCP133D7IP54 IP54 709

EVCP200D7IP31 IP31 Floor standing Top or Bottom 10 827


200 239.0 @ 690
EVCP200D7IP54 IP54 827

AccuSine+ Wall Mount IP20/UL Type 1 Conversion Kit


• Converts IP00 (UL Type Open) to IP20 (UL Type 1) wall-mounted enclosed assemblies.
• includes HMI mounting plate and cable entry enclosure for mounting on the bottom of the IP00
assemblies.

Assembled dimensions - IP20 IP20 Cable entry


assembly enclosure
DB300967

Wall mount kit Unit rating Height Width Depth Weight (kg) Weight (kg)
reference (A)
PCSPWMKIT60A 60 1530 421 349 97.3 8.7

PCSPWMKIT120A 120 1630 421 384 122 9.3

PCSPWMKIT300A 200 1642 575 435 180 8.6

PCSPWMKIT300A 300 1882 575 435 218.6 8.6

< >
se.com/au Life is On | Schneider Electric | E-197
Switchboard Manufacturers

Power Quality PowerLogic™


Dimensions and Installation Guidelines
AccuSine PSCn
Frame size Description Exterior dimensions
figure Height Width Depth
mm mm mm
12 AccuSine PCSn chassis IP00/UL Type OPEN 960 440 265

12 AccuSine PCSn wall mount IP20 960 440 265

13 AccuSine PCSn wall mount UL Type 1 1440 445 265

14 AccuSine PCSn rack mount 265 440 960

Note: UL Type OPEN dimensions exclude fuse kit

Frame size 12
E
Chassis mount IP00/UL Type OPEN Wall mount IP20
350 350
PHA2995900

PHA2996200

940 H 940 H

18mm
D W D W

• HMI only on main unit – supplied loose in the box for • HMI only on main unit.
mounting remotely. • Expansion unit has the same dimensions as the main
• Expansion unit has the same dimensions as the main unit, except no HMI provided.
unit, except no HMI provided.
Note: Fuse kit shall be installed on line side to maintain CULUS compliance.

Frame size 13
Wall mount UL Type 1
350
GDE38856900

1367 H

18mm
D W

HMI only on main unit.


Expansion unit has the same dimensions as the main unit, except no HMI provided.
Note: All dimensions are indicative. Please refer to the dimensions in the Installation manual and engineering drawings for design purposes.
E-198 | Life is On | Schneider Electric
< > se.com/au
Power Monitoring and Power Quality Correction

Dimensions and Installation Guidelines

Frame size Description Exterior dimensions


A
figure Height Width Depth
mm mm mm
12 AccuSine PCSn chassis IP00/UL Type OPEN 960 440 265 B
12 AccuSine PCSn wall mount IP20 960 440 265

13 AccuSine PCSn wall mount UL Type 1 1440 445 265


C
14 AccuSine PCSn rack mount 265 440 960

Note: UL Type OPEN dimensions exclude fuse kit D

Frame size 14
E
Rack mount
465
F
PHA2996500-PCSn

H (6U) 177.8 265 G


(6U)

H
= ; ........... = 3 ............ = 4 ............. 0
$%%*0+='>%> *0$&#'+&*(0 )"0' " =
3 < < ?5 ; 6 .! " +
/(#
REV. 00 + (0 0 %+ &*(0
> %&" *=$ ,B"657
4;

D W
• HMI only on main unit. I
• Expansion unit has the same dimensions as the main unit, except no HMI provided.

Accessories
Fuse kit Terminal kit
MFR7070101_Front

MFR7169501_Front

345
D

125

445

192

PCSNFUSKIT230 – for 20 & 30 A chassis models


MFR7169501

PCSNFUSKIT560 – for 50 & 60 A chassis models

Note: Fuse kit required on line side of chassis IP00 model


to maintain CULUS compliance.

PCSNBTMKIT01 - optional cable termination box for


chassis IP00 and wall mounted IP20 models

Note:
All dimensions are indicative. Please refer to the dimensions in the Installation manual and engineering drawings for design purposes.

< >
se.com/au Life is On | Schneider Electric | E-199
Switchboard Manufacturers

Power Quality PowerLogic™


Dimensions and Installation Guidelines
AccuSine PSC+ and PFV+
Frame size Exterior dimensions
figure
Height Width Depth
mm mm mm
1 1300 421 349
2 2100 800 500
3 1400 421 384
4 2100 800 500
5 1323 582 438
6 2100 900 600
7 1560 582 438
8 2100 900 600
E 9 2100 1300 500
10 2100 1400 600
11 2000 800 600

Frame size 1 Frame size 2


IP31 IP54

W W W W D DDD W W D DDD
DB300894

DB300895

DB300886

DB300887

DB300888

DB300889
WW D DDD WW WW

H HHH

H HHH H HHH

Frame size 3 Frame size 4


IP31 IP54
W W
WW D DDD W W
WW D DDD W W
WW D DDD
DB300898

DB300899

DB300886

DB300887

DB300888

DB300889

H HHH

H HHH H HHH

Note:
Dimensions are subject to change without notice.
Obtain current mechanical drawings at www.se.com.
Please refer to installation manual and engineering drawings for design purposes.

E-200 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Functions and characteristics

Frame size 5 Frame size 6 A


IP31 IP54
W D W D W D
B
DB300912

DB300913

DB300900

DB300901

DB300902

DB300903
C

D
H H

G
Frame size 7 Frame size 8
IP31 IP54 H
W D W D W D

I
DB300900

DB300901

DB300902

DB300903
DB300916

DB300917

H H

Frame size 9
IP31 IP54
W D W D
DB300890

DB300891

DB300892

DB300893

H H

Note: All dimensions are indicative. Please refer to the dimensions in the Installation manual and engineering drawings for design purposes.

< >
se.com/au Life is On | Schneider Electric | E-201
Switchboard Manufacturers

Power Quality PowerLogic™


Functions and characteristics
AccuSine PSC+ and PFV+
Frame size 10
IP31 600 Vac IP31 690 Vac
W D W D
DB300904

DB300905

DB300904

DB300905
E H H

IP54 600 Vac IP54 690 Vac


W D W D
DB300906

DB300907

DB300906

DB300907

H H

Frame size 11
UL Type 1 (IP20) 240-480 Vac
W D
DB421907

DB421908

Note: All dimensions are indicative. Please refer to the dimensions in the Installation manual and engineering drawings for design purposes.

E-202 | Life is On | Schneider Electric


< > se.com/au
Power Monitoring and Power Quality Correction

Power Quality Solutions


More Information

We deliver smart and cost-effective power quality solutions to improve our customers efficiency.
A
AccuSine
Active Power Correction for Harmonic Mitigation, Reactive Power
Compensation and Mains Current Balancing
B
Bring efficiency and reliability to your operation
C

E
Find out more visit
www.se.com
and download F
AMTED109015EN

I
Find out how to fix your power quality issues Real-time performance and capability of Take control of your operation today with
AccuSine PCSn AccuSine PCS+

VarSet Smart
Intelligent LV Capacitor Banks
Digitize your power factor correction

Find out more visit www.se.com


and download
998-1164795_GMA_VarSet_eBro

Relevant documents
Relevant documents published by Schneider Electric
• Electrical Installation Guide
• Expert Guide n° 4: Harmonic
• Expert Guide n° 6: Power Factor Correction and Harmonic Filtering Guide
• Technical Guide 152: Harmonic disturbances in networks, and their treatment
• Technical Guide n° 202: The singularities of the third harmonic
• White paper: controlling the impact of Power Factor and Harmonics on Energy Efficiency
• Harmonic mitigation - Solution Handbook (SLTED109014EN)
• AccuSine+ Installation and User Manuals
Relevant standards
• IEC 62477-1 - Safety requirements for power electronic converter systems and equipment
• IEEE 519 - Recommended practice and requirements for Harmonic Control in Electric Power Systems
• IEC 61642 - Application of filters and shunt capacitors for industrial a.c. networks affected by harmonics

< >
se.com/au Life is On | Schneider Electric | E-203
Switchboard Manufacturers

Power Quality Solutions


Functions and characteristics

The world’s most versatile rack enclosure for demanding IT environments

Rack Solutions
Enclosure and rack systems

E
Find out more visit
www.se.com
and download
998-4936_GMA-US_B

Cooling Solutions
Cooling Solutions for IT Equipment

Find out more visit


www.se.com
and download
998-1158592_GMA-US

Effective cooling and cable management

Improving Rack Cooling Planning Effective


Performance Using Airflow Power and Data Cable
Management™ Blanking Management in IT Racks
Panels Download
Download White Paper 203
White Paper 44

E-204 | Life is On | Schneider Electric


< > se.com/au

You might also like