KT 261 6.5 Min KT 222: CS-4000 CENTAUR Start Sequence
KT 261 6.5 Min KT 222: CS-4000 CENTAUR Start Sequence
6.5 min
KT 222
4 min
CCPS
VENTING
CLOSES
VALVE CLOSES Note: KT 222 - Prelube Timer KT 261 - Fail to Load Timer
AT 9 psig
KT 243 - Crank Timer KT 285 - Start Timer
KT 260 - Compressor Purge Timer KT 241 - Engine Purge Timer
KT 240 - Gas Fuel Leak Timer KT 246 - Light Off Timer
CS-4000 CENTAUR
CS-4000.XLS
START SEQUENCE
KT 261
5 min
VALVE SEQ
CONTROL S111 MALFUNCTION AUX. LUBE
TO LIGHTS PUMP ON
AUTO ILLUMINATES
& EXTINGUISH
SV FC
DV FC
BYPASS
LV FC VALVE
BV FO CLOSES
VV FO
PRELUBE
NO PRESSURE
>6 PSIG
YES
AUXILIARY
SEAL OIL
PUMP
ON
AUXILIARY
NO SEAL OIL
>16 psig
YES
LOADING
VALVE
OPENS
LOADING
VALVE
OPENS
KT260
30 sec
VENTING
VALVE CLOSES
Saturnsqc.XLS
KT 285
60 sec
KT 243 KT 246
15 sec 25 sec
NO NO
S/D
FAIL TO
IGNITE
COMPRESSOR NO
P <50 psig
CCPS
CLOSES
AT 9 psig
MAIN LUBE S/D
PRESSURE NO LOW LUBE
>35 psig PRESSURE
400 deg F PRELUBE
before PUMP
25 sec OFF AT
35 psig 60% NGP S/D
BEFORE NO FAIL TO
NO 60 sec START
S/D YES
FAIL TO
IGNITE
STARTER
MOTORS
OFF
NO
THROTTLE AUX. SEAL
CONTROL OIL PUMP
S/D OFF
FAIL TO
LOAD
SURGE
SYSTEM IN
CONTROL
S/D
FAIL TO
LOAD
SURGE
SYSTEM IN
CONTROL
BYPASS
YES VALVE LOADING
CLOSES SPEED
AUX. SEAL
OIL PUMP
OFF
SURGE
SYSTEM IN
CONTROL
SURGE
SYSTEM IN
CONTROL
CS-1200 SATURN
START SEQUENCE
KD 235
200 Sec
KD 243
30 Sec
MASTER S
S101
TO KD 222 KD 240
LOCAL 15 Sec 5 SEC
NO Z-244
PRE-POST PRIMARY MAINTAIN
LUBE FUEL KP 241 KD 246 KP 239 1170 oF
MALFUNCTION PUMP VALVE 10 SEC 15 SEC 2 MIN T5 TEMP.
LIGHTS ON OPEN ENGINE
NGP
S/D
illuminate & SPEED
90 %
NO FAIL TO
extinguish 60 %
SPEED
START
NGP
ENGINE
PRELUBE S/D
PRESSURE LOW SECONDARY S 342 PRIMARY T5 S/D
> 6 PSI NO PRELUBE FUEL OPENS FUEL VALVE ENGINE TEMP. FAIL TO
NO FIELD
PRESSURE VALVE OPENS > 350 oF IGNITE
OPENS
ENERGIZED FLASH
DE DE
STARTER ENERGIZED
NO ENERGIZED
ENERGIZED DE LUBE OIL
CIRCUIT CIRCUIT PRESSURE LUBE S/D S/D
IGNITION IGNITION > 35 psi PRESSURE LOW LUBE
85 % UNDER
NO NO
AUX LUBE > 35 PSI OIL
VOLTAGE VOLTAGE
PUMP OFF FAILURE
GENERATOR
Z 149 Z 149 PRESSURE
RAMP RAMP
S/D S/D GENERATOR GENERATOR
FUEL VALVE FUEL VALVE ENERGIZED DE GENERATOR GOVERNOR
FAILURE FAILURE ENERGIZED FIELD FLASH CONTROL
ENERGIZED ENERGIZED
Z-244
MAINTAIN
800 oF
T5 TEMP HOUR KP 255
METER 2 SEC TO LOAD
ENERGIZED READY
IGV'S ENGINE
ENERGIZED
SPEED
100 %
NGP
CENTAUR - 4000
START SEQUENCE
GENERATOR SET
FUEL GAS