Professional Documents
Culture Documents
Relay & HV Lab Manual - 2020 Latest-1
Relay & HV Lab Manual - 2020 Latest-1
Relay & HV Lab Manual - 2020 Latest-1
LABORATORY MANUAL
2021-22
APPARATUS REQUIRED:
CIRCUIT DIAGRAM:
Resistance 0-10A
AC1 T1
C
Relay TIMER
RELAY COIL Auxiliary
Contact
230V, 50Hz
.AC Supply C AC2 T2
PROCEDURE:
1) Do the connections as shown in the circuit diagram.
2) Keep the VARAIC to its Zero position.
3) Keep the Set CURRENT switch in OFF position
4) Now refer the front panel of the relay for settings of PMS and TMS settings.
5) For example now you set the current setting from the PMS by using key set to 0.75A
And set the TMS 0.5 Sec.
6) Switch ON the mains Supply, set the switch position to START position.
7) Now set the CURRENT slowly by varying the VARAIC more than the 0.75 for example 0.9A.
8) Now set the switch position to OFF position, now switch ON the switch to START POSITION
and note down the Operating time from the TIMER.( When the Red lamp indicates red)
9) Repeat the procedure No. 7 & 8 for different sets of currents like 1.0,, 1.2, 1.3, 1.4 1.5A. and
note down the operating for each reading.
10) Draw the Inverse time characteristic curve Load Current v/s Operating Time.
TABULAR CLUMN:
TABULAR CLUMN:
NATUR OF GRAPH:
4
S G BALEKUNDRI INSTITUTE OF TECHNOLOGY, BELAGAVI -10
Department of Electrical & Electronics Engineering
APPARATUS REQUIRED:
AC1 AC2 C1 C2
S1 0-400V AC S2 T1 TIMER INPUT T2
CIRCUIT DIAGRAM:
AC1 T1
0V C
0V
Auto Transformer
STEP UP TRANSFORMER
5
S G BALEKUNDRI INSTITUTE OF TECHNOLOGY, BELAGAVI -10
Department of Electrical & Electronics Engineering
PROCEDURE:
1) Do the connections as shown in the circuit diagram.
2) Keep the Dimmer stat to its Zero position.
3) Keep the Set voltage switch in OFF position
4) Now refer the front panel of the relay for settings of PMS and TMS settings.
5) For example now you set the Voltage setting from the PMS by using key set to 121V
And set the TMS 0.5 Sec.
6) Switch ON the mains Supply.
7) Now set the Voltages by multiplying the PMS with respect to 121 V x 1.1 and set the voltage
keeping the switch position to SET position and switch OFF the switch in OFF position; now
switch ON the switch to START POSITION .and note down the Operating time from the
TIMER.( When the Red lamp lamp indicates red)
8) Repeat the procedure No. 6 for different multiplier for 1.2, 1.3, 1.4, 1.5 1.6, & 1.7 for
different readings and note down the operating for each reading.
9) Draw the Inverse time characteristic curve PMS v/s Operating Time
TABULARCOLUMN:
Time Multiplier Plug Setting Supply Voltage Operating Time Voltage Multiplier
Setting Volts Sec.
1.1
1.2
0.5 Sec 121V 1.3
1.4
1.5
1.6
1.1
1.2
1 Sec 121V 1.3
1.4
1.5
1.6
6
S G BALEKUNDRI INSTITUTE OF TECHNOLOGY, BELAGAVI -10
Department of Electrical & Electronics Engineering
TABULARCOLUMN:
Time Multiplier Plug Setting Supply Voltage Operating Time Voltage Multiplier
Setting Volts Sec.
1.1
1.2
0.5 Sec 143V 1.3
1.4
1.5
1.6
1.1
1.2
1 Sec 143V 1.3
1.4
1.5
1.6
NATUR OF GRAPH:
7
S G BALEKUNDRI INSTITUTE OF TECHNOLOGY, BELAGAVI -10
Department of Electrical & Electronics Engineering
APPARATUS REQUIRED:
3 Phase A C Mains Phase Voltages Line Current Negative Sequence Fault Simulation
400V Relay
R Y B N R Phase R Line
VOLTMETER AMMETER AMMETER
R N R R Negative Sequence
Current
MAINS Y Phase Y Line TRIP RESET
VOLTMETER AMMETER SP
ON OFF BAL UNBAL
Y N Y Y Y Y
CIRCUIT DIAGRAM:
0-10A R R S
0-300V
R 0-10A Y Y
Y
B
0-300V
N 0-10A
B B
3- Phase, 415 V
50 Hz , LOADING RESISTANCE
AC Supply. 0-300V
8
S G BALEKUNDRI INSTITUTE OF TECHNOLOGY, BELAGAVI -10
Department of Electrical & Electronics Engineering
PROCEDURE:
1) First ensure that the 3 phase supply is switched OFF.
2) Do the connections as shown in the circuit diagram.
3) Switch ON the supply, and set the switch of negative sequence relay to balanced system position.
4) Now note down the readings of all the meters.
5) Vary the load resistance for different sets of readings and note down the readings of all the
Meters for balanced system.
6)For Unbalanced system: set the switch of negative sequence relay to unbalanced system
Position and vary the load resistance for different sets of readings and copy down all the meters
readings ( 3-4 set of readings)
7) For single phase system: set the switch of negative sequence relay to single phase system
Position and vary the load resistance for different sets of readings and copy down all the meters
readings ( 3-4 set of readings)
APPARATUS REQUIRED:
T=K (0.1+It)
RELAY ON RELAY TRIP 1 2 3 4
ON ON ON ON
TRIP TIME CHARACTERISTICS
RELAY AUX. CONTACT
S1 OUT PUT CURRENT S2 T1 TIMER INPUT T2 AC1 AC2
0-10A
C1 C1
RELAY COIL
CIRCUIT DIAGRAM:
Resistance
AC1 T1
A
C1
Relay TIMER
RELAY COIL Auxiliary
Contact
230V ACS
50Hz. C2 AC2 T2
PROCEDURE:
1) Do the connections as shown in the diagram.
2) Keep Current VARAIC to its zero position, select the Relay time on the Relay panel say for
Example 0.5 Sec. and load current to its 40%.
3) Now select required characteristics from the panel board by selecting the Trip Time Characteristics
Selector switches. ( For Example you need to draw the Normal Inverse Characteristics (1.3 Sec)of
OCR. Select the Time Characteristics selector switches in ( S 1,S2,S3,S4 all in OFF Positions) by
referring Table of Toggle switches to select the trip time characteristics for different Characteristics
4) Now you switch ON the mains Supply, SET the current by switching Switch position to SET position.
5) Apply the load current by varying the current VARAIC 0.5A, switch of the switch to OFF position
6) Now set the switch position to START position and note down operating time when the relay trips
Red lamp will be ON.
7) Repeat the procedure No. 6 for different load currents of 0.6, 0.7, 0.8, 0.9, 1.0 and 1.1 A.
8) Draw the Time – Current characteristics for different TMS.
Calculation:
TABULAR COLUMN:
1) Normal Inverse (1.3 Sec) Time Characteristics of Microprocessor Over Current Relay
2) Normal Inverse (3 Sec) Time Characteristics of Microprocessor based Over Current Relay
0.5 40%
1.0 40%
0.5 80%
1.0 80%
Current Time
Current Time
13
S G BALEKUNDRI INSTITUTE OF TECHNOLOGY, BELAGAVI -10
Department of Electrical & Electronics Engineering
NATURE OF GRAPH:
14
S G BALEKUNDRI INSTITUTE OF TECHNOLOGY, BELAGAVI -10
Department of Electrical & Electronics Engineering
APPARATUS REQUIRED:
VOLTS SECONDS
SET 0.05 0.1 0.2 0.4 µ C OVER
OFF
MAINS ON 2A SBF START RESET ON ON ON ON VOLTAGE RELAY
V S =¿
RELAY ON RELAY TRIP 0.1 0.2 0.4 0.8
ON ON ON ON
T = K (0.1 + t ) RELAY AUX. CONTACT N/O
AC1 AC2
1 2 3 4
OUT PUT VOLTAGE TIMER INPUT
0 – 400 AC ON ON ON ON C C
T1 T2 RELAY COIL
TRIP TIME CHARACTERISTICS
CIRCUIT DIAGRAM:
AC1 T1
C
0
0
0-600V Relay TIMER
V RELAY COIL Auxiliary
Contact
230 V
230V ACS 400V
50Hz. C AC2 T2
PROCEDURE:
1) Do the connections as shown in the diagram.
2) Keep VARAIC to its zero position, select the Relay time on the Relay panel says for Example 0.1
Sec. and calculated voltage 121 V X 1.1 = 133.1V
3) Now select required characteristics from the panel board by selecting the Trip Time Characteristics
Selector switches. ( For Example you need to draw the Normal Inverse Characteristics (3.5 Sec)of
OVR. Select the Time Characteristics selector switches in ( S 1,S2,S3,S4 ON, OFF OFF,OFF positions)
By referring Table of Toggle switches to select the trip time characteristics for different
Characteristics
4) Now you switch ON the mains Supply, SET the voltage by switching Switch position to SET position.
5) Now SET switch set to OFF positon
6) Now set the switch position to START position and note down operating time when the relay trips
Red lamp will be ON.
7) Repeat the procedure No. 4,5 & 6 for different voltage multipliers of 121X 1.2, 1.3, 1.4, 1.5 & 1.6.
8) Draw the Time v/s PMS characteristics curve.
Calculation:
For Normal Inverse (3.5 Sec)
1) VS¿ ¿ Take Vn = 110V standard value
VS = [ 1 + 0.05+0.05] X 110
= 1.1 X 110
VS = 121V.
Time Multiplier Plug Setting Supply Voltage Operating Time Voltage Multiplier
Setting Volts Sec.
1.1 X121 =133.1 V 1.1
1.2 X121 =145.2 V 1.2
0.1 Sec 121V 1.3 X121 =157.3 V 1.3
1.4 X121 =169.4 V 1.4
1.5 X121 =181.5 V 1.5
1.6 X121 =193.6 V 1.6
1.1 X121 =133.1 V 1.1
1.2 X121 =145.2 V 1.2
0.5 Sec 121V 1.3 X121 =157.3 V 1.3
1.4 X121 =169.4 V 1.4
1.5 X121 =181.5 V 1.5
1.6 X121 =193.6 V 1.6
Time Multiplier Plug Setting Supply Voltage Operating Time Voltage Multiplier
Setting Volts Sec.
1.1
1.2
0.1 Sec 132V 1.3
1.4
1.5
1.6
1.1
1.2
0.5 Sec 132V 1.3
1.4
1.5
1.6
17
NATURE OF GRAPH:
18
S G BALEKUNDRI INSTITUTE OF TECHNOLOGY, BELAGAVI -10
Department of Electrical & Electronics Engineering
APPARATUS REQUIRED:
VOLTS SECONDS
SET 0.05 0.1 0.2 0.4 µC Under
OFF
MAINS ON 2A SBF START RESET ON ON ON ON Voltage Relay
V S =¿
RELAY ON RELAY TRIP 0.1 0.2 0.4 0.8
ON ON ON ON
T = K (0.1 + t ) RELAY AUX. CONTACT N/O
AC1 AC2
1 2 3 4
OUT PUT VOLTAGE TIMER INPUT
0 – 400 AC ON ON ON ON C C
T1 T2 RELAY COIL
TRIP TIME CHARACTERISTICS
CIRCUIT DIAGRAM:
AC1 T1
C
0
0
0-600V Relay TIMER
V RELAY COIL Auxiliary
Contact
230 V
230V ACS 400V
50Hz. C AC2 T2
19
S G BALEKUNDRI INSTITUTE OF TECHNOLOGY, BELAGAVI -10
Department of Electrical & Electronics Engineering
PROCEDURE:
1) Do the connections as shown in the diagram.
2) Keep VARAIC to its zero position, select the Relay time on the Relay panel says for Example 0.1
Sec. and calculated voltage 110 V X 0.9 = 99V
3) Now select required characteristics from the panel board by selecting the Trip Time Characteristics
Selector switches. ( For Example you need to draw the Normal Inverse Characteristics (5.7 Sec)of
UVR. Select the Time Characteristics selector switches in ( S 1,S2,S3,S4 OFF, OFF OFF,OFF positions)By
referring Table of Toggle switches to select the trip time characteristics for different Characteristics
4) Now you switch ON the mains Supply, SET the voltage by switching Switch position to SET position.
5) Now switch OFF the SET switch to OFF position .
6) Now set the switch position to START position and note down operating time when the relay trips
Red lamp will be ON.
7) Repeat the procedure No. 4,5 & 6 for different voltage multipliers of 121X 1.2, 1.3, 1.4, 1.5 & 1.6.
8) Draw the Time v/s PMS characteristics curve.
20
S G BALEKUNDRI INSTITUTE OF TECHNOLOGY, BELAGAVI -10
Department of Electrical & Electronics Engineering
Calculation:
For Normal Inverse (3.5 Sec)
1) VS¿ ¿ Take Vn = 110V standard value
VS = [ 1 - 0.05+0.05] X 110
= 1 – 0.1= 0.9
VS = 0.9 X110 = 99 V.
Time Multiplier Plug Setting Supply Voltage Operating Time Voltage Multiplier
Setting Volts Sec.
0.9
0.85
0.5 Sec 110V 0.80
0.75
0.7
0.65
Time Multiplier Plug Setting Supply Voltage Operating Time Voltage Multiplier
Setting Volts Sec.
0.9
0.85
0.5 Sec 110V 0.80
0.75
0.7
0.65
21
S G BALEKUNDRI INSTITUTE OF TECHNOLOGY, BELAGAVI -10
Department of Electrical & Electronics Engineering
AIM : Study the various 3 phase A C Motor protection scheme using a microprocessor based Relay.
APPARATUS REQUIRED:
ON RPM
R N R R EF
I0(%Im) Im(A) OPEN CLOSE
MAINS Y Phase Y Line
Rin Yin Bin
Y Y Y Y RELAY
ON OFF
B Phase B Line
OUT PUT OPEN
R Y B N SP
R out Y out B out CLOSE
B B B
22
S G BALEKUNDRI INSTITUTE OF TECHNOLOGY, BELAGAVI -10
Department of Electrical & Electronics Engineering
0-300V
0-10A Y Y Mm
0-300V
0-10A 3 Ph. Induction Motor
N B B
3- Phase, 415 V
50 Hz , ACS.
0-300V
PROCEDURE:
NOTE: Before connecting the circuit diagram ensure that Three phase supply should be in OFF
position & Three phase dimmerstat should be in Zero position.
23
S G BALEKUNDRI INSTITUTE OF TECHNOLOGY, BELAGAVI -10
Department of Electrical & Electronics Engineering
CONCLUSION:
24
S G BALEKUNDRI INSTITUTE OF TECHNOLOGY, BELAGAVI -10
Department of Electrical & Electronics Engineering
SWITCH
AC DC
CIRCUIT DIAGRAM:
EL
R L 10 MΩ
0-100 mA
CONTROL 0 0
PANEL PLANE POINT
WITH
REGULATOR R
230 V PLANE PLANE
230V ACS 50KV
50Hz.
HV Transformer
0 - 230 V / 0-50KV AC/70 KV DC,
25
S G BALEKUNDRI INSTITUTE OF TECHNOLOGY, BELAGAVI -10
Department of Electrical & Electronics Engineering
PROCEDURE:
1) Ensure that all the supply switches should be in OFF position.
2) Connect the circuit as shown in the circuit diagram.
3) Adjust sphere gap setting to 0.5 cm, come out from the H V Transformer room and close the door.
4) Now select the DC switch for measurement of HVAC.
5) Keeping the Panel board auto transformer in zero position, now switch ON the single phase supply.
6) Vary the auto transformer slowly till the flash over of sphere.
7) Repeat the procedure for 3- 4 set of readings for different sets of spheres gaps (0.5, 1.0 & 1.5 cm)
8) copy the readings of V from the panel voltmeter in Kv.
9) Repeat the same procedure for different electrode.
S No. gap spacing in cm Break down voltage V in KV Average break down Potential Gradient
Voltage V in KV KV/cm
1 0.5 cm
2 1.0cm
3 1.5cm
S No. gap spacing in cm Break down voltage V in KV Average break down Potential Gradient
Voltage V in KV KV/cm
1 0.5 cm
2 1.0cm
3 1.5cm
S No. gap spacing in cm Break down voltage V in KV Average break down Potential Gradient
Voltage V in KV KV/cm
1 0.5 cm
2 1.0cm
3 1.5cm
S No. gap spacing in cm Break down voltage V in KV Average break down Potential Gradient
Voltage V in KV KV/cm
1 0.5 cm
2 1.0cm
3 1.5cm
26
S G BALEKUNDRI INSTITUTE OF TECHNOLOGY, BELAGAVI -10
Department of Electrical & Electronics Engineering
Calculations:
Draw the flash over characteristics: gap in spacing v/s Potential gradient.
27
SWITCH
AC DC
CIRCUIT DIAGRAM:
EL
R L 10 MΩ D
- --- -
CONTROL 0 0 Square
PANEL + PLANE POINT
WITH C
REGULATOR R Square
230 V -- PLANE PLANE
230V ACS 50KV
50Hz.
HV Transformer
0- 230 V/ 50KV AC/70KV DC,
28
PROCEDURE:
1) Ensure that all the supply switches should be in OFF position.
2) Connect the circuit as shown in the circuit diagram.
3) Adjust sphere gap setting to 0.5 cm , come out from the H V Transformer room and close the door.
4) Now select the DC switch for measurement of HVDC.
5) Keeping the Panel board auto transformer in zero position, now switch ON the single phase supply.
6) Vary the auto transformer slowly till the flash over of sphere.
7) Repeat the procedure for 3- 4 set of readings for different sets of spheres gaps (0.5, 1.0 & 1.5 cm)
8) copy the readings of V from the panel voltmeter in Kv.
9) Repeat the same procedure for different electrode.
29
S No. Gap spacing in cm Break down voltage V in KV Average break down Potential Gradient
Voltage V in KV KV/cm
1 0.5 cm
2 1.0cm
3 1.5cm
S No. Gap spacing in cm Break down voltage V in KV Average break down Potential Gradient
Voltage V in KV KV/cm
1 0.5 cm
2 1.0cm
3 1.5cm
S No. Gap spacing in cm Break down voltage V in KV Average break down Potential Gradient
Voltage V in KV KV/cm
1 0.5 cm
2 1.0cm
3 1.5cm
S No. Gap spacing in cm Break down voltage V in KV Average break down Potential Gradient
Voltage V in KV KV/cm
1 0.5 cm
2 1.0cm
3 1.5cm
Calculations:
Average break down voltage
Potential gradient = ------------------------------------------ --------- kv/cm.
Gap spacing
Draw the flash over characteristics: graph in spacing v/s Potential gradient.
30
SWITCH
AC DC
CIRCUIT DIAGRAM:
EL
RL 10 MΩ
MEASURING
CONTROL 0 0 SPHERE GAP
PANEL
WITH RM S
REGULATOR 280MΩ d
230 V
230V ACS 50KV TO CONTROL PANEL
50Hz.
HV Transformer
0- 230/ 50KV, 70KV DC.
d = diameter of spheres 100 mm.
EL= H.V.Electrode
S = Spacing in cm.
RL= Current limiting resistor
RM= Measuring resistor
31
CAUTION
Every time the gap spacing has to be changed manually inside the room ( for sphere , point and
plane electrode etc.) Ensure that the mains are switched OFF, before entering the room. Always
discharge all the equipments using the grounding rod, before touching any equipment. This is
necessary to discharge any static charge on the conducting surfaces.
32
S No. Sphere gap Measured Peak Average Peak Std. Voltage from V1- V __
spacing in Voltage V in KV Voltage V in KV the Table Vo ( ISI) V1 =K x VO % Error= --------- x100
cm 10 cm Sphere V1
1 0.5 cm
2 1.0cm
3 1.5cm
Calculations:
Measurement of HVAC
With reference to gap spacing from table V0 = ------ KV.
Measure the Air Temperature t = ------ C0
V1= KV0
V1 - V
% Error = ----------- X100
V1
33
d 0.70 0.72 0.80 0.85 0.90 0.95 1.0 1.05 1.10 1.15
k 0.72 0.77 0.82 0.86 0.91 0.95 1.0 1.05 1.09 1.12
34
SWITCH
AC DC
CIRCUIT DIAGRAM:
EL
R L 10 MΩ D
-
A CONTROL 0 0
PANEL
WITH C
REGULATOR R
230 V
230V ACS 50KV
50Hz.
HV Transformer
0- 230/50KV AC, 70KV DC.
35
S No. Sphere gap Measured Peak Average Peak Std. Voltage from V1- V __
spacing in Voltage V in KV Voltage V in KV the Table Vo ( ISI) V1 =K x VO % Error= --------- x100
cm 10 cm Sphere V1
1 0.5 cm
2 1.0cm
3 1.5cm
Calculations:
Measurement of HVDC
With reference to gap spacing From table V0 = ------ KV.
Measure the Air Temperature t = ------ C0
V1= KV0
V1 - V
% Error = ----------- X100
V1
36
AIM: To determine the Breakdown strength of the given Transformer oil at a specified gap distance.
APPARATUS REQUIRED:
CIRCUIT DIAGRAM:
Transformer oil
H V Transformer Electrode
Jar
0 0
0-60Kv
60Kv
230V
230V 50 Hz ACS
1 - Phase Autotransformer
0-230V AC.
PROCEDURE:
37
V 1 +V 2 +V 3 +V4 +V5
Vav = ----------------------------------
5
38
Apparatus Required:
CIRCUIT DIAGRAM:
Isolation Transformer
-
0
0
0-30V
PROCEDURE:
1) The electrodes as well as the inside surface of the tank should be cleaned.
2) Parallel plate model is placed inside the electrolytic tank.
3) Clean water is poured into the electrolytic tank up to the tips of the plates
4) Now drawing sheet is fixed on the glass plate of the electrolytic tank.
5) Connections are made as per the circuit diagram and keep multimeter knob in the AC mode.
6) Switch ON the supply.
7) Keep the pantograph needle on any one of the electrodes, then applying a small voltage of 20 Volts
by using auto Transformer.
8)First trace both the plates by using pantograph then trace equipotential lines corresponding to
voltages of 3V, 6V, 9V, 12, 15,18 V. mark them on drawing sheet.
9) Now start to trace 3V equipotential line where appears and mark on the drawing sheet till end of
the linear points.
10) Repeat the procedure No. 8 for 6V, 9V, 12V, 15V & 18V.
39
Standard values:
Permittivity Ɛ0 = 8.854x10—12
Relative permittivity Ɛr = 80.37
m lxh
Cth = Ɛ0 Ɛr x ----- x ------ - - - - - - Farads
n d
m l’
CExpt. = Ɛ0 Ɛr x ----- x ------ x h -- - - - - Farads
n b
CExpt -- Cth
% Error = --------------- x 100 -------- %
CExpt