Sắp xếp cable suất
Sắp xếp cable suất
Revision
DANIELI VSC - VIETNAM STEEL
AUTOMATION CORPORATION 0391ES90E99101 00
y VIETNAM
Remarks
00 23/07/2003 Preliminary Issue / Valid for Erection Engineering ZanotA ZanotA CodarinL
Table of contents
1 REFERENCE STANDARDS 2
2 CALCULATION DATA 2
2.1 working voltage ........................................................................................................................................ 2
2.2 operating conditions ................................................................................................................................. 2
2.3 cables type ............................................................................................................................................... 2
2.4 installation methods.................................................................................................................................. 3
3 CORRECTION FACTOR CALCULATION 4
3.1 layed in embedded conduits..................................................................................................................... 4
3.2 layed on cable trays.................................................................................................................................. 4
4 LAYING CORRECTED VALUES OF CABLES CURRENT-CARRYING CAPACITIES 6
4.1 Tables “A” : M.V. and L.V. Cables Layed In Embedded Conduits............................................................ 6
4.1.1 Single Core Cables (One Circuit) ............................................................................................................. 6
4.1.2 Single Core Cables (N°2 Circuits) ............................................................................................................ 7
4.1.3 Single Core Cables (N°4 Circuits) ............................................................................................................ 8
4.2 Tables “B” : L.V. cables Layed In Embedded Conduits........................................................................... 9
4.2.1 Multicores Cables (One Circuit) ............................................................................................................... 9
4.2.2 Multicores Cables (N°4 Circuits) ............................................................................................................ 10
4.2.3 Multicores Cables (N°9 Or More Circuits) .............................................................................................. 11
4.3 Tables “C” : M.V. Cables Layed On Cable Trays .................................................................................. 12
4.3.1 M.V.Single Core Cables (N°2 Circuits) .................................................................................................. 12
4.3.2 M.V.Single Core Cables (N°4 Circuits) .................................................................................................. 12
4.4 Tables “D” : L.V. Cables Layed On Cable Trays ................................................................................... 13
4.4.1 Single core Cables (n°2 circuits) ............................................................................................................ 13
4.4.2 Single core Cables (N°4 Circuits)........................................................................................................... 14
4.4.3 Single core Cables (N°9 or more Circuits) ............................................................................................. 15
4.5 Table “E” : L.V. Cables Layed On Cable Trays ..................................................................................... 16
4.5.1 Multicore Cables (n°2 circuits) ............................................................................................................... 16
4.5.2 Multicore Cables (n°4 circuits) ............................................................................................................... 17
4.5.3 Multicore Cables (N°9 or more Circuits)................................................................................................. 18
5 VOLTAGE DROP CALCULATION 19
6 SHORT CIRCUIT CURRENT CARRYING CAPACITY 19
OVERVIEW
The present technical specification explains the criteria applied to calculate the size of M.V and L.V.
power cables to be layed in the cold rolling steel plant VSC in VIETNAM.
The main scope is to set up the derating factor to be used in the calculation of current carrying capacity
of power circuits.
1 REFERENCE STANDARDS
IEC Publications 60364-5-52 “Current carrying capacities” . Second edition.
2 CALCULATION DATA
M.V. single core cables layed in free air ,single layer,2d spaced, on ladder cable trays.
Cable trays route with max. 2 or 3 power cable trays (vertical space between trays = 300mm)
L.V. multicore or single core cables layed in free air, single layer, touching, on ladder type cable trays.
Cable trays route with max. 2 or 3 power cable trays (vertical space between trays = 300mm)
· Reduction factor for groups of one circuit single core cable or multicore cable
(ref. IEC std, sh. 91 Table A.52-17) : Kt = 1
· Reduction factor for groups of n°4 circuits single core cable or multi core cable
(ref. IEC std, sh. 91 Table A.52-17) : Kt = 0,65
· Reduction factor for groups of n°2 circuits single core cable or multicore cable single layer
on ladder cable tray
(ref. IEC std, sh. 91 table A.52-17) : Kt = 0,87
· Reduction factor for groups of n°4 circuits single core cable or multi core cable single layer
on ladder cable tray
(ref. IEC std, sh. 91 Table A.52-17) : Kt = 0,8
· Reduction factor for groups of n°9 circuits single core cable or multi core cable single layer
on ladder cable tray
(ref. IEC std, sh. 91 Table A.52-17) : Kt = 0,78
4.1 TABLES “A” : M.V. AND L.V. CABLES LAYED IN EMBEDDED CONDUITS
Ktot = 0.63
A1) M.V. AND L.V. SINGLE PHASE CIRCUIT ÅÅ (IEC 60364-5-52 sh. 65 tab. A.52-3 method D)
A2) M.V. AND L.V. THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 69 tab. A.52-5 method D)
Ktot = 0,50
A3) M.V. AND L.V. SINGLE PHASE CIRCUIT ÅÅ (IEC 60364-5-52 sh. 65 tab. A.52-3 method D)
A4) M.V. AND L.V. THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 69 tab. A.52-5 method D)
Ktot = 0,40
A5) M.V. AND L.V. SINGLE PHASE CIRCUIT ÅÅ (IEC 60364-5-52 sh. 65 tab. A.52-3 method D)
A6) M.V. AND L.V. THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 69 tab. A.52-5 method D)
Ktot = 0.67
B1) L.V. SINGLE PHASE CIRCUIT ÅÅ (IEC 60364-5-52 sh. 65 tab. A.52-3 col.D)
2.5 34 23
4 44 29
6 56 37
10 73 49
16 95 64
25 121 81
35 146 98
50 173 116
70 213 143
95 252 169
120 287 192
150 324 217
B2) L.V. THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 69 tab. A.52-5 col.D)
2.5 29 19
4 37 25
6 46 31
10 61 41
16 79 53
25 101 68
35 122 82
50 144 96
70 178 119
95 211 141
120 240 161
150 271 181
Ktot = 0,47
B3) L.V. SINGLE PHASE CIRCUIT ÅÅ (IEC 60364-5-52 sh. 65 tab. A.52-3 col.D)
2.5 34 16
4 44 21
6 56 26
10 73 34
16 95 45
25 121 57
35 146 69
50 173 81
70 213 100
95 252 118
120 287 135
150 324 152
B4) L.V. THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 69 tab. A.52-5 col.D)
2.5 29 14
4 37 17
6 46 22
10 61 29
16 79 37
25 101 48
35 122 57
50 144 68
70 178 84
95 211 99
120 240 113
150 271 127
Ktot = 0,34
B5) L.V. SINGLE PHASE CIRCUIT ÅÅ (IEC 60364-5-52 sh. 65 tab. A.52-3 col.D)
2.5 34 12
4 44 15
6 56 19
10 73 25
16 95 32
25 121 41
35 146 50
50 173 59
70 213 72
95 252 86
120 287 98
150 324 110
B6) L.V. THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 69 tab. A.52-5 col.D)
2.5 29 10
4 37 13
6 46 16
10 61 21
16 79 27
25 101 34
35 122 41
50 144 49
70 178 61
95 211 72
120 240 82
150 271 92
Ktot = 0.68
Ktot = 0.63
Ktot = 0.65
D1) L.V. SINGLE PHASE OR D.C. CIRCUIT ÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.F)
D2) L.V. THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.F)
Ktot = 0.60
D3) SINGLE PHASE OR D.C. CIRCUIT ÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.F)
D4) THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.F)
Ktot = 0.58
D5) SINGLE PHASE OR D.C. CIRCUIT ÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.F)
D6) THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.F)
Ktot = 0.53
E1) L.V. SINGLE PHASE CIRCUIT ÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.E)
2.5 36 19
4 49 26
6 63 33
10 86 46
16 115 61
25 149 79
35 185 98
50 225 119
70 289 153
95 352 187
E2) L.V. THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.E)
2.5 32 17
4 42 22
6 54 29
10 75 40
16 100 53
25 127 67
35 158 84
50 192 102
70 246 130
95 298 158
120 346 183
150 399 211
Ktot = 0.50
E3) L.V. SINGLE PHASE CIRCUIT ÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.E)
2.5 36 18
4 49 25
6 63 32
10 86 43
16 115 58
25 149 75
35 185 93
50 225 113
70 289 145
95 352 176
E4) L.V. THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.E)
2.5 32 16
4 42 21
6 54 27
10 75 38
16 100 50
25 127 64
35 158 79
50 192 96
70 246 123
95 298 149
120 346 173
150 399 200
Ktot = 0,49
E5) L.V. SINGLE PHASE CIRCUIT ÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.E)
2.5 36 17
4 49 24
6 63 31
10 86 42
16 115 56
25 149 73
35 185 91
50 225 110
70 289 142
95 352 172
E6) L.V. THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.E)
2.5 32 15
4 42 20
6 54 26
10 75 37
16 100 49
25 127 62
35 158 77
50 192 94
70 246 120
95 298 146
120 346 170
150 399 196
The Voltage drop is calculated within the allowed limit, for a lenght of power line up to 100 mt
by the following relation:
Where:
Vd = K(R cosj + X sen j)
L = Line lenght (m)
I = Current (A)
R = Line resistance (W/Km)
X = Line reactance
cosj = Power factor
K = 1,73 for three phase circuit
= 2 for single phase circuit
The cables are calculated for shor circuit withstanding by the following:
S ³(Icc x Öt) /K
Where :
2
S = Conductor cross section (mm )
lcc = Short circuit current (A)
t = Upstreem protection clarification time (assumed 0.5 sec.)
K = Cable type factor. For XLPE (250°) = 143