Document Nr.

Revision
DANIELI VSC - VIETNAM STEEL
AUTOMATION CORPORATION 0391ES90E99101 00

y VIETNAM

Job Contractual item DANIELI item


3910 80.41
Title

Electrical General Systems


Cable calculations
Cables Sizing
Approvals

Remarks

00 23/07/2003 Preliminary Issue / Valid for Erection Engineering ZanotA ZanotA CodarinL

Rev . Date Description Drawn Checked Approved


According to law Danieli Automation Spa considers this document to be a company secret and therefore prohibits any person to reproduce or disclose it in whole or part to third parties,
without specific written authorization of Danieli Automation Spa Management

Certified by OneDoc 0391ES90E99101 Rev.00-E 1/21 #10491


Electrical General Systems - Cable calculations - Cables Sizing
yDANIELIAUTOMATION REFERENCE DOCUMENTS LIST

Document Nr. Rev Title

0391EN90E99111 00 Electrical General Systems - Design guideline - Cables Technical Specification

Certified by OneDoc 0391ES90E99101 Rev.00-E 2/21 #10491


Electrical General Systems - Cable calculations - Cables Sizing
yDANIELIAUTOMATION 1

Table of contents

1 REFERENCE STANDARDS 2
2 CALCULATION DATA 2
2.1 working voltage ........................................................................................................................................ 2
2.2 operating conditions ................................................................................................................................. 2
2.3 cables type ............................................................................................................................................... 2
2.4 installation methods.................................................................................................................................. 3
3 CORRECTION FACTOR CALCULATION 4
3.1 layed in embedded conduits..................................................................................................................... 4
3.2 layed on cable trays.................................................................................................................................. 4
4 LAYING CORRECTED VALUES OF CABLES CURRENT-CARRYING CAPACITIES 6
4.1 Tables “A” : M.V. and L.V. Cables Layed In Embedded Conduits............................................................ 6
4.1.1 Single Core Cables (One Circuit) ............................................................................................................. 6
4.1.2 Single Core Cables (N°2 Circuits) ............................................................................................................ 7
4.1.3 Single Core Cables (N°4 Circuits) ............................................................................................................ 8
4.2 Tables “B” : L.V. cables Layed In Embedded Conduits........................................................................... 9
4.2.1 Multicores Cables (One Circuit) ............................................................................................................... 9
4.2.2 Multicores Cables (N°4 Circuits) ............................................................................................................ 10
4.2.3 Multicores Cables (N°9 Or More Circuits) .............................................................................................. 11
4.3 Tables “C” : M.V. Cables Layed On Cable Trays .................................................................................. 12
4.3.1 M.V.Single Core Cables (N°2 Circuits) .................................................................................................. 12
4.3.2 M.V.Single Core Cables (N°4 Circuits) .................................................................................................. 12
4.4 Tables “D” : L.V. Cables Layed On Cable Trays ................................................................................... 13
4.4.1 Single core Cables (n°2 circuits) ............................................................................................................ 13
4.4.2 Single core Cables (N°4 Circuits)........................................................................................................... 14
4.4.3 Single core Cables (N°9 or more Circuits) ............................................................................................. 15
4.5 Table “E” : L.V. Cables Layed On Cable Trays ..................................................................................... 16
4.5.1 Multicore Cables (n°2 circuits) ............................................................................................................... 16
4.5.2 Multicore Cables (n°4 circuits) ............................................................................................................... 17
4.5.3 Multicore Cables (N°9 or more Circuits)................................................................................................. 18
5 VOLTAGE DROP CALCULATION 19
6 SHORT CIRCUIT CURRENT CARRYING CAPACITY 19

Certified by OneDoc 0391ES90E99101 Rev.00-E 3/21 #10491


Electrical General Systems - Cable calculations - Cables Sizing
yDANIELIAUTOMATION 2

OVERVIEW
The present technical specification explains the criteria applied to calculate the size of M.V and L.V.
power cables to be layed in the cold rolling steel plant VSC in VIETNAM.
The main scope is to set up the derating factor to be used in the calculation of current carrying capacity
of power circuits.

1 REFERENCE STANDARDS
IEC Publications 60364-5-52 “Current carrying capacities” . Second edition.
2 CALCULATION DATA

2.1 WORKING VOLTAGE

- Medium Voltage Network 3Ph 22kV ±5% Frequency 50 Hz ± 2%


- Short-circuit current up to 1 sec M.V side 20 kA(for 22kV)
- Controls & protection circuits 110VDC
- Low Voltage 3Ph 380V ±5% Frequency 50 Hz ± 2%
- Short-circuit current up to 1 s 50kA
- Auxiliary controls 1Ph 220VAC
- Controls & protection circuits 220VAC
- AC Motors 3Ph 380VAC ±10%
- AUX DRIVES 3Ph 690VAC ±10% Frequency 50 Hz ± 2%
3Ph 380VAC ±10% Frequency 50 Hz ± 2%
- A.C. DRIVES WITH M.V. INV. 3Ph 3150VAC ±10% Frequency 50 Hz ± 2%
- Lighting 1Ph 220VAC
- Auxiliary controls 1Ph 220VAC
2.2 OPERATING CONDITIONS
- Max. ambient temperature : + 40°C (Switchboard room)
- Min. ambient temperature : + 20°C (Switchboard room)
- Max. ambient temperature : + 45°C (Field)
- Min. ambient temperature : + 20°C (Field)
- Humidity : >10 % <90 % (not condensing)
- Altitude : < 1000 m A.S.L.
- Climate : Tropical
- Pollution : Metallurgical
2.3 CABLES TYPE

- M.V. rated voltage Uo/U : 18/30KV


- System category : B
- Conductor : thinned copper stranded
- Insulation : HEPR G7 OR XLPE
- Sheat : PVC
- Rated workingTemperature : 90°C
- Max Short circuit Temperature : 250°C
- L.V. rated voltage Uo/U : 0,6/1KV
- Test voltage : 4KV in c.a.
- Conductor : thinned copper stranded
- Insulation : HEPR G7 OR XLPE
- Sheat : PVC
- Rated workingTemperature : 90°C
- Max Short circuit Temperature : 250°C
2
Note: M.V Cable Single minimum core section 1x95 mm
2
L.V. Not shielded max multicore cable cross section = 95mm

Certified by OneDoc 0391ES90E99101 Rev.00-E 4/21 #10491


Electrical General Systems - Cable calculations - Cables Sizing
yDANIELIAUTOMATION 3

2.4 INSTALLATION METHODS

M.V. single core cables layed in free air ,single layer,2d spaced, on ladder cable trays.
Cable trays route with max. 2 or 3 power cable trays (vertical space between trays = 300mm)

L.V. multicore or single core cables layed in free air, single layer, touching, on ladder type cable trays.
Cable trays route with max. 2 or 3 power cable trays (vertical space between trays = 300mm)

Certified by OneDoc 0391ES90E99101 Rev.00-E 5/21 #10491


Electrical General Systems - Cable calculations - Cables Sizing
yDANIELIAUTOMATION 4

3 CORRECTION FACTOR CALCULATION

Ref. IEC 60364-5-52 Publication

3.1 LAYED IN EMBEDDED CONDUITS

· Reduction factor for max ground temperature +35°C


(ref. IEC std, sh. 89 Table A.52-15) : Kt = 0,89

· Reduction factor for groups of one circuit single core cable or multicore cable
(ref. IEC std, sh. 91 Table A.52-17) : Kt = 1

· Reduction factor for groups of n°2 circuits single core cable


(ref. IEC std, sh. 91 Table A.52-17) : Kt = 0,80

· Reduction factor for groups of n°4 circuits single core cable or multi core cable
(ref. IEC std, sh. 91 Table A.52-17) : Kt = 0,65

· Reduction factor for groups of n°9 circuits multi core cable


(ref. IEC std, sh. 91 Table A.52-17) : Kt = 0,50

· Reduction factor for laying method:


* single core cables : Kpu = 0,70
(ref. IEC std, sh. 95 Table A.52-19-B)
* multicore cables : Kpm = 0,75
(ref. IEC std, sh. 95 Table A.52-19-A)

· Total reduction factor Ktot:


* single core cables (n°1 circuit) : Ktot = 0,89x1x 0,70 @ 0,63
* single core cables (n°2 circuits) : Ktot = 0,89x0,8x 0,70 @ 0,50
* single core cables (n°4 circuits) : Ktot = 0,89x0,65x 0,70 @ 0,40
* multicore cables (n°1 circuit) : Ktot = 0,89x1 x 0,75 @ 0,67
* multicore cables (n°4 circuits) : Ktot = 0,89x0,65x 0,75 @ 0,47
* multicore cables (n°9 circuits) : Ktot = 0,89x0,50x 0,75 @ 0,34

3.2 LAYED ON CABLE TRAYS

We consider an air overtemperature, due to the machines working.

· Reduction factor for max ambient air temperature +45°C


(ref. IEC std, sh. 87 – table A.52-14) : Kt = 0,87

· Reduction factor for groups of n°2 circuits single core cable or multicore cable single layer
on ladder cable tray
(ref. IEC std, sh. 91 table A.52-17) : Kt = 0,87

· Reduction factor for groups of n°4 circuits single core cable or multi core cable single layer
on ladder cable tray
(ref. IEC std, sh. 91 Table A.52-17) : Kt = 0,8

· Reduction factor for groups of n°9 circuits single core cable or multi core cable single layer
on ladder cable tray
(ref. IEC std, sh. 91 Table A.52-17) : Kt = 0,78

Certified by OneDoc 0391ES90E99101 Rev.00-E 6/21 #10491


Electrical General Systems - Cable calculations - Cables Sizing
yDANIELIAUTOMATION 5

· Reduction factor for laying method:


M.V. single core cables spaced 2d . Trefoil or Horizontal
formation. : Kpu = 0,90
(ref. IEC std, sh. 99, Table. A.52-21 34)
L.V. single core cables, touching. Horizontal formation.
(ref. IEC std, sh. 99, Table. A.52-21 34) : Kpu = 0,86
single core cables, touching. Three cables in trefoil
formation. (ref. IEC std, sh. 99, Table. A.52-21 : Kpu = 0,86
34)
multicore cables, touching: (ref. IEC std, sh 97, Table.A.
52-20 34) : Kpm = 0,73

· Total reduction factor Ktot:


M.V.single core cables n°2 circuits (Three : Ktot = 0,87x0,87x0,90 @ 0,68
cables in trefoil formation).
L.V. single core cables , touching. n°2 circuits : Ktot = 0,87x0,87x0,86 @ 0,65
(Horizontal formation., or Three cables in trefoil
formation.)
L.V. multicore cables n°2 circuits : Ktot = 0,87x0,87x 0,73 @ 0,53

M.V.single core cables n°4 circuits (Three : Ktot = 0,87x0,80x0,90 @ 0,63


cables in trefoil formation).
L.V. single core cables , touching. n°4 circuits : Ktot = 0,87x0,80x0,86 @ 0,60
(Horizontal formation., or Three cables in trefoil
formation.)
L.V. single core cables , touching. n°9 circuits : Ktot = 0,87x0,78x0,86 @ 0,58
(Horizontal formation., or Three cables in trefoil
formation.)
L.V. multicore cables n°4 circuits : Ktot = 0,87x0,80x 0,73 @ 0,50
L.V. multicore cables n°9 circuits : Ktot = 0,87x0,78x 0,73 @ 0,49

Certified by OneDoc 0391ES90E99101 Rev.00-E 7/21 #10491


Electrical General Systems - Cable calculations - Cables Sizing
yDANIELIAUTOMATION 6

4 LAYING CORRECTED VALUES OF CABLES CURRENT-CARRYING CAPACITIES

4.1 TABLES “A” : M.V. AND L.V. CABLES LAYED IN EMBEDDED CONDUITS

4.1.1 SINGLE CORE CABLES (ONE CIRCUIT)

Ktot = 0.63

A1) M.V. AND L.V. SINGLE PHASE CIRCUIT ÅÅ (IEC 60364-5-52 sh. 65 tab. A.52-3 method D)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR AMBIENT
TEMP.20°C IN GROUND
2
mm A A
50 173 109
70 213 134
95 252 159
120 287 181
150 324 204
185 363 229
240 419 264
300 474 299

A2) M.V. AND L.V. THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 69 tab. A.52-5 method D)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR
AMBIENT TEMP.20°C
IN GROUND
2
mm A A
50 144 91
70 178 112
95 211 133
120 240 151
150 271 171
185 304 192
240 351 221
300 396 249

Certified by OneDoc 0391ES90E99101 Rev.00-E 8/21 #10491


Electrical General Systems - Cable calculations - Cables Sizing
yDANIELIAUTOMATION 7

4.1.2 SINGLE CORE CABLES (N°2 CIRCUITS)

Ktot = 0,50

A3) M.V. AND L.V. SINGLE PHASE CIRCUIT ÅÅ (IEC 60364-5-52 sh. 65 tab. A.52-3 method D)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR AMBIENT
TEMP.20°C IN GROUND
2
mm A A
50 173 87
70 213 107
95 252 126
120 287 144
150 324 162
185 363 182
240 419 210
300 474 237

A4) M.V. AND L.V. THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 69 tab. A.52-5 method D)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR
AMBIENT TEMP.20°C
IN GROUND
2
mm A A
50 144 72
70 178 89
95 211 106
120 240 120
150 271 136
185 304 152
240 351 176
300 396 198

Certified by OneDoc 0391ES90E99101 Rev.00-E 9/21 #10491


Electrical General Systems - Cable calculations - Cables Sizing
yDANIELIAUTOMATION 8

4.1.3 SINGLE CORE CABLES (N°4 CIRCUITS)

Ktot = 0,40

A5) M.V. AND L.V. SINGLE PHASE CIRCUIT ÅÅ (IEC 60364-5-52 sh. 65 tab. A.52-3 method D)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR AMBIENT
TEMP.20°C IN GROUND
2
mm A A
50 173 69
70 213 85
95 252 101
120 287 115
150 324 130
185 363 145
240 419 168
300 474 190

A6) M.V. AND L.V. THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 69 tab. A.52-5 method D)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR
AMBIENT TEMP.20°C
IN GROUND
2
mm A A
50 144 58
70 178 71
95 211 84
120 240 96
150 271 108
185 304 122
240 351 140
300 396 158

Certified by OneDoc 0391ES90E99101 Rev.00-E 10/21 #10491


Electrical General Systems - Cable calculations - Cables Sizing
yDANIELIAUTOMATION 9

4.2 TABLES “B” : L.V. CABLES LAYED IN EMBEDDED CONDUITS

4.2.1 MULTICORES CABLES (ONE CIRCUIT)

Ktot = 0.67

B1) L.V. SINGLE PHASE CIRCUIT ÅÅ (IEC 60364-5-52 sh. 65 tab. A.52-3 col.D)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR AMBIENT
TEMP.20°C IN GROUND
2
mm A A

2.5 34 23
4 44 29
6 56 37
10 73 49
16 95 64
25 121 81
35 146 98
50 173 116
70 213 143
95 252 169
120 287 192
150 324 217

B2) L.V. THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 69 tab. A.52-5 col.D)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE
IN AMPS FOR AMBIENT
TEMP.20°C IN GROUND
2
mm A A

2.5 29 19
4 37 25
6 46 31
10 61 41
16 79 53
25 101 68
35 122 82
50 144 96
70 178 119
95 211 141
120 240 161
150 271 181

Certified by OneDoc 0391ES90E99101 Rev.00-E 11/21 #10491


Electrical General Systems - Cable calculations - Cables Sizing
yDANIELIAUTOMATION 10

4.2.2 MULTICORES CABLES (N°4 CIRCUITS)

Ktot = 0,47

B3) L.V. SINGLE PHASE CIRCUIT ÅÅ (IEC 60364-5-52 sh. 65 tab. A.52-3 col.D)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR AMBIENT
TEMP.20°C IN GROUND
2
mm A A

2.5 34 16
4 44 21
6 56 26
10 73 34
16 95 45
25 121 57
35 146 69
50 173 81
70 213 100
95 252 118
120 287 135
150 324 152

B4) L.V. THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 69 tab. A.52-5 col.D)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE
IN AMPS FOR AMBIENT
TEMP.20°C IN GROUND
2
mm A A

2.5 29 14
4 37 17
6 46 22
10 61 29
16 79 37
25 101 48
35 122 57
50 144 68
70 178 84
95 211 99
120 240 113
150 271 127

Certified by OneDoc 0391ES90E99101 Rev.00-E 12/21 #10491


Electrical General Systems - Cable calculations - Cables Sizing
yDANIELIAUTOMATION 11

4.2.3 MULTICORES CABLES (N°9 OR MORE CIRCUITS)

Ktot = 0,34

B5) L.V. SINGLE PHASE CIRCUIT ÅÅ (IEC 60364-5-52 sh. 65 tab. A.52-3 col.D)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR AMBIENT
TEMP.20°C IN GROUND
2
mm A A

2.5 34 12
4 44 15
6 56 19
10 73 25
16 95 32
25 121 41
35 146 50
50 173 59
70 213 72
95 252 86
120 287 98
150 324 110

B6) L.V. THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 69 tab. A.52-5 col.D)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE
IN AMPS FOR AMBIENT
TEMP.20°C IN GROUND
2
mm A A

2.5 29 10
4 37 13
6 46 16
10 61 21
16 79 27
25 101 34
35 122 41
50 144 49
70 178 61
95 211 72
120 240 82
150 271 92

Certified by OneDoc 0391ES90E99101 Rev.00-E 13/21 #10491


Electrical General Systems - Cable calculations - Cables Sizing
yDANIELIAUTOMATION 12

4.3 TABLES “C” : M.V. CABLES LAYED ON CABLE TRAYS

4.3.1 M.V.SINGLE CORE CABLES (N°2 CIRCUITS)

Ktot = 0.68

C1) THREE PHASE CIRCUIT (IEC 60364-5-52 sh. 83 tab.A.52-12 col.G)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR AMBIENT
TEMP.30°C
2
mm A A
70 268 182
95 328 223
120 383 260
150 444 302
185 510 347
240 607 413

4.3.2 M.V.SINGLE CORE CABLES (N°4 CIRCUITS)

Ktot = 0.63

C2) THREE PHASE CIRCUIT (IEC 60364-5-52 sh. 83 tab.A.52-12 col.G)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR AMBIENT
TEMP.30°C
2
mm A A
70 268 169
95 328 207
120 383 241
150 444 280
185 510 321
240 607 382

Certified by OneDoc 0391ES90E99101 Rev.00-E 14/21 #10491


Electrical General Systems - Cable calculations - Cables Sizing
yDANIELIAUTOMATION 13

4.4 TABLES “D” : L.V. CABLES LAYED ON CABLE TRAYS

4.4.1 SINGLE CORE CABLES (N°2 CIRCUITS)

Ktot = 0.65

D1) L.V. SINGLE PHASE OR D.C. CIRCUIT ÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.F)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR AMBIENT
TEMP.30°C
2
mm A A
50 242 157
70 310 201
95 377 245
120 437 284
150 504 328
185 575 374
240 679 441
300 783 509

D2) L.V. THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.F)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR AMBIENT
TEMP.30°C
2
mm A A
50 207 135
70 268 174
95 328 213
120 383 249
150 444 289
185 510 331
240 607 394
300 703 457

Certified by OneDoc 0391ES90E99101 Rev.00-E 15/21 #10491


Electrical General Systems - Cable calculations - Cables Sizing
yDANIELIAUTOMATION 14

4.4.2 SINGLE CORE CABLES (N°4 CIRCUITS)

Ktot = 0.60

D3) SINGLE PHASE OR D.C. CIRCUIT ÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.F)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR AMBIENT
TEMP.30°C
2
mm A A
50 242 145
70 310 186
95 377 226
120 437 262
150 504 302
185 575 345
240 679 407
300 783 470

D4) THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.F)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR AMBIENT
TEMP.30°C
2
mm A A
50 207 124
70 268 161
95 328 197
120 383 230
150 444 266
185 510 306
240 607 364
300 703 422

Certified by OneDoc 0391ES90E99101 Rev.00-E 16/21 #10491


Electrical General Systems - Cable calculations - Cables Sizing
yDANIELIAUTOMATION 15

4.4.3 SINGLE CORE CABLES (N°9 OR MORE CIRCUITS)

Ktot = 0.58

D5) SINGLE PHASE OR D.C. CIRCUIT ÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.F)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR AMBIENT
TEMP.30°C
2
mm A A
50 242 140
70 310 180
95 377 219
120 437 253
150 504 292
185 575 333
240 679 394
300 783 454

D6) THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.F)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR AMBIENT
TEMP.30°C
2
mm A A
50 207 120
70 268 155
95 328 190
120 383 222
150 444 258
185 510 296
240 607 352
300 703 408

Certified by OneDoc 0391ES90E99101 Rev.00-E 17/21 #10491


Electrical General Systems - Cable calculations - Cables Sizing
yDANIELIAUTOMATION 16

4.5 TABLE “E” : L.V. CABLES LAYED ON CABLE TRAYS

4.5.1 MULTICORE CABLES (N°2 CIRCUITS)

Ktot = 0.53

E1) L.V. SINGLE PHASE CIRCUIT ÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.E)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR AMBIENT
TEMP.30°C
2
mm A A

2.5 36 19
4 49 26
6 63 33
10 86 46
16 115 61
25 149 79
35 185 98
50 225 119
70 289 153
95 352 187

E2) L.V. THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.E)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR AMBIENT
TEMP.30°C
2
mm A A

2.5 32 17
4 42 22
6 54 29
10 75 40
16 100 53
25 127 67
35 158 84
50 192 102
70 246 130
95 298 158
120 346 183
150 399 211

Certified by OneDoc 0391ES90E99101 Rev.00-E 18/21 #10491


Electrical General Systems - Cable calculations - Cables Sizing
yDANIELIAUTOMATION 17

4.5.2 MULTICORE CABLES (N°4 CIRCUITS)

Ktot = 0.50

E3) L.V. SINGLE PHASE CIRCUIT ÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.E)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR AMBIENT
TEMP.30°C
2
mm A A

2.5 36 18
4 49 25
6 63 32
10 86 43
16 115 58
25 149 75
35 185 93
50 225 113
70 289 145
95 352 176

E4) L.V. THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.E)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR AMBIENT
TEMP.30°C
2
mm A A

2.5 32 16
4 42 21
6 54 27
10 75 38
16 100 50
25 127 64
35 158 79
50 192 96
70 246 123
95 298 149
120 346 173
150 399 200

Certified by OneDoc 0391ES90E99101 Rev.00-E 19/21 #10491


Electrical General Systems - Cable calculations - Cables Sizing
yDANIELIAUTOMATION 18

4.5.3 MULTICORE CABLES (N°9 OR MORE CIRCUITS)

Ktot = 0,49

E5) L.V. SINGLE PHASE CIRCUIT ÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.E)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR AMBIENT
TEMP.30°C
2
mm A A

2.5 36 17
4 49 24
6 63 31
10 86 42
16 115 56
25 149 73
35 185 91
50 225 110
70 289 142
95 352 172

E6) L.V. THREE PHASE CIRCUIT ÅÅÅ (IEC 60364-5-52 sh. 83 tab. A.52-12 col.E)

SECT. NOMINAL CURRENT CORRECTED


CARRYING CAPACITY VALUE AMPS
IN AMPS FOR AMBIENT
TEMP.30°C
2
mm A A

2.5 32 15
4 42 20
6 54 26
10 75 37
16 100 49
25 127 62
35 158 77
50 192 94
70 246 120
95 298 146
120 346 170
150 399 196

Certified by OneDoc 0391ES90E99101 Rev.00-E 20/21 #10491


Electrical General Systems - Cable calculations - Cables Sizing
yDANIELIAUTOMATION 19

5 VOLTAGE DROP CALCULATION

The Voltage drop is calculated within the allowed limit, for a lenght of power line up to 100 mt
by the following relation:

DV = Vd x I x L/1000 DV% = DV/V x 100

Where:
Vd = K(R cosj + X sen j)
L = Line lenght (m)
I = Current (A)
R = Line resistance (W/Km)
X = Line reactance
cosj = Power factor
K = 1,73 for three phase circuit
= 2 for single phase circuit

The above is valable for DC also with : cosj =1 and sen j = 0

DC Max voltage drop allowable = 2%


AC Max voltage drop allowable = 5%

6 SHORT CIRCUIT CURRENT CARRYING CAPACITY

The cables are calculated for shor circuit withstanding by the following:
S ³(Icc x Öt) /K

Where :
2
S = Conductor cross section (mm )
lcc = Short circuit current (A)
t = Upstreem protection clarification time (assumed 0.5 sec.)
K = Cable type factor. For XLPE (250°) = 143

Certified by OneDoc 0391ES90E99101 Rev.00-E 21/21 #10491