MAHAGENCO - BHUSAWAL TPS 1 X 660 MW UNIT-6

Comments on Document/Drawing.- Single Line Diagram-Turbine Valve MCC #6KB


Drawing no: EP-4-SL-18001-009 Rev 02

SL. No. DCPL/MahaGenco Comments dtd 09.04.2021 BHEL reply DCPL/MahaGenco Comments dtd 20.06.2021 BHEL reply

A General Comments
BHEL to submit bus bar sizing calculation (thermal & short circuit) for Document approved in CAT-II Noted.
1 approval. Refer : EP-4-BB-18001-001
BHEL to confirm the make of all electrical components shall be from
2 Approved Mahagenco vendor list. Noted & same is mentioned in BOM Noted.

B Load List- 6KB

Load data has been furnished by respective process


group in line with their process
requirement/document/drawing. Also,
completeness & correctness of the feeder list till
Please submit the document in standard nameplate with proper document
1 no. project handover is BHEL's responsibility. Any Noted.
change in feeder rating, quantity, addition of feeder
shall be taken care by BHEL.
Refer request letter sent to Mahagenco after
discussion with Mahagenco.

BHEL PEM to ensure that quatity & rating of outgoing feeder considered are Refer reply at B.1
2 as per requirement indicated in Turbine P& ID.

As per MoM dated 23.02.2021, 10 % spare feeder of each type of feeder


shall be provided. Accordingly, M/s BHEL shall revise drawings mentioned at
3 10% spare of each type provided. Noted.
Sr.no. 2 above & also confirm that it will be incorporated in subject load
list/drawings without any financial implication to MAHAGENCO.

C Single Line Diagram

1 Tag no & kW rating of actuator of each outgoing feeder shall be indicated. Noted & revised. Noted.
BHEL confirms the selection of SFU & fuse for short
Noted. BHEL PED to select the rating of fuse circuit protection.
compitable to FLC of actuator motor. BHEL PEM to
BHEL to ensure that the rating of fuse provided are compitible with the down share data of Auma actuator. As this fuse will act as
2 stream contactor & OLR relau provided in integral actuator. BHEL confirms short circuit protection for actuator motor,
improper selector of fuse will damage the starter &
motor in the acutator.

As per MoM dated 23.02.2021, 10 % spare feeder of each type of feeder


shall be provided. Accordingly, M/s BHEL shall revise drawings mentioned at 10% spare of each type provided. Noted.
3 Sr.no. 2 above & also confirm that it will be incorporated in subject load
list/drawings without any financial implication to MAHAGENCO.

Board length shall be accomodated within layout to


BHEL PEM to ensure the no. of feeder can be accomodated within the space the extent possible. Pls note that 6kB board has Noted.
4 allocated for the panel.
already been accomodated in layout.

Additional comments

Cable size shall be selected as per Bid spec. Vol.IVA,


Sec8, Annexure-B, Module selection. BHEL confirms

Completeness of BOM with respect to approved SLD BHEL confirms


shall be M/ BHEL's repsonsibility.
DCPL/ MAHAGENCO remarks dated
29.06.2021

BHEL to ensure that if required, correct rating of


fuse shall be taken take at site before
commissioing.

As per Bid spec. Vol.IVA, Sec8, Annexure-B,


Module selection, feeders with motor rating 11.1
kW-29.9kW shall be 35 sq.mm. Pl. correct.

Noted.