Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Pub 50256

Revision A

Cutler-Hammer Intelligent Technology ( )


Instructions for Soft Starter Catalog Nos. T801T and T801V

The IT. Soft Starter features an electronic motor over- NOTE: Short circuit protection must be applied on the
load protection feature. This is intended to protect the line side of this soft starter.
motor and power wiring against overheating caused by
excessive current for extended periods of time. Trip current rating is fixed to 100% of the unit’s rated
current.
OVLD 5 10 20 30 Thermal memory is incorporated to accurately monitor
TRIP TRIP motor operating temperature. Ambient temperature does
CLASS not affect soft starter function within its operating limits.
B The default overload trip class is set to Class
C
Frame Catalog Max Value of Adjustment Settings (Amps)
30. This setting determines the time to trip, Size Number Current
A B C D
based on the severity of the overload condi-
T801T18N3D 180 180 180 180 180
A FLA D tion. 200mm 240 240 240 240 240
T801T24N3D
T801T T801T30N3D 304 304 304 304 304
T801V36N3D 360 360 360 360 360
AUTO/MANUAL RESET T801V42N3D 420 420 420 420 420
290mm T801V50N3D 500 500 500 500 500
Select auto or manual reset on the Control Interface T801V T801V65N3D 650 650 650 650 650
Module. T801V72N3D 720 720 720 720 720
T801V85N3D 850 850 850 850 850
When a fault is present, the auto-reset will attempt to
reset the fault every 2.5 seconds. If the fault is clear,
the system resets the fault(s), the soft starter is ready POWER WIRING
for use, and may be restarted by selecting “Run 1” No. of
Frame Lug Kit No. of Wire Sizes Torques
(assuming power is present). Size Options Conductors 75° C only Req’d. Kits
Req’d.
NOTE: The motor does NOT automatically restart after 4/0 - 500 MCM 28.2 N-m
a fault is reset. 200mm EML23 1 2
107 - 240mm (250 LB-IN)
4/0 - 500 MCM 28.2 N-m
NOTICE/AVIS EML24 2 2
107 - 150mm (250 LB-IN)
T801T 2
Automatic reset is not intended for two-wire control EML25 1
2/0 - 300 MCM
2
25.4 N-m
devices. 70 - 150mm (225 LB-IN)

Ce dispositif de reenclenchement automatique ne 2/0 - 300 MCM 25.4 N-m


EML26 2 2
70 - 150mm (225 LB-IN)
convient pas aux commandes a deux conducteurs.
4/0 - 500 MCM 28.2 N-m
290mm EML28 2 2
107 - 240mm (250 LB-IN)
12-pin terminal connection wiring capacity and torque
4/0 - 500 MCM 28.2 N-m
requirements for the control wiring: EML30 4
107 - 240mm
2
(250 LB-IN)
T801V 2
CONTROL WIRING 4/0 - 500 MCM 28.2 N-m
EML32 6* 2
107 - 240mm (250 LB-IN)
Number of
Wire Size Conductors Torque 2/0 - 300 MCM 25.4 N-m
EML33 4 2
70 - 150mm (225 LB-IN)
2
0.33 - 2.5mm 2 0.4 N-m (3.5 LB-IN)
(#22 - #14 AWG) * Requires special lug cover.
4.0mm 2
0.4 N-m (3.5 LB-IN) Check with EATON Cutler-Hammer for availability.
1
(#12 AWG)
MOV KITS
CONTROL CIRCUIT FUSEHOLDER KIT EMT40, 600V (max) MOV
Catalog Number Fuse Type for T801T and T801V Soft Start (Panel Mounted)
C320FBR Class CC
C-H 24V POWER SUPPLY KITS
SHORT CIRCUIT RATINGS Catalog Steady State Inrush Input
Number Wattage Wattage Voltage
Short Circuit Rating
Soft Starter Size PSS55A 55W 250W 115VAC
240V 480V 600V
PSS55B 55W 250W 230VAC
T801T (200mm) 18KA 18KA 18KA
T801V (290mm) 42KA 42KA 42KA PSS55C 55W 250W 360 - 480VAC

Effective 10/02

You might also like