171910 (SHEET 02 OF 09)

CONFIDENTIAL AND PROPRIETARY INFORMATION


STEP - 1 CHECK OPENINGS STEP - 4 FRAME ASSEMBLY STEP - 4 FRAME ASSEMBLY KAWNEER COMPANY INC.
THESE DRAWINGS ARE THE SOLE AND EXCLUSIVE PROPERTY OF KAWNEER AND CONTAIN
ELEVATIONS AND SLABS MUST BE WITHIN SENSITIVE, PRIVILEGED OR CONFIDENTIAL INFORMATION WHICH MAY BE USED ONLY FOR ITS
ATTACH ANCHORS TO MULLIONS WHERE APPLICABLE.
BENEFIT. THE DISCLOSURE OF THESE DRAWINGS TO UNAUTHORIZED PERSONS IS STRICTLY
ADJUSTMENT OF ANCHORING SYSTEM. SEE PROHIBITED. THIS DOCUMENT AND ALL COPIES MUST BE RETURNED UPON DEMAND.
APPROVED SHOP DRAWINGS FOR ALLOWABLE ANCHOR PREP MAY BE FABRICATED IN THE FIELD OR COPYRIGHT KAWNEER COMPANY, INC., 2011
ADJUSTMENT. FACTORY. CONSULT APPROVED SHOP DRAWINGS FOR
CORRECT METHOD.
ANCHORING SURFACES OF PERIMETER STEP - 5 INSTALL 162-310
CONSTRUCTION MUST BE LEVEL AND PLUMB STANDARD ANCHOR PREP IS THRU-BOLTED AT
WITHIN THE ADJUSTMENT LIMITS OF THE HEAD, INTERMEDIATE VERTICALS AND TAPPING PLATES ARE THERMAL BREAK
SILL AND JAMB. SEE APPROVED SHOP DRAWINGS USED AT JAMB VERTICALS. REFER TO APPROVED SHOP
FOR ALLOWABLE ADJUSTMENT. DRAWINGS FOR CORRECT METHOD.

WHEN WELDING ANCHORS, PROTECT INSTALLED GLASS


STEP - 2 LAY OUT ANCHOR AND AND METAL FROM WELD SPLATTER.

MULLION CENTERLINES
027-477 SEPARATOR
BETWEEN ANCHOR
USE WALL LINES ESTABLISHED BY THE GENERAL
AND MULLION
CONTRACTOR. ON EACH FLOOR LAY OUT A HEAD/SILL SHEAR BLOCK/ANCHOR
REFERENCE LINE TO ESTABLISH IN AND OUT WALL WHERE APPLICABLE AND SHOWN BELOW.
LOCATIONS. 162-310
162-314 6" & 6-3/4" SYSTEM AT JAMBS THERMAL
USE COLUMN CENTER LINES ESTABLISHED BY THE 162-315 7-1/2" & 8-1/4" SYSTEM AT JAMBS BREAK
GENERAL CONTRACTOR. ON EACH FLOOR LAY OUT 162-342 6" & 6-3/4" SYSTEM AT MULLIONS
MULLION CENTER LINES AND ANCHOR CENTER 162-343 7-1/2" & 8-1/4" SYSTEM AT MULLIONS
THERMAL BREAK
LINES. TO BE SAME
STRUCTURAL INTEGRITY OF ANCHOR AND
LENGTH AS
FASTENERS MUST BE CHECKED BY FACTORY
VERTICAL
ENGINEERING.
WELD PLATE MULLIONS

SIZE AND SPACING THERMAL BREAK


ANCHOR FASTENER TO BE 1/4" SHORT OPTION TO INSTALL THERMAL
OF WELD PER APPROVED SHOP DRAWINGS LOCATIONS PER BREAK AFTER VERTICALS AND
AT EACH END OF
C/L OF MULLION APPROVED SHOP HORIZONTALS ARE INSTALLED
HORIZONTALS
DRAWINGS
DO NOT OVER TIGHTEN ANCHOR CONNECTIONS.
TIGHTEN TO A "SNUG TIGHT" POSITION WITH
EXTERIOR PARTS BROUGHT INTO GOOD CONTACT. SHEAR BLOCK/ANCHOR INSTALL HEAD AND SILL END CAPS WHERE APPLICABLE
FACE OF BE SURE ANY SPRING TYPE LOCK WASHERS ARE 171309 1" FRAMING
BEAM OR COMPRESSED. THEN TIGHTEN APPROXIMATELY 128-396 SCREWS 171308 1-3/4" FRAMING
FLOOR SLAB 1/2 MORE TURN. #12 x 7/16" SET IN SEALANT
PAN HEAD TYPE B

VARIES
WITH JOB TYPICAL
CONDITIONS MULLION
ATTACH SHEAR BLOCKS.

STEP - 5 INSTALL 162-310


TYPICAL INTERMEDIATE SHEAR BLOCKS
162-377 6" & 6-3/4" SYSTEM
THERMAL BREAK
SEE APPROVED SHOP
162-378 7-1/2" & 8-1/4" SYSTEM
DRAWINGS FOR
ANCHOR LAYOUTS

DO NOT
STRETCH WHEN
STEP - 3 INSTALL PRESET REMOVING
HEAD AND SILL SHEAR BLOCKS FROM COIL
ANCHORS IF 162-331 6" & 6-3/4" SYSTEM AND CARTON
APPLICABLE 162-332 7-1/2" & 8-1/4" SYSTEM
1600UT SYSTEM 1
INSTALLATION
USING LOCATION LINES PREVIOUSLY DO NOT
ESTABLISHED INSTALL PRESET ANCHORS IN STRETCH
INSTRUCTIONS
PLACE PER APPROVED SHOP DRAWINGS. DURING Product Engineering & Development
INSTALLATION 162-310
95449-095
THERMAL BREAK
09/09/13
171910 (SHEET 02 OF 09)
171910 (SHEET 03 OF 09)
STEP - 6 PERIMETERS WHERE STEP - 7 INSTALL VERTICAL STEP - 7 INSTALL VERTICAL CONFIDENTIAL AND PROPRIETARY INFORMATION
APPLICABLE MULLIONS MULLIONS KAWNEER COMPANY INC.
THESE DRAWINGS ARE THE SOLE AND EXCLUSIVE PROPERTY OF KAWNEER AND CONTAIN
"F" AND "T" SENSITIVE, PRIVILEGED OR CONFIDENTIAL INFORMATION WHICH MAY BE USED ONLY FOR ITS
"F" OR "T" ANCHORS ANCHOR FASTENER HEAD/SILL SHEAR BLOCK/ANCHOR BENEFIT. THE DISCLOSURE OF THESE DRAWINGS TO UNAUTHORIZED PERSONS IS STRICTLY
INSTALL "C" CHANNEL AT JAMBS PER APPROVED WHERE APPLICABLE. PROHIBITED. THIS DOCUMENT AND ALL COPIES MUST BE RETURNED UPON DEMAND.
WHERE APPLICABLE LOCATIONS PER
SHOP DRAWINGS. COPYRIGHT KAWNEER COMPANY, INC., 2011
APPROVED SHOP
DRAWINGS 162-314 6" & 6-3/4" SYSTEM AT JAMBS
"C" CHANNEL 162-315 7-1/2" & 8-1/4" SYSTEM AT JAMBS STEP - 7 VERTICAL SPLICE
WITH MAX. 1/8" SHIM SPACE AT JAMB 162-342 6" & 6-3/4" SYSTEM AT MULLIONS JOINTS WHERE
162-343 7-1/2" & 8-1/4" SYSTEM AT MULLIONS APPLICABLE.
INSTALL
VERTICAL
MULLIONS SLEEVE IS FACTORY
TAPED ONTO THE
BOTTOM OF THE
TOP VERTICAL
128-396 SCREWS
#12 x 7/16"
THESE SHEAR PAN HEAD TYPE B
BLOCKS MAY NEED
TO BE REMOVED TO 128-284 SCREWS
REMOVE THE TAPE
INSTALL A ANCHOR #12 x 1 1/2
AND LET THE SLEEVE
FASTENER THAT FLAT HEAD
SLIDE DOWN TO THE
MIGHT BE TYPE AB
FACTORY APPLIED
LOCATED CLOSE FOR HORIZONTAL
STOP SCREW
TO THE MULLION ATTACHMENT

THE ABOVE SCREWS ARE ONLY USED AT THE FIELD APPLIED


OPTIONAL SHEAR BLOCK/ANCHORS. FIXING SCREW
128-348
STRUCTURAL SHIMMING IS REQUIRED AT #10 x 1 1/4"
BENCHMARK TO FACE OF
SILL TO ACCOMPLISH DESIGNED FLAT HEAD
PERIMETER MEMBER
PERIMETER SEAL WIDTH. SELF DRILLING
PER APPROVED SHOP
DRAWINGS SHOP APPLIED
ANCHOR FASTENER STOP SCREW
LOCATIONS 128-267 #12 x 1"
PER APPROVED PAN HEAD
SHOP DRAWINGS TYPE AB

STEP - 7 INSTALL VERTICAL "F" & "T" ANCHOR


FASTENER
MULLIONS LOCATIONS PER
APPROVED USE TEMPORARY
DIMENSION BUILD-UP CHECK SHOP DRAWINGS SPACERS FOR
JOINT DIMENSION
CHECK OVERALL FRAME DIMENSIONS ABOUT
EVERY FIVE MULLIONS ON LONG RUNS. AT MULLION JAMB SIDE,
THIS IS TO AVOID DIMENSIONAL BUILD-UP. APPLY (2) 128-396
SCREWS AS SHOWN
TO CENTER F-CLIPS
10 UNITS CHECK DIMENSION AS REQUIRED.
SPLICE JOINT
WHEN IT OCCURS
AT A HORIZONTAL.
1/8"
1 1/4"

1600UT SYSTEM 1
INSTALLATION
SILL SHOWN ANCHOR FASTENER INSTRUCTIONS
HEAD SIMILAR LOCATIONS Product Engineering & Development
5 UNITS CHECK DIM. PER APPROVED
SHOP DRAWINGS 95449-094
04/26/13
171910 (SHEET 03 OF 09)
171910 (SHEET 04 OF 09)
STEP - 8 INSTALL HEAD/SILL STEP - 8 INSTALL HEAD/SILL CONFIDENTIAL AND PROPRIETARY INFORMATION
INSTALLING CEILING INTERMEDIATE
AND INTERMEDIATE AND INTERMEDIATE OPEN BACK HORIZONTAL
KAWNEER COMPANY INC.
THESE DRAWINGS ARE THE SOLE AND EXCLUSIVE PROPERTY OF KAWNEER AND CONTAIN
HORIZONTALS HORIZONTALS SENSITIVE, PRIVILEGED OR CONFIDENTIAL INFORMATION WHICH MAY BE USED ONLY FOR ITS
BENEFIT. THE DISCLOSURE OF THESE DRAWINGS TO UNAUTHORIZED PERSONS IS STRICTLY
PROHIBITED. THIS DOCUMENT AND ALL COPIES MUST BE RETURNED UPON DEMAND.
OPEN BACK HORIZONTALS AND LAST BAY HORIZONTALS © COPYRIGHT KAWNEER COMPANY, INC., 2011
TUBULAR HORIZONTALS
FILLER AVAILABLE WHEN OPEN BACK IS EXPOSED
JUST BEFORE ASSEMBLING THE AND AT EYE LEVEL.
HORIZONTAL APPLY A GENEROUS A
BEAD OF SEALANT BETWEEN THE JUST BEFORE ASSEMBLING THE
FRONT FACE OF SHEAR BLOCK AND HORIZONTAL APPLY A GENEROUS
THE VERTICAL, AND EXTEND 3/4" BEAD OF SEALANT BETWEEN THE
TOP AND BOTTOM AS SHOWN. FRONT FACE OF SHEAR BLOCK AND A
THE VERTICAL AS SHOWN. INSTALLING STOOL INTERMEDIATE
CLEAN JOINTS PER SEALANT
TOP AND BOTTOM AS SHOWN. OPEN BACK HORIZONTAL
MANUFACTURERS' INSTRUCTIONS.
CLEAN JOINTS PER SEALANT
MANUFACTURERS' INSTRUCTIONS.

HEAD

JOINT PLUG
162-321 1" FRAME
171307 1-3/4" FRAME
STEP - 9 INSTALL JOINT PLUGS
INSTALL THE APPLY SEALANT TO
TRANSOM AS SHOWN ALL SURFACES AND GROOVES MUST BE THIS FACE OF JOINT PLUG
AND TOOL ANY CEILING CLEANED PER THE SEALANT MANUFACTURER'S
SQUEEZED OUT RECOMMENDATIONS.
SEALANT AND CLEAN
EXCESS FROM JUST BEFORE INSTALLING JOINT PLUGS APPLY
EXPOSED SURFACES SEALANT AS SHOWN FILLING GASKET POCKET
OF THE MULLION. AND ADAPTER GROOVE. ENSURE THAT THE
MULLION TONGUE RACEWAY AND THERMAL SEAL AROUND
SEPARATOR IS SEALED AND COMPLETELY JOINT PLUG EDGES
FILLED AT PLUG LOCATION. TOOL SEALANT

FILL
STOOL SECTION A-A
GASKET
POCKET

128-405 SCREWS
#12 X 7/8"
FILL
FLAT HEAD
ADAPTER
TYPE AB
GROOVE
SEAL AROUND
JOINT PLUG EDGES
TOOL SEALANT

SILL

THERMAL BREAK
TO BE 1/4" SHORT
AT EACH END OF
HORIZONTALS 1600UT SYSTEM 1
INSTALLATION
128-405 SCREWS INSTRUCTIONS
#12 X 7/8" Product Engineering & Development
FLAT HEAD
TYPE AB FACE VIEW 95449-82
06/24/11
171910 (SHEET 04 OF 09)
171910 (SHEET 05 OF 09)
STEP - 10 INSTALL SPANDREL WHEN USING 171004 ADAPTER AS 1/8" INFILL ADAPTER
STEP - 11 SEAL INTERIOR OF CONFIDENTIAL AND PROPRIETARY INFORMATION
ADAPTERS KAWNEER COMPANY INC.
VERTICAL SPLICE JOINTS
WHERE APPLICABLE THESE DRAWINGS ARE THE SOLE AND EXCLUSIVE PROPERTY OF KAWNEER AND CONTAIN
SENSITIVE, PRIVILEGED OR CONFIDENTIAL INFORMATION WHICH MAY BE USED ONLY FOR ITS
BENEFIT. THE DISCLOSURE OF THESE DRAWINGS TO UNAUTHORIZED PERSONS IS STRICTLY
PROHIBITED. THIS DOCUMENT AND ALL COPIES MUST BE RETURNED UPON DEMAND.
ALL SURFACES AND GROOVES ALL SURFACES AND GROOVES MUST BE © COPYRIGHT KAWNEER COMPANY, INC., 2011
MUST BE CLEANED PER THE CLEANED PER THE SEALANT MANUFACTURER'S
JUST BEFORE SEALANT MANUFACTURER'S RECOMMENDATIONS.
INSTALLING FILLERS RECOMMENDATIONS. STEP - 12 INSTALL INTERIOR
AND SPANDREL
ADAPTERS FACE SEAL
GLAZING GASKETS
JOINTS AT ALL 4

6"
CORNERS. ALSO SEAL GASKETS SHOULD BE INSTALLED JUST PRIOR TO GLASS TO
EXPANSION JOINT AVOID CONTAMINATION BY JOB SITE DEBRIS. GASKET
SCREW HEAD AT TOP LOCATED AT A
HALF OF HORIZONTAL GROOVES AND POCKETS SHOULD BE CLEAN.
HORIZONTAL
IN TEMPERATURES COLDER THAN 50° F ARRANGEMENTS
SHOULD BE MADE TO WARM GASKETS BEFORE INSTALLATION.
THIS WILL PREVENT EXCESSIVE GLAZING PRESSURE ON THE
GLASS DUE TO COLD, STIFF RUBBER GASKETS.
STEP - 11 SEAL INTERIOR OF
GASKETS CAN BECOME DEFORMED DURING STORAGE IN
VERTICAL SPLICE JOINTS CARTONS. THEY SHOULD BE REMOVED FROM CARTONS
SEVERAL HOURS PRIOR TO GLAZING AND LAID FLAT OR HUNG
TO ALLOW RECOVERY OF CORRECT SHAPE. TEMPERATURES
SHOULD BE AT LEAST 50° F TO ALLOW THIS.

GASKET INSTALLED LENGTH TO BE DAYLITE OPENING.


GASKETS TO BE CUT LONG FOR SOME "CROWD-IN". GASKETS
SEAL SHOULD NEVER BE " STRETCHED TO FIT".

"CROWD-IN" TO BE 1/8" PER FOOT UP TO 5"-0", 3/16" PER FOOT


UP TO 8'-0", 1/4" PER FOOT OVER 8'-0".
APPLY BOND
BREAKER
SPANDREL TAPE TO FACE JUST BEFORE
ADAPTER OF SLEEVE INSTALLING VERTICAL
AND HORIZONTAL
GASKETS FACE SEAL
JOINTS AT ALL 4
SEAL CORNERS. ALSO SEAL
SCREW HEAD AT TOP
EXPANSION JOINT HALF OF HORIZONTAL
LOCATED AT A
HORIZONTAL
APPLY BOND BREAKER
TAPE TO FACE OF SLEEVE

PERIMETER GASKET
WHEN USING 171004 ADAPTER AS 1/8" INFILL ADAPTER TYPICAL WHERE APPLICABLE

SEAL
APPLY & TOOL SEALANT
AT ALL FOUR ADAPTER
GASKET GASKET
CORNER JOINTS, ALONG SPANDREL APPLY BOND 027-850 027-857
ENTIRE LENGTH OF ADAPTER
171004 BREAKER
BOTTOM ADAPTER & SEAL
ADAPTER TAPE TO FACE
6" UP EACH JAMB
AS SHOWN
OF SLEEVE 1600UT SYSTEM 1
INSTALLATION
INSTRUCTIONS
APPLY BOND BREAKER
Product Engineering & Development
SPANDREL TAPE TO FACE OF SLEEVE
027-852 GASKET ADAPTER 95449-82
06/24/11
171910 (SHEET 05 OF 09)
171910 (SHEET 07 OF 09)
STEP - 16 INSTALL GLASS STEP - 17 INSTALL SIDE BLOCKS STEP - 18 INSTALL EXTERIOR CONFIDENTIAL AND PROPRIETARY INFORMATION
KAWNEER COMPANY INC.
PRESSURE PLATES THESE DRAWINGS ARE THE SOLE AND EXCLUSIVE PROPERTY OF KAWNEER AND CONTAIN
SENSITIVE, PRIVILEGED OR CONFIDENTIAL INFORMATION WHICH MAY BE USED ONLY FOR ITS
USE 162-350 GLAZING TEMPORARIES GLASS EDGE GLASS EDGE BENEFIT. THE DISCLOSURE OF THESE DRAWINGS TO UNAUTHORIZED PERSONS IS STRICTLY
PROHIBITED. THIS DOCUMENT AND ALL COPIES MUST BE RETURNED UPON DEMAND.
AS REQUIRED. USE 128-960 SCREWS. RECOMMEND USING TORQUE LIMIT COPYRIGHT KAWNEER COMPANY, INC., 2011
TOOL 162-399 SEE NOTE.

HOW TO SET TORQUE LIMIT

A A 1. ATTACH ANY CALIBRATED TORQUE INDICATOR TO


B B OUTPUT STUB (1) AND DETERMINE PRESENT TORQUE
C C SETTING WHILE HOLDING THE BODY (5), OR VICE-VERSA.
D D
2. REMOVE SNAP RING (2) AND LOCKING PLATE (3).
CENTER OF
VISION GLASS
GLASS 3. ADJUST NUT (4) WITH OPEN-END WRENCH : CLOCKWISE
HEIGHT TO INCREASE TORQUE, COUNTER- CLOCKWISE TO
DECREASE TORQUE.

4. OBTAIN NEW TORQUE READING WITH THE CALIBRATED


TORQUE INDICATOR. REPEAT PRECEDING STEP IF MORE
ADJUSTMENT IS NECESSARY TO REACH DESIRED LIMIT. CLEAN ALL JOINTS PER
SEALANT MANUFACTURER'S
5. REPLACE LOCKING PLATE INTO NOTCHES AND INSTALL RECOMMENDATIONS
SNAP RING. IF LOCKING PLATE DOES NOT "SEAT", MOVE
THE ADJUSTING NUT SLIGHTLY UNTIL IT DROPS IN PLACE.
THE DIRECTION IS BEST DETERMINED BY WHETHER A
JUST BEFORE INSTALLING VERTICAL
MAXIMUM TEMPORARY SPACING IS 30". MINIMUM TORQUE APPLICATION OR A MAXIMUM ONE IS
PRESSURE PLATES APPLY A GENEROUS
IF WINDS GREATER THAN 50 MPH (80KPH) ARE EXPECTED, SIDE BLOCK DESIRED.
AMOUNT OF SEALANT TO THE JOINT PLUG
ADDITIONAL TEMPORARIES MAY BE REQUIRED. CONSULT 027-855 1" GLASS FACE FILLING JOINTS AS SHOWN.
YOUR SEALANT AND/OR INFILL SUPPLIER FOR SPACING 027-856 1/4" GLASS
RECOMMENDATIONS. INSTALL PRESSURE PLATES WHERE 127-165 1-3/4" GLASS
POSSIBLE. FACE VIEW
5 2

INSTALL SIDE BLOCKS COMPRESSING AS SHOWN 3

1 4
A-A B-B
INSTALL PRESSURE PLATES USING SCREWS 128-960
1/4-14 X 1-3/4" HEX WASHER HEAD SELF DRILLING SCREWS.
SPANDREL
GLASS

SPANDREL
GLASS

027-855 027-856 SCREWS ARE TO BE LOCATED 9" ON CENTER MAXIMUM.


FOR PROJECTS DESIGNED FOR WIND LOADS GREATER THAN
60 PSF, APPLY PRESSURE PLATES SCREWS AT 6" ON CENTER.

C-C D-D ALWAYS LOCATE A SCREW AS CLOSE AS POSSIBLE TO A


HORIZONTAL JOINT. THIS WILL PROVIDE MAXIMUM PRESSURE
FOR THE CRITICAL JOINT SEALS.

INSTALL HORIZONTAL PRESSURE PLATES WITH WEEP HOLES


TOWARDS TOP OF HORIZONTAL.

AT EACH HORIZONTAL AND VERTICAL PRESSURE PLATE


INSTALL TWO SCREWS PART WAY, THEN INSTALL THE THIRD
SCREW ALL THE WAY, AND THEN TIGHTEN THE FIRST TWO 1600UT SYSTEM 1
SCREWS. THIS ELIMINATES LATERAL WALKING OF THE
PRESSURE PLATE POSITION. INSTALLATION
INSTRUCTIONS
127-165 027-855 TORQUE ALL SCREWS TO 90 TO 100 INCH POUNDS. DURING Product Engineering & Development
COLD WEATHER, TORQUE SCREWS TO 50 INCH POUNDS
UNTIL ALL 4 SIDES HAVE BEEN CLAMPED. THEN TORQUE 95449-094
SCREWS TO 90 TO 100 INCH POUNDS.
04/26/13
171910 (SHEET 07 OF 09)
171910 (SHEET 08 OF 09)
STEP - 18 INSTALL EXTERIOR VERTICAL EXPANSION JOINTS CONFIDENTIAL AND PROPRIETARY INFORMATION
PRESSURE PLATES INTERMEDIATE
KAWNEER COMPANY INC.
HORIZONTAL
THESE DRAWINGS ARE THE SOLE AND EXCLUSIVE PROPERTY OF KAWNEER AND CONTAIN
VISION OVER
INSTALL VERTICAL PRESSURE PLATES A SENSITIVE, PRIVILEGED OR CONFIDENTIAL INFORMATION WHICH MAY BE USED ONLY FOR ITS
SPANDREL BENEFIT. THE DISCLOSURE OF THESE DRAWINGS TO UNAUTHORIZED PERSONS IS STRICTLY
PROHIBITED. THIS DOCUMENT AND ALL COPIES MUST BE RETURNED UPON DEMAND.
© COPYRIGHT KAWNEER COMPANY, INC., 2011
NOTE - THE TORQUE LIMIT TOOL WAS DESIGNED TO
BE USED WITH A HAND DRIVEN DEVICE. THE TOOL A
SEAL BETWEEN
CAN BE ADAPTED TO A DRILL MOTOR IF USED AT A PRESSURE PLATE HEAD HORIZONTAL
MAXIMUM SPEED OF APPROX. 300 RPM. HIGHER B & HEAD/SILL END SILL SAME
SPEEDS CAN CAUSE OVERHEATING AND AFFECT THE CAP AS SHOWN
ACCURACY. AFTER APPROX. 1 HOUR OF TOOL USAGE
CHECK TORQUE SETTINGS WITH A TORQUE WRENCH. D

TOP OF VERTICAL D
INTERMEDIATE MULLION TO TOP SEAL JOINTS B E
HORIZONTAL OF PRESSURE AS SHOWN. SEAL JOINTS
VISION OVER PLATE IS 1-1/2" TOOL SEALANT. AS SHOWN.
SPANDREL THIS SEAL IS TO TOOL SEALANT.
JOIN AND ADHERE THIS SEAL IS TO
TO THE JOINT JOIN AND ADHERE C
PLUG SEALS. TO THE JOINT
E
PLUG SEALS.
027-850
C
GASKET
A-A CLEAN JOINT D-D CLEAN JOINT
PER SEALANT PER SEALANT
TOOL MANUFACTURER'S MANUFACTURER'S
EXCESS RECOMMENDATIONS RECOMMENDATIONS
SEALANT
DO NOT LET THE SEAL DO NOT LET THE SEAL
AT TOP PRESSURE INTERFERE WITH THE COVER SNAP. INTERFERE WITH THE COVER SNAP.
PLATE LOCATE STUFF BACKER ROD
SCREW CLOSE TO VERTICAL GASKET
HEAD CONDITION INTO JOINT TO BACK
VERTICAL GASKET THE MULLION JOINT STOPS 1"
SILL SAME UP SEALANT GASKET
STOPS 1" SHORT BUT NOT BELOW SHORT OF END
AT HEAD & SILL GASKET 027-857
THE JOINT.
027-850

B-B
CLEAN JOINT
PER SEALANT
E-E
MANUFACTURER'S
RECOMMENDATIONS GASKET
027-850

TOOL GASKET GASKET


EXCESS 027-850 027-850
SEALANT FACE VIEW
COMPLETELY SEAL JOINT.
DO NOT LET SEALANT FACE VIEW
INTERFERE WITH COVER SNAP.
THERMAL POCKET FILLER DO NOT LET THE SEAL
THERMAL POCKET FILLER VERTICAL GASKET OVERLAP PRESSURE PLATE FACE
HEAD HORIZONTAL INTERFERE WITH THE COVER SNAP.
HEAD HORIZONTAL STOPS 1" SHORT CREATING A BAND-AID SEAL.
SILL SAME
SILL SAME AT HEAD & SILL
D

GASKET
C-C GASKET
SEAL JOINTS D
INSTALL HORIZONTAL PRESSURE PLATES 027-850 027-850
AS SHOWN.
E
TOOL SEALANT.
171321 (1") THIS SEAL IS
171320 (1-3/4") CENTER HORIZONTAL PRESSURE PLATES TO JOIN AND 1600UT SYSTEM 1
THERMAL SO END GAPS ARE EQUAL. ADHERE TO INSTALLATION
POCKET FILLER THE JOINT C INSTRUCTIONS
TOOL PLUG SEALS.
E Product Engineering & Development
EXCESS
SEALANT C 95449-82
06/24/11
171910 (SHEET 08 OF 09)