Professional Documents
Culture Documents
Generator Set Load Sharing Module PWM Diagramas
Generator Set Load Sharing Module PWM Diagramas
Pruebas y Ajustes
Generator Set Load Sharing Module
Número de medio -RENR2471-03 Fecha de publicación -01/01/2002 Fecha de actualización -15/01/2002
i01169516
Wiring Diagrams
SMCS - 4490; 7566
Ver imagen
https://sis.cat.com/sisweb/sisweb/techdoc/content.jsp?calledpage=/sisweb/sisweb/medias... 25/09/2005
Service Information System Página 2 de 6
Illustration 1 g00623932
Refer to the following notes when you are using the Illustration 1.
Note 1: With a balanced three-phase load and unity power factor the current transformers should be
wired in the correct potential leg. The current transformers must be phased at the controls as follows.
https://sis.cat.com/sisweb/sisweb/techdoc/content.jsp?calledpage=/sisweb/sisweb/medias... 25/09/2005
Service Information System Página 3 de 6
Note 2: Power source current transformers should be sized to produce approximately 5 Amp secondary
current with maximum generator current. CT burden is essentially 0 VA.
Note 4:
Note 5: Place the jumper between T15 and T16 and between T17 to T18 when potential input at
terminals T1 through T3 is 95 to 130 VAC phase to phase (50 to 400 Hz).
Note 6: Place the jumper between T16 and T17 when potential input at terminals T1 through T3 is 190
to 260 VAC phase to phase (50 to 400 Hz).
Note 7: Potential transformer burden is 5 VA per phase with 230 VAC input and 2.5 VA per phase with
115 VAC input.
Note 8: Control signal lines should be twisted shielded pairs. The shield should be tied to the ground at
one end only.
Note 10: If speed trim potentiometer reference is used, connect a 10 K, ten turn potentiometer. Use 20
gage or larger shielded wire.
Ver imagen
https://sis.cat.com/sisweb/sisweb/techdoc/content.jsp?calledpage=/sisweb/sisweb/medias... 25/09/2005
Service Information System Página 4 de 6
Illustration 2 g00623934
Refer to the following notes when you are using the Illustration 2.
https://sis.cat.com/sisweb/sisweb/techdoc/content.jsp?calledpage=/sisweb/sisweb/medias... 25/09/2005
Service Information System Página 5 de 6
Note 1: With a balanced three-phase load and unity power factor the current transformers should be
wired in the correct potential leg. The current transformers must be phased at the controls as follows.
Note 2: Power source current transformers should be sized to produce approximately 5 Amp secondary
current with maximum generator current. CT burden is 0.1 VA.
Note 4:
Note 5: Potential transformer burden is 5 VA per phase with 230 VAC input and 2.5 VA per phase with
115 VAC input.
Note 6: Control signal lines should be twisted shielded pairs. The shield should be tied to the ground at
one end only.
Note 7: This is a protective earth ground. Use the ground as required by the regulations. Ground wire
must be at least as large as the wire on the terminals 1 through 9.
Note 8: Connect the synchronizer shields to the nearest chassis screw as indicated. Connect the speed
trim shields to the nearest chassis screw as indicated.
Note 9: The wire lugs on terminals 3 and 4 must have insulated sleeves. The wire lugs on terminals 3
and 4 must also have a creepage distance of 6.5 mm (0.256 inch) or greater in order to comply with the
European Union's Low Voltage Directive.
Note 10: Replace ammeters with jumpers if ammeters are not used.
https://sis.cat.com/sisweb/sisweb/techdoc/content.jsp?calledpage=/sisweb/sisweb/medias... 25/09/2005
Service Information System Página 6 de 6
https://sis.cat.com/sisweb/sisweb/techdoc/content.jsp?calledpage=/sisweb/sisweb/medias... 25/09/2005