Medical Ir
system
Powe 313
3.3.4 Power supply ducts for radiological or sim-
ilar equipment
Radiological devices and those with a power con
sumption in excess of KVAabsorb high value
currents from the power supply ine. For this rea-
son the sizing of the power supply conductors
must be assessed carefully in order to contain
voltage drops.
Radiological devices of the fixed type and devices
with power consumption greater than 5 HVA,
powered directly by the “ordinary” netwerk and in
general without the interposition of a socket/
plug group, can be protected with RCDs with a
differential current of 0.5,
I they may enter the patient environment itis
mandatory to adopt differential 30 mA thermo
‘magnetic miniature circuit breakers of tyoe “A”
(for single phase circuits) or *B” (especially for
three-phase circuits).
3.3.5 Selectivity of the protection devices
Particular care must be taken in implementing ef-
fective selectivity of the overcurrent protection
devices in order to guarantee maximum continu
ity of service
‘As far as possible, horizontal and verticalselec-
tivity must be implemented. With horizontal se-
lectivity, and therefore by subdividing the system
Medical it
system
@
Medical Ir
system
@)
into different circuits, downtime in the case of a
malfunction is reduced. Subdivision into several
circuits also makes it possible to prevent the ai
multaneous use of numerous devices connected
to the same circuit from causing the tripping of
the RCD (for example due to the capacitive earth
leakages of the devices).
A particular aspect of horizontal selectivity con-
‘cerns group 2 rooms: the standards require that
{for every patient treatment position (such as a
socket control panel, a wall-mounted power sup-
ply unit or the pensile stand) the plug sockets.
Powered by the Medical IT System must be alter-
natively (fig. 3.14)
+ connected to two distinct power supply circuits
(each equipped with the respective protection
device);
+ protected against overcurrents individually or in
groups (at least two).
With this provision. ifa plug socket downstream
fails, with tripping of the related protection de-
vice, only one socket or one group of sockets will
be out of service, while the others remain in oper-
ation.
Together with horizontal selectivity itis also nec
‘essary to guarantee vertical selectivity so that, in
the event of overcurrent, only the device for pro-
tection of the circuft affected by the malfunction
will rip, and not the device located upstream (fig
3.15),
‘Only this Miniature
circuit breaker must
be tripped #4
1 1
&
T
ch I
is
ARAL
bythe Medea System
Dprotectonin groups
single protection