Professional Documents
Culture Documents
Article Testing The State of High Voltage Insulation Hummel ENU
Article Testing The State of High Voltage Insulation Hummel ENU
Article Testing The State of High Voltage Insulation Hummel ENU
Partial discharges (PDs) can damage the insulation in electrical devices that are subjected to high voltages.
This can lead to the total destruction of the device. To prevent a sudden breakdown and carry out
preemptive repairs, partial discharges can be measured and evaluated. Partial discharge measuring
systems enable you to quickly assess the state of affected equipment - this can be done both offline and
online. The results indicate the current state of the insulation and enable asset managers, product
developers and users to quickly detect, assess and locate faults, to prevent breakdowns before they occur.
If the insulator is air, it is ionized during a partial discharge and therefore becomes a temporary conductor.
Due to air exchange and recombination, the insulation resistance of the air returns to its initial state for the
most part. If, however, partial discharges occur in solid insulation materials, they can be irreparably
damaged. Once damaged, most insulation materials lose their insulating property. As a result, the partial
discharges become more frequent and dangerous.
© OMICRON Page 1 of 6
Figure 1a Figure 1b Figure 1c
An electrical field in normal Cavity in the insulation The equipotentials indicate
running order material an accumulation near the
cavity
This should explain what causes such an excessively high field strength. Figure 1a depicts an electrode on
both the right and the left. Between these two, a homogeneous field forms in the solid insulation material.
Figure 1b shows the same scenario, except here there is a cavity in the insulation material. The dielectric
constant (εr) of the solid insulator is εr=3; but it is εr=1 for the gas -filled cavity. The variable dielectric
constants create an inhomogeneous field. The electrical field in the cavity is three times larger than that in
the solid insulator.
The equipotentials in figure 1c indicate an accumulation near the cavity. The voltage in the cavity is almost
three times larger than that in the solid insulator. If the electrical field strength is too high, it causes partial
discharges.
During production, impurities can accumulate, which then cause cavities to form. Thermal stresses to the
insulation material can cause cavities and tearing. Such thermal stresses can form under normal operation
due to cyclical heating and cooling or due to overheating.
As with plastic and air, it is always in those spots where insulation materials meet that have different
dielectric constants that the skin effect can occur. This is mostly undesirable and goes unnoticed.
If partial discharges go unnoticed, breakdowns can occur without warning and cause you to incur great
costs. If the equipment is damaged through an explosion or production is brought to a standstill, the costs of
a sudden breakdown are often higher than the device or its acquisition costs by a factor of four. By detecting
partial discharges early on, repairs or replacements can be planned and carried out for the affected parts.
The IEC 60270 norm sets out how you can carry out a partial discharge measurement offline with a separate
voltage source, a coupling capacitor and measuring impedances. Most limit values for equipment partial
discharges are set out in this norm. To test this, a higher-than-operating voltage is used.
Especially damage to the insulation shows hysteresis behavior regarding partial discharge inception and
extinction voltages. It is therefore possible that partial discharge inception occurs in the insulation during
short-term voltage surges, with extinction only occurring if the voltage is set a few kV lower t han operating
voltage.
These standard tests are especially recommended for equipment when it is being manufactured, once it has
been assembled, before use and thereafter during repeated testing. It often falls to the buyer to contractually
agree on such a test and carry them out with later users.
Figure 2
Partial discharge
measurement
Sudden changes in the intensity of partial discharges indicate a higher chance of the equipment breaking
down. By carrying out repeated tests or through continuous monitoring, the equipment's remaining life cycle
can be estimated. Equipment can therefore be used based on its status and not just on its running time.
Figure 3
Disturbance sources are excluded in the results thanks to specially developed methods. This allows
you to easily analyze different PD sources separately.
OMICRON offers PD measuring systems for diagnostics and for continuous monitoring. The measuring
systems have a modular design, meaning they can easily be added to if the user should need to do more
with it. The measuring systems can be used on all devices that run at high voltages. This not only includes
energy providers, high-voltage equipment and their manufacturers. These measuring systems are also used
in medicine, the automotive and aeronautical industries as well as at universities. www. omicron.at
Rene Hummel works for OMICRON in Berlin as an applications engineer on partial discharges. He studied
electrical engineering at the Technical University Berlin, with a focus on high-voltage technology, power
electronics, analog and digital electronics as well as microelectronics. As a partial discharge measuring
expert at OMICRON, Hummel carries out commissioning tests and runs specialized PD training programs
on-site for clients across the globe. As a member of the IEEE PES/ICC work group F04W, he helps to
establish directives for on-site PD measuring. He also teaches and lectures at universities on PD-related
topics.
.
Customers in more than 140 countries rely on the company’s ability to supply leading-
edge technology of excellent quality. Service centers on all continents provide a broad
base of knowledge and extraordinary customer support. All of this together with our
strong network of sales partners is what has made our company a market leader in the
electrical power industry.