Professional Documents
Culture Documents
Three-Phase Transformers: Experiment
Three-Phase Transformers: Experiment
Objectives:
1. To connect the primary and secondary of the given three-phase transformer in different
connections and to perform the load test on the transformer.
2. To understand the relation between line and phase voltages/currents.
3. To determine the voltage regulation of a loaded 3-phase transformer.
2. Wye-Delta (Y-Δ)
The primary voltage on each phase of the
transformer is given by VLP = √3 VФP. The
primary-phase voltage is related to the secondary-
phase voltage by the turns ratio of the transformer.
The phase voltage on the secondary is then related
to the line voltage on the secondary by VLS = VФS.
therefore, overall the voltage ratio on the
transformer is
The Y-Δ connection has no problem with third-harmonic components in its voltages, since
they are consumed in a circulating current on the Δ side. This connection is also more stable
with respect to unbalanced loads, since the Δ partially redistributes any imbalance that occurs.
The secondary voltage is shifted 30o relative to the primary voltage of the transformer. The fact
that a phase shift has occurred can cause problems in paralleling the secondaries of two
transformer banks together. The phase angles of transformer secondaries must be equal if they
are to be paralleled, which means that attention must be paid to the direction of the 30o phase
shift occurring in each transformer bank to be paralleled together.
3. Delta-Wye (Δ-Y)
The primary voltage on each phase of the
transformer is given by VLP = VФP. The primary-
phase voltage is related to the secondary-phase
voltage by the turns ratio of the transformer. The
phase voltage on the secondary is then related to
the line voltage on the secondary by VLS = √3
VФS. therefore, overall the voltage ratio on the
transformer is
Palestine Technical University-Kadoorie
Faculty of Engineering and Technology | Electrical Engineering Department
Electrical Machines Lab || Eng. TareQ FoQha
4. Delta-Delta (Δ- Δ)
VLP = VФP and VLS = VФS, so the relationship
between primary and secondary line voltages is:
The choice of connection of three phase transformer depends on the various factors likes the
availability of a neutral connection for grounding protection or load connections, insulation to
ground and voltage stress, availability of a path for the flow of third harmonics.
Usually it is a good practice to have as small as voltage regulation as possible. For an ideal
transformer, VR = 0 percent. It is not always a good idea to have a low-voltage regulation;
though-sometimes high-impedance and high-voltage regulation transformers are deliberately
used to reduce the fault currents in a circuit.
Necessary Material:
1. MATLAB Simulink
Palestine Technical University-Kadoorie
Faculty of Engineering and Technology | Electrical Engineering Department
Electrical Machines Lab || Eng. TareQ FoQha
Experimental Procedures:
Part I: Specifications of the Three-Phase Transformer.
1. Read the nameplate of the three-phase transformer and then tabulate the rating values of
the transformer in the following table.
Y-Y
4. Set the Three-Phase Transformer under load with the insertion of the resistive load (with
different values of the resistive load) and measure the following using the power
analyzer:
(a) Current drawn by the load (Line Current) (Iload) in mA.
(b) Terminal voltage of the synchronous generator (Line Voltage) (VT) in V.
(c) Power consumed by the load (P) in W.
5. Calculate the voltage regulation in each case.
6. Tabulate your result in the following table.
Connection Load Load Voltage (Line) Load Current (Line) Power Consumed (W) %VR
50 W
Y-Y 100 W
150 W
Palestine Technical University-Kadoorie
Faculty of Engineering and Technology | Electrical Engineering Department
Electrical Machines Lab || Eng. TareQ FoQha
7. Switch off the load and then switch off the power supply.
Figure (1)
Δ-Δ
4. Set the Three-Phase Transformer under load with the insertion of the resistive load (with
different values of the resistive load) and measure the following using the power
analyzer:
(a) Current drawn by the load (Line Current) (Iload) in mA.
(b) Terminal voltage of the synchronous generator (Line Voltage) (VT) in V.
(c) Power consumed by the load (P) in W.
5. Calculate the voltage regulation in each case.
6. Tabulate your result in the following table.
Connection Load Load Voltage (Line) Load Current (Line) Power Consumed (W) %VR
50 W
Δ-Δ 100 W
150 W
7. Switch off the load and then switch off the power supply.
Palestine Technical University-Kadoorie
Faculty of Engineering and Technology | Electrical Engineering Department
Electrical Machines Lab || Eng. TareQ FoQha
Δ-Y
4. Set the Three-Phase Transformer under load with the insertion of the resistive load (with
different values of the resistive load) and measure the following using the power
analyzer:
(a) Current drawn by the load (Line Current) (Iload) in mA.
(b) Terminal voltage of the synchronous generator (Line Voltage) (VT) in V.
(c) Power consumed by the load (P) in W.
5. Calculate the voltage regulation in each case.
6. Tabulate your result in the following table.
Connection Load Load Voltage (Line) Load Current (Line) Power Consumed (W) %VR
50 W
Δ-Y 100 W
150 W
7. Switch off the load and then switch off the power supply.
Y-Δ
Palestine Technical University-Kadoorie
Faculty of Engineering and Technology | Electrical Engineering Department
Electrical Machines Lab || Eng. TareQ FoQha
4. Set the Three-Phase Transformer under load with the insertion of the resistive load (with
different values of the resistive load) and measure the following using the power
analyzer:
(a) Current drawn by the load (Line Current) (Iload) in mA.
(b) Terminal voltage of the synchronous generator (Line Voltage) (VT) in V.
(c) Power consumed by the load (P) in W.
5. Calculate the voltage regulation in each case.
6. Tabulate your result in the following table.
Connection Load Load Voltage (Line) Load Current (Line) Power Consumed (W) %VR
50 W
Y-Δ 100 W
150 W
7. Switch off the load and then switch off the power supply.
Part VI: Phase Shift between the primary and the secondary voltages of different
connections of three phase transformers.
Phase Shift
Connection Δt T
Φ = Δt/T * 360
Y-Y
Y-Δ
Δ-Y
Δ-Δ
Palestine Technical University-Kadoorie
Faculty of Engineering and Technology | Electrical Engineering Department
Electrical Machines Lab || Eng. TareQ FoQha
Questions:
A 1-kVA three phase transformer has 500 turns on the primary and 100 turns on the secondary
winding, the transformer connection is Δ-Y, if the transformer supplied with a 400-V, 50-Hz
supply, calculate the secondary phase voltage.