ME13-T: REFRIGERATION ENGINEERING


ACTIVITY NO.___

NAME: BATONGHINOG, JOHN RYAN T. SCORE: ________


SECTION: BSMESEP-3A DATE: APRIL 4, 2023

INSTRUCTION: Show your solution clearly and neatly, box your final answer,
erasures on your final answer will be considered wrong.

1. A Refrigeration Plant decided to design a system in two working evaporators


with single compressor to provide 150 kW and 100 kW with -35oC and -16oC
respectively. The condensing temperature is limited to 35oC. Calculate the
following and use refrigerant 12.

PARAMETERS VALUES SHOULD HAVE UNIT


MASS FLOW RATE 2.367 kg/s
COMPRESSOR WORK 102.65 kW
HEAT REJECTED 352.69 kW
COP 2.44
EER 8.33

2. From problem no.1 redesign the system into one evaporator and two working
compressors, assume that the evaporating temperature will be -20 oC.

PARAMETERS VALUES SHOULD HAVE UNIT


MASS FLOW RATE AT STAGE 2 3.036 kg/s
COMPRESSOR WORK 80.6 kW
HEAT REJECTED 408.35 kW
COP 4.067
EER 13.88