Professional Documents
Culture Documents
4.1.5c Grid - Interconnection - Documents - Cypress-xxHz - EN - Doc-0075452 - 08
4.1.5c Grid - Interconnection - Documents - Cypress-xxHz - EN - Doc-0075452 - 08
4.1.5c Grid - Interconnection - Documents - Cypress-xxHz - EN - Doc-0075452 - 08
GE Renewable Energy
Technical Documentation
Wind Turbine Generator Systems
Cypress Platform - 50/60 Hz
Grid Interconnection
Applicable for Cypress Wind Turbine Generators
imagination at work
© 2021 General Electric Company. All rights reserved.
- Original Document -
GE Renewable Energy
Visit us at
www.gerenewableenergy.com
All technical data is subject to change in line with ongoing technical development!
This document is to be treated confidentially. It may only be made accessible to authorized persons. It may only
be made available to third parties with the expressed written consent of General Electric Company.
All documents are copyrighted within the meaning of the Copyright Act. The transmission and reproduction of
the documents, also in extracts, as well as the exploitation and communication of the contents are not allowed
without express written consent. Contraventions are liable to prosecution and compensation for damage. We
reserve all rights for the exercise of commercial patent rights.
GE and the GE Monogram are trademarks and service marks of General Electric Company.
Other company or product names mentioned in this document may be trademarks or registered trademarks of
their respective companies.
imagination at work
Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08
- Original Document -
Table of Contents
Document Revision Table ..................................................................................................................................................................... 4
1 Introduction ................................................................................................................................................................................................ 5
2 Technology .................................................................................................................................................................................................. 5
3 Turbine Transformer ............................................................................................................................................................................... 5
4 Frequency Tolerance .............................................................................................................................................................................. 6
5 Voltage Tolerance & Fault Ride-Thru ............................................................................................................................................... 6
6 Protection .................................................................................................................................................................................................... 7
7 Minimum Grid Strength ......................................................................................................................................................................... 8
8 Reactive Power Capability .................................................................................................................................................................... 9
9 WindFREE Reactive Power ................................................................................................................................................................... 9
10 WindINERTIA ......................................................................................................................................................................................... 9
11 Series Compensation Compatibility ........................................................................................................................................ 10
12 Plant Level Control and Voltage Regulation ......................................................................................................................... 11
13 Harmonic Distortion ....................................................................................................................................................................... 11
13.1 IEC 50 Hz Harmonics Distortion ........................................................................................................................................... 11
13.2 IEEE 60 Hz Harmonics Distortion ......................................................................................................................................... 12
14 System Modeling .............................................................................................................................................................................. 12
14.1 Wind Turbine Short Circuit Modeling ................................................................................................................................. 12
14.2 Wind Turbine Dynamic Modeling ......................................................................................................................................... 13
14.3 Wind Turbine Transient Modeling ........................................................................................................................................ 13
14.4 Wind Dynamic Model Validation .......................................................................................................................................... 13
14.5 Wind Turbine Transient Model Validation ........................................................................................................................ 13
15 Power Demand .................................................................................................................................................................................. 13
16 Generator Equivalent Data .......................................................................................................................................................... 13
17 Wind Farm Open Circuit Protection ......................................................................................................................................... 14
Appendix I – General Data (reference only) ......................................................................................................................................... 15
Appendix II – Active/Reactive Power Capability Curves ................................................................................................................. 16
Appendix III – WindRIDE-THRU ................................................................................................................................................................. 28
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08 x
- Original Document -
GE Renewable Energy Grid Interconnection
9 UPDATED Section 11
5 EDITED Section 3
9 EDITED Section 8
06 2021/07/19
10 ADDED new information in Section 11
10 EDITED Section 12
16 UPDATED Appendix II
07 2021/08/10
23 UPDATED figure`s 7 & 8
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
4/28 Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08
- Original Document -
1 Introduction
This document is intended to describe the electrical specifications of the Cypress wind turbines and highlight
common topics related to grid interconnection.
2 Technology
The Cypress wind turbine is variable speed and employs a doubly fed induction generator with a partial power
converter interfacing to the grid.
Unless stated otherwise, all the data shown is based on the secondary connection of the Wind Turbine Generator
System (WTGS) transformer (6000 V and 690 V connections).
3 Turbine Transformer
Each wind turbine should be connected through a three-winding step-up WTGS transformer to the MV wind farm
collection system.
The primary-side rated voltage of the system transformer is based on the nominal voltage of the medium-voltage
network. The secondary rated voltage of the system transformer is 6 kV, the tertiary side 690 V. The switching group
of the system transformer is Dyn11yn11.
Transformer rating details and parameters can be provided on request based on the wind turbine configuration
applicable for a project. Transformer nominal rating is temperature dependent.
Permanent changes to the steady state voltage at the LV terminals due to changes of the MV level in the grid or
collector system may result in a reduction of the active and reactive power range or even in a turbine trip. If such a
permanent change is desired, a turbine transformer tap changer can be used, which usually offer
+/- 2 x 2.5 % voltage change. If greater change in voltage is required a different transformer should be selected.
Additionally, changes to steady state voltages can be addressed utilizing the substation transformer where
applicable.
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08 5/28
- Original Document -
GE Renewable Energy Grid Interconnection
4 Frequency Tolerance
The Cypress wind turbine is capable of operating within the following frequencies and for the corresponding time
durations:
Where requested the Seller is also able to extend this fault ride through capability with the zero-voltage ride-thru
(ZVRT) optional feature described below.
The voltages in Table 2 are referenced to the turbine transformer MV side (e.g.: 30 kV).
NOTE
The capability described below depends on active and reactive current provision
from the turbine during LVRT and ZVRT events. If during such disturbances certain
limits to inject active and/or reactive current are required as a special exception,
project specific capability information according to these conditions can be
provided on request.
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
6/28 Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08
- Original Document -
6 Protection
The GE wind turbine has the following built-in protection functions:
Overvoltage/Undervoltage
Over Frequency/Under Frequency
Voltage Imbalance
Ground fault protection
Additionally, the medium voltage breaker which is located down-tower provides overcurrent protection and includes
configurable instantaneous, short-time and long-time settings.
These functions are designed to offer a level of protection to the wind turbine hardware from disturbances caused by
the electrical system.
1 A specific waveform based on field experience has been used to represent transients while evaluating capability against capacitor switch transients ride
through capability.
4 The converter will stop pulsing after 200 ms. No control of reactive power during initial voltage recovery.
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08 7/28
- Original Document -
GE Renewable Energy Grid Interconnection
The Seller strongly recommends protecting the MV system against transient and temporary overvoltage, which are
caused by:
The customer is responsible for overvoltage mitigation actions on the MV system. Grounding transformers,
automatic grounding switches on the feeder breakers or special surge arrester configurations will be required to
prevent MV over voltages when the feeder breakers are opened and the MV system loses its ground reference at the
substation.
The composite short circuit MVA should not include the short circuit contribution from the wind turbine generators
and other IBRs. The denominator in the calculation of CSCR is the sum of the nameplate MW and must include all
wind turbine generators in the proposed wind farm as well as other IBRs that are electrically close, which will need to
be determined on a project-specific basis for different grid conditions
The CSCR capability of 1.4 is determined based on a broad set of operating points, network parameters and grid
contingencies considering wind farm with only GE turbines in the electrical vicinity. It is to be noted that the grid
strength where the wind farm of interest is connecting is system-specific and cannot be fully ascertained based on
the CSCR metric. For a wind farm application involving complex networks with multiple wind farms or other power
electronic devices in the electrical vicinity, especially from multiple vendors, the minimum CSCR may be higher.
Depending on the outcome of the screening study a more in-depth study may be needed to quantify the grid
strength and assess the viability of the wind farm application. The evaluation of operation at low CSCR values is
typically based on transient simulations of the network considering a range of operating points, network parameters
and grid contingencies, which differ from project to project.
Detailed methodology for calculation of CSCR available upon request. For complex networks with multiple wind
farms in the vicinity of each other the information required to calculate CSCR accurately may be available only to the
grid operator.Coordination with grid authorities on performance requirements may be needed as CSCR approaches
1.4 since the controls may need to be tuned for slower response to maintain stability. Furthermore, the CSCR
capabilities indicated here are based on GE preferred converter configuration. If local grid codes require a different
converter configuration for a project, the minimum CSCR capability may be higher than stated here.
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
8/28 Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08
- Original Document -
NOTE
The CSCR capability described above depends on active and reactive current
provision from the turbine during LVRT and ZVRT events. If during such
disturbances certain limits to inject active and/or reactive current are required as
a special exception, project specific CSCR capability information according to
these conditions can be provided on request.
If a grid operator has a concern on the short circuit ratio, GE can provide a black box PSCAD model of the wind farm
that can be used for transient simulations of the network for the purpose of determining expected performance. If a
grid operator decides to perform such a study, it is essential that GE be involved to highlight how changes within the
product capability can achieve the desired performance. Alternatively, If the grid operator can define the
requirements for such a study and is willing to provide GE with the details of the network, then GE Energy Consulting
can be contracted to perform the study.
The wind turbine system protection is designed for a minimum short circuit of 40 MVA at the turbine medium
voltage (MV) terminals.
An option for expanded reactive power capability 0.87 leading to 0.87 lagging under de-rated conditions is available
upon request for 50 Hz only. This wider reactive power capability could help meet a 0.95 power factor requirement at
the point of interconnection. Under Noise Reduced Operation (NRO) modes, depending on ambient conditions and
grid voltage, the reactive power capability and/or the wind turbine generator system’s power output may be
affected. Please refer to Appendix II for the reactive power capability diagram.
10 WindINERTIA
With the optional “WindINERTIA” feature, the Cypress Platform – 50 and 60 Hz wind turbines can provide inertia-
based Fast Frequency Response (FFR) to help stabilizing grid frequency. This feature supports the grid during under
frequency events by providing a temporary increase in power production (5-10% rated power increase) for a short
duration (5-10 sec), contributing towards frequency recovery. This is e.g. achieved by tapping into the stored kinetic
energy in the rotor mass. The response can be configured based on requirements specified by the grid operator. For
the 5.8MW and higher ratings there is a reduced WindINERTIA capability around rated power (~ 11-13 m/s). Full
WindINERTIA capability is available as an option.
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08 9/28
- Original Document -
GE Renewable Energy Grid Interconnection
Coordination with grid authorities on performance requirements may be needed for projects with series-
compensation, as certain converter configurations designed to meet regional grid codes may adversely impact
performance/stability when used in series-compensated applications.
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
10/28 Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08
- Original Document -
WindCONTROL is available with the following optional grid friendly features (see WindCONTROL overview for more
info):
13 Harmonic Distortion
Harmonic distortion data for respective 50 Hz and 60 Hz machines are presented relevant to IEC and IEEE
requirements.
Switching procedures: The Cypress wind turbine does not have any significant in-rush kmax = Imax/InG = 1
(parameter as per IEC 61400-21).
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08 11/28
- Original Document -
GE Renewable Energy Grid Interconnection
Voltage @ PCC 3 < h < 11 11 ≤ h < 17 17 ≤ h < 23 23 ≤ h < 35 35 < h ≥ 50 Current TDD %
14 System Modeling
14.1 Wind Turbine Short Circuit Modeling
The Cypress wind turbine generator is a doubly-fed asynchronous generator with the stator directly connected to
the grid while the rotor is interfaced through a frequency converter to the grid. For most faults that occur on the grid,
the turbine will act as a controlled current source- contributing up to 3 per unit fault current for up to 5 cycles, after
which it returns to normal current contribution (i.e. 1 per unit). For faults on the grid, the contribution from the
turbines is minimal compared to that from the grid.
One exception is for “close in” faults (e.g.: inside the wind farm, at the wind farm substation etc.) where, depending
on the severity, the converter may “crowbar” (i.e. short-circuit itself to protect the power electronics within). In this
case the turbine rotor is short circuited like that of a squirrel cage induction generator.
According to the IEC 60909-0 ed. 2 the behavior can be calculated by applying the following parameters:
KWd factor for the calculation of the peak short-circuit current 1.7
Table 4: Parameters for the calculation of short circuit currents according to IEC 60909-0 ed. 2
Parameters for other rated voltages at WTGS transformer primary connection can be inter- or extrapolated
accordingly.
If other short circuit current calculation methods should be applied, the WTGS behavior can be approximated by
X’’ = 0.2, contributing a max of 5.0 per unit fault current given for the secondary/ tertiary side of the WTGS
transformer.
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
12/28 Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08
- Original Document -
15 Power Demand
The Power demand of the wind turbine generator system during calm wind periods can include e.g., yaw motor,
control system, lighting and hydraulic pump and amount to a maximum 80 kW if all loads are operating at the same
time.
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08 13/28
- Original Document -
GE Renewable Energy Grid Interconnection
Since charging capacitance plays a vital role in the level of protection that can be achieved, it is important that the
per turbine charging capacitance be calculated. In this calculation, the wind farm collection system and the portion of
the transmission lines outside the wind farm that may be part of the island should be considered. Guidelines for
calculation per turbine charging capacitance are provided in a GE white paper. Protection against an open-circuit
event is achieved if the per turbine charging capacitance is less than 1600 kVAR at the time of the event.
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
14/28 Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08
- Original Document -
Rated
50 60 50 60 50 60 50 60 50 60 50 50 60 Hz
Frequency
Rated Voltage
690/6000 V
(Rotor/Stator)
Apparent
Power
5333 5555 5889 6111 6444 6666 6777 kVA
(@ PF = 0.90
lag)
Power Factor
± 0.90
– Standard
Power Factor–
± 0.87 na ± 0.87 na ± 0.87 na ± 0.87 na ± 0.87 na ± 0.87 ± 0.87 na
Optional
Max
Frequency 4 Hz/sec
Drift
Rated Short
Time
Withstand
20 kA
Current on the
MV side (1
sec)5
Rated
Lightning
Impulse IEC 61400-24 level I kA
Withstand
Current
Max Voltage
4 %
Imbalance
5
20 kA at -30 °C internal ambient temperature while the WTGS is connected to the grid. MVSG will be disconnected from grid automatically
during cold soak for ambient temperatures below -30 °C.
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08 15/28
- Original Document -
GE Renewable Energy Grid Interconnection
For any curve in the diagram: if the ambient temperature or the altitude is higher than specified for the particular
model, or if the voltage is outside of the specified range, then de-rating may be necessary to meet the demanded
reactive power output.
Voltage depending active and/or reactive power limitation as shown on PQ capability diagrams might occur within
the specified voltage range.
When the WTGS is in Noise Reduced Operation (NRO) mode of operation, the reactive power capability and power
output will be affected by the combination of ambient temperature and grid voltage.
When the plant level controller is in the voltage control or in the VAR control mode, and de rating is required due to
the conditions listed above, the turbines will operate with a Q priority i.e. they will sacrifice active power if necessary
to meet the reactive power demand up to the listed capability in normal operation. Under NRO mode operation, the
listed capability may be affected by ambient temperature and grid voltage.
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
16/28 Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08
- Original Document -
Figure 1: Reactive Power Capability 4.8 – 50/60 Hz standard 0.9 pf VAR capability below 40°C; 4.8 - 50 Hz the optional 0.87 pf VAR capability
below 30°C
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08 17/28
- Original Document -
GE Renewable Energy Grid Interconnection
Figure 2: : Reactive Power Capability: 5.0 – 50/60 Hz standard 0.9 pf VAR capability below 40°C; 5.0 - 50 Hz the optional 0.87 pf VAR capability
below 30°C
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
18/28 Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08
- Original Document -
Figure 3: Reactive Power Capability 5.3– 50/60 Hz standard 0.9 pf VAR capability below 40°C; 5.3 - 50 Hz the optional 0.87 pf VAR capability
below 30°C
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08 19/28
- Original Document -
GE Renewable Energy Grid Interconnection
Figure 4: Reactive Power Capability 5.5 – 50/60 Hz standard 0.9 pf VAR capability below 35°C; 5.5 - 50 Hz the optional 0.87 pf VAR capability
below 30°C
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
20/28 Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08
- Original Document -
Figure 5: Reactive Power Capability 5.8 – 50/60 Hz standard VAR capability pf 0.9 below 30°C
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08 21/28
- Original Document -
GE Renewable Energy Grid Interconnection
Figure 6 : Reactive Power Capability 5.8 – 50 Hz optional VAR capability pf 0.87 below 30°C
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
22/28 Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08
- Original Document -
Figure 7: Reactive Power Capability 6.0 – 50 Hz standard VAR capability 0.9 pf below 25°C
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08 23/28
- Original Document -
GE Renewable Energy Grid Interconnection
Figure 8: Reactive Power Capability 6.0– 50 Hz option VAR capability 0.87 pf below 25°C
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
24/28 Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08
- Original Document -
Figure 9: Reactive Power Capability 6.1 – 50 Hz standard VAR capability 0.9 pf below 25°C
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08 25/28
- Original Document -
GE Renewable Energy Grid Interconnection
Figure 10 Reactive Power Capability 6.1 – 60 Hz standard VAR capability 0.9 pf below 25°C
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
26/28 Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08
- Original Document -
Figure 11 Reactive Power Capability 6.1 – 50 Hz option VAR capability 0.87 pf below 25°C
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08 27/28
- Original Document -
GE Renewable Energy Grid Interconnection
NOTE
This plot represents the standard settings for voltage ride through which meet
most grid codes. This does not represent the complete capability of these
features
CONFIDENTIAL - Proprietary Information. DO NOT COPY without written consent from General Electric Company and/or its affiliates.
UNCONTROLLED when printed or transmitted electronically.
© 2021 General Electric Company and/or its affiliates. All rights reserved.
28/28 Grid_Interconnection_Documents_Cypress-xxHz_EN_Doc-0075452_08