Fault Indicator = FI
Terms and Data Concentrator Unit = DCU
Abbreviation Earth Fault Indicator = EFI (detect earth fault only)
Fault Indicator Type and Products
Power Distribution
Power Distribution-Line Type
0 T
T2
Note: when happened fault (current value change over ΔI for about ΔT ),
if less than 30 seconds the power come back, then this is transient fault.
For transient fault, the default reset time is 12 hours.
Working Principle-Permanent Fault
I
Time duration (ΔT) Empirical Value (according to
State Grid in China, both ΔI
And ΔT can be set) :
T1: charging time, ≥30 secs
Current ΔT: settable
change (ΔI) T2: recover time, ≥ 30 secs
ΔI ΔT
20-1200(defaut) 20ms-3000ms
T1 changeable
Normal Load
Current
0 T
T2
Note: when happened fault (current value change over ΔI for about ΔT ),
if over 30 seconds the power NOT come back, then this is permanent fault.
For permanent fault, the default reset time is 12 hours.
But also will immediately reset if power is back less than 12 hours
Working Principle-Normal Current
I
Time duration (ΔT)
Current
change (ΔI)
T1
Normal Load
Current
0 T
Note: when the load current change ΔI, but keeps the load current over ΔT, this is still the
normal current, not fault current.
How to locate faulty section
The fault is located between the last indicator that has been triggered and the
first indicator which is still inactive. The path of the fault current from the
feeding point to the fault location is marked by the triggered indicators.
Example: The diagram below indicate that the fault section is between the
point 5 and point 6
Fault indicator Underground Line Application
introduction Fault Indicator case
Local Type and Remote Type
Local (Mechanical) Type Remote Type
Application Level:
Central Station
(SCADA)
GPRS/3G/4G
Communication Level:
Data Concentrator Unit
(DCU)
RF433
Device Level: Mechanical Flag
Indicator (Sensor) Three color LED
battery (replaceable)
Local Type Overhead Fault Indicator
Model No.
Item
JJZ-HW-FP JJZ-HW-LED
Product Picture
According to different customer's requirements, Four-Faith has launched new type overhead line fault indicator recently.
We have improved the limitations of the old type and add more functions on the new model
Overhead Line Fault Indicator Monitoring System
Product Picture
According to different customer's requirements, Four-Faith has launched new type overhead line fault indicator recently.
We have improved the limitations of the old type and add more functions on the new model
Overhead Fault Indicator
Model No. When fault happens Indicator Response
Get power from the monitoring line only when the flowing
current is over 10A; if less than 10A, then use battery power.
Get power from the monitoring line only when the flowing current
is over 5A; if less than 5A, then use battery power.
Get power from the monitoring line only when the flowing current
is over 5A; if less than 5A, then use battery power.
*Hand-Held Tool is for model JYZ-FF V2.0 and JYZ-HW V2.0 only.
Installation
-The indicator can be mounted under live conditions with the help of an
adapter and a hot stick.
-Four-faith offer the adapter like below. Hot stick not offer since it is universal.
Where to install the Fault Indicators
• Near the derivations (T)
• Along the route of the feeder (installation of a fault indicator is suggested every 3 to 5 km)
g y f low
Ener ion
C
B
ct
dire
A
RF
flow
C
rg y
Ene tion
B
c A
dire
RF
Sectionalizer
Where to install the Fault Indicators
Voltage measurement
Detect energy loss in the line (theft).
Measure Load Unbalances.
Detect Driver Theft
High impedance faults.
Contributions of distributed generation to the fault.
Identify (Locate) Fault Section
Hot-stick Line-mountable √ √
Remote Reset/Indication √
Specification - Indicator
Item Local (Mechanical) Remote
Applicable voltage range 0.23~138KV
Applicable current range 0~600A
Applicable power frequency range 45~60Hz
0A~100A: ±3A
Sensitivity & Accuracy 100A~600A: ±3%
Static power consumption less than 20uA
Auto reset time 1~48h user-selectable
Identification of fault current duration 20ms~3000ms
MTBF more than 70000h
Impulse current withstand 31.5kA for 2s
Protection level IP67
Weight less than 500g
Outline dimension Ф75mm * 115mm
Minimum Installation Spacing Phase to phase:
>10 years (When flowing current is ≥10A, indicators can self-sustained from the
Indicator Battery Life monitoring line; when flowing current is <10A, indicators is powered by built-in
lithium batter)
Specification – DCU(Remote only)
Item
Communication with indicator distance 50m
DC adapter, solar panel, storage lithium battery (last about
Power supply
14 days without charging)
Maximum Indicator quantity 1 DCU can communicate with 9 indicators
Protocol IEC101/IEC104/DNP3.0
DCU IP type Dynamic IP/Fixed IP
Support Sim card quantity 1 card / 2card
Remote IP type Fixed IP/Fixed domain Name
DNS server support
Specification - Fault Location System (Remote only)
Main function
Map Locate Support Google Map
Mimics Diagram Support
Real time Fault alarm Support
Load current Support curve and list
Device manage Support add/delete/modify DCU and indicator
User manage Support add/delete/modify user
What data upload to SCADA system ?
Telemetry: Teleindication:
Teleindication:
Issue by Experiment and Verification Center, State Issue by EMC Lab. For Automation Equipment,
Grid Electric Power Research Institute, China State Grid Co. of China
*State Grid Corporation of China is the largest power utility in the world
*For the Details please refer to full version of test
Local & Remote Comparison
Communication
Don’t need need
commissioning
Remote monitoring
no yes
function
Fault indicator Overhead Line
introduction Application case
Fault Indicator
Appearance – Local Type
Display Unit (indicator panel)
3* short circuit indicator (red LED)
1* earth fault indicator (red LED)
1* battery status indicator (yellow LED)
1* button (for test and reset)
2DI/2DO/RS232(485)
1* DC power supply
Inside Battery
LED
Hardware: Server/Cloud
Battery (replaceable)
Software: Fault Indicate
RF module
System/Data base
DCU
Housing
RF module
Industrial modem
Network topology
Local (Mechanical) Type Remote Type
Application Level:
Central Station
(SCADA)
GPRS/3G/4G
Communication Level: (Can communication with RTU/FRTU,
Data Concentrator Unit protocol converter, IP modem, etc. by
(DCU) RS232/485, MODBUS)
RS232/RS485
MODBUS RF433
Device Level:
Indicator (Sensor)
Installation
Fault happen
For Local Type
*For the Remote type, please Refer to Overhead Line Remote Type
Chile-ENEL Project
ENEL SCADA Vertice System
(local power utility) (system integrator)
2 Remote
Center
More than
2000 sets
Fault indicator Overhead Line Underground Line
introduction Fault Indicator Fault Indicator
Chile
Chile
Thank you!