Liebert.

PEX Series Air Conditioner


Technical Manual

Version V1.1
Revision date 2008-03-24
BOM 31020723

Emerson Network Power provides customers with technical support. Users may contact the nearest
Emerson local sales office or service center.

Copyright © 2007 by Emerson Network Power Co., Ltd.


All rights reserved. The contents in this document are subject to change without notice.

Emerson Network Power Co., Ltd.


Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057, Shenzhen China
Homepage: www.emersonnetworkpower.com.cn
E-mail: support@emersonnetwork.com.cn
Contents

Chapter 1 Preface ............................................................................................................................................................... 1


1.1 Special Requirement Of Machine Room Environment.......................................................................................... 1
1.2 Liebert.PEX Series AC.......................................................................................................................................... 1
Chapter 2 Product Introduction ........................................................................................................................................... 3
2.1 Appearance .......................................................................................................................................................... 3
2.2 Model Description ................................................................................................................................................. 4
2.3 Features................................................................................................................................................................ 4
2.4 Standard Components .......................................................................................................................................... 5
2.4.1 Indoor Unit ................................................................................................................................................. 5
2.4.2 Outdoor Unit ............................................................................................................................................ 8
2.4.3 Controlling System .................................................................................................................................... 8
2.5 Optional Compoents ............................................................................................................................................. 9
Chapter 3 Technical Data.................................................................................................................................................. 11
3.1 Technical Data Of Air Cooled Units .................................................................................................................... 11
3.1.1 Technical Data Of Upflow Air Cooled Units ............................................................................................. 11
3.1.2 Technical Data Of Downflow Air Cooled Units......................................................................................... 15
3.2 Technical Data Of Water Cooled Units ............................................................................................................... 19
3.2.1 Technical Data Of Upflow Water Cooled Units ........................................................................................ 19
3.2.2 Technical Data Of Downflow Water Cooled Units ................................................................................... 22
3.3 Application Conditons ......................................................................................................................................... 25
Chapter 4 Dimensions....................................................................................................................................................... 26
4.1 Mechanical Dimensions ...................................................................................................................................... 26
4.1.1 Indoor Units ............................................................................................................................................. 26
4.1.2 Outdoor Units .......................................................................................................................................... 31
4.2 Mounting Dase Frame Dimensions..................................................................................................................... 31
4.3 Plenum Dimensions ............................................................................................................................................ 32
4.4 Service Space..................................................................................................................................................... 33
Chapter 5 Instruction Of Application.................................................................................................................................. 34
5.1 Refrigerant Tubing System ................................................................................................................................. 34
5.1.1 General.................................................................................................................................................... 34
5.1.2 Piping....................................................................................................................................................... 35
5.1.3 Connection .............................................................................................................................................. 36
5.2 Water Cooled System ......................................................................................................................................... 37
5.2.1 General.................................................................................................................................................... 37
5.2.2 Piping....................................................................................................................................................... 38
5.2.3 Connection .............................................................................................................................................. 38
5.3 Air Cooled System .............................................................................................................................................. 39
5.3.1 General.................................................................................................................................................... 39
5.3.2 Piping....................................................................................................................................................... 40
5.4 Controller ............................................................................................................................................................ 40
5.4.1 Connection Of Mains Circuit .................................................................................................................... 40
5.4.2 Connection Of Controller ......................................................................................................................... 40
5.4.3 Multimachine And Group Control............................................................................................................. 41
Chapter 1 Preface 1

Chapter 1 Preface

This chapter mainly introduces the special requirement of machine room environment and the features of Liebert.PEX
series air conditioner (Liebert.PEX series AC for short).

1.1 Special Requirement Of Machine Room Environment


Precision environment control is critical to computer operation, which has strict requirements on the machine room
environment. The environment control that the general air conditioner (AC) cannot provide comprises the following
aspects:
Temperature control: The operation of computers and exchanges generates large amount of heat, whose density is
6~10 times larger than that in general offices. In order to optimize the equipment performance, the optimum
temperature of machine room is 22°C±1°C. So the AC unit must have sufficient cooling capacity and quick regulating
ability to prevent sharp change of temperature. Such requirements are beyond the ability of general AC.
Humidity control: Too high or too low humidity will damage the computer in computer room. Too high humidity will
condense the moisture in the computers and short or damage the computer hardware. When the humidity is too low,
the static accumulated in the machine room will make the computer unable to work or even crash. The general AC
cannot control the humidity within the required range.
Air flow / cleanness control: The operation of computers and exchanges generates large amount of heat. To
dissipate the heat, the AC should provide sufficient cooling air flow and long blowing distance. To be specific,
850~1020 m3/h air flow is required for each 3.5kW of cooling capacity. In addition, the strict requirement of air
cleanness requires that the AC should provide the air flow sufficient to circulate 30 times / hour, so as to filter the air.
Such requirements are also far beyond the ability of general AC.
Operation all year round: The general AC (cooling operation) is always used in summer, for 8h~10h each day. But
the machine room AC is required to work all the time throughout the year, and even in the winter when the outdoor
temperature is as low as -34°C.

1.2 Liebert.PEX Series AC


Liebert.PEX series AC is the professional AC of machine room. The models from 20kW ~ 100kW are available for big,
middle and small machine rooms. And precise temperature control, humidity control and reliability design can meet the
especial environment of machine room.
Precise temperature and humidity control: The temperature and humidity of Liebert.PEX series AC can set to ±1°C
and ±1%RH respectively. The intelligent micro-processing control technology can monitor the temperature change of
machine room in the past and take actions prior to the change, instead of passively responding to the environment
change.
Security and reliability: The machine room AC runs 24hrs a day, so the reliability is especially important. The
advanced micro-processing system of Liebert.PEX series AC can control the system automatically and minimize the
faults. The perfect functions of automatic alarm and diagnosis can protect the unit from malfunctions, and locate the
faults quickly, prolonging the system life span.
High performance: Liebert.PEX series AC uses Copeland scroll compressor with low vibration, low noise and high
reliability. Finned tube evaporator and the unique V-shaped distribution improve the efficiency of heat exchange. The
model-specific distributors can ensure the even distribution of refrigerant in each loop and improve the efficiency of
heat exchange. The elaborate system configuration can realize optimal system performance.
The comparisions between Liebert.PEX series AC and general AC are listed in Table 1-1.
Table 1-1 Comparisions between Liebert.PEX and genral AC
Key designed General AC Liebert.PEX series AC
Precision Generally ± 3°C ± 1°C, ± 1%RH
Humidity control Generally no humidity control Humidity and dehumidity control
Monitoring None Local and remote monitoring
Operation all year No refrigeration required in winter Refrigerating operation all year
Air filtering No standard requirement Compliant with ASHRAE 52-76

PeX Series AC Technical Data Manual


Key designed General AC Liebert.PEX series AC
Commissioning in factory Simple commissioning Strict commissioning
Control design Central processor Precision control

PeX Series AC Technical Data Manual


Chapter 2 Product Introduction 3

Chapter 2 Product Introduction

Liebert.PEX series AC is a medium- large size precision environmental control system and specially designed for the
cooling of electrical equipment. It features high reliability, high sensible heat ratio and big air flow to provide a sound
operational environment for the precision equipments (such as sensitive equipment, industrial processing equipment,
communication equipment and computers).
This chapter introduces the appearance, model designation, features, standard configuration and optional
components of Liebert.PEX series AC.

2.1 Appearance
The upflow indoor unit of Liebert.PEX series AC is shown in Figure 2-1.

Figure 2-1 Upflow indoor u nit of Liebert.PEX series AC (two bay)

The downflow indoor unit of Liebert.PEX series AC is shown in Figure 2-2.

Figure 2-2 Downflow indoor unit of Liebert.PEX series AC (two bay)

PeX Series AC Technical Data Manual


4 Chapter 2 Product Introduction

2.2 Model Description


The model description of Liebert.PEX series AC is shown in Figure 2-3.

P1 020 U W P M S 1 R
Humidity type: 0-none; R-infrared; S-steam generating
Reheat type: 0-none;1-one stage -standard;2-two stage
iCOM display: S-standard display; L-large display
Power supply: M-three phase/50Hz/400V
System configuration: R-R22 , scroll,2 compressors; P-R22, scroll,1 compressor
S-R407C,scroll, 2 compressors; Z-R407C, scroll,1compressor
Cooling type: A-air cooled; W-water cooled; G-glycol cooled
Air path: U-upflow; F-downflow; D-duct
Cooling capacity class: kW
Unit frame: 1-one bay; 2-two bay; 3-three bay
PEX series

Figure 2-3 Model description

2.3 Features
1. Type diversification
Liebert.PEX series AC is classified into air cooled series and water cooled series in terms of the cooling mode. Each
series is further classified into upflow type and downflow type in terms of the airflow mode. The diversified modes can
adjust to different installation and operation environments.
The water cooled series uses the plate heat exchanger with high performance, featuring compact structure, high
energy efficiency and low noise pollution to the outdoor environment.
The air cooled series can select Liebert.PEX condenser or Liebert low temperature outdoor unit CD(D)F_S series (low
temperature outdoor unit for short) according to the field conditions.
Liebert.PEX condenser is a new outdoor unit which features stable structure, low noise, stepless speed variation,
corrosion resistance aluminum structure, three-phase power supply and high efficiency; The low temperature outdoor
unit can reduce the noise pollution to the minimum while meeting the system cooling requirement. In addition, it can
modulate the system pressure and adjust to the lower outdoor temperature through the combined control of the fan
speed controller and the temperature switch.
2. Precision control
Liebert.PEX series AC can control the temperature and humidity accurately. The temperature and humidity can be set
to ±1°C and ±1%RH respectively.
3. High energy efficiency
Liebert.PEX series AC uses Copeland scroll compressor with high performance, unique V-shaped finned tube heat
exchanger, carefully designed liquid distributing and more rational inner distribution. Such design achieves more
evenly distributed air flow and more reasonably distributed refrigerant, greatly improving the heat exchanging
efficiency of the heat exchanger, and making AC unit more energy efficient.
4. Convenience and durability
Durable components, compact structure and low profile design; Unique frame secured with carbon steel rivets, is not
only stable and firm but can also dismantled easily for transportation in extreme conditions.; The frame contains two
layers, inside layer and outside layer, with fire insulation asbestos in between, contributing to good insulation
performance; The structures of one bay, two bay and three bay can be used by many conditions, and they reduce the
specification of some components consumed easily (for example drainer).
5. Infrared humidification
The Liebert.PEX series AC adopts an advanced infrared humidification technology to reduce the dependence on water
quality. The humidity control will be more precise and quicker.
6. Compatibility with green refrigerant
The system is compatible with R407C, to suit the international requirement on green refrigerant.
7. Multiple protections

PeX Series AC Technical Data Manual


Chapter 2 Product Introduction 5

Perfect automatic alarm and diagnosis function provide all-around protections for the AC unit effectively, prevent faults,
locate the faults more quickly and ultimately prolong the life span of the system.
8. Easy maintenance
The front doors make all components accessible from the front and save space. The maintenance of compressor,
plate heating exchanger and strainer, which adopt Rotalock connection model, is easy.

2.4 Standard Components

2.4.1 Indoor Unit


The Liebert.PEX series indoor unit consists of compressor, evaporator, thermal expansion valve, fan, sight glass, filter
drier, infrared humidifier, heater element, safety controlling device, filter and water leak detecting system. The water
cooled model also contains the plate heating exchanger with high performance and water regulating valve.
Compressor
The Copeland scroll compressor (as shown in Figure 2-4) features low vibration, low noise and high reliability. The
connection model of Rotalock makes the maintenance easier.

Figure 2-4 Compressor

Evaporator
The finned tube evaporator with high heat dissipation efficiency, The distributor designed specifically for each model
makes sure that the refrigerant is distributed evenly in each loop.
Thermal expansion valve
The thermal expansion valve with external equalizer (as shown in Figure 2-5) can automatically regulate the flow of
refrigerant according to the operation condition of refrigeration system when the ambience temperature changes and
optimize the performance of unit.

Figure 2-5 Thermal expansion valve

PeX Series AC Technical Data Manual


6 Chapter 2 Product Introduction

Fan
The centrifugal fan of high performance and reliability is shown in Figure 2-6. It drives by the belt and features big
airflow, long distance, long airflow distance, easy disassembly and convenient maintenance. The over heat protecting
device can protect the motor effectively. The advanced no air flow protection can sense the reduce of airflow that
results from abnormal operation of the belt or motor and stop the refrigeration, heating or humidifying, with generating
the alarm signal.

Figure 2-6 Fan

Sight glass
The sight glass is the window of system cycle. You can observe the state of refrigerant and detect the moisture content
of system. The color will change from green to yellow, when the moisture content of system exceeds.
Filter drier
The filter drier (as shown in Figure 2-7) can effectively eliminate the moisture in refrigeration system. At the same time
it can filter out the impurity in system and make sure that the system can operate normally.

Figure 2-7 Filter drier

Infrared humidifier
The infrared humidifier (as shown in Figure 2-8) is controlled by the microprocessor. It features simple structure and
easy for disassembly, cleaning and maintenance. The quartz light, hanged over the moistening water pan of stainless
steel, eradiate the far ultrared ray and ultrared ray. In 5 ~ 6 minutes, these rays make the water molecule absorb the
辐射能 to cast off the strain of water and evaporate on the state of purity. The application of infrared humidifier
reduces the dependence on water quality. And the function of automatic swashing makes the water pan cleaner.

Figure 2-8 Infrared humidifier

PeX Series AC Technical Data Manual


Chapter 2 Product Introduction 7

Heater element
The screw finned U type heater is made of stainless steel (as shown in Figure 2-9). Its radiating speed is quick, and
the thermal value is even. The thermal value doesnot only keep the dry bulb temperature, but also compensate the
temperature drop caused by dehumidifying to make the lower surface temperature of heater to prevent the air from
forming ionization and prolong its using life.

Figure 2-9 Heater element

Safety controlling device


Each cooling system contains high pressure protection device, low pressure protection device and discharge
temperature protection device. When the discharge pressure or discharge temperature of compressor exceeds, it will
generate urgent alarm and protect the refrigeration system. When the suction pressure of compressor is too low
tooperate normally, alarms will be generated and the protection device will be triggered. The over heat protecting relay
fixed on each fan will protect the fan in time, when the fan is overloaded. The no air flow switch and the filter clogging
switch can monitor the air flow system of the AC in real time.
Filter
The system uses standard filter, which is easy to replace. The efficiency level G4 (EN 799) and the average efficiency
of up to 90% (ASHRAE52.1-1992) ensures the cleanness of machine room.
Water leak detecting system
The advanced water leak detecting system can supply the alarm information to AC unit or a stand-alone monitoring
system.
Plate heat exchanger (only for water cooled series)
The system uses the brazed plate heat exchanger with the function of automatic cleaning (as shown in Figure 2-10). It
features compact structure and high heat exchanging efficiency.

Figure 2-10 Plate heat exchanger

PeX Series AC Technical Data Manual


8 Chapter 2 Product Introduction

Water regulating valve (only for water cooled series)


The water regulating valve (as shown in Figure 2-11) regulates the valve position, controls the rate of discharge of
water of the plate heat exchanger and keeps the unchanged condensing pressure and condensing temperature,
according to the high pressure signal, to make the operation of system more steady.

Figure 2-11 Water regulating valve

2.4.2 Outdoor Unit


The outdoor unit is only for Liebert.PEX air cooled series AC.
Liebert.PEX condenser
Liebert.PEX condenser is the newly standard configurable outdoor unit of Liebert.PEX air cooled AC. It adopts
corrugated finned tube heat exchanger which features high heat dissipation efficiency, convenient cleaning and
maintenance. External rotor axial fan with unique ‘sickle’ shape metal fan has the superior aerodynamic property. The
six and eight pole fan makes the air flow noise through the significant reduction. The high performance three-phase
motor, which is customized for the base station power grid environment, can applicable to the wide voltage range and
has the higher reliability. The advanced fan speed control system regulates the voltage output by detecting the
condensing pressure of system to control the fan speed outdoors, adapting the system pressure and heat load. It
makes sure that the AC unit can operate stably, reliably and efficiently.
Low temperature outdoor unit
The low temperature outdoor unit adopts six-level fan to reduce the noise, and increases the heat exchanging area of
condenser to make up the reduction of heat exchanging ability resulting from the reduction of the fan airflow.
It adopts both P66 fan speed controller and temperature switch to realize the low ambience refrigeration for operation
down to -29°C.

2.4.3 Controlling System


The microprocessor of Liebert.PEX series AC is designed for the special requirement of machine room. It features
good stability, high controlling precision and intelligence.
The front door of indoor unit provides the operating panel. The simple operating interface makes the operators
observe easily and deal with problems in time. This system also supports the multi-unit controlling model, and realizes
extension content intelligently. The more reserved interfaces can realize many monitoring types. The microprocessor
panel is shown in Figure 2-12.

PeX Series AC Technical Data Manual


Chapter 2 Product Introduction 9

Figure 2-12 The microprocessor panel

LCD screen
The microprocessor of Liebert.PEX series AC adopts 128 × 64 dot matrix, blue backlight LCD screen to display the
present temperature, humidity, setting value, the percentage graph of unit output (fan, compressor, refrigeration,
heating, desiccation, and humidity) and alarm information. You can browse or set all setting values, event records,
graph data, sensor data and alarm setting through the screen. The backlight of LCD screen is designed for saving
energy. If there is not key operation over some time (the factory default is 5 minutes, configured by the menu), the
backlight will be off. Once any key is pressed, the backlight is on.
Microprocessor
The advanced microprocessor makes Liebert.PEX series AC control the temperature and humidity of the machine
room accurately. Its features are as follows:
z Easy operation interface, multiple code protection to prevent unlawful operation.
z The controller has the restoration of a power-down and high, low voltage protection function.
z Getting the operating time of important components by the menu.
z Malfunction diagnosis system of expert class can automatically display the present malfunction information to
make the maintenance easy.
z 400 historical records, the type contains MESSAGE, WARNING and ALARM.
z RS485 interface. Adopting the communication protocol of industry information department.
The microprocessor can monitor and configure the following parameters:
z Temperature: temperature setting value, the range is 5°C ~ 40°C.
z Humidity: humidify setting value, the range is 20%RH~80%RH.
z Humidity control: humidify controlling model selected, the model contains Pred, Comp, Rel.
z Air temperature limit enabling: Enable and Disable can be selected.
z Air temperature limit: the setting value, the range is 5°C ~ 25°C.
Alarm Signal
The microprocessor is capable of generating audible/visual alarm. The normal signals contain: high temperature alarm,
low temperature alarm, high humidity alarm, low humidity alarm, high pressure alarm, low pressure alarm, drainer
blockage alarm, no air flow alarm and some defined alarms.

2.5 Optional Compoents


Two-stage electrical heater
The model of the two-stage heater contains: 2.0 kW × 3 (for one bay system), 3.0 kW × 3 (for two bay system), 4.0 kW
× 3 (for three bay system). The two-stage heater can be selected by using environment and the Liebert.PEX AC model.
The two-stage heater can be divided into two levels by controlling of microprocessor. The heater element starts up
hierarchically by the condition of the machine room. Keeping the temperature, it can reduce the energy dissipation by
a long way.
Upflow plenum
The plenum dimensions of upflow units can be selected same as units. All plenums have grills to make the air flow
even. You also can regulate the grills manually. See 4.3 Plenum Dimensions for plenum dimensions.

PeX Series AC Technical Data Manual


10 Chapter 2 Product Introduction

Extended piping kit (air cooled models)


The extended piping kit is optional for long connecting line. The extended piping kit, by using both check valve and
solenoid valve, can prevent the refrigerant from returning and concentrating after the compressor donot run, and make
the system safer. The extended piping kit of long connecting pipe contains two models: 12 mm liquid line and 16 mm
liquid line.
Condenser pump
The condenser pump that can be fitted to the base of the AC unit contains tank, pump, motor and automatic controlling.
It is an assembly, and its delivery lift is 58 kpa (about 6m water column pressure).
Analog leak alarm
The area model, dot model leak detector can supply units or a stand-alone monitoring system with the analog alarm
signal to trigger the alarm of AC units and cut the humidify system. The zoster leakage alarm can accurately show the
leakage location.
Smoke detector
The smoke detector can trigger the alarm system at once and turn off the unit when smoke is detected.
Fire detecor
The fire detector is used to monitor the field return air temperature. Once it detects high temperature, it cuts off the AC
unit at once. It is indispensable to some key machine rooms.
High efficient filter
The high efficient drainer is available to the environment where the higher air cleanliness class is required.
Electrode humidifier
The electrode humidifier consists of discharge valve, controlling system and steam distributor. It makes the water
become the conductor of current, and form a loop by electrifying three electrodes in the humidifying bucket. The
temperature of water arises to boil and then the humidifying steam is produced. The advanced automatic flushing
controller can delay the using life of humidifier, and the knock-down humidifying bucket makes manual flushing and
maintenance easy.

PeX Series AC Technical Data Manual


Chapter 3 Technical Data 11

Chapter 3 Technical Data

This chapter mainly introduces the technical data of air cooled units and water cooled units, and the application conditions of AC units.

3.1 Technical Data Of Air Cooled Units

3.1.1 Technical Data Of Upflow Air Cooled Units


The technical data of upflow air cooled units is shown in Figure 3-1.
Table 3-1 The technical data of upflow air cooled units
Model
Type P1020U P1025U P1030U P1035U P2040U P2045U P2050U P2055U P2060U P2070U P3080U P3090U P3100U
A A A A A A A A A A A A A
Cooling
capacity 19.4 22.1 29.2 32.4 39.5 44.4 45.7 52 57.9 65.9 79.4 87.2 97.9
24°CdB
Cooling Sensible
50%RH
capacity and cooling
Sensible capacity 18.3 20.7 25.9 28 37.2 40.7 42 46.1 51.6 56.3 69.2 77.5 83.9
cooling Cooling
capacity capacity 19.3 21.9 28.1 31.8 39.8 42.9 44.5 49.7 56.4 63.5 76.7 83.5 96.5
24°CdB
(kW) Sensible
45%RH
cooling
capacity 19.1 21.7 27.4 29.9 39.5 42.6 44.2 48.8 55.1 59.7 73.5 82.2 89.9
Standard flow
volume (m3/h) 5400 6300 7866 7920 10440 11610 12240 13032 15390 15480 19188 22770 22860
Fan Fan number 1 1 1 1 2 2 2 2 2 2 3 3 3
Static pressure out
25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200
of unit (Pa)
Compressor1 Number 1 1 1 1 2 2 2 2 2 2 3 3 3
Evaporator Upwind arae (m2) 0.42 0.42 0.42 0.42 0.92 0.92 0.92 0.92 0.92 0.92 1.43 1.43 1.43
coil2 Face velocity (m/s) 1.7 1.9 2.3 2.3 1.6 1.7 1.7 1.9 2.1 2.1 2.1 2.1 2.1
Electric
Power (kW) 6 6 6 6 9 9 9 9 9 9 12 12 12
heater 3

PeX Series AC Technical Data Manual


Chapter 3 Technical Data 12

Model
Type P1020U P1025U P1030U P1035U P2040U P2045U P2050U P2055U P2060U P2070U P3080U P3090U P3100U
A A A A A A A A A A A A A
Humidifying
4.5 4.5 4.5 4.5 10 10 10 10 10 10 10 10 10
Infrared capacity (kg/h)
humidifier Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles
Humidifying pan
s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel
666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816
Dimension (mm)
Drainer 4 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95
Number 1 1 1 1 2 2 2 2 2 2 3 3 3
Liquid return line
16 16 16 16 16 16 16 16 16 16 16 16 16
(mm)
Interface Dicharge line (mm) 22 22 22 22 22 22 22 22 22 22 22 22 22
dimensions Infrared humidifier
6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35
of indoor unit water in line (mm)
Condenser water
19 19 19 19 19 19 19 19 19 19 19 19 19
out line (mm)
Net weight (kg) 320 330 340 350 590 560 610 570 640 650 910 930 950
FLA5(A) AWG10 AWG10 AWG9 AWG9 AWG7 AWG7 AWG7 AWG6 AWG6 AWG6 AWG5 AWG5 AWG5
Air braker 32 32 40 40 63 63 63 63 80 80 100 100 100
Electrical
Reconmended
parameter AWG10 AWG10 AWG9 AWG9 AWG7 AWG7 AWG7 AWG6 AWG6 AWG6 AWG5 AWG5 AWG5
cable specification6
(5.26) (5.26) (6.6) (6.6) (10.6) (10.6) (10.6) (13.3) (13.3) (13.3) (16.4) (16.4) (16.4)
(mm2)
Notes:
1: Scroll compressor, R22 refrigerant (compatible with R407C).
2: V type, copper tube, aluminiun fin.
3: Helical fin, U type stainless steel, electrical heater.
4: Based on ASHRAE52.1-1992, the average filter efficiency is more than 90%, and the filter efficiency class is G4 (EN779).
5: The full load curent of unit. The maximum full load current value of unit is not the sum of rated maximm full load current value of all components, but the sum of rated maximm full load current
value of the operating components which may operate at the same time on the working condition of maximum load.
6. The using temperature of the recommended calbe is 25°C. Please match yourself according to the site condition or consult the Rearch & Development Dept of Emerson if the environment
temperature exceeds

PeX Series AC Technical Data Manual


Chapter 3 Technical Data 13

The condensers’ technical data of upflow air cooled units is as follows:

Note
Please consult the corresponding Rearch & Development Dept of Emerson, if the data, which you need, is not included in preceding tables.

1. Technical data of Liebert.PEX condenser


The technical data of Liebert.PEX condenser is listed in Table 3-2 and Table 3-3.
Table 3-2 Technical data of Liebert.PEX condenser (R22, environment temperature 35°C)
Model of condenser Corresponding indoor unit model Fan number Net weight (kg) Connection size of liquid pipe (mm) Connection size of discharge pipe (mm)
LSF24 P1020UA 1 105 16 22
LSF32 P1025UA 1 110 16 22
LSF38 P1030UA 1 120 16 22
LSF42 P1035UA 1 130 16 22
LSF24×2 2 210 16 22
P2040UA
LDF42 1 130 16 22
LSF52 P2045UA 1 140 16 22
LSF32×2 2 220 16 22
P2050UA
LDF52 1 140 16 22
LSF62 P2055UA 2 150 22 28
LSF38×2 2 240 16 22
P2060UA
LDF62 2 160 22 28
LSF42×2 P2070UA 2 260 16 22
LSF52×2 P3080UA 2 280 16 22
LSF52×2 P3090UA 2 280 16 22
LSF62×2 P3100UA 4 300 22 28

Table 3-3 Technical data of Liebert.PEX condenser (R407, environment temperature 35°C)
Model of condenser Corresponding indoor unit model Fan number Net weight (kg) Connection size of liquid pipe (mm) Connection size of discharge pipe (mm)
LSF32 P1020UA 1 110 16 22
LSF38 P1025UA 1 120 16 22
LSF42 P1030UA 1 130 16 22
LSF52 P1035UA 1 140 16 22
LSF32×2 2 220 16 22
P2040UA
LDF52 1 140 16 22
LSF62 P2045UA 2 150 22 28

PeX Series AC Technical Data Manual


Chapter 3 Technical Data 14

Model of condenser Corresponding indoor unit model Fan number Net weight (kg) Connection size of liquid pipe (mm) Connection size of discharge pipe (mm)
LSF38×2 2 240 16 22
P2050UA
LDF62 2 160 16 22
LSF70 P2055UA 2 160 22 28
LSF42×2 P2060UA 2 260 16 22
LSF52×2 P2070UA 2 280 16 22
LSF52×2 P3080UA 2 280 16 22
LSF62×2 P3090UA 4 300 22 28
LSF70×2 P3100UA 4 320 22 28
2. Technical data of low temperature outdoor unit
The technical data of low temperature outdoor unit is listed in Table 3-4 and Table 3-5.
Table 3-4 Technicla data of low temperature outdoor unit (R22, environment temperature 35°C)
Model of condenser Corresponding indoor unit model Fan number Power (kW) Net weight (kg) Connection size of liquid pipe (mm) Connection size of discharge pipe (mm)
P1020UA/
CSF078S 2 0.6 73 19 25.4
P1025UA
CSF113S P1030UA 2 0.6 97 19 25.4
CSF141S P1035UA 3 0.8 110 19 25.4
CSF078SX2 4 1.1 146 19 25.4
P2040UA
CDF141S 3 0.8 110 19 25.4
CSF171S P2045UA 4 1.1 135 19 25.4
CSF078SX2 4 1.1 146 19 25.4
P2050UA
CDF171S 4 1.1 135 19 25.4
CSF194S P2055UA 4 1.1 162 19 25.4
CSF113SX2 P2060UA 4 1.1 196 19 25.4
CSF141SX2 P2070UA 6 1.7 220 19 25.4
CSF171SX2 P3080UA 8 2.2 270 19 25.4
CSF194SX2 P3090UA 8 2.2 270 19 25.4
CSF194S X2 P3100UA 8 2.2 324 19 25.4
Note:
The low temperature outdoor of double system is not recommended in the region where the outdoor temperature is lower than -15°C

Table 3-5 Technicla data of low temperature outdoor unit (R407C, environment temperature 35°C)
Model of condenser Corresponding indoor unit model Fan number Power (kW) Net weight (kg) Connection size of liquid pipe (mm) Connection size of discharge pipe (mm)
CSF078S P1020UA 2 0.6 73 19 25.4
CSF113S P1025UA 2 0.6 97 19 25.4
CSF141S P1030UA 3 0.8 110 19 25.4
CSF171S P1035UA 4 1.1 135 19 25.4

PeX Series AC Technical Data Manual


Chapter 3 Technical Data 15

Model of condenser Corresponding indoor unit model Fan number Power (kW) Net weight (kg) Connection size of liquid pipe (mm) Connection size of discharge pipe (mm)
CSF078S×2 4 1.1 146 19 25.4
P2040UA
CDF171S 4 1.1 135 19 25.4
CSF194S P2045UA 4 1.1 162 19 25.4
CSF113S×2 4 1.1 196 19 25.4
P2050UA
CDF194S 4 1.1 162 19 25.4
CSF141S×2 P2060UA 6 1.7 220 19 25.4
CSF171S×2 P2070UA 8 2.2 270 19 25.4
CSF171S×2 P3080UA 8 2.2 270 19 25.4
CSF194S×2 P3090UA 8 2.2 324 19 25.4
Note:
The low temperature outdoor of double system is not recommended in the region where the outdoor temperature is lower than -15°C

3.1.2 Technical Data Of Downflow Air Cooled Units


The technical data of downflow air cooled units is listed in Table 3-10.
Table 3-6 Technical data of downflow air cooled units

Model
Type P1020F P1025F P1030F P1035F P2040F P2045F P2050F P2055F P2060F P2070F P3080F P3090F P3100F
A A A A A A A A A A A A A
Cooling
capacity 20 23.1 30.1 33.1 41 45 46.4 53.2 60.6 66.9 81.4 89.3 100
24°CdB
50%RH Sensible
Cooling
cooling
capacity and
capacity 18.9 21.5 26.6 29.4 38.5 41.7 43.2 47.3 53.5 59 71.1 79.6 88.4
Sensible
cooling Cooling
capacity (kW) capacity 19.7 22.4 28.8 31.8 40.4 44 45.6 51.6 58.2 64.6 78.6 85.5 97.9
24°CdB
45%RH Sensible
cooling
capacity 19.5 22.2 28.1 31.2 40.1 43.6 45.2 50.5 56.7 62.7 75.6 84.3 94.5
Standard flow
volume (m3/h) 5670 6660 8280 8190 10980 12240 12960 13680 16200 16020 20160 23940 23760
Number 1 1 1 1 2 2 2 2 2 2 3 3 3
Fan
Static
pressure out of unit 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200
(Pa)

PeX Series AC Technical Data Manual


Chapter 3 Technical Data 16

Model
Type P1020F P1025F P1030F P1035F P2040F P2045F P2050F P2055F P2060F P2070F P3080F P3090F P3100F
A A A A A A A A A A A A A

Compressor1
Number 1 1 1 1 2 1 2 1 2 2 2 2 2
Evaporator Upwind arae (m2) 0.42 0.42 0.42 0.42 0.92 0.92 0.92 0.92 0.92 0.92 1.43 1.43 1.43
coil2 Face velocity (m/s) 1.7 1.9 2.3 2.3 1.6 1.7 1.7 1.9 2.1 2.1 2.1 2.1 2.1
Electric
Power (kW) 6 6 6 6 9 9 9 9 9 9 12 12 12
heater 3
Humidifying
4.5 4.5 5 5 10 10 10 10 10 10 10 10 10
Infrared capacity (kg/h)
humidifier Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles
Humidifying pan
s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel
790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790
Dimension (mm)
Drainer4 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95
Number 1 1 1 1 2 2 2 2 2 2 3 3 3
Liquid return line
16 16 16 16 16 16 16 16 16 16 16 16 16
(mm)
Interface Dicharge line (mm) 22 22 22 22 22 22 22 22 22 22 22 22 22
dimensions Infrared humidifier
6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35
of indoor unit water in line (mm)
Condenser water
19 19 19 19 19 19 19 19 19 19 19 19 19
out line (mm)
Net weight (kg) 320 330 340 350 590 560 610 570 640 650 910 930 950
FLA5 (A) 25.5 28 34.1 38 50.5 55.6 56.4 61.5 69.8 77.6 89.4 94.4 97.8
Air braker 32 32 40 40 63 63 63 63 80 80 100 100 100
Electrical
Recommended
parameter AWG10 AWG10 AWG9 AWG9 AWG7 AWG7 AWG7 AWG6 AWG6 AWG6 AWG5 AWG5 AWG5
calbe specification6
(5.26) (5.26) (6.6) (6.6) (10.6) (10.6) (10.6) (13.3) (13.3) (13.3) (16.4) (16.4) (16.4)
(mm2)
Notes:
1: Scroll compressor, R22 refrigerant (compatible with R407C).
2: V type, copper tube, aluminiun fin.
3: Helical fin, U type stainless steel, electrical heater.
4: Based on ASHRAE52.1-1992, the average filter efficiency is more than 90%, and the filter efficiency class is G4 (EN779).
5: The full load curent of unit. The maximum full load current value of unit is not the sum of rated maximm full load current value of all components, but the sum of rated maximm full load current
value of the operating components which may operate at the same time on the working condition of maximum load.
6. The using temperature of the recommended calbe is 25°C. Please match yourself according to the site condition or consult the Rearch & Development Dept of Emerson if the environment
temperature exceeds

PeX Series AC Technical Data Manual


Chapter 3 Technical Data 17

The condensers’ technical data of downflow air cooled units are as follows:

Note
Please consult the corresponding Rearch & Development Dept of Emerson, if the data, which you need, is not included in preceding tables.

1. Technical data of Liebert.PEX condenser


The technical data of Liebert.PEX condenser is listed in Table 3-7 and Table 3-8.
Table 3-7 Technical data of Liebert.PEX condenser (R22, environment temperature 35°C)
Model of condenser Corresponding indoor unit model Fan number Net weight (kg) Connection size of liquid pipe (mm) Connection size of discharge pipe (mm)
LSF24 P1020FA 1 105 16 22
LSF32 P1025FA 1 110 16 22
LSF38 P1030FA 1 120 16 22
LSF42 P1035FA 1 130 16 22
LSF24×2 2 210 16 22
P2040FA
LDF42 1 130 16 22
LSF52 P2045FA 1 140 16 22
LSF32×2 2 220 16 22
P2050FA
LDF52 1 140 16 22
LSF62 P2055FA 2 150 22 28
LSF38×2 2 240 16 22
P2060FA
LDF62 2 160 22 28
LSF42×2 P2070FA 2 260 16 22
LSF52×2 P3080FA 2 280 16 22
LSF52×2 P3090FA 2 280 16 22
LSF62×2 P3100FA 4 300 22 28

Table 3-8 Technical data of Liebert.PEX condenser (R407C, environment temperature 35°C)
Model of condenser Corresponding indoor unit model Fan number Net weight (kg) Connection size of liquid pipe (mm) Connection size of discharge pipe (mm)
LSF32 P1020FA 1 110 16 22
LSF38 P1025FA 1 120 16 22
LSF42 P1030FA 1 130 16 22
LSF52 P1035FA 1 140 16 22
LSF32×2 2 220 16 22
P2040FA
LDF52 1 140 16 22
LSF62 P2045FA 2 150 22 28

PeX Series AC Technical Data Manual


Chapter 3 Technical Data 18

Model of condenser Corresponding indoor unit model Fan number Net weight (kg) Connection size of liquid pipe (mm) Connection size of discharge pipe (mm)
LSF38×2 2 240 16 22
P2050FA
LDF62 2 160 16 22
LSF70 P2055FA 2 160 22 28
LSF42×2 P2060FA 2 260 16 22
LSF52×2 P2070FA 2 280 16 22
LSF52×2 P3080FA 2 280 16 22
LSF62×2 P3090FA 4 300 22 28
LSF70×2 P3100FA 4 320 22 28

2. Technical data of low temperature outdoor unit


The technical data of low temperature outdoor unit are listed in Table 3-9 and Table 3-10.
Table 3-9 Technical data of low temperature outdoor unit (R22, environment temperature 35°C)
Model of condenser Corresponding indoor unit model Fan number Power (kW) Net weight (kg) Connection size of liquid pipe (mm) Connection size of discharge pipe (mm)
CSF078S P1020FA/P1025FA 2 0.6 73 19 25.4
CSF113S P1030FA 2 0.6 97 19 25.4
CSF141S P1035FA 3 0.8 110 19 25.4
CSF078SX2 4 1.1 146 19 25.4
P2040FA
CDF141S 3 0.8 110 19 25.4
CSF171S P2045FA 4 1.1 135 19 25.4
CSF078SX2 4 1.1 146 19 25.4
P2050FA
CDF171S 4 1.1 135 19 25.4
CSF194S P2055FA 4 1.1 162 19 25.4
CSF113SX2 P2060FA 4 1.1 196 19 25.4
CSF141SX2 P2070FA 6 1.7 220 19 25.4
CSF171SX2 P3080FA/P3090FA 8 2.2 270 19 25.4
CSF194SX2 P3100FA 8 2.2 324 19 25.4
Note:
The low temperature outdoor of double system is not recommended in the region where the outdoor temperature is lower than -15°C

Table 3-10 Technical data of low temperature outdoor unit (R407C, environment temperature 35°C)
Model of condenser Corresponding indoor unit model Fan number Power (kW) Net weight (kg) Connection size of liquid pipe (mm) Connection size of discharge pipe (mm)
CSF078S P1020FA 2 0.6 73 19 25.4
CSF113S P1025FA 2 0.6 97 19 25.4
CSF141S P1030FA 3 0.8 110 19 25.4
CSF171S P1035FA 4 1.1 135 19 25.4

PeX Series AC Technical Data Manual


Chapter 3 Technical Data 19

Model of condenser Corresponding indoor unit model Fan number Power (kW) Net weight (kg) Connection size of liquid pipe (mm) Connection size of discharge pipe (mm)
CSF078S×2 4 1.1 146 19 25.4
P2040FA
CDF171S 4 1.1 135 19 25.4
CSF194S P2045FA 4 1.1 162 19 25.4
CSF113S×2 4 1.1 194 19 25.4
P2050FA
CDF194S 4 1.1 162 19 25.4
CSF141S×2 P2060FA 6 1.7 220 19 25.4
CSF171S×2 P2070FA 8 2.2 270 19 25.4
CSF171S×2 P3080FA 8 2.2 270 19 25.4
CSF194S×2 P3090FA 8 2.2 324 19 25.4
Note:
The low temperature outdoor of double system is not recommended in the region where the outdoor temperature is lower than -15°C

3.2 Technical Data Of Water Cooled Units

3.2.1 Technical Data Of Upflow Water Cooled Units


The technical data of upflow water cooled units is listed in Table 3-11.
Table 3-11 Technical data of upflow water cooled units
Model
Type P1020U P1025U P1030U P1035U P2040U P2045U P2050U P2055U P2060U P2070U P3080U P3090U P3100U
W W W W W W W W W W W W W
Cooling
capacity 19.4 22.1 29.2 32.4 39.5 44.4 45.7 52 57.9 65.9 79.4 87.2 97.9
24°CdB
Sensible
Cooling 50%RH
cooling
capacity and
capacity 18.3 20.7 25.9 28 37.2 40.7 42 46.1 51.6 56.3 69.2 77.5 83.9
Sensible
Cooling
cooling
capacity 19.3 21.9 28.1 31.8 39.8 42.9 44.5 49.7 56.4 63.5 76.7 83.5 96.5
capacity (kW) 24°CdB
Sensible
45%RH
cooling
capacity 19.1 21.7 27.4 29.9 39.5 42.6 44.2 48.8 55.1 59.7 73.5 82.2 89.9

PeX Series AC Technical Data Manual


Chapter 3 Technical Data 20

Model
Type P1020U P1025U P1030U P1035U P2040U P2045U P2050U P2055U P2060U P2070U P3080U P3090U P3100U
W W W W W W W W W W W W W
Standard flow volume
(m3/h) 5400 6300 7866 7920 10440 11610 12240 13032 15390 15480 19188 22770 22860
Fan Number 1 1 1 1 2 2 2 2 2 2 3 3 3
Static
25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200
pressure out of unit (Pa)

Compressor1
Number 1 1 1 1 2 1 2 1 2 2 2 2 2
Evaporator Upwind area (m2) 0.42 0.42 0.42 0.42 0.92 0.92 0.92 0.92 0.92 0.92 1.43 1.43 1.43
coil2 Face velocity (m/s) 1.7 1.9 2.3 2.3 1.6 1.7 1.7 1.9 2.1 2.1 2.1 2.1 2.1
Electric
Power (kW) 6 6 6 6 9 9 9 9 9 9 12 12 12
heater3
Humidifying capacity
4.5 4.5 5 5 10 10 10 10 10 10 10 10 10
Infrared (kg/h)
humidifier Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles
Humidifying pan
s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel
666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816
Dimension (mm)
Drainer4 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95
Number 1 1 1 1 2 2 2 2 2 2 3 3 3
water
regulating Dimension (inch) 1-1/4 1-1/4 1-3/8 1-3/8 1-1/4 1-3/8 1-1/4 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8
valve5
Quantity of water intake
(24°C)l/s 0.5 0.6 0.7 0.8 0.5 1.1 0.6 1.3 0.6 0.8 1.0 1.0 1.2
Pressure drop (kpa) 7.3 9.3 8.78 7.62 7.34 12.6 9.32 12.8 6.9 7.63 9.53 12 11.8
Condenser
Quantity of water intake
water supply
(30°C)l/s 0.9 1.0 1.3 1.5 0.9 2.0 1.0 2.4 1.2 1.5 1.7 1.9 2.3
require
Pressure drop (kpa) 22 28.3 26.6 23.3 22.2 38.4 28.2 39.3 20.9 23.2 29 36.4 36.1
Ment6
Quantity of water intake
(32°C)l/s 1.3 1.5 1.9 2.1 1.3 2.8 1.4 3.3 1.6 2.1 2.4 2.7 3.2
Pressure drop (kpa) 40.5 53.4 50 42.8 40.9 74.6 53.3 76.3 38.4 42.9 54.9 70.4 69.5

PeX Series AC Technical Data Manual


Chapter 3 Technical Data 21

Model
Type P1020U P1025U P1030U P1035U P2040U P2045U P2050U P2055U P2060U P2070U P3080U P3090U P3100U
W W W W W W W W W W W W W
Infrared humidifier water
6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35
in line (mm)
Interface Condenser water out line
19 19 19 19 19 19 19 19 19 19 19 19 19
dimensins of (mm)
indoor units Plate exchanger water
in/out line (screw thread, G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4
inch)
Net weight (kg) 375 385 395 399 647 557 691 599 700 710 850 857 867
FLA7(A) 22 24.3 28.5 31.5 44 46.2 47.3 51.8 55.1 60.9 68 73 84.2
Electrical Air braker 25 25 32 32 50 50 50 63 63 63 80 80 100
parameter Recommjended calbe AWG10 AWG10 AWG10 AWG9 AWG8 AWG8 AWG8 AWG7 AWG7 AWG7 AWG6 AWG6 AWG5
specification8 (mm2) (5.26) (5.26) (5.26) (6.6) (8.37) (8.37) (8.37) (10.6) (10.6) (10.6) (13.3) (13.3) (16.4)
Notes:
1: Scroll compressor, R22 refrigerant (compatible with R407C).
2: V type, copper tube, aluminiun fin.
3: Helical fin, U type stainless steel, electrical heater.
4: Based on ASHRAE52.1-1992, the average filter efficiency is more than 90%, and the filter efficiency class is G4 (EN779).
5. Standard pressure, the three way valve pressure is matched optional .
6. The water pressure designed is up to 1034Kpa at the temperature of 41°C (the water temperature is 37°C).
7: The full load curent of unit. The maximum full load current value of unit is not the sum of rated maximm full load current value of all components, but the sum of rated maximm full load current value of the
operating components which may operate at the same time on the working condition of maximum load.
8. The using temperature of the recommended calbe is 25°C. Please match yourself according to the site condition or consult the Rearch & Development Dept of Emerson if the environment temperature
exceeds

Note
1. The data in preceding Table is available for the refrigerant R407C.
2. Please consult professional engineers of factory, if water pressure exceeds 1.34 k pa.
3. Please consult the corresponding Rearch & Development Dept. of Emerson, if the data you need is not included in this Table.

PeX Series AC Technical Data Manual


Chapter 3 Technical Data 22

3.2.2 Technical Data Of Downflow Water Cooled Units


The technical data of downflow water cooled units is listed in Table 3-12.
Table 3-12 Technical data of floor downwater cooled units
Model
Type P1020F P1025F P1030F P1035F P2040F P2045F P2050F P2055F P2060F P2070F P3080F P3090F P3100F
W W W W W W W W W W W W W
Cooling
capacity 20 23.1 30.1 33.1 41 45 46.4 53.2 60.6 66.9 81.4 89.3 100
24°CdB
Sensible
Cooling 50%RH
cooling
capacity and
capacity 18.9 21.5 26.6 29.4 38.5 41.7 43.2 47.3 53.5 59 71.1 79.6 88.4
Sensible
Cooling
cooling
capacity 19.7 22.4 28.8 31.8 40.4 44 45.6 51.6 58.2 64.6 78.6 85.5 97.9
capacity (kW) 24°CdB
Sensible
45%RH
cooling
capacity 19.5 22.2 28.1 31.2 40.1 43.6 45.2 50.5 56.7 62.7 75.6 84.3 94.5
Standard flow
volume (m3/h) 5670 6660 8280 8190 10980 12240 12960 13680 16200 16020 20160 23940 23760
Number 1 1 1 1 2 2 2 2 2 2 3 3 3
Fan
Static
pressure out of 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200
unit (Pa)

Compressor1
Number 1 1 1 1 2 1 2 1 2 2 2 2 2
Evaporator Upwindarea (m2) 0.42 0.42 0.42 0.42 0.92 0.92 0.92 0.92 0.92 0.92 1.43 1.43 1.43
coil2 Face velocity (m/s) 1.7 1.9 2.3 2.3 1.6 1.7 1.7 1.9 2.1 2.1 2.1 2.1 2.1
Electric
Power (kW) 6 6 6 6 9 9 9 9 9 9 12 12 12
heater 3
Humidifying capacity
4.5 4.5 5 5 10 10 10 10 10 10 10 10 10
Infrared (kg/h)
humidifier Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles
Humidifying pan
s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel
790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790
Dimension (mm)
Drainer4 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95
Number 1 1 1 1 2 2 2 2 2 2 3 3 3
water
regulating Dimension (inch) 1-1/4 1-1/4 1-3/8 1-3/8 1-1/4 1-3/8 1-1/4 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8
valve5

PeX Series AC Technical Data Manual


Chapter 3 Technical Data 23

Model
Type P1020F P1025F P1030F P1035F P2040F P2045F P2050F P2055F P2060F P2070F P3080F P3090F P3100F
W W W W W W W W W W W W W
Quantity of water
intake (24°C)l/s 0.5 0.6 0.7 0.8 0.5 1.1 0.6 1.3 0.6 0.8 1.0 1.0 1.2
Pressure drop (kpa) 7.3 9.3 8.78 7.62 7.34 12.6 9.32 12.8 6.9 7.63 9.53 12 11.8
Condenser
Quantity of water
water supply
intake (30°C) l/s 0.9 1.0 1.3 1.5 0.9 2.0 1.0 2.4 1.2 1.5 1.7 1.9 2.3
require
Pressure drop (kpa) 22 28.3 26.6 23.3 22.2 38.4 28.2 39.3 20.9 23.2 29 36.4 36.1
ment6
Quantity of water
intake (32°C) l/s 1.3 1.5 1.9 2.1 1.3 2.8 1.4 3.3 1.6 2.1 2.4 2.7 3.2
Pressure drop (kpa) 40.5 53.4 50 42.8 40.9 74.6 53.3 76.3 38.4 42.9 54.9 70.4 69.5
Infrared humidifier
6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35
water in line (mm)
Interface Condenser water out
19 19 19 19 19 19 19 19 19 19 19 19 19
dimensins of line (mm)
indoor units Plate exchanger
water in/out line G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4
(screw thread, inch)
Net weight (kg) 375 385 395 399 647 557 691 599 700 710 599 857 867
FLA7 (A) 22 24.3 28.5 31.5 44 46.2 47.3 51.8 55.1 60.9 68 73 84.2
Air braker 25 25 32 32 50 50 50 63 63 63 80 80 100
Electrical
Recommended
parameter AWG10 AWG10 AWG10 AWG9 AWG8 AWG8 AWG8 AWG7 AWG7 AWG7 AWG6 AWG6 AWG5
cabel specification8
(5.26) (5.26) (5.26) (6.6) (8.37) (8.37) (8.37) (10.6) (10.6) (10.6) (13.3) (13.3) (16.4)
(mm2)
Notes:
1: Scroll compressor, R22 refrigerant (compatible with R407C).
2: V type, copper tube, aluminiun fin.
3: Helical fin, U type stainless steel, electrical heater.
4: Based on ASHRAE52.1-1992, the average filter efficiency is more than 90%, and the filter efficiency class is G4 (EN779).
5. Standard pressure, the three way valve pressure is matched optional .
6. The water pressure designed is up to 1034Kpa at the temperature of 41°C (the water temperature is 37°C).
7: The full load curent of unit. The maximum full load current value of unit is not the sum of rated maximm full load current value of all components, but the sum of rated maximm full load current
value of the operating components which may operate at the same time on the working condition of maximum load.
8. The using temperature of the recommended calbe is 25°C. Please match yourself according to the site condition or consult the Rearch & Development Dept of Emerson if the environment
temperature exceeds

Notes
1. The residual pressure out of units of downflow unit is 20pa.

PeX Series AC Technical Data Manual


Chapter 3 Technical Data 24

2. The data in preceding Table is available for R407C.


3. Please consult professional engineers of factory, if water pressure exceeds 1.34 kpa.
4. Please consult the corresponding Rearch & Development Dept. of Emerson, if the data you need is not included in this Table.

PeX Series AC Technical Data Manual


Chapter 3 Technical Data 25

3.3 Application Conditons


The application conditions of Liebert.PEX series AC are listed in Table 3-13.
Table 3-13 Using conditons
Item Condition
Indoor: 0°C~40°C
Environmental temperature Outdoor: 1. water cooled models: 4°C~+45°C
2. air cooled models: -34℃~+45℃
Protection class (outdoor uint) IP55
Aptitude <1000m
Operting voltage range 380V [-10% ~ +15%], 3P ~ 50Hz

Notes
Please consult professional engineer, whenever AC unit are used on the following conditions.
1. The AC unit voltages are over 10% or under 90% of the rated voltage.
2. The derating is required, if the aptitude exceeds 1000 m.

PeX Series AC Technical Data Manual


26 Chapter 4 Dimensions

Chapter 4 Dimensions

This chapter mainly introduces the mechanical dimensions of indoor units and outdoor units, the mounting set
dimensions of indoor units and the dimensions of plenums.

4.1 Mechanical Dimensions

4.1.1 Indoor Units


Mechanical dimensions of indoor units
Mechanical dimensions of indoor units are shown in Figure 4-1 and Figure 4-2.

PeX Series AC Technical Data Manual


Chapter 4 Dimensions 27

54 54
6 853 256
25 17
24 04
0
40
0

6
25
400 42
0
40
0

1970

1970
4

874
87

54 2
256 40
40
0
42
0 25
53
40
0
46
5
40
0
1970

4
87

Figure 4-1 Dimensions of upflow type unit (unit: mm)

PeX Series AC Technical Data Manual


28 Chapter 4 Dimensions

853

17
04

1970

1970
4

4
87

87

25
53

1970

4
87

Figure 4-2 Dimensions of downflow type unit (unit: mm)

PeX Series AC Technical Data Manual


Chapter 4 Dimensions 29

Cut-out location dimensions of bases


The cut-out location dimensions of bases are shown in Figure 4-3 and Figure 4-4. The side panels have been removed,
and the distance between the dashed lines and the rear panels is 25 mm, where is the fitting place of inner side panel.
160 530
4- 13
F
F

45
25
530

72
25
D WO /LL WI /DL
2- 35 109
80

IRWI 2- 64
40
200

67.5

164
F
F

72.5
45 72 45

One bay upflow series

120 730

F F
45

4- 13
25

25
683

166 81 WO /LL /D WI /DL 116

WI /DL /IRWI WO /LL P 40

60
186

F 4- 64 F
70

70

45 81 45

Two bay upflow series

120 730 1000 530

F F
F F
45

8- 13
25
683

72
166 WO /LL /D 25
81 WI/DL 116 WO/LL WI /DL
2- 35 109
80

WI /DL /IRWI WO /LL P 2- 40


143

67.5
186

P
164

F 6- 64 F
F F
70

72.5

45 81 90 72 45

Three bay upflow series


Figure 4-3 Cut-out location dimensions of upflow unit bases

IRWI:Infrared humidifier water in D: Drain P:Power cable entry(Φ30)


F: Unit set screw K:Knock-out LL/DL:Liquid line / discharge line (air cooled models)
WI/WO:Condenser water inlet and outlet (water cooled
models)

PeX Series AC Technical Data Manual


30 Chapter 4 Dimensions

160 530

45

26
F
F
4- 13

310
Fan aperture
530

195 410
25 25

160
70
D WI /DL 40
IRWI
WO /LL
80

67.5
P
2- 2- 64
35
143

86
F

72.5
45 75 45

One bay floor flow series

120 730
26
45

4- 13
F F
265
310

Fan aperture Fan aperture


25 25

410 301 .5

45 45
WO/LL /D WI /DL
4- 13
F WI /DL /IRWI F
4- 64
70

40
160

WO /LL P
45
123 80 80 148

Two bay floor flow series

1000 530
120 730
26

45
26

8-
3
F
F F F
265
310
310

Fan aperture Fan aperture Fan aperture


25

497.5 410
410 301.5 25
45 160
45 70
WI /DL
2- 40
WO /LL /D WI /DL
80

WO/LL P
F WI /DL /IRWI F
67.5

6- 64 2- 35
70
160

P
143

WO /LL F
86

F
72.5

123 80 80 148 45 75 45

Three bay floor flow series

Figure 4-4 Cut-out location dimensions of downflow unit bases

P:Power cable entry D:Drain


IRWI:Infrared humidifier water in K:Knock-out(250×120)
WI/WO:Condenser water inlet and outlet (water cooled models) LL/DL:Liquid line / discharge line (air cooled models)
F:Unit set screw

PeX Series AC Technical Data Manual


Chapter 4 Dimensions 31

Knock-out dimensions of side panel


The knock-out dimensions of side panel are shown in Figure 4-5.

Figure 4-5 Knock-out dimensions of side panel

4.1.2 Outdoor Units


Liebert.PEX condenser
Refer to Liebert.PEX Condenser Technical Manual for the structure parameters of Liebert.PEX condensers.
Low temperature outdoor unit
Refer to Low Temperature Outdoor Unit Technical Manual for the structure parameters of low temperature outdoor unit

4.2 Mounting Dase Frame Dimensions


The mounting base frame outline and dimensions of indoor unit are shown in Figure 4-6 and Table 4-1.
L

2 Rubber
82 washer Angle iron (60×60×3)
H
(8mm)

Adiabatic washer is affixed on the back of flow


Rubber washer Anchoring hole of
affixed around deflector 1.2mm zincification armor plate(5mm)
projecting stud (M8×6)
(3mm)

Supported armor plate(150mm×150mm×5mm)


Rubber washer(8mm)
Adiabatic washer(5mm)
Figure 4-6 Outline and dimensions
Table 4-1 Dimensions of mounting base frame (unit: mm)
Model L H
One bay 850 H = 150mm (upflow type unit)
Two bay 1700 H ≥ 200mm (downflow type unit, decided by the
Three bay 2550 ply of floor)
Note:
1. Only three bay units need the middle support legs (front and rear)
2. The upflow units need not flow deflector

Note
The holes of mounting base frame are drilled according to the factual anchoring holes, and the aperture is Φ10 mm.

PeX Series AC Technical Data Manual


32 Chapter 4 Dimensions

4.3 Plenum Dimensions


To upflow models, the plenums with grills can be selected by requirement. The outline drawings are shown in Figure
4-7, Figure 4-8 and Figure 4-9, and the detailed dimensions are listed in Table 4-2.

A B

Figure 4-7 One bay plenum

A B

Figure 4-8 Two bay plenum

A
B

Figure 4-9 Three bay plenum


Table 4-2 Plenum dimensions (unit: mm)
Model A B C
One bay 867 853 400 (600, optional )
Two bay 867 1704 400 (600, optional )
Three bay 867 2553 400 (600, optional )

Notes
Please consult the factory for nonstandard product, if the length of plenum exceeds 600 mm.

PeX Series AC Technical Data Manual


Chapter 4 Dimensions 33

4.4 Service Space


Normally, the min. front service access of AC unit is 873 mm, as shown in Figure 4-10.

7
83

Figure 4-10 Service space

The required min. service access is described in Table 4-3.


Table 4-3 Service access min. (unit: mm)
Position Air cooled model Water cooled model
Front 600 600
Left 0 600*
Right 0 600*
Rear 0 0
Notes:
1.They provide the service spaces for some componets, such as changing drainer, regulating fan, cleaning humidifier, and so on.
2. Those marked * are the data of water cooled models with charge lines on side panel. The service space is not required, if the
charge lines is fitted on base

PeX Series AC Technical Data Manual


34 Chapter 5 Instruction Of Application

Chapter 5 Instruction Of Application

This chapter introduces the piping for refrigerant tubing system, water cooled units and air cooled units, as well as the
connection of controller.

5.1 Refrigerant Tubing System

5.1.1 General
The water cooled system requires no outdoor unit. The piping for the refrigerant is required for the indoor unit and
outdoor unit of the air cooled system. The general arrangement diagram of the refrigeration system is shown in Figure
5-1.

Condenser coil

Evaporator coil

Check valve
Distributor

Traps(every 7.5m
of vertical lift)

Thermal expansion valve

Sight glass
Filter drier Hot gas Dehum solenoid valve
Solenoid valve bypass valve #1 circuit only
(single compressor)

Sensing bulb
Ball
valves
High pressure switch
Low pressure switch
Charging port
Discharge line Suction line

Service valve
Scroll compressor

Figure 5-1 The general arrangement diagram of air cooled models

It is the installer’s responsibility to confirm that the equivalent length of refrigerant line is appropriate for site conditions
and decide the connection type. The equivalent length of lines should include the allowance for all kinds of bends.
Please refer to the principles as follows.
1. Consult the factory before installation whether measures like adding extended pipe assembly should be taken, if the
equivalent length of single line exceeds 30m, or the vertical difference between the indoor unit and outdoor unit
exceeds the values in Table 5-1.
Table 5-1 The verticla difference between indoor unit and outdoor unit
Indoor unit above Max. :+20m
Outdoor unit above Max. : -5m

PeX Series AC Technical Data Manual


Chapter 5 Instruction Of Application 35

2. The recommended line sizes in Table 5-2 are equivalent length, which include the allowance for bends and valves.
The installers should confirm whether the sizes are appropriate for site conditions.
Table 5-2 The equivalent length
The equivalent length (m)
Diameter of liquid line (inch)
90°bend 45°bend T type
3/8 0.21 0.10 0.76
1/2 0.24 0.12 0.76
5/8 0.27 0.15 0.76
3/4 0.3 0.18 0.76
7/8 0.44 0.24 1.1
1 1/8 0.56 0.3 1.4

3. When the vertical difference between the indoor unit and outdoor unit is comparatively big, an oil trap is required for
every 7.5m of vertical lift. The over long piping line should be charged with enough compressor oil. Please consult
factory for details before installation.

5.1.2 Piping
Please refer to the Figure 5-2 and Figure 5-3 for piping while piping.

Notes
When the condenser is installed higher than the compressor, the back bend is fitted to the supply discharge line and the return
liquid line of the condenser to avoid the liquid return to the compressor. Make sure that the top end of the back bend is higher
than the topmost copper line of condenser.

Outdoor unit Inverted bend(above the topmost copper line of condenser)

Liquid line(do not expose liquid line to sun)

Trap Indoor unit


Max.20m

Max. 7.5m

Slope dicharge
The earth surface
Humidifier water in

Condenser water out

Seal
Heat insulation floor Floor

Figure 5-2 Condenser installed higher than compressor

PeX Series AC Technical Data Manual


36 Chapter 5 Instruction Of Application

Indoor unit

Slope dicharge
Seal
The earth surface
Humidifier water in
Max.5m Condenser water out

Slope liquid
Heat insulation floor Floor
Outdoor unit

Figure 5-3 Compressor installed higher than condenser

5.1.3 Connection
The indoor unit and outdoor unit connect by jointing (as shown in Figure 5-4). The wet material must be wrapped on
the ball valve before jointing. Please note the notices and labels, which are affixed on the lower panel and side panel of
the AC unit near the ball valve while jointing.
Horizontal sections of discharge lines should be sloped downward from the compressor, with a slope of at least 1:2000
(5 mm down for each 1 m run). Discharge lines should be insulated where they are routed in the conditioned space
(including under a raised floor).
The liquid pressure drop should not exceed 40 kPa (5~6 psi), provided that there is no allowance of refrigeration. The
liquid line pressure drop is the sum of liquid flow resistance from the tubing and fitting (including the drier), plus the
loss of head pressure due to elevation above the condenser. If the liquid temperature is 38°C, the static pressure loss
is 11 kPa (1.6 psi) per meter of lift.

Ball valve(liquid line)


Ball valve(discherge line)

Figure 5-4 Jointing position of unit lines

Considering the influence of the O.D. copper on the pressure drop of system, the O.D. copper of indoor unit and
outdoor unit must follow the recommended line sizes in Table 5-3.
Table 5-3 Recommended line sizes
Recommended line size
Model P1020 P1025 P1030 P1035 P2040 P2045 P2050
Eq.Lgth D L D L D L D L D L D L D L
10m 22 13 22 13 22 13 22 13 22 13 22 13 22 13
20m 22 13 22 13 22 13 22 16 22 13 22 16 22 13
30m 22 13 22 13 22 16 25 16 22 13 25 16 22 13
40m* 22 13 22 13 22 16 25 16 22 13 25 16 22 13
50m* 22 13 22 16 25 16 25 16 22 13 28 19 22 16
60m* 22 16 22 16 25 16 25 19 22 16 28 19 22 16

PeX Series AC Technical Data Manual


Chapter 5 Instruction Of Application 37

Recommended line size


Model P2055 P2060 P2070 P3080 P3090 P3100
Eq.Lgth D L D L D L D L D L D L
10m 22 16 22 13 22 13 22 13 22 13 22 16
20m 25 16 22 13 22 16 22 16 25 16 25 16
30m 28 19 22 16 25 16 25 16 25 16 28 19
40m* 28 19 22 16 25 16 25 16 25 16 28 19
50m* 28 19 25 16 25 16 28 19 28 19 28 19
60m* 32 19 25 16 25 19 28 19 28 19 32 19
Notes:
1. Eq.Lgth added * should add the extended discretenesses
2. D: discharge line, L: liquid line
3. Consult factory if the line length exceeds 60 m

5.2 Water Cooled System

5.2.1 General
The especial water line connection is required because the water cooled system should supply condenser water to
plate heat exchanger. The general arrangement diagram of water cooled unit is given in Figure 5-5.
Evaporator coil

Distributor

Thermal expansion valve


Sight glass
Dehum solenoid valve
Filter drier #1 circuit only
Hot gas
bypass valve
(single compressor)
Sensing bulb

Liquid
bypass High pressure
valve switch Low pressure switch
Discharge Charging port
line
Suction line
Water nipple joints Service valve
Pressure gauges
Scroll compressor

Plate heat exchanger


Condenser water out
Isolation valves Water regulating valve
Strainer
Balancing valve
Condenser water in

Figure 5-5 The general arrangement diagram of water cooled unit

The water pressure of lines is required to overcome the water pressure drop from all components of water cooled
system. Considering that the incrustation scale and impurity because of long-term operation may result in rise of the
water pressure, the delivery lift components (such as water pump) is required for 25%~30% space. Please refer to the
following principles for the connections of water lines.

PeX Series AC Technical Data Manual


38 Chapter 5 Instruction Of Application

1. A strainer (with 1 mm mesh) and isolation valves should be fitted to the condenser water supply for each unit. One of
these isolation valves may be a balancing valve. It is suggested that the pressure gauges is fitted to the water supply
and return lines of the plate heat exchanger. These allow the water flow rate to be adjusted to the requirement by the
factual pressure drop.
2. The water pump efficiency of plate heat exchanger system with the balancing valve is better. And it can control the
water discharge more accurately. And the water regulating valve can keep the optimum condenser temperature by
regulating the inner water flow.
3. It is preferable to be able to isolate individual refrigeration circuits, so that one can be kept in operation, while
service work is carried out on the other circuit.

5.2.2 Piping
Please refer to Figure 5-6 for piping. There are some piping places on the lower plate and side plate of AC unit. Please
consider the piping position by the site conditions while installation.

Isolation Pressure
valves gauges
Raised floor
Condenser water out

Condenser water in

Drainer Insulate under raised Floor


floor against heat gain

Figure 5-6 Piping of water cooled unit

5.2.3 Connection
The in and out lines of Liebert.PEX indoor unit are male joints, as shown in Figure 5-7. The female joints can be
selected by the field condition, and the jointing also can be used. The nipple connection is recommended and the seal
of joints must be ensured.

Notes
Must ensure the seal of joints.

PeX Series AC Technical Data Manual


Chapter 5 Instruction Of Application 39

Plate heat exchanger


Nipple joint
Water
out
Nipple joint
Water
in

Water regulating valve

Figure 5-7 Connection of water cooled unit

5.3 Air Cooled System

5.3.1 General
The indoor unit of Liebert.PEX series AC is classified into upfloor and downfloor in terms of the air flow mode. The
connection of air cooled system can choose duct or plenum (for room unit). It should be considered synthetically.

Discharge outlet Discharge inlet

Discharge inlet Discharge outlet

Figure 5-8 Discharge models

Please refer to the following principles for installing ducts.


1. The ratio between long side and short side of the rectangular duct shall not exceed 4:1.
2. The arc or slash rectangular bend can be adopted for angular pipe of the rectangular duct. The flow deflector is
required, if the side length is or greater than 500mm.
3. The reinforcing measurement is required, if the side length of the rectangular duct is or over 630 mm, the side length
of heat insulating duct is or over 800mm, and the length of duct is over 1200 mm.
4. The exterior of duct and its accessories should be smooth. Their arcs should be even, and the gap of joints should
be sealed. The joints and the regulating device of duct and its accessories cannot be fitted on the wall or in the ceiling.
5. The sealed test of duct must be in accordance with the norms of air leak check with lighting.

PeX Series AC Technical Data Manual


40 Chapter 5 Instruction Of Application

5.3.2 Piping
Note that: the interference between AC units should be reduced even avoided, when the AC units use the same air
plenum.

5.4 Controller

5.4.1 Connection Of Mains Circuit


The mains supply requirement of Liebert.PEX series AC unit: 380Vac, 50Hz and 3×L+N+PE. The power supply is
mainly used in indoor unit, as shown in Figure 5-9. Please refer to the full load current on the nameplate of AC unit and
see Table 3-1, Table 3-10, Table 3-19 and Table 3-20 for the recommended cable specifications.

N PE

L1 L2 L3
N PE

Figure 5-9 The power wiring of indoor unit

5.4.2 Connection Of Controller


The especial terminal block (as shown in Figure 5-10) provided by Liebert.PEX series AC unit provides some exterior
interfaces, including the remote controlling interface and alarm monitoring interface, to users. Its first half part is
connected with AC units, and the second half part is the controlling interface of users and controlling signal line
interface.
Connecting with smoke sensor,
91# is its common terminal Alarm output of smoke sensor

42 44 82 58 59 84 85 37C 38C 37B 38B 37 38 24 50 51 55 56 70 71 71A 71B

41 43 83 88 89 75 76 94 95 96 97 91 92 93 80 81 11 12 77 78 72 73

41 43 83 88 89 75 76 94 95 96 97 91 92 93 80 81 11 12 77 78 72 73

42 44 82 58 59 84 85 37C 38C 37B 38B 37 38 24 50 51 55 56 70 71 71A 71B

Connecting with common alarm Connecting with monitoring system


Short connecting line, no short line if 50,51,55,56# is defined alarm terminals,
the remote shut down is connected 24# is its common terminal

Figure 5-10 The controlling terminal block

Users can connect the following controlling and alarm devices with the controller.

PeX Series AC Technical Data Manual


Chapter 5 Instruction Of Application 41

1. Water under floor. The sensor of water under floor is the normal accessory of AC unit, which is fitted to the
recommended place on the base of AC unit. One end is connected to 51# of terminal block, and the other is connected
to 24#, which is the common end of remote alarm. Any number of sensors can be linked in parallel, and there is one
alarm for water under floor indication per AC unit.
2. Remote shut down. The 37#, 38# of terminal block can be connected with the remote shut down switch. The 37#
and 38# had been shorted in factory. The short line is not needed when the remote shut down is required. When the
37# and 38# are disconnected, the AC unit is also turned off.
3. Monitoring system. The AC unit provides the special monitoring communication interface, which is connected with
the monitoring system.
4. Smoke detecting. The 91#, 92# and 93# of terminal block are used to connect with the smoke sensors. The 91# is a
common terminal. 92# is a normally open contactor. 93# is a normally closed contactor. Users can select a normally
open or normally closed contact by the logic of configured smoke sensor. The 80# and 81# are used to connect with
the alarm output of smoke sensor.
5. Control signal of outdoor unit. 70#, 71# and 70A#, 71A# are two teams of control signal access terminal of outdoor
unit. The switch status is the same as that of compressor.
6. Defined alarm terminals. The AC unit has four defined alarm terminals. The defined alarm 4 had been defined for
electrical heater alarm in factory. The other three terminals respond to the terminals of 50#, 51#, 55#, which can be
connected with four sensors. The 24# is the common end. These terminals can be defined as fire sensor and water
under floor. After connecting with alarm signals, the defined terminals should set the contact condition of
corresponding defined alarm by the microprocessor. For example, the alarm condition is set to be closed. If there is not
alarm, the contact cuts off and the input state of defined terminal is open. After alarm happens, the contactor is close
and the state of defined terminal is shorted. At this time, the LCD screen of indoor unit will display the alarm
information in conjunction with an audible alarm of the AC unit.
It is recommended: the remote alarm can be connected between 50# and 24#.
The access point of water under floor is defined in factory between 51# and 24#.
The protection switch of condensate pump (optional) is defined in factory between 55# and 24#.
7. Common alarm terminals. The 75# and 76# can be connected with the exterior common alarm. These two terminals
are controlled by the common alarm relay of the circuit board K3, and their output is used to connect with the devices
of exterior alarm (such as alarm indicator). When the critical alarm happens, the contactor cuts off. These terminals
can be used to generate the remote alarm, transmitting signal to the building manage system and dialing the calling
system. Users should provide the power of common alarm system circuit.

5.4.3 Multimachine And Group Control


AC Units can be controlled together to realize the function of group control and main unit tour round. Multi-machine
and group control can be realized through the CAN bus. The maximum connecting number is 16 (0~15) and the AC
unit 1 (whose address is 0) is defaulted as the main controlling unit. If the communication and net working of main
controlling AC unit is fail, other AC units operate solely. The main controlling AC unit sends the controlling commands
to each controlled AC unit timely (the time is 5 s). The controlled AC units send the measure data and unit state to
each AC unit.
The functions follow as:
1. No group control. All AC units operate solely. The function of standby and tour around is allowed but the cascade
function is not allowed.
2. The parameters of all AC units are shared. The main controlling AC unit calculates the requirement of total
refrigeration (heat, de-humidity and humidity) and distributes the requirement by the address. The controlled AC units
operate according to the requirement distributed by the main controlling AC unit. The functions of standby, tour around
and cascade are allowed. The requirement is distributed evenly.
3. The parameters of all AC units are shared. The main controlling AC unit checks the total requirement by the
condition of controlled AC units and estimates whether the refrigeration (heat, de-humidity and humidity) is needed.
Then the main controlling AC unit controls the operating mode of controlled AC units. The function of standby is
allowed but functions of tour around and cascade are not allowed.
4. The parameters of all AC units are shared. The main controlling AC unit calculates the requirement of total
refrigeration (heat, de-humidity and humidity) and distributes by the requirement of controlled AC units. The controlled

PeX Series AC Technical Data Manual


42 Chapter 5 Instruction Of Application

AC units operate according to the requirement distributed by the main controlling AC unit. The functions of standby
and cascade are allowed, but tour around is not allowed. This mode is applicable where the heating load is not even.

PeX Series AC Technical Data Manual