Liebert PEX Technical Manual
Liebert PEX Technical Manual
Version V1.1
Revision date 2008-03-24
BOM 31020723
Emerson Network Power provides customers with technical support. Users may contact the nearest
Emerson local sales office or service center.
Chapter 1 Preface
This chapter mainly introduces the special requirement of machine room environment and the features of Liebert.PEX
series air conditioner (Liebert.PEX series AC for short).
Liebert.PEX series AC is a medium- large size precision environmental control system and specially designed for the
cooling of electrical equipment. It features high reliability, high sensible heat ratio and big air flow to provide a sound
operational environment for the precision equipments (such as sensitive equipment, industrial processing equipment,
communication equipment and computers).
This chapter introduces the appearance, model designation, features, standard configuration and optional
components of Liebert.PEX series AC.
2.1 Appearance
The upflow indoor unit of Liebert.PEX series AC is shown in Figure 2-1.
P1 020 U W P M S 1 R
Humidity type: 0-none; R-infrared; S-steam generating
Reheat type: 0-none;1-one stage -standard;2-two stage
iCOM display: S-standard display; L-large display
Power supply: M-three phase/50Hz/400V
System configuration: R-R22 , scroll,2 compressors; P-R22, scroll,1 compressor
S-R407C,scroll, 2 compressors; Z-R407C, scroll,1compressor
Cooling type: A-air cooled; W-water cooled; G-glycol cooled
Air path: U-upflow; F-downflow; D-duct
Cooling capacity class: kW
Unit frame: 1-one bay; 2-two bay; 3-three bay
PEX series
2.3 Features
1. Type diversification
Liebert.PEX series AC is classified into air cooled series and water cooled series in terms of the cooling mode. Each
series is further classified into upflow type and downflow type in terms of the airflow mode. The diversified modes can
adjust to different installation and operation environments.
The water cooled series uses the plate heat exchanger with high performance, featuring compact structure, high
energy efficiency and low noise pollution to the outdoor environment.
The air cooled series can select Liebert.PEX condenser or Liebert low temperature outdoor unit CD(D)F_S series (low
temperature outdoor unit for short) according to the field conditions.
Liebert.PEX condenser is a new outdoor unit which features stable structure, low noise, stepless speed variation,
corrosion resistance aluminum structure, three-phase power supply and high efficiency; The low temperature outdoor
unit can reduce the noise pollution to the minimum while meeting the system cooling requirement. In addition, it can
modulate the system pressure and adjust to the lower outdoor temperature through the combined control of the fan
speed controller and the temperature switch.
2. Precision control
Liebert.PEX series AC can control the temperature and humidity accurately. The temperature and humidity can be set
to ±1°C and ±1%RH respectively.
3. High energy efficiency
Liebert.PEX series AC uses Copeland scroll compressor with high performance, unique V-shaped finned tube heat
exchanger, carefully designed liquid distributing and more rational inner distribution. Such design achieves more
evenly distributed air flow and more reasonably distributed refrigerant, greatly improving the heat exchanging
efficiency of the heat exchanger, and making AC unit more energy efficient.
4. Convenience and durability
Durable components, compact structure and low profile design; Unique frame secured with carbon steel rivets, is not
only stable and firm but can also dismantled easily for transportation in extreme conditions.; The frame contains two
layers, inside layer and outside layer, with fire insulation asbestos in between, contributing to good insulation
performance; The structures of one bay, two bay and three bay can be used by many conditions, and they reduce the
specification of some components consumed easily (for example drainer).
5. Infrared humidification
The Liebert.PEX series AC adopts an advanced infrared humidification technology to reduce the dependence on water
quality. The humidity control will be more precise and quicker.
6. Compatibility with green refrigerant
The system is compatible with R407C, to suit the international requirement on green refrigerant.
7. Multiple protections
Perfect automatic alarm and diagnosis function provide all-around protections for the AC unit effectively, prevent faults,
locate the faults more quickly and ultimately prolong the life span of the system.
8. Easy maintenance
The front doors make all components accessible from the front and save space. The maintenance of compressor,
plate heating exchanger and strainer, which adopt Rotalock connection model, is easy.
Evaporator
The finned tube evaporator with high heat dissipation efficiency, The distributor designed specifically for each model
makes sure that the refrigerant is distributed evenly in each loop.
Thermal expansion valve
The thermal expansion valve with external equalizer (as shown in Figure 2-5) can automatically regulate the flow of
refrigerant according to the operation condition of refrigeration system when the ambience temperature changes and
optimize the performance of unit.
Fan
The centrifugal fan of high performance and reliability is shown in Figure 2-6. It drives by the belt and features big
airflow, long distance, long airflow distance, easy disassembly and convenient maintenance. The over heat protecting
device can protect the motor effectively. The advanced no air flow protection can sense the reduce of airflow that
results from abnormal operation of the belt or motor and stop the refrigeration, heating or humidifying, with generating
the alarm signal.
Sight glass
The sight glass is the window of system cycle. You can observe the state of refrigerant and detect the moisture content
of system. The color will change from green to yellow, when the moisture content of system exceeds.
Filter drier
The filter drier (as shown in Figure 2-7) can effectively eliminate the moisture in refrigeration system. At the same time
it can filter out the impurity in system and make sure that the system can operate normally.
Infrared humidifier
The infrared humidifier (as shown in Figure 2-8) is controlled by the microprocessor. It features simple structure and
easy for disassembly, cleaning and maintenance. The quartz light, hanged over the moistening water pan of stainless
steel, eradiate the far ultrared ray and ultrared ray. In 5 ~ 6 minutes, these rays make the water molecule absorb the
辐射能 to cast off the strain of water and evaporate on the state of purity. The application of infrared humidifier
reduces the dependence on water quality. And the function of automatic swashing makes the water pan cleaner.
Heater element
The screw finned U type heater is made of stainless steel (as shown in Figure 2-9). Its radiating speed is quick, and
the thermal value is even. The thermal value doesnot only keep the dry bulb temperature, but also compensate the
temperature drop caused by dehumidifying to make the lower surface temperature of heater to prevent the air from
forming ionization and prolong its using life.
LCD screen
The microprocessor of Liebert.PEX series AC adopts 128 × 64 dot matrix, blue backlight LCD screen to display the
present temperature, humidity, setting value, the percentage graph of unit output (fan, compressor, refrigeration,
heating, desiccation, and humidity) and alarm information. You can browse or set all setting values, event records,
graph data, sensor data and alarm setting through the screen. The backlight of LCD screen is designed for saving
energy. If there is not key operation over some time (the factory default is 5 minutes, configured by the menu), the
backlight will be off. Once any key is pressed, the backlight is on.
Microprocessor
The advanced microprocessor makes Liebert.PEX series AC control the temperature and humidity of the machine
room accurately. Its features are as follows:
z Easy operation interface, multiple code protection to prevent unlawful operation.
z The controller has the restoration of a power-down and high, low voltage protection function.
z Getting the operating time of important components by the menu.
z Malfunction diagnosis system of expert class can automatically display the present malfunction information to
make the maintenance easy.
z 400 historical records, the type contains MESSAGE, WARNING and ALARM.
z RS485 interface. Adopting the communication protocol of industry information department.
The microprocessor can monitor and configure the following parameters:
z Temperature: temperature setting value, the range is 5°C ~ 40°C.
z Humidity: humidify setting value, the range is 20%RH~80%RH.
z Humidity control: humidify controlling model selected, the model contains Pred, Comp, Rel.
z Air temperature limit enabling: Enable and Disable can be selected.
z Air temperature limit: the setting value, the range is 5°C ~ 25°C.
Alarm Signal
The microprocessor is capable of generating audible/visual alarm. The normal signals contain: high temperature alarm,
low temperature alarm, high humidity alarm, low humidity alarm, high pressure alarm, low pressure alarm, drainer
blockage alarm, no air flow alarm and some defined alarms.
This chapter mainly introduces the technical data of air cooled units and water cooled units, and the application conditions of AC units.
Model
Type P1020U P1025U P1030U P1035U P2040U P2045U P2050U P2055U P2060U P2070U P3080U P3090U P3100U
A A A A A A A A A A A A A
Humidifying
4.5 4.5 4.5 4.5 10 10 10 10 10 10 10 10 10
Infrared capacity (kg/h)
humidifier Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles
Humidifying pan
s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel
666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816
Dimension (mm)
Drainer 4 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95
Number 1 1 1 1 2 2 2 2 2 2 3 3 3
Liquid return line
16 16 16 16 16 16 16 16 16 16 16 16 16
(mm)
Interface Dicharge line (mm) 22 22 22 22 22 22 22 22 22 22 22 22 22
dimensions Infrared humidifier
6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35
of indoor unit water in line (mm)
Condenser water
19 19 19 19 19 19 19 19 19 19 19 19 19
out line (mm)
Net weight (kg) 320 330 340 350 590 560 610 570 640 650 910 930 950
FLA5(A) AWG10 AWG10 AWG9 AWG9 AWG7 AWG7 AWG7 AWG6 AWG6 AWG6 AWG5 AWG5 AWG5
Air braker 32 32 40 40 63 63 63 63 80 80 100 100 100
Electrical
Reconmended
parameter AWG10 AWG10 AWG9 AWG9 AWG7 AWG7 AWG7 AWG6 AWG6 AWG6 AWG5 AWG5 AWG5
cable specification6
(5.26) (5.26) (6.6) (6.6) (10.6) (10.6) (10.6) (13.3) (13.3) (13.3) (16.4) (16.4) (16.4)
(mm2)
Notes:
1: Scroll compressor, R22 refrigerant (compatible with R407C).
2: V type, copper tube, aluminiun fin.
3: Helical fin, U type stainless steel, electrical heater.
4: Based on ASHRAE52.1-1992, the average filter efficiency is more than 90%, and the filter efficiency class is G4 (EN779).
5: The full load curent of unit. The maximum full load current value of unit is not the sum of rated maximm full load current value of all components, but the sum of rated maximm full load current
value of the operating components which may operate at the same time on the working condition of maximum load.
6. The using temperature of the recommended calbe is 25°C. Please match yourself according to the site condition or consult the Rearch & Development Dept of Emerson if the environment
temperature exceeds
Note
Please consult the corresponding Rearch & Development Dept of Emerson, if the data, which you need, is not included in preceding tables.
Table 3-3 Technical data of Liebert.PEX condenser (R407, environment temperature 35°C)
Model of condenser Corresponding indoor unit model Fan number Net weight (kg) Connection size of liquid pipe (mm) Connection size of discharge pipe (mm)
LSF32 P1020UA 1 110 16 22
LSF38 P1025UA 1 120 16 22
LSF42 P1030UA 1 130 16 22
LSF52 P1035UA 1 140 16 22
LSF32×2 2 220 16 22
P2040UA
LDF52 1 140 16 22
LSF62 P2045UA 2 150 22 28
Model of condenser Corresponding indoor unit model Fan number Net weight (kg) Connection size of liquid pipe (mm) Connection size of discharge pipe (mm)
LSF38×2 2 240 16 22
P2050UA
LDF62 2 160 16 22
LSF70 P2055UA 2 160 22 28
LSF42×2 P2060UA 2 260 16 22
LSF52×2 P2070UA 2 280 16 22
LSF52×2 P3080UA 2 280 16 22
LSF62×2 P3090UA 4 300 22 28
LSF70×2 P3100UA 4 320 22 28
2. Technical data of low temperature outdoor unit
The technical data of low temperature outdoor unit is listed in Table 3-4 and Table 3-5.
Table 3-4 Technicla data of low temperature outdoor unit (R22, environment temperature 35°C)
Model of condenser Corresponding indoor unit model Fan number Power (kW) Net weight (kg) Connection size of liquid pipe (mm) Connection size of discharge pipe (mm)
P1020UA/
CSF078S 2 0.6 73 19 25.4
P1025UA
CSF113S P1030UA 2 0.6 97 19 25.4
CSF141S P1035UA 3 0.8 110 19 25.4
CSF078SX2 4 1.1 146 19 25.4
P2040UA
CDF141S 3 0.8 110 19 25.4
CSF171S P2045UA 4 1.1 135 19 25.4
CSF078SX2 4 1.1 146 19 25.4
P2050UA
CDF171S 4 1.1 135 19 25.4
CSF194S P2055UA 4 1.1 162 19 25.4
CSF113SX2 P2060UA 4 1.1 196 19 25.4
CSF141SX2 P2070UA 6 1.7 220 19 25.4
CSF171SX2 P3080UA 8 2.2 270 19 25.4
CSF194SX2 P3090UA 8 2.2 270 19 25.4
CSF194S X2 P3100UA 8 2.2 324 19 25.4
Note:
The low temperature outdoor of double system is not recommended in the region where the outdoor temperature is lower than -15°C
Table 3-5 Technicla data of low temperature outdoor unit (R407C, environment temperature 35°C)
Model of condenser Corresponding indoor unit model Fan number Power (kW) Net weight (kg) Connection size of liquid pipe (mm) Connection size of discharge pipe (mm)
CSF078S P1020UA 2 0.6 73 19 25.4
CSF113S P1025UA 2 0.6 97 19 25.4
CSF141S P1030UA 3 0.8 110 19 25.4
CSF171S P1035UA 4 1.1 135 19 25.4
Model of condenser Corresponding indoor unit model Fan number Power (kW) Net weight (kg) Connection size of liquid pipe (mm) Connection size of discharge pipe (mm)
CSF078S×2 4 1.1 146 19 25.4
P2040UA
CDF171S 4 1.1 135 19 25.4
CSF194S P2045UA 4 1.1 162 19 25.4
CSF113S×2 4 1.1 196 19 25.4
P2050UA
CDF194S 4 1.1 162 19 25.4
CSF141S×2 P2060UA 6 1.7 220 19 25.4
CSF171S×2 P2070UA 8 2.2 270 19 25.4
CSF171S×2 P3080UA 8 2.2 270 19 25.4
CSF194S×2 P3090UA 8 2.2 324 19 25.4
Note:
The low temperature outdoor of double system is not recommended in the region where the outdoor temperature is lower than -15°C
Model
Type P1020F P1025F P1030F P1035F P2040F P2045F P2050F P2055F P2060F P2070F P3080F P3090F P3100F
A A A A A A A A A A A A A
Cooling
capacity 20 23.1 30.1 33.1 41 45 46.4 53.2 60.6 66.9 81.4 89.3 100
24°CdB
50%RH Sensible
Cooling
cooling
capacity and
capacity 18.9 21.5 26.6 29.4 38.5 41.7 43.2 47.3 53.5 59 71.1 79.6 88.4
Sensible
cooling Cooling
capacity (kW) capacity 19.7 22.4 28.8 31.8 40.4 44 45.6 51.6 58.2 64.6 78.6 85.5 97.9
24°CdB
45%RH Sensible
cooling
capacity 19.5 22.2 28.1 31.2 40.1 43.6 45.2 50.5 56.7 62.7 75.6 84.3 94.5
Standard flow
volume (m3/h) 5670 6660 8280 8190 10980 12240 12960 13680 16200 16020 20160 23940 23760
Number 1 1 1 1 2 2 2 2 2 2 3 3 3
Fan
Static
pressure out of unit 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200
(Pa)
Model
Type P1020F P1025F P1030F P1035F P2040F P2045F P2050F P2055F P2060F P2070F P3080F P3090F P3100F
A A A A A A A A A A A A A
Compressor1
Number 1 1 1 1 2 1 2 1 2 2 2 2 2
Evaporator Upwind arae (m2) 0.42 0.42 0.42 0.42 0.92 0.92 0.92 0.92 0.92 0.92 1.43 1.43 1.43
coil2 Face velocity (m/s) 1.7 1.9 2.3 2.3 1.6 1.7 1.7 1.9 2.1 2.1 2.1 2.1 2.1
Electric
Power (kW) 6 6 6 6 9 9 9 9 9 9 12 12 12
heater 3
Humidifying
4.5 4.5 5 5 10 10 10 10 10 10 10 10 10
Infrared capacity (kg/h)
humidifier Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles
Humidifying pan
s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel
790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790
Dimension (mm)
Drainer4 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95
Number 1 1 1 1 2 2 2 2 2 2 3 3 3
Liquid return line
16 16 16 16 16 16 16 16 16 16 16 16 16
(mm)
Interface Dicharge line (mm) 22 22 22 22 22 22 22 22 22 22 22 22 22
dimensions Infrared humidifier
6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35
of indoor unit water in line (mm)
Condenser water
19 19 19 19 19 19 19 19 19 19 19 19 19
out line (mm)
Net weight (kg) 320 330 340 350 590 560 610 570 640 650 910 930 950
FLA5 (A) 25.5 28 34.1 38 50.5 55.6 56.4 61.5 69.8 77.6 89.4 94.4 97.8
Air braker 32 32 40 40 63 63 63 63 80 80 100 100 100
Electrical
Recommended
parameter AWG10 AWG10 AWG9 AWG9 AWG7 AWG7 AWG7 AWG6 AWG6 AWG6 AWG5 AWG5 AWG5
calbe specification6
(5.26) (5.26) (6.6) (6.6) (10.6) (10.6) (10.6) (13.3) (13.3) (13.3) (16.4) (16.4) (16.4)
(mm2)
Notes:
1: Scroll compressor, R22 refrigerant (compatible with R407C).
2: V type, copper tube, aluminiun fin.
3: Helical fin, U type stainless steel, electrical heater.
4: Based on ASHRAE52.1-1992, the average filter efficiency is more than 90%, and the filter efficiency class is G4 (EN779).
5: The full load curent of unit. The maximum full load current value of unit is not the sum of rated maximm full load current value of all components, but the sum of rated maximm full load current
value of the operating components which may operate at the same time on the working condition of maximum load.
6. The using temperature of the recommended calbe is 25°C. Please match yourself according to the site condition or consult the Rearch & Development Dept of Emerson if the environment
temperature exceeds
The condensers’ technical data of downflow air cooled units are as follows:
Note
Please consult the corresponding Rearch & Development Dept of Emerson, if the data, which you need, is not included in preceding tables.
Table 3-8 Technical data of Liebert.PEX condenser (R407C, environment temperature 35°C)
Model of condenser Corresponding indoor unit model Fan number Net weight (kg) Connection size of liquid pipe (mm) Connection size of discharge pipe (mm)
LSF32 P1020FA 1 110 16 22
LSF38 P1025FA 1 120 16 22
LSF42 P1030FA 1 130 16 22
LSF52 P1035FA 1 140 16 22
LSF32×2 2 220 16 22
P2040FA
LDF52 1 140 16 22
LSF62 P2045FA 2 150 22 28
Model of condenser Corresponding indoor unit model Fan number Net weight (kg) Connection size of liquid pipe (mm) Connection size of discharge pipe (mm)
LSF38×2 2 240 16 22
P2050FA
LDF62 2 160 16 22
LSF70 P2055FA 2 160 22 28
LSF42×2 P2060FA 2 260 16 22
LSF52×2 P2070FA 2 280 16 22
LSF52×2 P3080FA 2 280 16 22
LSF62×2 P3090FA 4 300 22 28
LSF70×2 P3100FA 4 320 22 28
Table 3-10 Technical data of low temperature outdoor unit (R407C, environment temperature 35°C)
Model of condenser Corresponding indoor unit model Fan number Power (kW) Net weight (kg) Connection size of liquid pipe (mm) Connection size of discharge pipe (mm)
CSF078S P1020FA 2 0.6 73 19 25.4
CSF113S P1025FA 2 0.6 97 19 25.4
CSF141S P1030FA 3 0.8 110 19 25.4
CSF171S P1035FA 4 1.1 135 19 25.4
Model of condenser Corresponding indoor unit model Fan number Power (kW) Net weight (kg) Connection size of liquid pipe (mm) Connection size of discharge pipe (mm)
CSF078S×2 4 1.1 146 19 25.4
P2040FA
CDF171S 4 1.1 135 19 25.4
CSF194S P2045FA 4 1.1 162 19 25.4
CSF113S×2 4 1.1 194 19 25.4
P2050FA
CDF194S 4 1.1 162 19 25.4
CSF141S×2 P2060FA 6 1.7 220 19 25.4
CSF171S×2 P2070FA 8 2.2 270 19 25.4
CSF171S×2 P3080FA 8 2.2 270 19 25.4
CSF194S×2 P3090FA 8 2.2 324 19 25.4
Note:
The low temperature outdoor of double system is not recommended in the region where the outdoor temperature is lower than -15°C
Model
Type P1020U P1025U P1030U P1035U P2040U P2045U P2050U P2055U P2060U P2070U P3080U P3090U P3100U
W W W W W W W W W W W W W
Standard flow volume
(m3/h) 5400 6300 7866 7920 10440 11610 12240 13032 15390 15480 19188 22770 22860
Fan Number 1 1 1 1 2 2 2 2 2 2 3 3 3
Static
25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200 25-200
pressure out of unit (Pa)
Compressor1
Number 1 1 1 1 2 1 2 1 2 2 2 2 2
Evaporator Upwind area (m2) 0.42 0.42 0.42 0.42 0.92 0.92 0.92 0.92 0.92 0.92 1.43 1.43 1.43
coil2 Face velocity (m/s) 1.7 1.9 2.3 2.3 1.6 1.7 1.7 1.9 2.1 2.1 2.1 2.1 2.1
Electric
Power (kW) 6 6 6 6 9 9 9 9 9 9 12 12 12
heater3
Humidifying capacity
4.5 4.5 5 5 10 10 10 10 10 10 10 10 10
Infrared (kg/h)
humidifier Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles
Humidifying pan
s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel
666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816 666*816
Dimension (mm)
Drainer4 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95
Number 1 1 1 1 2 2 2 2 2 2 3 3 3
water
regulating Dimension (inch) 1-1/4 1-1/4 1-3/8 1-3/8 1-1/4 1-3/8 1-1/4 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8
valve5
Quantity of water intake
(24°C)l/s 0.5 0.6 0.7 0.8 0.5 1.1 0.6 1.3 0.6 0.8 1.0 1.0 1.2
Pressure drop (kpa) 7.3 9.3 8.78 7.62 7.34 12.6 9.32 12.8 6.9 7.63 9.53 12 11.8
Condenser
Quantity of water intake
water supply
(30°C)l/s 0.9 1.0 1.3 1.5 0.9 2.0 1.0 2.4 1.2 1.5 1.7 1.9 2.3
require
Pressure drop (kpa) 22 28.3 26.6 23.3 22.2 38.4 28.2 39.3 20.9 23.2 29 36.4 36.1
Ment6
Quantity of water intake
(32°C)l/s 1.3 1.5 1.9 2.1 1.3 2.8 1.4 3.3 1.6 2.1 2.4 2.7 3.2
Pressure drop (kpa) 40.5 53.4 50 42.8 40.9 74.6 53.3 76.3 38.4 42.9 54.9 70.4 69.5
Model
Type P1020U P1025U P1030U P1035U P2040U P2045U P2050U P2055U P2060U P2070U P3080U P3090U P3100U
W W W W W W W W W W W W W
Infrared humidifier water
6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35
in line (mm)
Interface Condenser water out line
19 19 19 19 19 19 19 19 19 19 19 19 19
dimensins of (mm)
indoor units Plate exchanger water
in/out line (screw thread, G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4
inch)
Net weight (kg) 375 385 395 399 647 557 691 599 700 710 850 857 867
FLA7(A) 22 24.3 28.5 31.5 44 46.2 47.3 51.8 55.1 60.9 68 73 84.2
Electrical Air braker 25 25 32 32 50 50 50 63 63 63 80 80 100
parameter Recommjended calbe AWG10 AWG10 AWG10 AWG9 AWG8 AWG8 AWG8 AWG7 AWG7 AWG7 AWG6 AWG6 AWG5
specification8 (mm2) (5.26) (5.26) (5.26) (6.6) (8.37) (8.37) (8.37) (10.6) (10.6) (10.6) (13.3) (13.3) (16.4)
Notes:
1: Scroll compressor, R22 refrigerant (compatible with R407C).
2: V type, copper tube, aluminiun fin.
3: Helical fin, U type stainless steel, electrical heater.
4: Based on ASHRAE52.1-1992, the average filter efficiency is more than 90%, and the filter efficiency class is G4 (EN779).
5. Standard pressure, the three way valve pressure is matched optional .
6. The water pressure designed is up to 1034Kpa at the temperature of 41°C (the water temperature is 37°C).
7: The full load curent of unit. The maximum full load current value of unit is not the sum of rated maximm full load current value of all components, but the sum of rated maximm full load current value of the
operating components which may operate at the same time on the working condition of maximum load.
8. The using temperature of the recommended calbe is 25°C. Please match yourself according to the site condition or consult the Rearch & Development Dept of Emerson if the environment temperature
exceeds
Note
1. The data in preceding Table is available for the refrigerant R407C.
2. Please consult professional engineers of factory, if water pressure exceeds 1.34 k pa.
3. Please consult the corresponding Rearch & Development Dept. of Emerson, if the data you need is not included in this Table.
Compressor1
Number 1 1 1 1 2 1 2 1 2 2 2 2 2
Evaporator Upwindarea (m2) 0.42 0.42 0.42 0.42 0.92 0.92 0.92 0.92 0.92 0.92 1.43 1.43 1.43
coil2 Face velocity (m/s) 1.7 1.9 2.3 2.3 1.6 1.7 1.7 1.9 2.1 2.1 2.1 2.1 2.1
Electric
Power (kW) 6 6 6 6 9 9 9 9 9 9 12 12 12
heater 3
Humidifying capacity
4.5 4.5 5 5 10 10 10 10 10 10 10 10 10
Infrared (kg/h)
humidifier Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles Stainles
Humidifying pan
s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel s steel
790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790 790*790
Dimension (mm)
Drainer4 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95 *95
Number 1 1 1 1 2 2 2 2 2 2 3 3 3
water
regulating Dimension (inch) 1-1/4 1-1/4 1-3/8 1-3/8 1-1/4 1-3/8 1-1/4 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8
valve5
Model
Type P1020F P1025F P1030F P1035F P2040F P2045F P2050F P2055F P2060F P2070F P3080F P3090F P3100F
W W W W W W W W W W W W W
Quantity of water
intake (24°C)l/s 0.5 0.6 0.7 0.8 0.5 1.1 0.6 1.3 0.6 0.8 1.0 1.0 1.2
Pressure drop (kpa) 7.3 9.3 8.78 7.62 7.34 12.6 9.32 12.8 6.9 7.63 9.53 12 11.8
Condenser
Quantity of water
water supply
intake (30°C) l/s 0.9 1.0 1.3 1.5 0.9 2.0 1.0 2.4 1.2 1.5 1.7 1.9 2.3
require
Pressure drop (kpa) 22 28.3 26.6 23.3 22.2 38.4 28.2 39.3 20.9 23.2 29 36.4 36.1
ment6
Quantity of water
intake (32°C) l/s 1.3 1.5 1.9 2.1 1.3 2.8 1.4 3.3 1.6 2.1 2.4 2.7 3.2
Pressure drop (kpa) 40.5 53.4 50 42.8 40.9 74.6 53.3 76.3 38.4 42.9 54.9 70.4 69.5
Infrared humidifier
6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35
water in line (mm)
Interface Condenser water out
19 19 19 19 19 19 19 19 19 19 19 19 19
dimensins of line (mm)
indoor units Plate exchanger
water in/out line G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4 G1-1/4
(screw thread, inch)
Net weight (kg) 375 385 395 399 647 557 691 599 700 710 599 857 867
FLA7 (A) 22 24.3 28.5 31.5 44 46.2 47.3 51.8 55.1 60.9 68 73 84.2
Air braker 25 25 32 32 50 50 50 63 63 63 80 80 100
Electrical
Recommended
parameter AWG10 AWG10 AWG10 AWG9 AWG8 AWG8 AWG8 AWG7 AWG7 AWG7 AWG6 AWG6 AWG5
cabel specification8
(5.26) (5.26) (5.26) (6.6) (8.37) (8.37) (8.37) (10.6) (10.6) (10.6) (13.3) (13.3) (16.4)
(mm2)
Notes:
1: Scroll compressor, R22 refrigerant (compatible with R407C).
2: V type, copper tube, aluminiun fin.
3: Helical fin, U type stainless steel, electrical heater.
4: Based on ASHRAE52.1-1992, the average filter efficiency is more than 90%, and the filter efficiency class is G4 (EN779).
5. Standard pressure, the three way valve pressure is matched optional .
6. The water pressure designed is up to 1034Kpa at the temperature of 41°C (the water temperature is 37°C).
7: The full load curent of unit. The maximum full load current value of unit is not the sum of rated maximm full load current value of all components, but the sum of rated maximm full load current
value of the operating components which may operate at the same time on the working condition of maximum load.
8. The using temperature of the recommended calbe is 25°C. Please match yourself according to the site condition or consult the Rearch & Development Dept of Emerson if the environment
temperature exceeds
Notes
1. The residual pressure out of units of downflow unit is 20pa.
Notes
Please consult professional engineer, whenever AC unit are used on the following conditions.
1. The AC unit voltages are over 10% or under 90% of the rated voltage.
2. The derating is required, if the aptitude exceeds 1000 m.
Chapter 4 Dimensions
This chapter mainly introduces the mechanical dimensions of indoor units and outdoor units, the mounting set
dimensions of indoor units and the dimensions of plenums.
54 54
6 853 256
25 17
24 04
0
40
0
6
25
400 42
0
40
0
1970
1970
4
874
87
54 2
256 40
40
0
42
0 25
53
40
0
46
5
40
0
1970
4
87
853
17
04
1970
1970
4
4
87
87
25
53
1970
4
87
45
25
530
72
25
D WO /LL WI /DL
2- 35 109
80
IRWI 2- 64
40
200
67.5
164
F
F
72.5
45 72 45
120 730
F F
45
4- 13
25
25
683
60
186
F 4- 64 F
70
70
45 81 45
F F
F F
45
8- 13
25
683
72
166 WO /LL /D 25
81 WI/DL 116 WO/LL WI /DL
2- 35 109
80
67.5
186
P
164
F 6- 64 F
F F
70
72.5
45 81 90 72 45
160 530
45
26
F
F
4- 13
310
Fan aperture
530
195 410
25 25
160
70
D WI /DL 40
IRWI
WO /LL
80
67.5
P
2- 2- 64
35
143
86
F
72.5
45 75 45
120 730
26
45
4- 13
F F
265
310
410 301 .5
45 45
WO/LL /D WI /DL
4- 13
F WI /DL /IRWI F
4- 64
70
40
160
WO /LL P
45
123 80 80 148
1000 530
120 730
26
45
26
8-
3
F
F F F
265
310
310
497.5 410
410 301.5 25
45 160
45 70
WI /DL
2- 40
WO /LL /D WI /DL
80
WO/LL P
F WI /DL /IRWI F
67.5
6- 64 2- 35
70
160
P
143
WO /LL F
86
F
72.5
123 80 80 148 45 75 45
2 Rubber
82 washer Angle iron (60×60×3)
H
(8mm)
Note
The holes of mounting base frame are drilled according to the factual anchoring holes, and the aperture is Φ10 mm.
A B
A B
A
B
Notes
Please consult the factory for nonstandard product, if the length of plenum exceeds 600 mm.
7
83
This chapter introduces the piping for refrigerant tubing system, water cooled units and air cooled units, as well as the
connection of controller.
5.1.1 General
The water cooled system requires no outdoor unit. The piping for the refrigerant is required for the indoor unit and
outdoor unit of the air cooled system. The general arrangement diagram of the refrigeration system is shown in Figure
5-1.
Condenser coil
Evaporator coil
Check valve
Distributor
Traps(every 7.5m
of vertical lift)
Sight glass
Filter drier Hot gas Dehum solenoid valve
Solenoid valve bypass valve #1 circuit only
(single compressor)
Sensing bulb
Ball
valves
High pressure switch
Low pressure switch
Charging port
Discharge line Suction line
Service valve
Scroll compressor
It is the installer’s responsibility to confirm that the equivalent length of refrigerant line is appropriate for site conditions
and decide the connection type. The equivalent length of lines should include the allowance for all kinds of bends.
Please refer to the principles as follows.
1. Consult the factory before installation whether measures like adding extended pipe assembly should be taken, if the
equivalent length of single line exceeds 30m, or the vertical difference between the indoor unit and outdoor unit
exceeds the values in Table 5-1.
Table 5-1 The verticla difference between indoor unit and outdoor unit
Indoor unit above Max. :+20m
Outdoor unit above Max. : -5m
2. The recommended line sizes in Table 5-2 are equivalent length, which include the allowance for bends and valves.
The installers should confirm whether the sizes are appropriate for site conditions.
Table 5-2 The equivalent length
The equivalent length (m)
Diameter of liquid line (inch)
90°bend 45°bend T type
3/8 0.21 0.10 0.76
1/2 0.24 0.12 0.76
5/8 0.27 0.15 0.76
3/4 0.3 0.18 0.76
7/8 0.44 0.24 1.1
1 1/8 0.56 0.3 1.4
3. When the vertical difference between the indoor unit and outdoor unit is comparatively big, an oil trap is required for
every 7.5m of vertical lift. The over long piping line should be charged with enough compressor oil. Please consult
factory for details before installation.
5.1.2 Piping
Please refer to the Figure 5-2 and Figure 5-3 for piping while piping.
Notes
When the condenser is installed higher than the compressor, the back bend is fitted to the supply discharge line and the return
liquid line of the condenser to avoid the liquid return to the compressor. Make sure that the top end of the back bend is higher
than the topmost copper line of condenser.
Max. 7.5m
Slope dicharge
The earth surface
Humidifier water in
Seal
Heat insulation floor Floor
Indoor unit
Slope dicharge
Seal
The earth surface
Humidifier water in
Max.5m Condenser water out
Slope liquid
Heat insulation floor Floor
Outdoor unit
5.1.3 Connection
The indoor unit and outdoor unit connect by jointing (as shown in Figure 5-4). The wet material must be wrapped on
the ball valve before jointing. Please note the notices and labels, which are affixed on the lower panel and side panel of
the AC unit near the ball valve while jointing.
Horizontal sections of discharge lines should be sloped downward from the compressor, with a slope of at least 1:2000
(5 mm down for each 1 m run). Discharge lines should be insulated where they are routed in the conditioned space
(including under a raised floor).
The liquid pressure drop should not exceed 40 kPa (5~6 psi), provided that there is no allowance of refrigeration. The
liquid line pressure drop is the sum of liquid flow resistance from the tubing and fitting (including the drier), plus the
loss of head pressure due to elevation above the condenser. If the liquid temperature is 38°C, the static pressure loss
is 11 kPa (1.6 psi) per meter of lift.
Considering the influence of the O.D. copper on the pressure drop of system, the O.D. copper of indoor unit and
outdoor unit must follow the recommended line sizes in Table 5-3.
Table 5-3 Recommended line sizes
Recommended line size
Model P1020 P1025 P1030 P1035 P2040 P2045 P2050
Eq.Lgth D L D L D L D L D L D L D L
10m 22 13 22 13 22 13 22 13 22 13 22 13 22 13
20m 22 13 22 13 22 13 22 16 22 13 22 16 22 13
30m 22 13 22 13 22 16 25 16 22 13 25 16 22 13
40m* 22 13 22 13 22 16 25 16 22 13 25 16 22 13
50m* 22 13 22 16 25 16 25 16 22 13 28 19 22 16
60m* 22 16 22 16 25 16 25 19 22 16 28 19 22 16
5.2.1 General
The especial water line connection is required because the water cooled system should supply condenser water to
plate heat exchanger. The general arrangement diagram of water cooled unit is given in Figure 5-5.
Evaporator coil
Distributor
Liquid
bypass High pressure
valve switch Low pressure switch
Discharge Charging port
line
Suction line
Water nipple joints Service valve
Pressure gauges
Scroll compressor
The water pressure of lines is required to overcome the water pressure drop from all components of water cooled
system. Considering that the incrustation scale and impurity because of long-term operation may result in rise of the
water pressure, the delivery lift components (such as water pump) is required for 25%~30% space. Please refer to the
following principles for the connections of water lines.
1. A strainer (with 1 mm mesh) and isolation valves should be fitted to the condenser water supply for each unit. One of
these isolation valves may be a balancing valve. It is suggested that the pressure gauges is fitted to the water supply
and return lines of the plate heat exchanger. These allow the water flow rate to be adjusted to the requirement by the
factual pressure drop.
2. The water pump efficiency of plate heat exchanger system with the balancing valve is better. And it can control the
water discharge more accurately. And the water regulating valve can keep the optimum condenser temperature by
regulating the inner water flow.
3. It is preferable to be able to isolate individual refrigeration circuits, so that one can be kept in operation, while
service work is carried out on the other circuit.
5.2.2 Piping
Please refer to Figure 5-6 for piping. There are some piping places on the lower plate and side plate of AC unit. Please
consider the piping position by the site conditions while installation.
Isolation Pressure
valves gauges
Raised floor
Condenser water out
Condenser water in
5.2.3 Connection
The in and out lines of Liebert.PEX indoor unit are male joints, as shown in Figure 5-7. The female joints can be
selected by the field condition, and the jointing also can be used. The nipple connection is recommended and the seal
of joints must be ensured.
Notes
Must ensure the seal of joints.
5.3.1 General
The indoor unit of Liebert.PEX series AC is classified into upfloor and downfloor in terms of the air flow mode. The
connection of air cooled system can choose duct or plenum (for room unit). It should be considered synthetically.
5.3.2 Piping
Note that: the interference between AC units should be reduced even avoided, when the AC units use the same air
plenum.
5.4 Controller
N PE
L1 L2 L3
N PE
41 43 83 88 89 75 76 94 95 96 97 91 92 93 80 81 11 12 77 78 72 73
41 43 83 88 89 75 76 94 95 96 97 91 92 93 80 81 11 12 77 78 72 73
Users can connect the following controlling and alarm devices with the controller.
1. Water under floor. The sensor of water under floor is the normal accessory of AC unit, which is fitted to the
recommended place on the base of AC unit. One end is connected to 51# of terminal block, and the other is connected
to 24#, which is the common end of remote alarm. Any number of sensors can be linked in parallel, and there is one
alarm for water under floor indication per AC unit.
2. Remote shut down. The 37#, 38# of terminal block can be connected with the remote shut down switch. The 37#
and 38# had been shorted in factory. The short line is not needed when the remote shut down is required. When the
37# and 38# are disconnected, the AC unit is also turned off.
3. Monitoring system. The AC unit provides the special monitoring communication interface, which is connected with
the monitoring system.
4. Smoke detecting. The 91#, 92# and 93# of terminal block are used to connect with the smoke sensors. The 91# is a
common terminal. 92# is a normally open contactor. 93# is a normally closed contactor. Users can select a normally
open or normally closed contact by the logic of configured smoke sensor. The 80# and 81# are used to connect with
the alarm output of smoke sensor.
5. Control signal of outdoor unit. 70#, 71# and 70A#, 71A# are two teams of control signal access terminal of outdoor
unit. The switch status is the same as that of compressor.
6. Defined alarm terminals. The AC unit has four defined alarm terminals. The defined alarm 4 had been defined for
electrical heater alarm in factory. The other three terminals respond to the terminals of 50#, 51#, 55#, which can be
connected with four sensors. The 24# is the common end. These terminals can be defined as fire sensor and water
under floor. After connecting with alarm signals, the defined terminals should set the contact condition of
corresponding defined alarm by the microprocessor. For example, the alarm condition is set to be closed. If there is not
alarm, the contact cuts off and the input state of defined terminal is open. After alarm happens, the contactor is close
and the state of defined terminal is shorted. At this time, the LCD screen of indoor unit will display the alarm
information in conjunction with an audible alarm of the AC unit.
It is recommended: the remote alarm can be connected between 50# and 24#.
The access point of water under floor is defined in factory between 51# and 24#.
The protection switch of condensate pump (optional) is defined in factory between 55# and 24#.
7. Common alarm terminals. The 75# and 76# can be connected with the exterior common alarm. These two terminals
are controlled by the common alarm relay of the circuit board K3, and their output is used to connect with the devices
of exterior alarm (such as alarm indicator). When the critical alarm happens, the contactor cuts off. These terminals
can be used to generate the remote alarm, transmitting signal to the building manage system and dialing the calling
system. Users should provide the power of common alarm system circuit.
AC units operate according to the requirement distributed by the main controlling AC unit. The functions of standby
and cascade are allowed, but tour around is not allowed. This mode is applicable where the heating load is not even.