Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

RC2-V Series

Design for wide range of displacement Variable Frequency Drive


Screw compressor dedicated to R134a
RC2-V Series
Screw Compressor

HANBELL PRECISE MACHINERY CO., LTD WWW.HANBELL.COM


WWW.HANBELL.COM

Highlights of RC2-V Series Screw Compressor


Higher CPO with Frequency Inverter (VFD)

Capacity modulated between 30~70Hz (Consult Hanbell for higher frequency s application)

Compatible with all frequency inverters (especially Hanbell refrigerant-cooled inverter), less doubt
of interruption and condensation compared to build-in inverter

Higher volumetric efficiency resulting from higher rotation speed

Constantly compatible Vi resulting in smaller power consumption under both part and full load

High-efficiency Motor

Optimal motor design for variable-speed rotation

Reinforced insulation suitable for wide range of
frequency spectrum

Patented motor-cooling design in passage of refrigerant
flow encompassing stator provides best heat absorption

Sliding-fit stator easier for installation and removal

High-efficiency Screw Rotor Profile



5-to-6 rotor profile patented in Taiwan, US, UK, and China

Designed according to characteristics of refrigerants

Hyper volume efficiency and minimum clearance

Durable Bearing Structure



Eleven high-quality bearings for radial
and axial resistance

Additional two bearings for axial
resistance in reverse running

α balance piston against axial thrust

Heavy-duty design

Resulted in longer bearing life compared
to traditional 9-bearing design

2
WWW.HANBELL.COM

Wide VI Selection

Built-in volume ratio (VI)-2.2, 2.6, 3.0, 3.5, 4.8 VI 2.2 VI 4.8

Exactly match pressure ratio without over- or
under-compression
VI

Suitable for separate applications like
refrigeration, water-cooled chiller, air-cooled
chiller and heat pump

High-performance Integral Oil Separator



Detachable demister for cleaning

Finer size of mesh

Low pressure drop and oil carry-over

Total Protection & Accessories


1. Motor Temperature Sensor :

“Built-in” Pt100/Pt1000 installed in motor winding

Accurately reflect corresponding resistance (converted to the motor temperature)

Controller can precisely regulate timing and volume of liquid injection accordingly
2. Discharge Thermister & Motor Temperature Thermistor

Totally integrated

Effectively protect compressor in advance when any abnormal alarm occurs
3. Liquid Injection and Oil Cooler Function (Port & Stop Pin)

Both available on every Hanbell screw compressor
4. Oil Level and Oil Flow Switch

Ensure sufficient lubricant in compressor for better lubrication,
cooling and sealing
5. Heater (150W & 300W)

Increase lubricant’s flow-ability when compressor restarts after
long-term stop
6. Connection for Pressure Differential Switch

Easily detect clog in of oil filter

Assure effective lubrication

Other Advantages Compressor Nomenclature



Low noise level and minute vibration R C 2 - xxxx x v

Fewer quantity of parts in screw
compressor than those in reciprocating Variable Speed Model
compressor Refrigerant Code A = R134a

Easy for maintenance and overhaul Displacement at 50Hz

Compact geometry, easy for layout
RC model 2nd Version

Approval and Certification



Production by SOP conformed to major quality standards

Approved by ISO 9001-2000, UL, CE(PED), Electronic Apparatus for Explosive
Atmospheres (EX, China), Lloyd’s Register (Vessel), Symbol of Excellence in Taiwan

3
WWW.HANBELL.COM

Technical Data RC2-AV

Hydrostatic
WWW.HANBELL.COMCOMPRESSOR MOTOR Lubricant Oil
Pressure WEIGHT
charge Heater
MODEL Test
Displacement Rated Nominal Voltage
Speed VI Type Starting Insulation Protection
50Hz(m³/hr) (Hp) (V) L W Kg/cm²G kg
(rpm)
RC2-100AV 98 1750~4750 30 19 7 275

RC2-140AV 137 1750~4750 42 26 7 280

RC2-180AV 180 1750~4750 56 35 7 300

RC2-200AV 193 1750~4750 59 37 8 420

RC2-230AV 230 1750~4750 70 44 14 540

RC2-260AV 257 1750~4750 78 49 14 545

RC2-300AV 293 1750~4750 90 56 16 590

RC2-310AV 308 1750~3550 71 59 16 575


3 Phase, 2 Pole, Squirrel Cage, Induction Motor

RC2-320AV 320 1750~3550 72 60 16 595

RC2-340AV 339 1750~4750 102 64 16 600

RC2-370AV 366 1750~3550 84 70 16 610


2.2
RC2-410AV 407 1750~4750 125 78 16 730
2.6
RC2-430AV 423 1750~4750 125 78 16 735
3.0 △ start 380~460 Class F PTC 150/300 42
RC2-470AV 471 1750~4750 144 90 18 800
3.5
RC2-510AV 508 1750~3550 117 98 20 760
4.8
RC2-550AV 549 1750~4750 168 105 23 820

RC2-580AV 583 1750~3550 131 109 20 805

RC2-620AV 619 1750~4750 182 114 23 850

RC2-710AV 713 1750~3550 158 131 28 1099

RC2-790AV 791 1750~3550 175 146 28 1140

RC2-830AV 825 1750~3550 183 152 28 1150

RC2-930AV 929 1750~3550 212 176 28 1180

RC2-1020AV 1017 1750~3550 227 189 40 1500

RC2-1130AV 1122 1750~3550 248 206 40 1520

RC2-1270AV 1268 1750~3550 286 238 53 2100

RC2-1530AV 1539 1750~3550 331 275 53 2200

Unit : m³/hr 0 500 1000 1500

Nominal horse power:


All the above Nominal Hp values are not the maximum compressor Hp. Please refer to Hanbell
selection software for rated current according to various operating conditions while sizing inverter,
AC reactor, contactor, cable, fuse and wirings, etc…

4
WWW.HANBELL.COM

Electrical Installation of VFD

Variable Frequency Drive (VFD)


Input Voltage

AC Reactor Inverter AC Reactor Motor


(Optional)

3Φ,2P,△
Control Circuit

Control Voltage

Voltage/Frequency Characteristics of Motor

The motor of RC2-V series compressor is designed for variable speed control.
Its voltage vs frequency characteristic diagram is shown as below.
When setting the inverter with its operation manual, please choose the same
V/F characteristic as below in order to operate the compressor under proper settings.

VMAX FMIN: Minimum output frequency


VMIN: Minimum output voltage
FB: Middle output frequency
VC VC: Middle output voltage
FMAX: Maximum output frequency
VMAX: Maximum output voltage

VMIN

Hz
FMIN FB FMAX

Motor V/F Characteristic Diagram

5
WWW.HANBELL.COM

RC2-100AV~RC2-180AV Outline

Dimens ions Unit : mm


MOD EL
A B C D E F G H I J K L M N O P Q R S T U

RC2-100AV 213 196 196 75 70 61 400 101 57 53 416.5 300 186.5 205 249 260 548.5 196 156 86 135

RC2-140AV 213 196 196 75 70 61 400 101 57 53 416.5 300 186.5 205 249 260 548.5 196 156 86 135

RC2-180AV 283 196 196 75 81 68.5 410 101 57 53 486.5 386 196 205 239 362 548.5 196 156 95 123

RC2-710AV~RC2-930AV Outline

Dimens ions Unit : mm


MOD EL
A B C D E F G H I J K L M N O P Q R S T U V W X Y

RC2-710AV 1898.5 560 275 466 130 262.5 514.5 161 822.5 353 690 617 131.5 103 105 325 263 215.5 124 350 426 701 270 230 269

RC2-790AV 1963.5 560 275 466 130 262.5 514.5 161 822.5 418 690 617 131.5 103 105 325 263 215.5 124 350 426 701 270 230 230

RC2-830AV 1963.5 560 275 466 130 262.5 514.5 161 822.5 418 690 617 131.5 103 105 325 263 215.5 124 350 426 701 270 230 230

RC2-930AV 2033.5 560 275 466 130 262.5 584.5 161 822.5 418 760 617 131.5 103 105 325 263 215.5 124 350 426 701 270 230 230

6
WWW.HANBELL.COM

RC2-200AV~RC2-580AV Outline RC2-550AV~RC2-620AV Outline

Dimens ions Unit : mm


MOD EL
A B C D E F G H I J K L M N O P Q R S T U

RC2-200AV 345 229 378 75 82 69 447 101 57 53 536 228 341 225 245 362 592 225 225 95 196
RC2-230AV 365 250 405 86 97 85 502 106 67 61 567 251 399 257 289 391 624 240 240 107 225
RC2-260AV 365 250 405 86 97 85 502 106 67 61 567 251 399 257 289 391 624 240 240 107 225
RC2-300AV 408 250 405 86 97 85 502 106 67 61 610 285 399 257 289 391 624 240 240 107 229
RC2-310AV 408 250 405 86 97 85 502 106 67 61 610 251 444 257 289 391 624 240 240 107 225
RC2-320AV 408 250 405 86 97 85 502 106 67 61 610 285 399 257 289 391 624 240 240 107 229
RC2-340AV 408 250 405 95 103 105 502 121 81 69 610 285 447 257 310 391 624 240 240 130 228
RC2-370AV 408 250 405 95 103 105 502 121 81 69 610 285 447 257 310 391 624 240 240 130 228
RC2-410AV 392 275 453 95 103 105 553 120 81 69 613 288 433 275 315 413 655 270 230 130 255
RC2-430AV 392 275 453 95 103 105 553 120 81 69 613 288 433 275 315 413 655 270 230 130 255
RC2-470AV 440 275 453 95 103 105 553 120 81 69 661 320 433 275 315 413 655 270 230 130 255
RC2-510AV 465 275 453 107 103 105 560 131.5 96.5 88 696 288 484 275 331 413 655 270 230 130 254
RC2-550AV 484 275 451.5 107 103 105 572 131.5 96.5 88 720 320 580 280 331 411.5 659 270 230 130 112
RC2-580AV 465 275 453 107 103 105 560 131.5 96.5 88 696 320 484 275 331 413 655 270 230 130 255
RC2-620AV 484 275 451.5 107 220 124 572 131.5 96.5 88 720 320 525 280 331 411.5 659 270 230 161 112

RC2-1020AV~RC2-1530AV Outline

Dimens ions Unit : mm


MOD EL
A B C D E F G H I J K

RC2-1020AV/1130AV 1120 350 480 45 656 325 410 365 350 1000 470
RC2-1270AV/1530AV 1112 445 575 50 677 325 430 505 395 1020 550

Dimens ions Unit : mm


MOD EL
L M N O P Q R S T U V

RC2-1020AV/1130AV 723 370 451 499 715 728 325 275 100 100 60
RC2-1270AV/1530AV 768 370 590 480 825 770 325 275 100 90 115

7
Application Limits

R134a APPLICATION LIMITS


Additional cooling

60 140
Condensing Temperature

Motor A

50 122 High-efficiency Mod


RC2 Series
40 104
Screw Compressor
30 Hz

30 86

With min.
20 68 pressure valve

℉ -4 14 32 50

℃ -20 -10 0 10

Evaporating Temperature

HANBELL PRECISE MACHINERY CO., LTD.


NO.5 Kongsan Road, Kuan-Yin Industrial Park, Kuan-Yin
Shiang, Tao-Yuan Hsien, Taiwan, R.O.C.
SHANGHAI HANBELL PRECISE MACHINERY TEL:+886-3-4836215
CO., LTD FAX:+886-3-4836223
No.8289, Tingfeng RD, Fengjing Area, JinShan District, http://www.hanbell.com
Shanghai E-mail:sales@hanbell.com
TEL:+86-21-57350280 FAX:+86-21-57352004 HANBELL EUROPE
http://www.shahanbell.com.cn Via dei Campazzi 25 / 27, 21040 Gerenzano
E-mail:sales@shahanbell.com (VA), Italia
TEL:+39-02-962-80188
CONG TY THNN MAY CHINH XAC HANBELL FAX:+39-02-962-48011
VIET NAM http://www.comer-srl.com
LO 28-30-32 DUONG SO 11, KHU CONG NGHIEP TAN DUC, E-mail:vincentyen@hanbell.com
XA HUU THANH, HUYEN DUC HOA TINH LONG AN. E-mail:michelletseng@hanbell.com
TEL: (072) 3769688 FAX: (072) 3769690
HBCE-RC2V-11-A(1000)