2. THE CONTRACTOR SHALL PUT ALL EQUIPMENT INTO FULL OPERATION 9. ALL NEW DUCTWORK CONSTRUCTED FOR +4.0" W.G. SHALL BE LEAK 2. CONTRACTOR SHALL INCLUDE ALL LABOR, MATERIALS, AND COSTS B. REFRIGERATION
SECTION 011000 - GENERAL CONDITIONS AND REQUIREMENTS AND CONTINUE ITS OPERATION DURING EACH WORKING DAY OF TESTED IN ACCORDANCE WITH SMACNA LEAK TESTING MANUAL, REQUIRED TO FACILITATE CONSTRUCTION OF THE NEW WORK AND
TESTING AND BALANCING. NO TESTING AND BALANCING WORK SHALL LEAKAGE CLASS 6. REMODELING OF THE EXISTING SYSTEMS. 1. THERE IS NO REFRIGERATION AS PART OF THIS PROJECT.
1. THE WORK UNDER THESE SPECIFICATIONS SHALL INCLUDE ALL START UNTIL ALL OF THE AIR HANDLING EQUIPMENT HAS NEW 10. PROTECT DUCTWORK FROM THE ELEMENTS AND FOREIGN MATERIAL 3. THE COST FOR ALL PERMITS, LICENSES, APPROVALS, AND OTHER
LABOR, SERVICES, MATERIALS AND EQUIPMENT, AND PERFORMANCE FILTERS INSTALLED AND COILS HAVE BEEN CLEANED BY THE AND COMPLY WITH INTERMEDIATE DUCT CLEANLINESS LEVEL IN ARRANGEMENTS FOR WORK SHALL BE INCLUDED IN THE
OF ALL WORK REQUIRED FOR THE INSTALLATION OF ALL MECHANICAL CONTRACTOR. THE TESTING AND BALANCING CONTRACTOR SHALL BE ACCORDANCE WITH SMACNA'S "DUCT CLEANLINESS FOR NEW CONTRACTOR'S BID.
WORK AS SHOWN ON THE DRAWINGS AND HEREIN SPECIFIED. KEPT INFORMED DURING THE CONSTRUCTION OF THE PROJECT OF CONSTRUCTION GUIDELINES". 4. CONTRACTOR SHALL FURNISH ALL LABOR AND MATERIALS
2. SHOULD THERE BE ANY DISCREPANCIES OR A QUESTION OF INTENT, ANY MAJOR CHANGES MADE TO THE HVAC SYSTEM. TESTING AND NECESSARY FOR THE INSTALLATION OF A COMPLETE AND PROPER
REFER THE MATTER TO THE ARCHITECT FOR A DECISION BEFORE BALANCING CONTRACTOR SHALL BE PROVIDED WITH ONE (1) SET OF 1.2 DUCTWORK FITTINGS FUNCTIONING SYSTEM.
ORDERING ANY EQUIPMENT OR MATERIALS OR BEFORE STARTING SHOP DRAWINGS ON ALL EQUIPMENT WHICH THEY WILL BE REQUIRED 5. CONTRACTOR IS RESPONSIBLE FOR IDENTIFYING AND INCLUDING
ANY RELATED WORK. TO WORK ON WHEN BALANCING THE HVAC SYSTEM. 1. ALL NEW DUCT TURNS, ELBOWS, AND TEES SHALL BE INSTALLED ANY ITEMS NOT INDICATED ON THE DRAWINGS BUT NECESSARY FOR HVAC SYMBOLS AND LEGEND
3. WHERE WORK CONNECTS TO THAT OF ANOTHER TRADE, OR TO 3. CONTRACTOR SHALL NOTIFY THE ARCHITECT AND BUILDING WITH TURNING VANES OR MINIMUM 1-1/2 RADIUS ELBOWS. THE PROPER OPERATION OF THE MECHANICAL SYSTEMS.
PIPING OR EQUIPMENT IN PLACE, TAKE MEASUREMENTS IN THE FIELD ENGINEER OF THE T&B SCHEDULE A MINIMUM OF 5 DAYS PRIOR TO 2. RADIUS ELBOWS, 18" WIDTH AND LARGER, SHALL BE PROVIDED WITH 6. CONTRACTOR IS RESPONSIBLE FOR COORDINATING MECHANICAL
TO MAKE CONNECTING WORK COME TRUE AND LINE UP WITH THE T&B ACTIVITIES. DURING TESTING AND BALANCING, NOTIFY TURNING BLADES AT 1/3 AND 1/2 THE WIDTH OF THE DUCT FROM THE
EXISTING DUCTWORK, PIPING OR EQUIPMENT
WORK WITH THE WORK OF ALL OTHER TRADES, MAKING ANY
ITEM BEING CONNECTED. ARCHITECT IMMEDIATELY OF ANY EQUIPMENT OR OUTLETS THAT INSIDE RADIUS. TURNING VANES SHALL BE PROVIDED WITH HEMMED NECESSARY MODIFICATIONS INCLUDING OFFSETS TO MECHANICAL
1
4. MINOR ITEMS AND ACCESSORIES OR DEVICES REASONABLY
INFERABLE AS NECESSARY, TO THE COMPLETE AND PROPER 4.
CANNOT BE SATISFACTORILY BALANCED TO DESIGN REQUIREMENTS.
THE FINAL TEST RESULTS SHALL BE TABULATED AND DIGITAL COPIES 3.
ENDS.
SQUARE ELBOWS SHALL BE USED ONLY WHERE INDICATED OR 7.
WORK AT NO ADDITIONAL COST.
REFER TO ARCHITECTURAL, ELECTRICAL, PLUMBING, AND SPRINKLER
DUCTWORK, PIPING OR EQUIPMENT TO BE REMOVED HYATT
INSTALLATION AND OPERATION OF ANY SYSTEM, SHALL BE PROVIDED (PDF FORMAT) SHALL BE SUBMITTED FOR REVIEW THROUGH THE WHERE REQUIRED TO FIT CONSTRUCTION AND ONLY ON LOW DRAWINGS FOR ADDITIONAL DETAILS.
BY THE CONTRACTOR FOR SUCH SYSTEM WHETHER OR NOT THEY NORMAL SUBMITTAL PROCEDURES PRIOR TO PUNCH LIST PRESSURE SYSTEMS. PROVIDE ALL SQUARE ELBOWS WITH 8. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF NEW DUCTWORK, PIPING OR EQUIPMENT 2233 S Martin Luther King Dr
ARE SPECIFICALLY CALLED FOR BY THE SPECIFICATIONS OR WALK-THROUGH. ALL EQUIPMENT SHOWN IN BALANCING REPORT DOUBLE-WALL TURNING VANES. EQUIPMENT, PARTITIONS, WALLS, LIGHT FIXTURES AND GENERAL Chicago IL 60616
DRAWINGS. SHALL HAVE AN EQUIPMENT ID TAG WHICH SHALL CORRESPOND TO 4. PROVIDE CONICAL, BELLMOUTH OR MITERED RECTANGULAR TO CONSTRUCTION. FLEXIBLE DUCT
5. IF NEW WORK IS TO CONNECT TO EXISTING BASE-BUILDING SYSTEMS TAG SHOWN ON MECHANICAL AS BUILT DRAWING. ROUND FITTING AT ALL RECTANGULAR TO ROUND TAKEOFFS IN 9. SUBMIT SKETCHES INDICATING ANY DEVIATIONS FROM THE
OR RISERS, A TEST AND BALANCE CONTRACTOR SHALL PROVIDE 5. MECHANICAL CONTRACTOR SHALL ADJUST PATTERNS OF MEDIUM PRESSURE DUCTWORK AND AT INLETS TO TERMINAL UNITS. DRAWINGS TO THE ARCHITECT FOR APPROVAL PRIOR TO
INITIAL PRESSURE, SUPPLY TEMPERATURES AND FLOW ADJUSTABLE OUTLETS FOR PROPER DISTRIBUTION TO ELIMINATE 5. PROVIDE CONICAL, BELLMOUTH, FLANGED OR SPIN-IN FITTING WITH INSTALLATION. NEW SUPPLY AIR DIFFUSER
MEASUREMENTS AT MAJOR CONNECTION LOCATIONS AND DURING DRAFTS OR AS INDICATED ON DRAWINGS PRIOR TO ANY BALANCING VOLUME DAMPER AT ALL RECTANGULAR TO ROUND DUCT TAKEOFFS 10. THE MECHANICAL DRAWINGS ARE DIAGRAMMATIC AND SHALL BE
NORMAL SYSTEM OPERATION PRIOR TO ANY DEMOLITION OR NEW ACTIVITIES. COOLING OUTLETS TO BE SET FOR AIR DIFFUSION ALONG IN LOW PRESSURE DUCTWORK. PROVIDE EXTENDED COLLAR FOR FOLLOWED AS CLOSELY AS ACTUAL CONSTRUCTION OF THE
EXISTING SUPPLY AIR DIFFUSER
WORK BEING ACCOMPLISHED. ADDITIONAL INFORMATION IS CEILING AND HEATING ONLY OUTLETS TO BE SET TO DIRECT AIR AT DAMPER SHAFT AT ALL LOCATIONS WHERE DUCTWORK IS TO BE BUILDING AND THE WORK OF OTHER TRADE CONTRACTORS WILL
PROVIDED UNDER SECTION 230579. PERIMETER. INSULATED. PERMIT. ALL CHANGES FROM DRAWINGS NECESSARY TO MAKE THE
6. PRIOR TO START OF DEMOLITION WORK, CONTRACTOR TO PROVIDE WORK OF EACH CONTRACTOR CONFORM TO THE BUILDING NEW RETURN/EXHAUST AIR DIFFUSER 11 East Madison Street Tel 312.456.0123
TESTING AND VERIFICATION AS REQUIRED TO ENSURE EXISTING 1.2 AIR SYSTEMS 1.3 FLEXIBLE DUCTWORK CONSTRUCTION AND THE WORK OF OTHER TRADE CONTRACTORS Suite 300 Fax 312.456.0124
EQUIPMENT INDICATED TO REMAIN OR BE REUSED IS IN ACCEPTABLE SHALL BE DONE AT THE APPROPRIATE TRADE CONTRACTOR'S Chicago, IL 60602
WORKING ORDER. 1. BALANCING CONTRACTOR SHALL VERIFY THAT RETURNS, 1. FLEXIBLE DUCTWORK SHALL BE FACTORY FABRICATED ASSEMBLY OF EXPENSE. EXISTING RETURN/EXHAUST AIR DIFFUSER United States
SPECIFICALLY LIGHTING FIXTURE SLOTS, ARE OPEN AND SHALL CORROSION RESISTANT REINFORCING WIRE HELIX PERMANENTLY 11. IN GENERAL, ALL PIPING, DUCTWORK AND SIMILAR ITEMS SHALL BE
2 SECTION 200170 - SERVICES EXECUTION REQUIREMENTS NOTIFY MECHANICAL CONTRACTOR IF THEY ARE NOT. BONDED AND ENCLOSED IN HEAVY COATED FIBERGLASS FABRIC. INSTALLED CONCEALED FROM VIEW ABOVE THE CEILING, IN NEW LINEAR SLOT DIFFUSER
2. CONTRACTOR TO CONFIRM FILTERS ARE CLEAN. DUCT SHALL BE UL LISTED 181 CLASS I AND SHALL COMPLY WITH PARTITIONS, SHAFTS, OR CHASES, UNLESS OTHERWISE INDICATED.
NFPA 90A AND 90B AND ALL OTHER GOVERNMENTAL AUTHORITIES 12. LOCATION OF ITEMS NOT DEFINITELY FIXED BY DIMENSIONS ARE
1.1 QUALITY ASSURANCE 3. BALANCE EACH AIR SUPPLY AND EXHAUST SYSTEM TO WITHIN 10% HAVING JURISDICTION. EXISTING LINEAR SLOT DIFFUSER
APPROXIMATE ONLY AND EXACT LOCATIONS NECESSARY TO SECURE
OF QUANTITY SHOWN ON DRAWINGS. 2. DUCT MATERIAL SHALL BE FACTORY WRAPPED WITH FIBERGLASS
1. EACH MAJOR COMPONENT OF EQUIPMENT SHALL HAVE THE THE BEST CONDITIONS AND RESULTS SHALL BE DETERMINED AT THE
MANUFACTURER'S NAME, ADDRESS, MODEL NUMBER AND RATING ON 4. FOR VAV SYSTEMS, BALANCING CONTRACTOR TO DETERMINE AND INSULATION WITH A C FACTOR OF .23 OR LESS. THE INSULATION SITE, SUBJECT TO REVIEW. XXX-S CFM SUPPLY AIR
A PLATE SECURELY AFFIXED IN A CONSPICUOUS PLACE. RECORD MINIMUM DUCT STATIC PRESSURE SETPOINT REQUIRED TO SHALL BE ENCASED IN A FIRE RETARDANT VAPOR BARRIER JACKET. 13. SPACES THAT ARE SEPARATED FROM THE RETURN AIR PLENUM WITH
2. CODE RATINGS, LABELS OR OTHER DATA WHICH ARE DIE-STAMPED ACHIEVE PROPER AIRFLOW AT ALL OUTLETS. 3. FLEXIBLE DUCTS SHALL NOT BE LONGER THAN 5'-0" SLAB TO SLAB PARTITIONS WILL REQUIRE TRANSFER AIR OPENINGS
OR OTHERWISE AFFIXED TO THE SURFACE OF THE EQUIPMENT SHALL 5. BALANCING CONTRACTOR SHALL COORDINATE WITH CONTROLS 4. FLEXIBLE DUCTWORK SHALL BE SUPPORTED. SHARP BENDS, KINKS, TO ALLOW SPACE EXHAUST AIR TO RETURN TO THE RISER. XXX-E CFM EXHAUST AIR
BE IN A VISIBLE LOCATION. CONTRACTOR TO SET ALL SCHEDULED MINIMUM AND MAXIMUM AND CONDITIONS THAT RESTRICT AIR FLOW IN ANY WAY WILL NOT BE TRANSFER AIR OPENINGS SHALL BE SIZED NOT TO EXCEED 300 FPM
3. ALL EQUIPMENT PROVIDED UNDER THESE SPECIFICATIONS SHALL SETPOINTS AND CORRESPONDING CONTROL SIGNALS. ACCEPTED. AND SHALL BE REVIEWED WITH ARCHITECT
5. FLEXIBLE DUCT SHALL BE FLEXMASTER 4M OR APPROVED EQUAL. XXX-R CFM RETURN AIR
PERFORM WITH THE LEAST POSSIBLE NOISE AND VIBRATION 6. BALANCING REPORT MUST SHOW PRIMARY AIR INLET STATIC 14. CONTRACTOR SHALL PROTECT ALL EXISTING BUILDING SURFACES,
CONSISTENT WITH ITS DUTY. QUIETNESS OF OPERATION OF ALL PRESSURE, MAXIMUM SETPOINT CFM AND MINIMUM SHUT-OFF CFM EQUIPMENT, AND FIXTURES FROM DAMAGE FROM THE
EQUIPMENT IS A REQUIREMENT. ANY EQUIPMENT, AS DETERMINED BY AT EACH TERMINAL UNIT. REPORT MUST ALSO SHOW MINIMUM AND 1.4 DUCT LINING CONSTRUCTION WORK FOR THIS PROJECT. ANY DAMAGE CAUSED BY XXX-T CFM TRANSFER AIR
THE BUILDING OWNER'S REPRESENTATIVE, OR ENGINEER TO BE MAXIMUM PRIMARY AND FAN CFMS AND CORRESPONDING CONTROL THE CONTRACTOR SHALL BE REPAIRED AT THE CONTRACTOR'S
PRODUCING OBJECTIONABLE NOISE OR TRANSMITTING NOISE OR SIGNALS DURING HEATING AND COOLING MODE. 1. ALL ACOUSTICAL DUCT LINING MATERIALS SHALL HAVE FIRE AND EXPENSE.
FUEL CONTRIBUTED AND SMOKE HAZARD RATINGS, AS TESTED BY NEW FAN POWERED BOX
VIBRATION TO THE BUILDING SHALL BE REPAIRED OR REMOVED AND 7. BELTS AND SHEAVE CHANGES REQUIRED TO MEET SPECIFIED AIR 15. CONTRACTOR SHALL MAKE ALL ARRANGEMENTS WITH THE BUILDING
REPLACED. VOLUMES SHALL BE INCLUDED AS REQUIRED. PROCEDURE ASTM E-84, NOT GREATER THAN: OWNER'S REPRESENTATIVE REGARDING BUILDING RULES AND
4. ALL WORK SHALL BE IN ACCORDANCE WITH LOCAL CODES. THESE 8. RECORD AMP DRAW FOR AC AND FAN COIL UNITS AND VERIFY UNIT REGULATIONS INCLUDING WORKING HOURS, REFUSE DISPOSAL, EXISTING FAN POWERED BOX
3 a. FLAME SPREAD - 25
CODES SHALL BE FOLLOWED AS A MINIMUM. CONTRACTOR SHALL CAPACITY. SECURITY, INTERRUPTIONS OF BUILDING UTILITIES OR FUNCTIONS,
b. FUEL CONTRIBUTED & SMOKE DEVELOPED - 50
PROVIDE HIGHER GRADES OF MATERIAL AND WORKMANSHIP THAT 9. RECORD DISCHARGE AIR TEMPERATURE AT RISER, BOX, AND OWNERSHIP OF SALVAGED MATERIALS AND ANY OTHER ITEM
MAY EXCEED MINIMUM CODE REQUIREMENTS WHERE SPECIFIED OR DIFFUSER IN BOTH COOLING AND HEATING MODES OF OPERATION. 2. DUCT LINING, WHERE INDICATED, AND/OR AS HEREINAFTER DEEMED TO BE OF MUTUAL INTEREST. NEW VAV BOX
REQUIRED. PROVIDE ALL TESTS REQUIRED BY LOCAL CODES AND AS SPECIFIED SHALL HAVE MAXIMUM CONDUCTIVITY AS FOLLOWS: 16. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO STORE HIS
SPECIFIED. 1.3 WATER SYSTEMS MATERIALS IN A MANNER THAT WILL MAINTAIN AN ORDERLY CLEAN EXISTING VAV BOX
a. TYPEI, FLEXIBLE: 0.27 BTU X IN./H X SQ. FT. X DEGF AT 75 DEGF APPEARANCE. IF STORED ON-SITE IN OPEN OR UNPROTECTED
MEAN TEMPERATURE. AREAS, ALL EQUIPMENT AND MATERIAL SHALL BE KEPT OFF THE ESD Global
1.2 SUBMITTALS, SHOP DRAWINGS AND AS-BUILTS 1. BALANCE WATER FLOW TO WITHIN 10% OF QUANTITY SHOWN ON XXX
b. TYPEII, RIGID: 0.23 BTU X IN./H X SQ. FT. X DEGF AT 75 DEGF EQUIPMENT TAG MEP/FP Engineers
DRAWINGS. GROUND BY MEANS OF PALLETS OR RACKS AND COVERED WITH XXX 233 South Wacker Drive
1. SHOP DRAWINGS, PRODUCT DATA AND/OR SAMPLES SHALL BE 2. BEFORE TESTING CONTRACTOR SHALL CONFIRM STRAINERS ARE MEAN TEMPERATURE TARPAULINS. EQUIPMENT AND MATERIAL, IF LEFT OUT IN THE OPEN Suite 5300
SUBMITTED FOR ALL EQUIPMENT AS SPECIFIED OR SCHEDULED. CLEAN. c. TYPE I LINER SHALL BE USED WITH RECTANGULAR DUCTS AND AND DAMAGED, SHALL BE REPAINTED OR OTHERWISE REFURBISHED T NEW THERMOSTAT Chicago, IL
SHOP DRAWING PLANS SHALL BE MINIMUM 1/4“=1'-0” SCALE AND 3. FOR VARIABLE FLOW SYSTEMS, BALANCING CONTRACTOR TO TYPE II WITH ROUND DUCTS. AT THE DISCRETION OF THE BUILDING OWNER'S REPRESENTATIVE. Tel 312.372.1200
SHALL INDICATE COORDINATED AND DIMENSIONED LAYOUT OF ALL DETERMINE AND RECORD MINIMUM DIFFERENTIAL PRESSURE 3. SHOP APPLICATION OF DUCT LINER FOR RECTANGULAR DUCTS EQUIPMENT AND MATERIAL IS SUBJECT TO REJECTION AND
EQUIPMENT, DUCTS, DIFFUSERS, BOXES, PIPING, THERMOSTATS, AS SETPOINT REQUIRED TO ACHIEVE PROPER WATER FLOW AT ALL SHALL COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION REPLACEMENT IF, IN THE OPINION OF THE ENGINEER OR T EXISTING THERMOSTAT
WELL AS ASSOCIATED SIZES AND CFMS. SUBMIT SECTIONS AND DEVICES. STANDARDS - METAL AND FLEXIBLE". MANUFACTURER, THE EQUIPMENT HAS DETERIORATED OR BEEN
ELEVATIONS AS REQUIRED TO CLARIFY LAYOUT OF VERTICAL DUCT 4. RECORD GPM, SUPPLY AND RETURN TEMPERATURES AND PRESSURE 4. SHOP APPLICATION OF DUCT LINER FOR ROUND DUCTS SHALL DAMAGED TO THE EXTENT THAT ITS IMMEDIATE USE IS
QUESTIONABLE, ITS APPEARANCE HAS BEEN COMPROMISED OR THAT
H NEW HUMIDISTAT
AND PIPE SECTIONS. MODIFIED COPIES OF DESIGN DOCUMENTS ARE DROP FOR EACH UNIT. COMPLY WITH INSULATION MANUFACTURER'S INSTALLATION
ITS NORMAL LIFE EXPECTANCY HAS BEEN CURTAILED. Date Description
NOT ACCEPTABLE. SUBMIT DIGITAL FILE (PDF FORMAT) OF ALL 5. FOR TENANT CIRCULATION PUMPS RECORD ACTUAL AND DESIGN INSTRUCTIONS.
SUBMITTALS AND SHOP DRAWINGS FOR ARCHITECT REVIEW. VALUES FOR GPM, STATIC SYSTEM PRESSURE, DYNAMIC HEAD 5. ALL TRANSFER DUCTS AND EXHAUST FAN DUCTWORK SHALL HAVE 1" 17. PROVIDE ALL HOLES, SLEEVES, CUTTING, PATCHING AND CAULKING H EXISTING HUMIDISTAT 1 1/X/2020 ISSUED FOR CD
4 2. FINAL AS-BUILT DUCTWORK, EQUIPMENT AND PIPING PLAN LAYOUTS: PRESSURE AT PUMP INLET AND OUTLET, VOLTAGE, AMPERAGE AND DUCT LINING. FOR INSTALLATION OF THIS WORK. CAULKING SHALL CONFORM TO
SHOP DRAWINGS SHALL BE UPDATED ELECTRONICALLY TO REFLECT TEMPERATURE. 6. PROVIDE 1" DUCT LINING FOR ALL LOW-PRESSURE DUCTWORK THE FIRE RATING OF THE WALLS. SEAL ALL PENETRATIONS THROUGH
FINAL AS-BUILT CONDITIONS INCLUDING ALL FIELD MODIFICATIONS 6. CONTRACTOR SHALL SIMULATE A PUMP FAILURE TO TEST BLOCK WALLS. NEW CONNECTION
DOWNSTREAM FROM TERMINAL UNITS.
DURING CONSTRUCTION. CONTRACTOR SHALL SUBMIT ONE SET OF SEQUENCER FUNCTION IF APPLICABLE. 18. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATION OF ANY
AUTOCAD FILES, ONE SET OF DIGITAL COPIES (PDF FORMAT) AND MINOR INTERFERENCES, INCLUDING CONDUIT, HANGERS, ETC., AT NO VOLUME DAMPER
TWO SETS OF FULL-SIZE PRINTS TO BUILDING OWNER'S 1.5 ACCESS PANELS ADDITIONAL COST TO OWNER.
SECTION 230700 - HVAC INSULATION
REPRESENTATIVE. AND ONE SET OF AUTOCAD FILES AND DIGITAL 1. PROVIDE ACCESS PANELS IN ALL DUCTS AT THE FOLLOWING 19. WHERE PIPES ARE LOCATED INSIDE PARTITIONS, OR FURRED OUT
COPIES (PDF FORMAT) TO ENGINEER SHOWING AS-BUILT CONDITIONS LOCATIONS AND MINIMUM SIZES (IF DUCT SIZE DOES NOT ALLOW SPACES AND CHASES, OBTAIN INFORMATION AS TO THEIR EXACT BACKDRAFT DAMPER
OF ALL CONTRACT WORK. 1.1 DUCT INSULATION LOCATION AND SIZE AND INSTALL WORK SO AS TO BE ENTIRELY
PANEL SIZE SHOWN, PROVIDE REMOVABLE DUCT SECTION WITH 8X5
3. PRODUCT DATA/O & M MANUALS: FURNISH OWNER WITH THREE 1. FOR ALL MEDIUM PRESSURE UNLINED CONCEALED SUPPLY ACCESS PANEL): CONCEALED IN THE ALLOTTED SPACE. IF CONFLICTS ARISE MAKING
MOTOR OPERATED DAMPER
INSTRUCTION MANUALS IN BOUND FORM CONTAINING DATA DUCTWORK, PROVIDE 1-1/2" FLEXIBLE FIBERGLASS BLANKET THIS IMPOSSIBLE, OBTAIN INSTRUCTIONS FROM THE ARCHITECT
COVERING CAPACITIES, MAINTENANCE, AND OPERATION OF ALL INSULATION WITH VAPOR BARRIER: ASTM C553 TYPE I, II, AND ASTM C a. ADJACENT TO AUTOMATIC DAMPERS (HEAD/SHOULDER: 21X14) BEFORE PROCEEDING WITH THE WORK.
EQUIPMENT AND APPARATUS. MANUALS SHALL BE EDITED TO BE 1290; FHC 25/50 PER ASTM E84, 3/4 LB. PER CUBIC FOOT DENSITY, b. AT FIRE DAMPERS AND SMOKE DAMPERS (HEAD/SHOULDER: 20. CONTRACTOR SHALL COMPLY WITH BASE BUILDING SPECIFICATIONS SMOKE DAMPER
PROJECT SPECIFIC FOR PRODUCTS AND ACCESSORIES ACTUALLY MAXIMUM LABELED THERMAL CONDUCTIVITY OF 0.29 BTU/HR./SQ. 21X14) FOR ALL STANDARDS OF WORKMANSHIP REQUIRED, METHODS OF
INSTALLED. FT./DEG. AT 75 DEG F MEAN TEMP PER INCH OF THICKNESS SPECIFIED CONTROL, SAFETY DEVICES, ETC., FOR ALL NEW EQUIPMENT AND
c. AT INTAKE AND EXHAUST LOUVERS (HEAD/HAND: 18X10) FIRE DAMPER - IN WALL
4. ALL REQUESTS FOR SUBSTITUTIONS SHALL BE SUBMITTED TO FACED WITH RATED ALUMINUM FOIL, FIBERGLASS REINFORCED MATERIALS BEING INSTALLED.
d. BOTH SIDES OF DUCT COILS (HEAD/HAND: 18X10) 21. DURING CONSTRUCTION, PROVIDE FILTER MEDIA ON RETURN AIR
ARCHITECT FOR APPROVAL IN A TIMELY MANNER, AND INCLUDE SCRIM WITH KRAFT PAPER BACKING (FSK).
REASON FOR SUBSTITUTION, DOCUMENTATION TO SHOW THAT OPENINGS AND ALL EQUIPMENT INCLUDING FAN POWERED BOX FIRE DAMPER - IN FLOOR
2. FOR ALL LOW PRESSURE UNLINED CONCEALED SUPPLY DUCTWORK, 2. ACCESS PANELS IN DUCTWORK SHALL BE OF 22 GAUGE GALVANIZED
SUBSTITUTED PRODUCT IS EQUAL TO OR BETTER THAN SPECIFIED RECIRCULATION INLETS (NEW AND EXISTING). FILTER MEDIA SHALL BE
PROVIDE 1-1/2" FLEXIBLE FIBERGLASS BLANKET INSULATION WITH SHEET METAL WITH NEOPRENE GASKETS. PANELS IN INSULATED
5 PRODUCT, OWNER COST SAVINGS AND/OR OTHER BENEFITS CHANGED IF REQUIRED DURING THE DURATION OF THE PROJECT AND
VAPOR BARRIER: ASTM C553 TYPE I, II, AND ASTM C 1290; FHC 25/50 DUCTWORK, SHALL HAVE 1" THICK FIBERGLASS INSULATION CAP
PROVIDED, AND COMPATIBILITY WITH OTHER DISCIPLINES OR REMOVED AT THE CONCLUSION OF THE PROJECT.
PER ASTM E84, 3/4 LB. PER CUBIC FOOT DENSITY, MAXIMUM LABELED BETWEEN TWO THICKNESS OF SHEET METAL. THE AIRSIDE SHEET
PORTIONS OF THE PROJECT. SUBSTITUTION CANNOT REQUIRE 22. ALL SYSTEMS SHALL BE INDEPENDENTLY SUPPORTED.
THERMAL CONDUCTIVITY OF 0.29 BTU/HR./SQ. FT./DEG. AT 75 DEG F METAL ON INSULATED PANELS SHALL BE WELDED OR MECHANICALLY
ADDITIONAL WORK OR COST FOR OTHER TRADES, ARCHITECT OR 23. VOLTAGE FOR ALL EQUIPMENT SHALL BE VERIFIED BY THE
MEAN TEMP PER INCH OF THICKNESS SPECIFIED FACED WITH RATED LOCKED IN POSITION. PANELS UP TO 15" SHALL BE PROVIDED WITH
OWNER. CONTRACTOR PRIOR TO ORDERING.
ALUMINUM FOIL, FIBERGLASS REINFORCED SCRIM WITH KRAFT TWO CAM LATCHES, ONE ON EACH SIDE. PANELS OVER 15" SHALL BE
24. THE CONTRACTOR SHALL REPLACE ANY FIREPROOFING REMOVED IN
PAPER BACKING (FSK). PROVIDED WITH FOUR CAM LATCHES, TWO ON EACH SIDE. ALL
1.3 DEMOLITION AND DISPOSITION OF REMOVED EQUIPMENT THE PERFORMANCE OF THE CONTRACTOR'S WORK.
3. FOR ALL MEDIUM PRESSURE UNLINED SUPPLY DUCTWORK EXPOSED PANELS SHALL BE OF SUFFICIENT SIZE FOR EASY ACCESS TO AND
25. FINAL INSPECTION AND TESTS SHALL BE COORDINATED WITH THE
TO VIEW PROVIDE 1-1/2" FLEXIBLE FIBERGLASS BLANKET INSULATION THE SERVICING OF DAMPERS, DAMPER MOTORS, COILS, ETC.
1. THE CONTRACTOR SHALL REMOVE EXISTING MECHANICAL BUILDING OWNER'S REPRESENTATIVE BY THE CONTRACTOR
EQUIPMENT AND MATERIALS AS SPECIFIED OR AS REQUIRED, WITH VAPOR BARRIER: ASTM C553 TYPE I, II, AND ASTM C 1290; FHC RESPONSIBLE FOR THE INSTALLATION. ALL NEW AND EXISTING
WHETHER SHOWN ON THE DRAWINGS OR NOT TO PREPARE FOR THE 25/50 PER ASTM E84, 1.0 LB. PER CUBIC FOOT DENSITY, MAXIMUM 1.6 FIRE DAMPERS EQUIPMENT INCLUDED IN THE SCOPE OF WORK SHALL BE CLEANED
NEW WORK. CONTRACTOR SHALL TAKE POSSESSION OF REMOVED LABELED THERMAL CONDUCTIVITY OF 0.29 BTU/HR./SQ. FT./DEG. AT 75 AND ADJUSTED AS REQUIRED TO OPERATE SATISFACTORILY. EACH
DEG F MEAN TEMP PER INCH OF THICKNESS SPECIFIED FACED WITH 1. PROVIDE 1-1/2 HOUR FIRE DAMPERS IN DUCT PENETRATIONS
EQUIPMENT AND MATERIALS AND REMOVE THEM FROM THE SITE CONTRACTOR SHALL SUPPLY ALL LABOR, MATERIALS, INSTRUMENTS,
FACTORY APPLIED ALL SERVICE JACKET (ASJ). THROUGH ALL RATED WALLS OF 1 HOUR AND 2 HOURS. PROVIDE 3
PROMPTLY, EXCEPT AS SPECIFIED BELOW OR UNLESS OTHERWISE AND MISCELLANEOUS EQUIPMENT REQUIRED FOR TESTS.
4. SEAL ALL DUCT INSULATION SEAMS WITH TAPE AND ADHESIVE PER HOUR RATED DAMPERS IN ALL DUCT PENETRATIONS THROUGH
NOTED ON THE DRAWINGS. 26. PROVIDE COMPETENT OPERATING TECHNICIAN TO INSTRUCT THE
MANUFACTURERS INSTRUCTIONS TO PROVIDE A CONTINUOUS AND RATED WALLS 3 HOURS OR GREATER.
2. ALL SALVAGEABLE MATERIAL AND EQUIPMENT, INCLUDING BUT NOT BUILDING OWNER'S REPRESENTATIVE IN THE OPERATION AND
UNBROKEN VAPOR BARRIER 2. PROVIDE 1-1/2 HOUR FIRE DAMPERS IN TRANSFER OPENINGS
NECESSARILY LIMITED TO HEATING UNITS, AC UNITS, TERMINAL MAINTENANCE OF THE INSTALLED EQUIPMENT.
THROUGH ALL RATED WALLS OF 1 HOUR AND 2 HOURS. PROVIDE 3
UNITS, ETC., SHALL BE REMOVED AND MAINTAINED IN AS GOOD 27. CONTRACTOR SHALL GUARANTEE ALL WORK AND MATERIAL FOR ONE
HOUR RATED DAMPERS IN ALL TRANSFER OPENINGS THROUGH
CONDITION AS POSSIBLE AND TURNED OVER TO THE BUILDING SECTION 233100 - HVAC DUCTS AND ACCESSORIES YEAR AFTER FINAL ACCEPTANCE AGAINST ALL DEFECTS OF
6 RATED WALLS OF 3 HOURS OR GREATER.
OWNER'S REPRESENTATIVE. HOWEVER, IF THE BUILDING OWNER'S MATERIAL, EQUIPMENT, AND WORKMANSHIP. ANY DEFECTIVE
3. ALL FIRE DAMPERS ARE TO BE DYNAMIC TYPE Seal / Signature
REPRESENTATIVE DECIDES ANY SUCH MATERIALS ARE OF NO VALUE 1.1 DUCT CONSTRUCTION MATERIALS OR WORKMANSHIP AS WELL AS DAMAGE TO THE WORK
4. FIRE DAMPERS SHALL BE FUSIBLE LINK CURTAIN OR LOUVER TYPE
TO THE BUILDING THEN THEY SHALL BECOME THE PROPERTY OF THE OF ALL TRADES RESULTING FROM SAME SHALL BE REPLACED OR
AND SHALL BE UL LABELED AND INSTALLED IN ACCORDANCE WITH UL
CONTRACTOR WHO SHALL REMOVE SUCH DISCARDED WORK FROM 1. ALL DUCTWORK SHALL BE GALVANIZED SHEET METAL AND MEET THE REPAIRED AS DIRECTED FOR THE DURATION OF THE STIPULATED
STANDARD 555 AND NFPA 90A.
THE PREMISES AND DISPOSE OF SAME. REQUIREMENTS OF "HVAC DUCT CONSTRUCTION STANDARDS" GUARANTEE PERIOD.
5. PROVIDE TYPE C FRAMES IN ALL SUPPLY DUCTS. PROVIDE TYPE B
3. EXISTING EQUIPMENT OR SYSTEMS WHICH ARE SPECIFIED TO BE PUBLISHED BY "SHEET METAL AND AIR CONDITIONING CONTRACTORS
OR C FRAMES IN ALL EXHAUST OR RETURN DUCTWORK AND IN ALL
REPLACED BY NEW EQUIPMENT OR SYSTEMS SHALL NOT BE NATIONAL ASSOCIATION, INC.," LATEST EDITION. DUCT PRESSURE CITY OF CHICAGO NOTES
TRANSFER OR UNDUCTED OPENINGS.
REMOVED FROM SERVICE UNTIL THE NEW EQUIPMENT OR SYSTEMS CLASSES SHALL BE AS FOLLOWS UNLESS NOTED OTHERWISE:
6. FIRE DAMPERS SHALL BE INSTALLED IN ACCORDANCE WITH
HAVE ACTUALLY ARRIVED AT THE PROJECT SITE. A. VENTILATION
a. DUCTS DOWNSTREAM OF TERMINAL UNITS: +1.0" W.G. MANUFACTURER'S INSTALLATION INSTRUCTIONS.
b. TRANSFER DUCTS AND EXHAUST DUCTS: -1.0" W.G. 7. PROVIDE ACCESS DOOR OF MINIMUM 21”X14” TO ALLOW HEAD AND 1. ALL DUCTWORK SHALL BE GALVANIZED SHEET METAL OF GAUGES
SECTION 230579 - TESTING, ADJUSTING AND BALANCING c. RETURN DUCTS: -2.0” W.G. SHOULDER ACCESS, OR REMOVABLE DUCT SECTION WITH MINIMUM AND CONSTRUCTION IN ACCORDANCE WITH SMACNA AND ASHRAE
d. SUPPLY DUCTS UPSTREAM OF TERMINAL UNITS: +4.0" W.G. 8” x 5” ACCESS DOOR IN SHEET METAL DUCT ADJACENT TO FIRE STANDARDS.
DAMPER TO ENABLE MAINTENANCE. Project Name
1.1 GENERAL REQUIREMENTS 2. ALL DUCT JOINTS, SEAMS AND CONNECTIONS SHALL BE SEALED IN
2. ALL SUPPLY AND RETURN DUCTWORK SHALL BE CONSTRUCTED TO ACCORDANCE WITH THE CHICAGO ENERGY CONSERVATION CODE. HYATT REGENCY MCCORMICK PLACE MEETING ROOMS
1. TESTING AND BALANCING CONTRACTOR SHALL BE INDEPENDENT OF SMACNA SEAL CLASS "A". SEALANT MUST COMPLY WITH UL181B. 3. FLEXIBLE DUCTS SHALL NOT BE LONGER THAN 5'-0". RENOVATION
GENERAL NOTES
THE MECHANICAL CONTRACTOR AND A CERTIFIED MEMBER OF 3. ALL DUCT SIZES SHOWN ON PLAN SHALL BE INSIDE CLEAR 4. THE CONTRACTOR SHALL GUARANTEE THAT THE PLENUM CHAMBER
EITHER ASSOCIATED AIR BALANCE COUNCIL (AABC), NATIONAL DIMENSIONS. 1. CONTRACTOR SHALL BE RESPONSIBLE FOR VISITING THE SITE AND USED FOR RECIRCULATION OF AIR WILL BE OF TIGHT CONSTRUCTION Project Number
C:\00-REVIT LOCALS\HYATT_MCCORMICK_MECH_R18_jmagarzo.rvt

BALANCING COUNCIL (NBC), NATIONAL ENVIRONMENTAL BALANCING 4. MECHANICAL CONTRACTOR SHALL PROVIDE (AT NO EXTRA COST) ALL VERIFYING ALL EXISTING FIELD CONDITIONS PRIOR TO SUBMISSION AND THAT ALL SOURCES OF AIR CONTAMINATION FROM TRAPS, SOIL
7 BUREAU (NEBB) OR TESTNG ADJUSTING AND BALANCING BUREAU NECESSARY RISES, DROPS, AND OFFSETS IN DUCTWORK TO SATISFY OF HIS BID. THE CONTRACT DOCUMENTS INDICATE APPROXIMATE STACKS, DOWNSPOUTS, VENTS, BE ENCLOSED SO THAT NO 21.0457.000
(TABB). THE CONTRACTOR SHALL COOPERATE WITH THE TESTING FIELD CONDITIONS. LOCATION OF EXISTING DUCTWORK AND SYSTEM COMPONENTS AND CONTAMINATED AIR WILL BE RECIRCULATED.
AND BALANCING CONTRACTOR AND SHALL PROVIDE SUFFICIENT TIME 5. UPON COMPLETION OF THE INSTALLATION OF DUCTWORK, CLEAN ARE DIAGRAMMATIC IN NATURE. THE MECHANICAL CONTRACTOR 5. ALL EQUIPMENT INSTALLED IN A PLENUM CEILING SHALL HAVE A U.L.,
BEFORE FINAL COMPLETION OF HIS WORK, SO THAT TESTING AND ENTIRE SYSTEM OF RUBBISH, PLASTER, DIRT, ETC. BEFORE SHALL BE RESPONSIBLE FOR DETERMINING THE ACTUAL LOCATION, CSA, OR ETL LABEL AND MUST BE APPROVED FOR USE IN THE CITY Scale
BALANCING CAN BE ACCOMPLISHED. THE CONTRACTOR SHALL INSTALLING GRILLES OR DIFFUSERS. ROUTING AND SIZE OF THE DUCTWORK AND COMPONENTS. NO OF CHICAGO. 1/8" = 1'-0"
PROVIDE ALL LABOR AND TOOLS TO MAKE ANY CORRECTIONS TO THE 6. PROVIDE VOLUME DAMPERS AT ALL BRANCH TAKE-OFFS. EXTRA CHARGES WILL BE ACCEPTED BY THE BUILDING OWNER'S 6. EQUIPMENT NOISE LEVEL SHALL NOT EXCEED 55 DB AT THE LOT LINE.
SYSTEM WHEN REQUIRED TO BALANCE THE SYSTEM WITHOUT UNDUE 7. DUCTWORK SHALL BE SUPPORTED FROM STRUCTURE WITH REPRESENTATIVE FOR WORK THAT HAS TO BE PERFORMED DUE TO 7. ALL FRESH AIR INTAKE OPENINGS SHALL BE A MINIMUM OF 15'-0"
DELAY TO THE TESTING AND BALANCING CONTRACTOR. STANDARD GALVANIZED BAND STEEL HANGERS. THE MECHANICAL CONTRACTOR'S FAILURE TO ADEQUATELY VERIFY AWAY FROM ANY EXHAUST OR POINT OF CONTAMINATED DISCHARGE Description
8. FLEXIBLE CONNECTIONS AND TAKE-OFF TO DIFFUSERS SHALL BE THE EXISTING CONDITIONS. AND MINIMUM 10'-0" ABOVE GRADE OR HAVE ADEQUATE MEANS TO
SIZE OF THE DIFFUSER INLET. REMOVE DUST. MECHANICAL SYMBOLS AND LEGEND, SPECIFICATIONS
AND GENERAL NOTES

M1.100
© 2019 Gensler
K J H G F E D C B A
K J H G F E D C B A

SHEET NOTES

NECK SIZING SCHEDULE DIFFUSERS / REGISTERS / GRILLES

INTEGRAL VOLUME DAMPER


AIR QUANTITY RANGE

MAX NOISE CRITERIA


1
HYATT

NUMBER OF SLOTS
DESIGNATION

MANUFACTURER
BOOT LENGTH
DESIGNATION
NECK SIZE

REMARKS

SLOT WIDTH
2233 S Martin Luther King Dr

MODEL NO.
NECK SIZE
Chicago IL 60616

FACE SIZE

REMARKS
TYPE

TYPE
CFM INCH -
0-150 6 INCH INCH INCH INCH NC
PLENUM SLOT 2-SLOT - 1 INCH SLOT 151-200 8 S EXISTING SUPPLY DIFFUSER - - - - - - - - -
S-1 4' PLENUM
WIDTH 201-230 10 11 East Madison Street Tel 312.456.0123
S-1 PLENUM SLOT DIFFUSER - NECK SCHED 1 2 NECK SCHED 25 NO TITUS TBDI-80 Suite 300 Fax 312.456.0124
231-300 12 Chicago, IL 60602
S-2 PLENUM SLOT DIFFUSER - NECK SCHED 1.5 4 NECK SCHED 25 NO TITUS TBDI-80 United States
0-250 6
2 251-350 8 S-3 24x24 LAY-IN PLAQUE 24x24 - - - NECK SCHED 25 NO TITUS OMNI
PLENUM SLOT 4-SLOT - 1.5 INCH SLOT
S-2 4' PLENUM S-4 DOUBLE DEFLECTION SUPPLY REGISTER SEE PLANS - - - SEE PLANS 25 YES TITUS 300-RL
WIDTH 351-400 10
401-550 12 R EXISTING RETURN DIFFUSER - - - - - - - - -
0-150 6 - R-1 24x24 LAY-IN PLAQUE 24x24 - - - 15" 25 YES TITUS OMNI
151-300 8 - R-2 RETURN REGISTER - 35 DEG DEFL BLADES - - - - SEE PLANS 25 YES TITUS 350-RL
S-3 24X24 LAY-IN PLAQUE 301-390 10 -
E-1 EXHAUST REGISTER - 35 DEG DEFL BLADES - - - - SEE PLANS 25 YES TITUS 350-RL
391-490 12 -
T-1 TRANSFER GRILLE - 35 DEG DEFL BLADES - - - - SEE PLANS 25 YES TITUS 350-RL
491-570 14 -
ALUMINUM LINEAR 2-SLOT - 1 INCH SLOT
R-1 0-520 - RETURN W/ 4' LENGTH NOTES:
WIDTH
1 PROVIDE SIGHT BAFFLES FOR EACH RETURN AIR GRILLE AND SLOT
NOTES: 2 PROVIDE 24X24X12D LINED PLENUM BOX ABOVE RETURN DIFFUSER FOR SOUND ATTENUATION
3 1 ALL NECK SIZES TO BE SELECTED FOR MAX NC-25 3 CONFIRM BORDER TYPE AND FINISH WITH ARCHITECT
2 ALL NECK SIZES TO BE SELECTED FOR MAX PRESSURE DROP OF 0.1 INCH WG
4 COORDINATE ALL TRIM AND BORDER TYPES WITH ARCHITECT
5 PROVIDE BLANK OFFS FOR UNUSED PORTIONS OF THE PERIMETER SLOT
6 PROVIDE LINED SHEET METAL ELBOWED BOOT ON RETURN PORTION OF DIFFUSER FOR SOUND ATTENUATION. SEE DETAIL ESD Global
MEP/FP Engineers
7 PROVIDE BLANK OFFS PAINTED BLACK FOR UNUSED PORTION OF SLOT DIFFUSERS 233 South Wacker Drive
Suite 5300
8 SUBMIT TRIM AND T-BARS TO ARCHITECT FOR APPROVAL. TYPICAL FOR ALL Chicago, IL
Tel 312.372.1200

Date Description

BASE BUILDING AIR SUMMARY VENTILATION SCHEDULE 1 1/X/2020 ISSUED FOR CD


4

ORDINANCE
FLOOR ACTUAL BUILDING FAN SYSTEM
ROOM REQUIREMENTS
ROOM NAME CODE PURPOSE AREA REMARKS
NO. DEDICATED
(SQ. FT.) SUPPLY EXHAUST SUPPLY EXHAUST SUPPLY/ RETURN
STATIC PRESSURE

EXHAUST
H-200 CORRIDOR CORRIDOR 3373 N.R. N.R. 10410 10410 AHU-1-1, 1-2/RF-1-1, 1-2
FAN SYSTEM

H-201 BOARD ROOM 1 OFFICE 702 421 211 1500 1500 AHU-1-1, 1-2/RF-1-1, 1-2
MOTOR HP
LOCATION

REMARKS
AIRFLOW

H-202 ELEVATOR LOBBY CORRIDOR 282 N.R. N.R. 300 300 AHU-1-1, 1-2/RF-1-1, 1-2
H-203 BOARD ROOM 2 OFFICE 697 418 209 1500 1500 AHU-1-1, 1-2/RF-1-1, 1-2
H-204 BOARD ROOM 3 OFFICE 676 406 203 1500 1500 AHU-1-1, 1-2/RF-1-1, 1-2
H-205 BOARD ROOM 4 OFFICE 676 406 203 1500 1500 AHU-1-1, 1-2/RF-1-1, 1-2
CFM INCH W.G
H-206 BOARD ROOM 5 OFFICE 480 288 144 1500 1500 AHU-1-1, 1-2/RF-1-1, 1-2
5 AHU-1 ROOF 25,000 4.8 25 TRANE 40B AHU-1-1, 1-2/RF-1-1, 1-2
H-207 STAIR 5 CORRIDOR 331 N.R. N.R. - -
RF-1 ROOF 25,000 1.97 15 TRANE 40A H-208 MEN TOILET ROOM 293 N.R. 586 250 1000 AHU-1-1, 1-2/RF-1-1, 1-2 TE-3-1 SA TRANSFER FROM CORR.
AHU-2 ROOF 25,000 4.8 25 TRANE 40B H-211 PREFUNCTION ASSEMBLY PRE-FUNCTION 3900 7800 5850 10460 10460 SU-3-1/RF-3-1
RF-2 ROOF 25,000 1.97 15 TRANE 40A H-212 BALLROOM BALL ROOM 11786 23572 17679 39900 39900 SU-3-3/RF-3-3&4
AHU-4 ROOF 30,000 3.58 30 TRANE 66B H-300 CORRIDOR CORRIDOR 3167 N.R. N.R. 10410 10410 AHU-1-1, 1-2/RF-1-1, 1-2
H-301 MEETING SUITE 1 OFFICE 698 419 209 1500 1500 AHU-1-1, 1-2/RF-1-1, 1-2
RF-4 ROOF 30,000 1.54 15 TRANE 66A
H-302 MEETING SUITE 2 OFFICE 696 418 209 1500 1500 AHU-1-1, 1-2/RF-1-1, 1-2
AHU-5 ROOF 30,000 3.58 30 TRANE 66B
H-303 MEETING SUITE 3 OFFICE 675 405 203 1500 1500 AHU-1-1, 1-2/RF-1-1, 1-2
RF-5 ROOF 30,000 1.54 15 TRANE 66A AHU-1-1, 1-2/RF-1-1, 1-2
H-304 MEETING SUITE 4 OFFICE 676 406 203 1280 1280
AHU-1-1 LEVEL 1 30,000 3.81 30 YORK CSI 578 H-305 MEETING SUITE 5 OFFICE 535 321 161 1500 1500 AHU-1-1, 1-2/RF-1-1, 1-2
RF-1-1 LEVEL 1 25,000 2 20 YORK CSI 356 H-306 ELEVATOR LOBBY CORRIDOR 295 N.R. N.R. 300 300 AHU-1-1, 1-2/RF-1-1, 1-2
AHU-1-2 LEVEL 1 30,000 3.81 30 YORK CSI 578 H-307 STAIR 5 CORRIDOR 329 N.R. N.R. - - AHU-1-1, 1-2/RF-1-1, 1-2
6 RF-1-2 LEVEL 1 25,000 2 20 YORK CSI 356 H-308 RESTROOM TOILET ROOM 78 N.R. 156 - 160 AHU-1-1, 1-2/RF-1-1, 1-2 TE-3-1 SA TRANSFER FROM CORR.
Seal / Signature
SU-3-1 LEVEL 3 MEZZ 11,000 2.14 10 YORK CSI 217 H-309 RESTROOM TOILET ROOM 63 N.R. 126 - 150 AHU-1-1, 1-2/RF-1-1, 1-2 TE-3-1 SA TRANSFER FROM CORR.
RF-3-1 LEVEL 3 MEZZ 11,000 1 7.5 YORK CSI 156 H-310 RESTROOM TOILET ROOM 53 N.R. 106 - 150 AHU-1-1, 1-2/RF-1-1, 1-2 TE-3-1 SA TRANSFER FROM CORR.
SU-3-3 LEVEL 3 MEZZ 40,000 4.43 40 YORK CSI 754 H-311 RESTROOM TOILET ROOM 71 N.R. 142 - 150 AHU-1-1, 1-2/RF-1-1, 1-2 TE-3-1 SA TRANSFER FROM CORR.
RF-3-3 LEVEL 3 MEZZ 35,000 2 30 YORK CSI 490 CC-100 CONCOURSE CORRIDOR 5943 N.R. N.R. 30000 30000 AHU-5 / RF-5
RF-3-4 LEVEL 3 MEZZ 7,000 1.5 5 YORK CSI 113 CC-104 MEETING ROOM SPACE OFFICE 5207 3124 1562 6240 6240 AHU-1 / RF-1
CC-105 MEETING ROOM SPACE OFFICE 2589 1553 777 3120 3120 AHU-2 / RF-2
CC-106 MEETING ROOM SPACE OFFICE 5149 3089 1545 6240 6240 AHU-2 / RF-2
CC-300 NORTH LOBBY CORRIDOR 2374 N.R. N.R. 3600 3600 AHU-1 / RF-1 Project Name

CC-303 CONCOURSE CORRIDOR 5237 N.R. N.R. 30000 30000 AHU-4 /RF-4 HYATT REGENCY MCCORMICK PLACE MEETING ROOMS
RENOVATION
CC-306 MEETING ROOM SPACE OFFICE 1881 1129 564 2880 2880 AHU-1 / RF-1
CC-307 MEETING ROOM SPACE OFFICE 1887 1132 566 2880 2880 AHU-1 / RF-1 Project Number
C:\00-REVIT LOCALS\HYATT_MCCORMICK_MECH_R18_jmagarzo.rvt

7 CC-308 MEETING ROOM SPACE OFFICE 1887 1132 566 2880 2880 AHU-1 / RF-1 21.0457.000

CC-309 MEETING ROOM SPACE OFFICE 1886 1132 566 2880 2880 AHU-1 / RF-1
CC-310 MEETING ROOM SPACE OFFICE 1838 1103 551 2880 2880 AHU-1 / RF-1 Scale

1/8" = 1'-0"

TOTAL FOR SUPPLY FAN SYSTEM 66410 48674 25909 180410 181770
Description

MECHANICAL SCHEDULES

© 2019 Gensler
K J H G F E D C B A
K J H G F E D C B A

C D E F G H H.5 J J.3 K K.4 L L.4


KEYNOTES
1 CAP EXISTING BRANCH DUCT
TAKEOFF.
2 CAP EXISTING EXHAUST DUCT.
3 REBALANCE EXISTING FAN
3.9 POWERED BOX BASED ON THE
CFM INDICATED TO EACH
DIFFUSERS.
150 - S

RESTROOM RESTROOM
H-311 H-308
1500 -R
750 - R1 750 - R1 750 - R1 750 - R1 750 - R1 750 - R1 150-E1 160-E1 4
STORAGE
1

MEETING SUITE 1
STORAGE
EX52
EX53
MEETING SUITE 2
MEETING SUITE 3
320 - S
MEETING SUITE 4
320 - S 375 - S
1500 -R
375 - S
5 HYATT
ELEVATOR H-303 H-304
H-301 100 - S 100 - S H-302
1 LOBBY 1 1 2 2233 S Martin Luther King Dr
Chicago IL 60616
H-306
1
375 - S 375 - S 375 - S MEETING SUITE 5
375 - S 375 - S 375 - S RESTROOM
ELEVATOR 10x8 H-305
200 - S
LOBBY H-309
1
EX51 CORRIDOR 150-E1 375 - S
H-312 6
3 150-E1 STAIR 5
3 3 3 375 - S 11 East Madison Street Tel 312.456.0123
RESTROOM 3 H-307 Suite 300 Fax 312.456.0124
150 - S
375 - S 375 - S 375 - S 375 - S 375 - S 375 - S 320 - S 320 - S H-310 6.4 Chicago, IL 60602
United States

CORRIDOR
H-300

7
350 - S 350 - S 350 - S 350 - S 350 - S 350 - S OPEN
(TYP.4) (TYP.4) (TYP.4) (TYP.4) (TYP.4) (TYP.4) TO
BELOW 2A

OPEN TO BELOW

335 - S 335 - S
(TYP.3) (TYP.3)

10
8
DRAWING LEGEND
EXISTING WALLS/PARTITIONS ESD Global
MEP/FP Engineers
233 South Wacker Drive
EXISTING BUILDING AREAS TO Suite 5300
REMAIN Chicago, IL
Tel 312.372.1200
EXISTING CONSTRUCTION TO BE
DEMOLISHED

MH_LEVEL 03 HOTEL - MEETING SUITES


1 SCALE: 1/8" = 1'-0" 0 24 48 96 192 Date Description

4
GENERAL NOTES 1 1/X/2020 ISSUED FOR CD
C D E F G H H.5 J J.3 K K.4 L L.4
1. ALL FAN POWERED BOXES,
THERMOSTSTS, DUCTWORK AND
ASSOCIATED DIFFUSERS SHOWN
ON LEVEL 02 BOARD ROOMS ARE
ALL EXISTING TO REMAIN AND FOR
REFERENCE ONLY.

3.9
150 - S

4
BOARD ROOM 1 STORAGE STORAGE
5 375-S 375-S 375-S 100 - S 150 - S 375-S
H-201 ELEVATOR EX250 EX251 (TYP.4) BOARD ROOM 2 (TYP.4) BOARD ROOM 3 (TYP.4) BOARD ROOM 4 5
LOBBY BUSINESS (TYP.4)
100 - S 100 - S H-203 H-204 H-205
H-202 CENTER
EX351 MEN
375-S ELEVATOR H-208
(TYP.4) BOARD ROOM 5 STAIR 5
LOBBY 100 - S
OFFICE H-206 H-207
EX252
EX352
300 - S 6
100 - S
150 - S 100 - S 6.4
1A
6
CORRIDOR Seal / Signature

H-200 CORRIDOR
H-210
347 - S
(TYP.6) 7
347 - S 347 - S 347 - S 347 - S 347 - S 347 - S
(TYP.4) (TYP.4) (TYP.4)
(TYP.4) (TYP.4) (TYP.4) 2A
Project Name

HYATT REGENCY MCCORMICK PLACE MEETING ROOMS


OPEN TO BELOW RENOVATION

Project Number
C:\00-REVIT LOCALS\HYATT_MCCORMICK_MECH_R18_jmagarzo.rvt

7 21.0457.000
10
8
Scale

1/8" = 1'-0"

Description

MECHANICAL VENTILATION PLAN - LEVELS 02 AND 03


HOTEL - BOARD ROOMS & MEETING SUITES

2 MH_LEVEL 02 BOARD ROOMS


SCALE: 1/8" = 1'-0" 0 24 48 96 192
MH1.200
© 2019 Gensler
K J H G F E D C B A
K J H G F E D C B A

KEYNOTES
K K.4 L L.4 M M.6 M.8 N N.2 N.5 N.8 P R 1 COORDINATE LOCATION AND
INSTALLATION OF SLOT
DIFFUSERS WITH ARCHITECT
(TYPICAL).

1A

4
5
1
WOMEN
H-209
250 - S
2A
HYATT
MEETING
BOARD ROOM 5 STAIR 5 2233 S Martin Luther King Dr
SUITE 5
H-206 H-207 Chicago IL 60616

MEN
6
H-208
2A.5
6.4
JANITOR'S
CLOSET 11 East Madison Street Tel 312.456.0123
Suite 300 Fax 312.456.0124
150 - R EX253 375-S2 Chicago, IL 60602
(TYP.6) United States

1
2
150 - S T

347 - S CORRIDOR
3A
(TYP.4)
H-200
390-S2
(TYP.6)
7

1
375-S2
(TYP.6)
3A.5
390-S2
(TYP.6)
1

375-S2 10
8
(TYP.6) T
3

4A
DRAWING LEGEND
375-S2
(TYP.6)
1 EXISTING WALLS/PARTITIONS ESD Global
MEP/FP Engineers
270 - S 233 South Wacker Drive
(TYP.4) 500-S2 EXISTING BUILDING AREAS TO Suite 5300
(TYP.4) REMAIN Chicago, IL
Tel 312.372.1200
4A.5 EXISTING CONSTRUCTION TO BE
DEMOLISHED
440-S2
1 500-S2 (TYP.4)
270 - S BALLROOM
(TYP.4) Date Description
(TYP.4) T H-212

4
T GENERAL NOTES 1 1/X/2020 ISSUED FOR CD
500-S2 440-S2
1
(TYP.4) (TYP.4) 5A

440-S2
270 - S (TYP.4)
(TYP.4)

PREFUNCTION
5A.5
H-211

415-S2
T (TYP.12)
270 - S
5 (TYP.4) 1

415-S2 6A
(TYP.12)

270 - S 1
(TYP.4) 415-S2 T
(TYP.12) 6A.5
1 T
T

6 270 - S
7A
(TYP.4) Seal / Signature
7A.2
800 - S

220 - S
(TYP.3)
270 - S
(TYP.4) Project Name
420 - S HYATT REGENCY MCCORMICK PLACE MEETING ROOMS
(TYP.2) RENOVATION

Project Number
350 - S
C:\00-REVIT LOCALS\HYATT_MCCORMICK_MECH_R18_jmagarzo.rvt

7 (TYP.4) 21.0457.000

Scale

1/8" = 1'-0"

Description

MECHANICAL VENTILATION PLAN - LEVEL 02 HOTEL -


BALLROOM

MH_LEVEL 02 BALLROOM
1 SCALE: 1/8" = 1'-0" 0 24 48 96 192
MH1.201
© 2019 Gensler
K J H G F E D C B A
K J H G F E
17c 18c 19c 20c 21c 22cD 23c C
24c B
26.7c A

KEYNOTES
1 COORDINATE LOCATION AND
INSTALLATION OF SLOT
DIFFUSERS WITH ARCHITECT
(TYPICAL).
240 - S 240 - S UP TO AHU-1
BOH CORRIDOR
A.3c VAV UP TO E-111
C2.9 AHU-4 CC
VAV VAV
C2.8 C2.6 VAV
C2.5
1560 -R 1560 -R 1600 -R 1600 -R UP TO AHU-1 1560 -R 218 - S
A.3d
1

WOMEN MEN Jf
HYATT
218 - S
CC-103 CC-102 2233 S Martin Luther King Dr
Chicago IL 60616
1 1
1
Bc 195-S1 200-S1
MEETING ROOM
195-S1
1
SPACE 218 - S
(TYP.8) (TYP.8) (TYP.8)
CC-104

NORTH LOBBY
200-S1 CC-101 218 - S
(TYP.8) STORAGE 11 East Madison Street Tel 312.456.0123
Suite 300 Fax 312.456.0124
EX151 Chicago, IL 60602
United States
Cc
218 - S
2

383 - S 383 - S

Dc
11 218 - S

218 - S
CONCOURSE (TYP-2)
5000 -S 5000 -S 5000 -S CC-100
(TYP.2)
(TYP.2) (TYP.2)
(TYP.2) (TYP.2)
(TYP.2)

Ec
9
3

E.3c
DRAWING LEGEND
EXISTING WALLS/PARTITIONS ESD Global
MEP/FP Engineers
233 South Wacker Drive
27c EXISTING BUILDING AREAS TO
REMAIN
Suite 5300
Chicago, IL
Tel 312.372.1200
EXISTING CONSTRUCTION TO BE
DEMOLISHED
25c 26c
MH_LEVEL 01 CONFERENCE CENTER NORTH
1 SCALE: 1/8" = 1'-0" 0 24 48 96 192
GENERAL NOTES 1
Date

1/X/2020
Description

ISSUED FOR CD
4

11.1c
12 11.4c 11.2c 12.1c 12c 13c 14c 15c 16c 17c

589 - S
UP TO UP TO
AHU-5 AHU-2
UP TO A.3c
AHU-2
VAV VAV VAV VAV VAV VAV
C2.16 C2.15 C2.14 C2.12 C2.11 C2.10
1560 - R
5 1500 - R 1600 - R 1560 - R 1560 - R 1560 - R
A.3d
(TYP-6)
Jf
MEETING ROOM MEETING ROOM
SPACE SPACE
CC-106 CC-105
1 1 1 1 195-S1 1
190-S1 200-S1 1 195-S1
(TYP.8)
195-S1
(TYP.8)
195-S1 (TYP.8)
Bc
(TYP.8) (TYP.8) (TYP.8)

6
Cc Seal / Signature

11 Dc
11

Project Name
240 - S
HYATT REGENCY MCCORMICK PLACE MEETING ROOMS
5000 -S 5000 -S RENOVATION
5000 -S CONCOURSE
(TYP-2) (TYP-2) (TYP-2)
CC-100 Project Number
C:\00-REVIT LOCALS\HYATT_MCCORMICK_MECH_R18_jmagarzo.rvt

7
Ec
9 Ec
9 21.0457.000

Scale

1/8" = 1'-0"
E.3c E.3c
Description

MECHANICAL VENTILATION PLAN - LEVEL 01 CONFERENCE


CENTER - MEETING ROOMS

2 MH_LEVEL 01 CONFERENCE CENTER SOUTH


SCALE: 1/8" = 1'-0" 0 24 48 96 192
MH1.202
© 2019 Gensler
K J H G F E D C B A
K J H G F E D C B A

KEYNOTES
17c 18c 19c 20c 21c 22c 23c 24c 26.7c
1 COORDINATE LOCATION AND
BOH INSTALLATION OF SLOT
DIFFUSERS WITH ARCHITECT
EX304 (TYPICAL).
UP TO AHU-1

A.3c VAV
UP TO VAV
AHU-4 VAV VAV
C4.7 C4.3
C4.2 C4.1

VAV VAV 360 - S


900 - R UP TO 900 - R 900 - R 900 - R 900 - R 900 - R
C4.6 C4.5
AHU-4
A.3d UP TO AHU-1 BOH CORRIDOR
1
240-S1
(TYP.4)
EX304
Jf
HYATT
240-S1
2233 S Martin Luther King Dr
1 (TYP.4) 1 240-S1 1 240-S1 Chicago IL 60616
240-S1
(TYP.4) (TYP.4) (TYP.4)
MEETING ROOM MEETING ROOM
Bc SPACE SPACE
CC-307 CC-306
WOMEN MEN
360 - S
CC-305 CC-304
240-S1
(TYP.4) 11 East Madison Street Tel 312.456.0123
STORAGE
Suite 300 Fax 312.456.0124
EX305 Chicago, IL 60602
United States
Cc
2

CONCOURSE
CC-303
11
Dc
11

NORTH LOBBY
OPEN TO BELOW
CC-300

Ec
9
3

E.3c
DRAWING LEGEND
EXISTING WALLS/PARTITIONS ESD Global
MEP/FP Engineers
233 South Wacker Drive
27c EXISTING BUILDING AREAS TO
REMAIN
Suite 5300
Chicago, IL
Tel 312.372.1200
EXISTING CONSTRUCTION TO BE
DEMOLISHED
26c
25c Date Description

MH_LEVEL_03_CONFERENCE CENTER NORTH


GENERAL NOTES 1 1/X/2020 ISSUED FOR CD
4
1 SCALE: 1/8" = 1'-0" 0 24 48 96 192

11.1c
12 11.4c 11.2c 12.1c 12c 13c 14c 15c 16c 17c

A.3c VAV
VAV VAV VAV VAV VAV VAV VAV VAV
C4.11
C4.20 C4.19 C4.17 C4.16 C4.15 C4.13 C4.12 C4.10

5 900 - R 900 - R UP TO 900 - R UP TO 900 - R 900 - R 900 - R 900 - R 900 - R UP TO 900 - R 900 - R
UP TO AHU-2
AHU-5 AHU-5
A.3d AHU-2

1
1
1 1 Jf
1
WOMEN MEN
240-S1
CC-312 CC-311 240-S1 240-S1 240-S1 240-S1 240-S1 240-S1 240-S1 240-S1
(TYP.4)
(TYP.4) (TYP.4) (TYP.4) (TYP.4) (TYP.4) (TYP.4) (TYP.4) (TYP.4)
Bc MEETING ROOM MEETING ROOM
SPACE SPACE
CC-310 CC-309
WEST
CONCOURSE
MEETING ROOM
EX307 SPACE
STORAGE
EX306 CC-308
6
Cc Seal / Signature

Dc
11 240 - S

OPEN TO BELOW
Project Name

HYATT REGENCY MCCORMICK PLACE MEETING ROOMS


RENOVATION

Project Number
C:\00-REVIT LOCALS\HYATT_MCCORMICK_MECH_R18_jmagarzo.rvt

7
Ec
9 21.0457.000

Scale

1/8" = 1'-0"
E.3c
Description

MECHANICAL VENTILATION PLAN - LEVEL 03 CONFERENCE


CENTER - MEETING ROOMS

2 MH_LEVEL_03 - CC - South
SCALE: 1/8" = 1'-0" 0 24 48 96 192
MH1.203
© 2019 Gensler
K J H G F E D C B A
K J H G F E D C B A

C D E F G H H.5 J J.3 K K.4 L L.4


KEYNOTES
1 REMOVE EXISTING BRANCH
DUCTWORK AND ASSOCIATED
DIFFUSER.
2 CUT EXISTING DUCTWORK AND
3.9 ABANDON DUCTWORK IN PLACE.
3 EXISTING FAN POWERED BOX
AND ALL ASSOCIATED
DUCTWORK AND DIFFUSERS
SERVING THE CORRIDOR TO
REMAIN UNCHANGED.
4 EXISTING FAN POWERED BOX TO
REMAIN. REMOVE PORTION OF
1 4 DUCTWORK AND DIFFUSER AS
1

1
1 1
1
1 5
INDICATED.
HYATT
2 1
1 2233 S Martin Luther King Dr
Chicago IL 60616

2
1

1
6
4 4 4 4 11 East Madison Street Tel 312.456.0123
Suite 300 Fax 312.456.0124
3 4 6.4 Chicago, IL 60602
United States

2
3
3

3
3
7

OPEN 2A
TO
BELOW

10
8
DRAWING LEGEND
EXISTING WALLS/PARTITIONS ESD Global
MEP/FP Engineers
233 South Wacker Drive
EXISTING BUILDING AREAS TO Suite 5300
REMAIN Chicago, IL
Tel 312.372.1200
EXISTING CONSTRUCTION TO BE
DEMOLISHED

MHD_LEVEL 03 HOTEL - MEETING SUITES


2 SCALE: 1/8" = 1'-0" 0 24 48 96 192 Date Description

4
GENERAL NOTES 1 1/X/2020 ISSUED FOR CD
C D E F G H H.5 J J.3 K K.4 L L.4
1. ALL FAN POWERED BOXES,
THERMOSTSTS, DUCTWORK AND
ASSOCIATED DIFFUSERS SHOWN
ON LEVEL 02 BOARD ROOMS ARE
ALL EXISTING TO REMAIN AND FOR
REFERENCE ONLY.

3.9

4
5
5

6.4
1A
6
Seal / Signature

2A

Project Name

HYATT REGENCY MCCORMICK PLACE MEETING ROOMS


OPEN TO BELOW RENOVATION

Project Number
C:\00-REVIT LOCALS\HYATT_MCCORMICK_MECH_R18_jmagarzo.rvt

7 21.0457.000
10
8
Scale

1/8" = 1'-0"

Description

MECHANICAL DEMOLITION PLAN - LEVELS 02 AND 03 HOTEL


- BOARD ROOMS & MEETING SUITES

1 MHD_LEVEL 02 BOARD ROOMS


SCALE: 1/8" = 1'-0" 0 24 48 96 192
MHD1.100
© 2019 Gensler
K J H G F E D C B A
K J H G F E D C B A

KEYNOTES
K K.4 L L.4 M M.6 M.8 N N.2 N.5 N.8 P R 1 EXISTING EXHAUST DUCTWORK
AND ALL ASSOCIATED
DIFFUSERS SERVING THE TOILET
ROOMS TO REMAIN UNCHANGED.
2 EXISTING SUPPLY DUCTWORK
1A AND ALL ASSOCIATED
DIFFUSERS SERVING THE
PREFUNCTION ROOM TO REMAIN
4 UNCHANGED.
3 EXISTING SUPPLY DUCT TO
REMAIN. REMOVE BRANCH DUCT
5 AND DIFFUSERS AS INDICATED
TO BE DEMOLISHED. SEE NEW
1

1
1
2A
WORK PLAN FOR DETAILS.
4 EXISTING DUCT HEATER AND ALL
HYATT
MEETING ASSOCIATED THERMOSTATS AND
2233 S Martin Luther King Dr
MOTORIZED DAMPERS TO
SUITE 5 REMAIN. Chicago IL 60616

2A.5
6.4
11 East Madison Street Tel 312.456.0123
Suite 300 Fax 312.456.0124
Chicago, IL 60602
United States

3A
7

4
3

4 3A.5
3

10
8
3

4A
3
DRAWING LEGEND
EXISTING WALLS/PARTITIONS ESD Global
MEP/FP Engineers
233 South Wacker Drive
EXISTING BUILDING AREAS TO Suite 5300
REMAIN Chicago, IL
Tel 312.372.1200
4A.5 EXISTING CONSTRUCTION TO BE
DEMOLISHED

4
Date Description

4
4 GENERAL NOTES 1 1/X/2020 ISSUED FOR CD

5A

4
2 5A.5
3
3

5
3
6A
4
3

4
6A.5
T

2 4
6
7A
Seal / Signature
7A.2
2

Project Name

HYATT REGENCY MCCORMICK PLACE MEETING ROOMS


RENOVATION

Project Number
C:\00-REVIT LOCALS\HYATT_MCCORMICK_MECH_R18_jmagarzo.rvt

7 21.0457.000

Scale

1/8" = 1'-0"

Description

MECHANICAL DEMOLITION PLAN - LEVEL 02 HOTEL -


BALLROOM

MHD_LEVEL 02 BALLROOM
1 SCALE: 1/8" = 1'-0" 0 24 48 96 192
MHD1.101
© 2019 Gensler
K J H G F E D C B A
K J H G F E D C B A

KEYNOTES
17c 18c 19c 20c 21c 22c 23c 24c 26.7c
1 EXISTING VAV BOX TO REMAIN.
REMOVE PORTION OF
DUCTWORK AND DIFFUSER AS
INDICATED.
2 EXISTING SUPPLY DUCTWORK
AND ALL ASSOCIATED
A.3c DIFFUSERS SERVING THE
CORRIDOR TO REMAIN
1 1 1 1 UNCHANGED.

A.3d
1

Jf
HYATT
2
2233 S Martin Luther King Dr
Chicago IL 60616

Bc

11 East Madison Street Tel 312.456.0123


Suite 300 Fax 312.456.0124
Chicago, IL 60602
United States
Cc
2

Dc
11

Ec
9 Ec
9
3

E.3c E.3c
DRAWING LEGEND
EXISTING WALLS/PARTITIONS ESD Global
MEP/FP Engineers
233 South Wacker Drive
27c EXISTING BUILDING AREAS TO
REMAIN
Suite 5300
Chicago, IL
Tel 312.372.1200
EXISTING CONSTRUCTION TO BE
DEMOLISHED

25c 26c
Date Description

MHD_LEVEL 01 CONFERENCE CENTER NORTH GENERAL NOTES 1 1/X/2020 ISSUED FOR CD


4
1 SCALE: 1/8" = 1'-0" 0 24 48 96 192

11.1c
12 11.4c 11.2c 12.1c 12c 13c 14c 15c 16c 17c

A.3c
1 1 1 1 1 1

A.3d
Jf
2

Bc

6
Cc Seal / Signature

Dc
11

Project Name
2
HYATT REGENCY MCCORMICK PLACE MEETING ROOMS
RENOVATION

Project Number
C:\00-REVIT LOCALS\HYATT_MCCORMICK_MECH_R18_jmagarzo.rvt

7
Ec
9 Ec
9 21.0457.000

Scale

1/8" = 1'-0"
E.3c E.3c
Description

MECHANICAL VENTILATION PLAN - LEVEL 01 CONFERENCE


CENTER - MEETING ROOMS

2 MHD_LEVEL 01 CONFERENCE CENTER SOUTH


SCALE: 1/8" = 1'-0" 0 24 48 96 192
MHD1.102
© 2019 Gensler
K J H G F E D C B A
K J H G F E D C B A

KEYNOTES
17c 18c 19c 20c 21c 22c 23c 24c 26.7c
1 EXISTING VAV BOX TO REMAIN.
REMOVE PORTION OF
DUCTWORK AND DIFFUSER AS
INDICATED.
2 EXISTING SUPPLY DUCTWORK
AND ALL ASSOCIATED
A.3c 1 1 1 DIFFUSERS SERVING THE
1 1 1
CORRIDOR TO REMAIN
2
UNCHANGED.

A.3d
1

Jf
HYATT
2233 S Martin Luther King Dr
Chicago IL 60616

Bc

2 2
11 East Madison Street Tel 312.456.0123
Suite 300 Fax 312.456.0124
Chicago, IL 60602
United States
Cc
2

Dc
11

OPEN TO BELOW

Ec
9
3

E.3c
DRAWING LEGEND
EXISTING WALLS/PARTITIONS ESD Global
MEP/FP Engineers
233 South Wacker Drive
27c EXISTING BUILDING AREAS TO
REMAIN
Suite 5300
Chicago, IL
Tel 312.372.1200
EXISTING CONSTRUCTION TO BE
DEMOLISHED
25c 26c
Date Description

MHD_LEVEL_03_CONFERENCE CENTER NORTH GENERAL NOTES 1 1/X/2020 ISSUED FOR CD


4
1 SCALE: 1/8" = 1'-0" 0 24 48 96 192
12c 13c 14c 15c 16c 17c

11.1c
12 11.4c 11.2c 12.1c

A.3c 1
1 1 1 1 1 1 1 1

A.3d 2

Jf

Bc

2 2

6
Cc Seal / Signature

Dc
11

Project Name

HYATT REGENCY MCCORMICK PLACE MEETING ROOMS


RENOVATION

Project Number
C:\00-REVIT LOCALS\HYATT_MCCORMICK_MECH_R18_jmagarzo.rvt

7
Ec
9 21.0457.000

Scale

1/8" = 1'-0"
E.3c
Description

MECHANICAL DEMOLITION PLAN - LEVEL 03 CONFERENCE


CENTER - MEETING ROOMS

2 MHD_LEVEL_03 - CC - South
SCALE: 1/8" = 1'-0" 0 24 48 96 192
MHD1.103
© 2019 Gensler